User Manual: Sequence Controller
User Manual: Sequence Controller
User manual
Ref:
TABLE OF CONTENTS
1 OPERATING LIMITS………………………………………………………………………………………………………...C
1 FEATURES OF THE PROGRAMME ...........................................................................................................................0
4 ALARM DESCRIPTION................................................................................................................................................9
5 DESCRIPTION OF PARAMETERS............................................................................................................................10
6 CONNECTIONS ...........................................................................................................................................................19
6.1 HARDWARE ARCHITECTURE .......................................................................................................................................19
6.2 MAIN BOARD - LAYOUT.............................................................................................................................................20
7 MEANING OF INPUTS AND OUTPUTS....................................................................................................................22
INSTALLATION OF EPROMS..................................................................................................................................................24
8 CONNECTION OF OPTIONAL BOARDS..................................................................................................................24
8.1 SERIAL PRINTER ........................................................................................................................................................24
8.2 CLOCK BOARD ..........................................................................................................................................................24
9 APPENDIX A: TROUBLESHOOTING .......................................................................................................................25
OPERATING LIMITS
The McQuay sequencer is capable of controlling a system of Chillers or Heat Pumps, installed in a single
system, in order to control the common leaving water temperature of the evaporators, for improved and
complete system management.
The McQuay sequencer can control up to a maximum of 10 units installed in a single system,
The control point is a temperature probe installed in the common leaving water pipe from the units,
reference ELWT (Evaporator Leaving Water Temperature)
The McQuay sequencer also has a second temperature probe CWTR (Cooling Tower Water Return)
capable of controlling the cooling tower steps in the case where some water-condensed refrigerators are
installed in the system (series WHR, WHS, PFS, WHZ, PEH, PFH, WSC, WDC).
In the case where a CTWR probe is installed, the number of units which can controlled is limited,
The sequener can only control a maximum number of 10 devices.
Example:
a) Up to 10 air-cooled units (ALS, ALR, AGR, ALZ) without any added control requiring the
use of digital outputs.
b) In the case where cooling tower control is required, the maximum number of units
controlled cannot exceed 10 minus GT,
GT being the number of Tower Steps to be controlled.
c) In the case where cooling tower control by inverter is required (without added On/Off
steps), the maximum number of units controlled is 10.
d) In the case where control of a bypass valve on the cooling circuit is required, as well as
tower step control, the maximum number of units that can be controlled is 10 minus GT,
GT being the number of Tower Steps to be controlled.
2) Load limiter: With an external signal of 4-20mA, it is possible to limit the number of
refrigerators in terms of limiting electrical absorption at certain periods of the day.
The number of units set will be subdivided proportionally in terms of the external
signal set. The system divides the difference between the maximum and minimum
signal (20-4 = 16 mA) by the number of refrigerators set in the controller and the
enables/disables for each increase in signal sent.
2 USER INTERFACE
2.1 Keyboard-display terminal: front panel view with front door closed
Figure 1 references
COMPRESSORS
1. External function-indicator LEDs
Bar Bar FANS
2. Rubber external buttons
°C °C SET 2
3. LED display
°F °F
SET EXT 4. Front window
NETWORK
Figure 1
Figure 2
References Figure 2
1. On/off button: turns the unit on and off. When the unit is on, the LED button is lit (a green colour)
- an unlit LED indicates that the unit is OFF;
- a flashing LED indicates that the unit has been turned off by a supervisor or by remote control, by means of a digital
input;
2. Alarm button: it is used to display the alarms, to reset them manually and to silence the buzzer.
If the button is lit (red), it means that at least one alarm has been detected.
3. The arrow pointing upwards sets the values of the control parameters (not back lit), or to disable manual procedure.
4. The arrow pointing downwards sets the values of the control parameters (not back lit), or to disable manual procedure.
5. Enter button: to scan the messages on the display. The button is continuously lit (yellow light) and indicates that the
power is On.
2.3 Front view with front door open
COMPRESSORS
Figure 3 references
FANS
Bar Bar
°C °C SET 2
1. Polycarbonate - coated mechanical buttons
°F °F
SET EXT
3. Adhesive polycarbonate
4. Silicone rubber buttons.
Figure 3
2.4 Use of the buttons
permits display of values detected by the probe ELWT (cooled water) and by probe CTWR (cooling water)
permits access to the values related to the hour counters, to the manual procedure of the devices connected
and to probe setting
gives access to the set of parameters for operating the printer (where required)
permits display of the status of inputs and outputs, both digital and analogue
permits display/programming of the clock (if present) and of related time bands with setpoint variation
permits setting of the various operating parameters (protections, thresholds), as well as the parameters relating
to unit configuration
The LEDs beside the listed buttons light up when pressed, and remain in this status until any one of the above-mentioned
buttons is pressed.
