Diesel Engine Fire Pump Controllers

February 2009
Field Connections
FD120 Diesel Plus Engine Controllers

Field Connections
Engine Board Terminal Blocks Inputs

90-240VAC
POWER

FUEL & WATER SOLENOID VALVE


ENGINE RUN SW.
OVERSPEED SW.
OIL PRESSURE SW.
ENGINE WATER TEMP. SW.
BATTERY #1 INPUT(+)

BATTERY #2 INPUT(+)

BATTERY #1 CRANK
BATTERY #2 CRANK
BATTERIES (-)

BATTERIES (-)

FUEL SOLENOID
ECM IN ALTERNATE
FUEL INJECTOR FAIL

Outputs

ENGINE RUN LOW FUEL

ENGINE RUN LOW FUEL

FUTURE #1 AUTO MODE

FUTURE #1 AUTO MODE

FUTURE #2 COMMON ALARM


(NORMALLY ENERGIZED)

FUTURE #2 COMMON ALARM


(NORMALLY ENERGIZED)

Technical Data and Specifications


Line Terminals (Incoming Cables)
Recommended Wire Size Terminal Number Distance

I/O Board
Stranded # 14 (1.63 mm) 11, 34-49, 60-95 N. A.
Stranded # 14 (1.63 mm) Option Board Terminals N. A.
Engine Board
Stranded # 14 (1.63 mm) 1-5, 9, 10, 12, 301, 302, L, N, G N. A.
Battery Wire
Stranded # 10 (2.59 mm) 6, 8, 11 0 feet to 25 feet (7.62m)
Stranded # 8 (3.26 mm) 6, 8, 11 25 feet to 50 feet (7.62 - 15.24m)

N. Y. C.
APPROVED

ES05805164K For more information visit: www.chfire.com