1
2.5 Display
COMPRESSORS
FANS
Bar Bar
°C °C SET 2
°F °F
SET EXT
NETWORK
Figure 4
Features
• number of digits: 6
• colour: green
• height: 13mm
• number of side indicator LEDs: 5
• number of LEDs indicating the displayed function: 3+3
The 6 LEDs placed in the display indicate the unit of measure of the values detected by the two linked probes (settings made
in the programming-code section):
2
3 LIST OF PARAMETERS
All parameters in boldface are described from page 12
In the following tables there are two Default columns: in the right column there are the values determined by McQuay. Default
values are stored in the memory of every system (see page 21). In the left column the user may write his/her own values as
a memo.
Maintenance button
3
Printer button
I/O button
Clock button
4
5
C10 year setting 0 0÷99
C11 band start hour with secondary set 0 0÷23 h
C12 band end hour with secondary set 24 0÷24 h
C13 Sunday with secondary set 0 0→no; 1→yes
C14 Monday with secondary set 0 0→no; 1→yes
C15 Tuesday with secondary set 0 0→no; 1→yes
C16 Wednesday with secondary set 0 0→no; 1→yes
C17 Thursday with secondary set 0 0→no; 1→yes
C18 Friday with secondary set 0 0→no; 1→yes
C19 Saturday with secondary set 0 0→no; 1→yes
C20 half a day exclusion 0 0÷7
C21 exclusion start 0 C11÷C12 h
C22 exclusion end 0 C21÷C12 h
Setpoint button
6
Programming button
7
P39 °C or °F display 0 0→°C;→°F
P40 remote on/off enable 1 0→disable 1→enable
P41 clock enable 1 0→disable 1→enable
P42 printer enable 0 0→disable 1→enable
P43 identification number 1 0÷999
P44 automatic or manual reset alarms 0 0→autom. 1→manual
P45 alarm relay operation delay 0 0÷999 min
P46 ON/OFF button disable with machine ON 0 0→disable 1→enable
P47 serial communication baud-rate 1 0→1200 1→2400
2→4800 3→9600
4→19200
P61 machine stop mode 0 0→full 1→partial
P62 cold/hot 0 0→cold 1→hot
Info button
8
4 ALARM DESCRIPTION
For description of how to control Alarms, see parameter P44 on page 18
Alarm button
9
5 DESCRIPTION OF PARAMETERS
t1÷t12 - refrigerator hour display
These parameters indicate the number of operating hours of the individual refrigerators. When displaying these parameters, the
identification number code alternates, every two seconds, with the number of operating hours of the refrigerator corresponding to the
code.
T 1 NUMBER OF HOURS:
IDENTIFICATION CODE
0 3 5 1 7 8
MOST SIGNIFICANT PART LEAST SIGNIFICANT PART
When the number of operating hours of the individual refrigerator exceeds the operating hour threshold (th), indication is given by
alarms AL 1 ÷ AL 12. Caution: when the analogue outputs dedicated to the fan inverter and to the device 1/valve inverter are used
(parameters t11 and t12), the displayed operating hours refer to the calculation with the corresponding outputs at a value higher
than 0 volt.
th - operating hour threshold
When the operating hours of the refrigerator exceed this value, an alarm signal is produced, indicating that maintenance of
the refrigerator is needed. If this parameter is given the value 0, this control is automatically excluded.
Caution. setting must be made in h x 1000.
n1÷n12 - manual operation of the refrigerators
These parameters permit manual activation of the individual device, without the help of timers, rotation, and independently of the
values measured by the probes. The sole support of control in manual operation is alarm management. Manual activation of the
inverter devices makes it possible to force their analogue outputs to the value of 10 volts. The manual procedure can be activated
only if the unit is OFF. Therefore, all the parameters n1÷n12 are not enabled if the unit is ON. The flashing LED of the menu button
indicates that the manual procedure is enabled. If, after pressing the menu button, the “Up” button or “Down” button, is kept pressed
down for more than 2 seconds, the whole manual procedure is disabled. In any case, the manual procedure is automatically
completed after 30 minutes.
CL1, CL2, CL3 - probe calibration
These parameters allow software calibration of the probes ELWT, CTWR and OAT. The value given to these parameters is
actually added (positive value) or subtracted (negative value) to the measurements detected by the respective probes. The
offset of calibration may be changed from -5.0 to +5.0 with the accuracy of one decimal point. The CL3 parameter is visible
only when the relative probe OAT (P22=1) has been selected.
Pr1 - immediate printing request
This parameter allows the printout of the unit ‘s main data such as: values detected by the probes, active devices and the
setpoints programmed.
Pr2 - cyclic printing time
This parameter indicates the cyclic printing time, i.e. the T period between one printout and the next.
Ai3 - meaning of the analogue input B3 (see figure 30).
This parameter allows the display of the value detected by the third analogue input that can be:
- variable setpoint by using a potentiometer (P21=1);
- if the parameter is P21=0 and P22=1, then the detected value represents the temperature probe of the ambient air
(necessary for controlling the setpoint compensation).
i11 - digital input ID11 (see figure 30).
This parameter allows the display of the status of digital input no.11. This input can be:
- the shutdown of device no.11 if it has been previously selected;
- the shutdown of the fan inverter if device no.11 has not been selected.
C11=C12 - selection of the start and end time of the reduced setpoint.
The parameter C11 allows the start of time bands with reduced setpoint to be set; the parameter C12 makes it possible to set
the end hour. Examples:
- Time band during the day. C11=12, C12=16: the reduced setpoint is enabled from 12:00 a.m. to 3:59 p.m.;
- Time band between two successive days. C11=14, C12=9: the reduced setpoint is enabled from 2:00 p.m. to 8:59 a.m. of
the following day;
- C11=C12: the reduced setpoint is enabled throughout the whole day (24 hours).
IMPORTANT: Never set the value C11=C12=0.
C20= selection of the day with time band exclusion.
The parameter allows time band exclusion with secondary setpoint for a selected day. The start hour (C21) and end hour
(C22) are programmable. The data that can be selected are the following:
0 time band exclusion not enabled;
1 time band exclusion with secondary set for the day of Monday;
2 time band exclusion with secondary set for the day of Tuesday;
3 time band exclusion with secondary set for the day of Wednesday;
4 time band exclusion with secondary set for the day of Thursday;
5 time band exclusion with secondary set for the day of Friday;
6 time band exclusion with secondary set for the day of Saturday;
7 time band exclusion with secondary set for the day of Sunday.
C21 - time band exclusion start.
The start of time band exclusion with secondary set is required (see parameter C20).
10
C22 - time band exclusion end.
The end of time band exclusion with secondary set is required (see parameter C20).
Caution: do no enable at the same time the time bands with reduced setpoint and regulation of setpoint from analogue input
because both options have priority over the setpoint set.
St3, St5 - minimum setpoint
They establish the minimum value that can be set for the setpoints. The user is prevented from entering a setpoint lower than
the value St3( ELWT) and a setpoint lower than the value St5. (CTWR)
St4, St6 - maximum setpoint
These points establish the maximum value that can be set for the setpoints. The user is prevented from entering a setpoint
higher than the value St3( ELWT) and a setpoint higher than the value St5. (CTWR).
St7 - secondary setpoint
Allows setting of secondary setpoint, that is valid when time bands are enabled.
d1, d2 - device differentials
These parameters establish the values of the differentials of the devices managed by probe ELWT and CTWR .
setpoint
differential
Figure 5
Volt
10
0
setpoint
differential value measured
Figure 6
Where either d3 or d4 are concerned, the differential refers to the device 1/valve inverter or to the fan inverter respectively.
These parameters are visible only if the outputs for the inverter (P20=1 and P35=1) are provided for. Furthermore, in the
case of the circuit 1/valve inverter, the side band control must be selected (P14=1).
Sr1 - device 1 inverter step (see figure 14).
The parameter is visible only if the presence of the inverter on device 1 has been selected, and also control is in neutral
zone. It establishes the increase and decrease of device 1 inverter (see parameter P20).
Sr2 - device 1 inverter deviation (see figure 14).
The parameter is visible only when the presence of the inverter on device no. 1 has been selected, and control is in neutral
zone. It is essential for calculating device no. 1 inverter connection (see parameter P20).
Sr3 - minimum opening of device 1/valve inverter.
The parameter is visible only when the presence of the inverter on device no.1/valve has been selected. This parameter
makes it possible to apply a minimum voltage to the inverter/valve output. If the conditions require application of a value
below Sr3, this value is compulsory.
Sr4 - minimum opening of device 1/valve inverter continuously applied.
The parameter is visible only when the presence of the inverter on device no.1/valve has been selected (parameter P20). If
SR4 is equal to 1, the minimum opening of device 1/valve inverter (parameter Sr3) is applied even in case of an alarm being
present on this device or when (if P14=0) compressor 1 is OFF. Only when the unit is OFF does the output of the
inverter/valve remain at 0 in all cases.
SH1, SH2 - high temperature alarm threshold
It represents the threshold of high of probe ELWT and CTWR respectively. When the value detected by the probe exceeds
the set value, the alarm is activated.
11
SL1, SL2 - low temperature alarm threshold
It represents the threshold of low of probe ELWT and CTWR respectively. When the value detected by the probe falls below
the set value, the alarm is activated.
SC, dC, dt - setpoint, differential and compensation delta
See parameter P23.
P1, P24 - probe type
The parameters make it possible to specify the type of probes used. The following selections are available.
0 probe is absent;
2 temperature NTC probe;
P4 - number of refrigerators controlled by probe ELWT
The parameter represents the number of refrigerators controlled by probe ELWT. The number of refrigerators may range
from 0 to 11. If 11 devices are selected, it is not possible to connect any cooling tower step to the secondary circuit.
P5 - number of refrigerators operating with probe ELWT out of order
In the case where the alarm of probe ELWT is found to be broken or not connected (AL14), parameter P5 indicates the
minimum number of refrigerators ON.
P9 - choke operation in full/part mode (not enabled)
P10 - minimum refrigerator operating time
This sets the minimum refrigerator operating time (in seconds). As a consequence, when enabled, the devices must remain ON
for the same length of time as the one set by the above-mentioned parameter.
connection
ON
request OFF
device
ON
OFF
P10
Figure 7
12
P11 - minimum refrigerator stop time
This sets the minimum refrigerator stop time. The refrigerators are not started again unless the minimum time set from the
last stop time has elapsed.
connecti
ON
on OFF
device
ON
OFF
P11
Figure 8
device 1 ON
OFF
device n ON
OFF
P12
Figure 9
connecti
ON
on OFF
device
ON
OFF
P13
Figure 10
3 devices
on a single circuit
dev. 1 dev. 2 dev. 3
setpoint differential value detected
Figure 11
In neutral zone there is a zone where no refrigerator is activated or deactivated.
The activation point of the refrigerators is when the measure detected exceeds the neutral zone (measure
detected>set+differential). The number of refrigerators to be activated is variable, depending on the time elapsed in this
condition. The refrigerators are stopped when the measure detected falls below the neutral zone (measure detected <set),
and in this case too it depends on the time. See timers P17, P32 and P18, P33.
connection
neutral zone
dev. 3
setpoint dev. 2
dev. 1
13
P16, P31 - integration time
These parameters indicate the integration time of circuits ELWT and CTWR, if a Proportional + Integral regulation has been
selected (P15=1 and/or P30=1).
P17, P32 - minimum refrigerator startup request time
These parameters allow the setting of the time between successive requests for startup of the refrigerators controlled by
probes ELWT and CTWR.
They are present only if control is in neutral zone.
P18, P33 - minimum refrigerator stop request time
These parameters allow the setting of the time between successive requests for stop of the refrigerators controlled by probes
ELWT and CTWR. They are present only if control is in neutral zone.
P19 - refrigerator rotation enable
This parameter allows the rotation type to be selected
0= rotation disabled: last refrigerator to be started up is first to be stopped.
1= "FIFO" rotation: first refrigerator to be started up is first to be stopped; machines are stopped in order of startup.
2= "in-time" rotation: first refrigerator to be started up is the one with the lowest number of operating hours, the first to be
stopped is the one with the highest number of operating hours.
P20 - selection of device no. 1/valve inverter
This parameter enables the presence of the inverter on device no.1 of circuit 1, controlled by probe 1, or of a 0-10 Volt valve,
depending on the presence of neutral-zone or lateral-band regulation.
This is displayed if P1>0 and P4>0 and if chokes (P6>0) and Neutral Zone (P14=0) have not been enabled at the same time.
Therefore the parameter is displayed if: P1>0, P4>0, P6=0, P14=0;
P1>0, P4>0, P6>0, P14=1.
Volt
10
0
setpoint value detected by
device differential device 1 probe 1
Figure 13
neutral zone
devices
setpoint value detected by
neutral zone differential neutral probe 1
zone devices
device 1 inverter
deviation inverter increase zone
inverter neutral
value detected by
inverter decrease zone zone probe 1
Figure 14
Caution: when device no.1/valve inverter is enabled and regulation takes place with neutral zone, activation of the devices
occurs as follows:
- device no.1, which is controlled by the inverter, is activated as soon as startup is requested;
- if the request remains, the output of device no.1 inverter is increased;
- if the request is still present, and the output of the inverter reaches 10 Volts, the other devices are requested, one at a
time, with rotation (if selected) and according to the timers.
The stop stage occurs as follows:
- the inverter output is decreased;
- when the inverter output has already reached 0 Volts, the other devices are stopped, one at a time, according to the
timers and rotation;
- the last device that is stopped is no.1.
14
P21 - function not enabled
compensation
delta
external air
compensation differential temperatur
compensation setpoint e
Figure 15
Volt
1
0
0
inverter value detected by
setpoint differential inverter probe 2
Figure 16
15
P43 - identification number
The parameter allows the setting of the unit identification number (useful only in case of connection to a system of
supervision and/or remote assistance).
P44 - alarms with automatic or manual reset
P44=0 ⇒ automatic. In the event that one or more alarm conditions are detected, these are indicated by:
- red LED below “alarm” key lit;
- buzzer activated;
- alarm relay (switching relay normally on) opens
Pressing “alarm” key silences the buzzer and the alarm codes are displayed. If the causes of the alarms are reset, the status
of the indication alarm relays becomes:
- alarm relay disconnects (switches from NO a NC);
- the buzzer, if it has not been disconnected by pressing “alarm” button, is de-activated;
- red LED below “alarm” button flashes.
If in this situation new alarms are operated, the initial situation is shown.
The flashing red LED tells the user that there have been alarms during the day and that now these have already been
restored. The codes of the alarms remain, however, in the memory, so that, by pressing the “alarm” button, they can be
displayed. If after having displayed them, the “alarm” button is pressed again, they are cancelled and the red LED also finally
goes out.
P44=1 ⇒ manual. In the event that one or more alarms are detected, they are indicated by:
- red LED below “alarm” button lit;
- buzzer activated;
- alarm relay (switching relay normally on) opens
Pressing the “alarm” button silences the buzzer and alarm codes are displayed.
If the causes of the alarms are reset, the flashing red LED tells the user that there have been alarms during the day, and that
they have already been restored. In this situation the alarm relay remains with contact NC closed to indicate fault.
If in this situation new alarms are operated, the initail situation is shown.
Cancellation is made by pressing “alarm” during alarm message display. If the causes have actually been cancelled, the
status of the indication devices becomes:
- alarm relay disconnects (switches from NO a NC);
- the buzzer, if it has not been silenced yet by pressing “alarm” button, is de-activated;
- red LED below “alarm” button is disconnected.
On the other hand, if the causes of the alarms have not been cancelled, the initial situation is shown.
P45 - delay in activating alarm relay
The parameter allows the user to set a delay time (in minutes) between the activation of any alarm and the start of the
indication relay (digital output no.11). If P45 is set at 0, alarm relay activation is immediate.
P46 - “On-Off” button disable from refrigerator ON
This parameter makes it possible to disable the operation of the “on-off” button for disconnecting the unit. If parameter 46 is
set at 0, the “on-off” button can either connect or disconnect the unit; if parameter 46 is set st 1, the “on-off” button can only
connect the unit.
P47 - serial communication baud-rate
This parameter permits the serial communication baud-rate to be selected. When the RS485 serial board is connected it is
possible to choose the data transmission speed :
0 1200 baud
1 2400 baud
2 4800 baud
3 9600 baud
4 19200 baud.
16
P61 - not enabled
P62 - cold/hot
With this parameter it will be possible to decide whether the devices belonging to circuit ELWT are used to produce cold
(P62=0; e.g. refrigerators) or hot (P62=1; e.g. heat pumps).
pressure or
differential pressure or differential
set set temperature
temperature
request switch on
devices
request switch on
devices
set set
differential pressure or differential pressure or
temperature temperature
17
AL14, AL15, AL34 - probe not operating
The relevant probe is broken or not connected. Check the wiring and functional capacity of the probe.
If AL14 is present, the devices programmed with the P5 parameter are forced to start up, and the inverter of device
no.1/valve, if enabled, is forced to 10 volts. The remaining devices can be switched on according to the value measured by
probe 1. If AL15 is present all the devices connected to circuit 2 are forced to switch on and the fan inverter is forced to 10 volts.
If AL34 is present, the compensation (if enabled) does not operate. These alarms can only be reset manually, and so they do
not reset until the user presses the alarm button on the pCO terminal in order to clear the alarms.
AL17 - flow regulator
Alarm message AL17 indicates water flow alarm.
AL33 - selected refrigerator number incorrect
If the sum of the number of refrigerators of the primary and secondary circuit exceeds the number of outputs actually
available, alarm AL33 is generated.
PSt, PSC, PSS, Psn - password
These four codes listed refer to the Passwords of the Maintenance, Clock, Setpoint and Programming branches respectively.
For each of the sections listed, the number to be set in order to have access to the subsequent parameters is:
- xxx (Maintenance, Clock, Setpoint);
- xxx (Programming).
Main display: Menu
After pressing the Menu button the probe ELWT reading is displayed on the left side of the display, whereas on the right side
of the display the probe CTWR reading is displayed. If one of two probes has not been selected (P1=0 and/or P24=0), the
symbol “----” appears instead of the reading. The LED located on the left of each display lights up beside the unit of
measurement (ºC , ºF) corresponding to the type of probe selected.
Initial Lamp-Test
Whenever the pCO is powered up, the display lights up all its LEDs and shows the figures “8.8.8. 8.8.8.” for a few seconds.
After the Lamp-Test the probe readings are displayed and only the LEDs required for the operation are lit. During this
procedure it is possible to check whether all the LEDs are operating.
Setting of negative parameters
Many parameters that can be set from the terminal may have negative values. When these parameters are included between
“-99” and “-10” it is impossible to set the decimal value. Therefore the whole value without decimal is always accepted. From
the control monitor, on the other hand, it is also possible to set the decimal value.
For this reason, when selecting from the control monitor negative parameters with values between -99 and -10, it is
necessary to set only values with 0 as the decimal part.
Installation of the Default Values _
automatic installation: in the software a control is implemented that carries out automatic installation of the
default values when the initial programme startup is carried out or when the EPROM is substituted
for another different version (check the version and date indicated on the EPROM label);
manual installation: if the user wants to reprogramme the unit, he must put it into the OFF status. Afterwards
he must press simultaneously the MENU+PROG buttons until the letters “rST 0” appear. By
pressing 5 or 6, the symbol “8.8.8. 8.8.8.” is displayed and all the LEDs stay lit for a few
seconds and in the meantime the software installs the default values.
18
6 CONNECTIONS
For an exhaustive description of the hardware and of the installation procedure please refer to the Microtech II “Installation
and Usage manual", available on request.
Terminal
with LED or LCD display
programme eprom
Connector
for RS422
Connection cable
serial board
Connector
for clock board
Main board
with screw or plug-in terminals
Figure 17
19
6.2 Main board - Layout
Below is a description of the sequencer main board with reference to the basic layout.
6
1
4
7 1J
G 1
G0
7
14
J9 J8
8 1J
J29 J28
B8
15
19 + 2 4Vc c
1J
1 B7
17 18
2 5
9 1J
3 16 B6
A V SS
B5
B4
12
J 15 J14
A V SS
2J
1
B3
VG 0
0 2J
B2
VG 1
13 Y1
Y0 1
A V SS
B1
ID 1 1 -2 2 0 Va c 1 ID C M 2
ID 1 1 -2 4 Va c ID 1 0
ID 1 1 -C o m ID 9
11 3J
1 2J
- - -- - -- - ID 8
ID 1 2 -C o m ID 7
ID 1 2 -2 4 Va c 1 ID 6
ID 1 2 -2 2 0 Va c
ID C M 1 10
1 ID 5
NO 11
ID 4
C 11
ID 3
4J
NC 11
ID 2
-- - -- - -
1 ID 1
2 2J
NO 10
C 10
NC 10 C1
-- - -- - - NO 1
NO 9 -- - -- -
5J
C9 C2
NC 9 1 NO 2
9 NO 8
1 C3
C8 NO 3
-- - -- -
NO 7
-- - -- -
C4
9
C7 NO 4
4 2J
-- - -- - -- - -- -
N06 C5
6J
C6 NO 5
-- - -- - -- - -- -
N013 C 12
C 13 NO 12
1
Figure 18
The main board is the basic core of the controller ; inside it 3 different parts can be identified:
20
Figure 18 references, page 22
1. Power supply connector 24V~50-60 Hz 15VA or 24V 10W (see note on page 28)
2. Telephone-type connector for connection to the user terminal (MMI-Man Machine Interface)
3. Real-time clock board (optional)
4. RS422/RS485 optoinsulated board (optional) for connection to a monitoring remote assistance serial line
5. Pin strip for analogue-input adapter boards that may be set up, upon request only
6. EPROM containing application programme
7. Jumpers to select the local network communication modes
J8 in position 1-2 allows connection of the board to a terminal and, possibly, to the control monitor; in position 2-3 only
connection to the local network is enabled
J9 in position 1-2 enables control monitor to be able to reset the board, in position 2-3 makes board independent of reset
action of control monitor
The interface boards purchased from McQuay have both jumpers in position 1-2
Caution: this EPROM does not support “local network” control
8. Fuse 230 V~, 2A delayed
9. Digital outputs (switchable power 2300VA, 10A/230V~):
NO(n): Output contact normally open (n)
NC(n): Output contact normally closed (n)
C(n): Common contact for output contact (n)
10. Digital inputs (24V~, 10mA)
ID(n): Digital inputs 1÷10
IDCM1: Common reference for digital inputs 1÷5
IDCM2: Common reference for digital inputs 6÷10
11. Digital inputs (230V~, 10mA)
ID11, ID12: Digital inputs 11 and 12
ID11R, ID12R: common reference for the digital inputs ID11 and ID12 respectively
12. Analogue inputs
B(n): Analogue input 1÷8
AVSS: Common reference of analogue inputs B(n)
13. Analogue outputs 0÷10 V
Y(n): Analogue outputs 1 and 2
VG1: External power supply for analogue outputs (24V~ or 24V )
VG0: Reference for power supply and signal of analogue outputs Y0 and Y1
14. Mains ON LED
15. Analogue inputs
B(n): analogue inputs 7 and 8
+24 Vcc: Power supply for external active probes 24V (n) current
16. Jumper J15 selecting analogue input B6 in 0÷1 V or 4÷20 mA (1-2=4÷20 mA, 2-3=0÷1 V )
17. Jumper J14 selecting analogue input B5 in 0÷1 V or 4÷20 mA (1-2=4÷20 mA, 2-3=0÷1 V )
18. Jumper J28 selecting analogue input B7 in 0÷1 V or 4÷20 mA (1-2=4÷20 mA, 2-3=0÷1 V )
19. Jumper J29 selecting analogue input B8 in 0÷1 V or 4÷20 mA (1-2=4÷20 mA, 2-3=0÷1 V )
21
7 MEANING OF INPUTS AND OUTPUTS
Power supply
CONNECTOR SIGNALS DESCRIPTION
J17 – 1 G Power supply + 24 V 10 W or 24V~50/60 Hz 15 VA (see note on
page 28)
J17 – 2 G0 Power supply reference
J1 – 2 +24 Power supply for external active probes 24 V (max. power that can
be supplied: 80mA
Connection with terminal
CONNECTOR SIGNALS DESCRIPTION
J19 Terminal 6-way telephone cable connection with terminal
Analogue inputs
CONNECTOR SIGNALS DESCRIPTION
J2 – 1 B1 Probe ELWT (only when probe is NTC passive type)
J2 – 2 AVSS Common analogue inputs
J2 – 3 B2 Probe CTWR (only when probe is NTC passive type)
J2 – 4 B3 OAT Probe
J2 – 5 AVSS Common analogue inputs
J2 – 6 B4 Remote on/off (optional)
J2 – 7 B5 Not used
J2 – 8 AVSS Common analogue inputs
J2 – 9 B6 Not used
J1 B7 External setpoint reset
J1 B8 Load limiter
Digital inputs
CONNECTOR SIGNALS DESCRIPTION
J4 – 1 ID1 Refrigerator 1 alarm
J4 – 2 ID2 Refrigerator 2 alarm
J4 – 3 ID3 Refrigerator 3 alarm
J4 – 4 ID4 Refrigerator 4 alarm
J4 – 5 ID5 Refrigerator 5 alarm
J4 – 6 IDCM1 Digital common inputs ID1-ID5
J3 – 1 ID6 Refrigerator 6 alarm
J3 – 2 ID7 Refrigerator 7 alarm
J3 – 3 ID8 Refrigerator 8 alarm
J3 – 4 ID9 Refrigerator 9 alarm
J3 – 5 ID10 Refrigerator 10 alarm
J3 – 6 IDCM2 Digital common inputs ID6-ID10
J21 –1 ID11-230Vac Common digital input ID11 at 230 V~ or 24 V~
J21 – 2 ID11-24Vac Fan inverter lock – 24 V~ digital input
J21 – 3 ID11 - Com Fan inverter lock – 230 V~ digital input
J21 – 4 Not connected
J21 – 5 ID12 - Com Common digital input ID12 at 230 V~ or 24 V~
J21 – 6 ID12-24 Vac Digital input flow regulator at 24 V~
J21 – 7 ID12-230 Vac Digital input flow regulator at 230 V~
Digital outputs
CONNECTOR SIGNALS DESCRIPTION
J22 – 1 NO11 General alarms - contact normally open
J22 – 2 C11 Common general alarms
J22 – 3 NC11 General alarms - contact normally closed
J22 – 4 Not connected
J22 – 5 NO10 Refrigerator 10 - contact normally open
J22 – 6 C10 Common device 10
J22 – 7 NC10 Refrigerator 10 - contact normally closed
J22 – 8 Not connected
J22 – 9 NO9 Refrigerator 9 - contact normally open
J22 – 10 C9 Common device 9
J22 – 11 NC9 Refrigerator 9 - contact normally closed
J24 – 1 NO8 Refrigerator 8 - contact normally open
J24 – 2 C8 Common refrigerator 8
J24 – 3 Not connected
J24 – 4 NO7 Refrigerator 7 - contact normally open
J24 – 5 C7 Common refrigerator 7
22
J24 – 6 Not connected
J24 – 7 NO6 Refrigerator 6 - contact normally open
J24 – 8 C6 Common refrigerator open
J24 – 9 Not connected
J24 – 10 NO13 Not connected
J24 – 11 C13 Not connected
J6 – 1 NO12 Refrigerator 11 - contact normally open
J6 – 2 C12 Common refrigerator 11
J6 – 3 Not connected
J6 – 4 NO5 Refrigerator 5 - contact normally open
J6 – 5 C5 Common refrigerator 5
J6 – 6 Not connected
J6 – 7 NO4 Refrigerator 4 - contact normally open
J6 – 8 C4 Common refrigerator 4
J6 – 9 Not connected
J6 – 10 NO3 Refrigerator 3 - contact normally open
J6 – 11 C3 Common refrigerator 3
J5 – 1 NO2 Refrigerator 2 - contact normally open
J5 – 2 C2 Common refrigerator 2
J5 – 3 Not connected
J5 – 4 NO1 Refrigerator 1 - contact normally open
J5 – 5 C1 Common refrigerator 1
Analogue ouputs 0-10 Vdc
CONNECTOR SIGNALS DESCRIPTION
J20 – 1 VG0 Reference signal Y0
J20 – 2 VG1 Reference signal Y1
J20 – 3 Y1 Inverter
J20 – 4 Y0 Inverter
G
G
24V~ / 24V 0
J1
7
23
Installation of EPROMs
Before connecting / disconnecting the EPROM, shut down power to Microtech II board. For correct operation of the system,
the EPROM must be connected to the appropriate socket on the main board, ensuring that the “notch” on the surface of
the EPROM matches one marked on the socket.
Connect the EPROM to the corresponding main board socket, checking that all the pins are correctly inserted into their slots.
When removing the EPROM be careful not to touch the SMD components
mounted on the board in the space inside the socket.
IMPORTANT: Electrical damage that occurs on the electronic components is usually due to electrostatic discharges
caused by the operator. The utmost care is therefore needed when using this kind of component, and particularly:
• before handling any electronic component or card, touching an earth contact (not touching the materials is not enough,
since a discharge of 10000 V, a voltage very easily reached with static electricity, produces an arc of about 1 cm);
• as far as possible, materials should be left inside their original packaging. If it is necessary to remove the main board from
a pack, transfer the product to an antistatic pack without touching the rear of the board with your hand;
• as far as possible avoid using plastic bags, polystyrene or non-antistatic sponges;
• take only one EPROM at a time out of the original antistatic packs;
• avoid touching the pins of the EPROM with your hands.
This figure shows the real time clock board, code CLK0000000, which allows current date and
time to be displayed.
In the event that time bands are to be used (in programmes that control them), this board is
essential.
When there is no power supply to the pC0, the rechargable lithium battery (45 mA/h; 12 h
maximum charge time), keeps the check board operational for over one month.
24
9 APPENDIX A: TROUBLESHOOTING
Unit does not start (mains ON LED on main board is off, LCD is off, other LEDs are off).
Check:
a) that there is mains voltage;
that downstream of the 230V~ - 240V~ power voltage transformer there are 24V~;
b) that 24V~ power connector has been correctly plugged in;
c) that protection fuse is intact (Figure 18);
d) that telephone connection cable between terminal (if present) and main board has been correctly connected.
25
Notes: ___________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
________________________________________________________________________________
___________________________________________________________________________________________
26
27
Agenzia / Agency: