Unit 2 19-20 Online
Unit 2 19-20 Online
1
2
The functions of an excitation system:
2.
3
a)Generator considerations:
4
b)Power system considerations:
contribute to effective control of system voltage and improvement of system
stability.
5
1. Meet specified response criteria.
2. Provide limiting and protective functions are required to prevent damage to
itself, the generator, and other equipment.
3. Meet specified requirements for operating flexibility
4. Meet the desired reliability and availability, by incorporating the necessary
level of redundancy and internal fault detection and isolation capability.
6
ELEMENTS OF EXCITATION SYSTEM
7
ELEMENTS OF EXCITATION SYSTEM
Exciter: provides dc power to the generator field winding
Regulator: processes and amplifies input control signals to a level and form appropriate for
control of the exciter
Terminal voltage transducer and load compensator: senses generator terminal voltage,
rectifies and filters it to dc quantity and compares with a reference; load compensator may be
provided if desired to hold voltage at a remote point
Power system stabilizer: provides additional input signal to the regulator to damp power
system oscillations
Limiters and protective circuits: ensure that the capability limits of exciter and generator are
not exceeded
8
Exciter System
The main objective of the excitation system is to control the field current of the
synchronous machine.
The field current is controlled so as to regulate the terminal voltage of the machine.
As the field circuit time constant is high (of the order of a few seconds), fast control of
the field current requires field forcing.
Thus exciter should have a high ceiling voltage which enables it to operate transiently
with voltage levels that are 3 to 4 times the normal.
The rate of change of voltage should also be fast. Because of the high reliability
required, unit exciter scheme is prevalent where each generating unit has its
individual exciter.
There are three distinct types of excitation systems based on the power source for
exciter.
1. DC Excitation Systems (DC) which utilize a DC generator with commutator.
2. AC Excitation Systems (AC) which use alternators and either stationary or rotating
rectifiers to produce the direct current needed.
3. Static Excitation Systems (ST) in which the power is supplied through transformers
and rectifiers.
The first two types of exciters are also called rotating exciters which are mounted on the
same shaft as the generator and driven by the prime mover. 9
10
11
MODERN CONTROL AND PROTECTIVE FUNCTIONS
12
13
1. AC Regulator and DC Regulator
AC Regulator:
Basic function is to maintain generator stator voltage
In addition, other auxiliary control and protection functions act through the ac
regulator to control generator field voltage.
DC Regulator:
It is holds constant generator field voltage and in commonly referred to as manual
control.
It is used primarily for testing and start-up, and when ac regulator is faulty.
In this mode of operation , it is the field voltage that is regulated; only operator
intervention by adjusting the set-point will modify the field voltage.(For manual )
In some excitation systems, facilities for automatic set-point tracking are provided.
2. Excitation System Stabilizing Circuits
Excitation systems with significant time delays have poor characteristic dynamic
performance.
This is particularly true of DC and AC type excitation system.
unless very low steady-state regulator gain is used, the excitation control action is
unstable when generator is on open-circuit.
Therefore, excitation control system stabilization, comprising either series or feedback
compensation is used to improve the dynamic response of the control system . 14
The input signal for PSS is derived from speed/ frequency, or accelerating
power or a combination of these signals.
The objective of PSS is to provide damping of the rotor oscillations
whenever there is a transient disturbance.
Power system dynamic performance is improved by the damping of the
rotor oscillations .
15
16
with RC and XC positive, the compensator regulates a voltage at a point
within the generator; and provides voltage droop.
used to ensure proper sharing of reactive power (VARs) between generators
bussed together at their terminals , sharing a common step-up transformer.
Such an arrangement is commonly used with hydro units and cross-
compound thermal units.
17
With RC and XC negative, the compensator regulates voltage at a point beyond
the generator terminals.
Commonly used to compensate for voltage drop across step-up transformer
when two or more generator are connected through individual transformers
19
Volts per Hertz Limiter and Protection:
Used to protect generator and step-up transformer from damage due to
excessive magnetic flux resulting from low frequency and/or overvoltage
excessive magnetic flux, if sustained, can cause overheating and damage the
unit transformer and the generator core
Typical V/Hz limitations:
V/Hz limiter (or regulator) controls the field voltage so as to limit the
generator voltage when V/Hz exceeds a preset value
V/Hz protection trips the generator when V/Hz exceeds the preset value for
a specified time 20
Note: The unit step-up transformer low voltage rating is frequently 5% below
the generator voltage rating
Modeling of Excitation Systems
21
Excitation System Modelling
22
IEEE Type 1 can also represent the static excitation system by specifying the
following parameters KE = 1, TE = 0, SE = 0 and VRMAX = KpVT shows that the
upper limits on the regulator and exciter outputs are directly related to the
terminal voltage (Vr) of the generator.
26
3 Excitation System Stabilizer (ESS) and Transient Gain Reduction
(TGR)
This is used for increasing the stable region of operation of the excitation
system and permit higher regulator gains.
It is to be noted that feedback control systems, of which the excitation system
is an example, often require lead/lag compensation or derivative (rate)
feedback.
The feedback transfer function for ESS is shown in Figure
27
Realization of ESS
28
Transient Gain Reduction(TGR)
Here Tc is usually less than TB. Hence, this means of stabilization is termed
as Transient Gain Reduction (TGR).
The objective of TGR is to reduce the transient gain or gain at higher
frequencies, thereby minimizing the negative contribution of the regulator to
system damping.
However if Power System Stabilizer (PSS) is specifically used to enhance
system damping, the TGR may not be required. A typical value of the
transient gain reduction factor (TB /Tc) is 10.
29
4 Power System Stabilizer (PSS)
The stabilization provided by PSS is not to be confused with that by ESS.
While ESS is designed to provide effective voltage regulation under
open or short circuit conditions, the objective of PSS is to provide damping
of the rotor oscillations whenever there is a transient disturbance.
Its function is to suppress power system low-frequency oscillations or
increase system damping.
The damping of these oscillations (whose frequency varies from 0.2 to 2.0
Hz) can be impaired by the provision of high gain AVR, particularly at high
loading conditions when a generator is connected through a high external
impedance (due to weak transmission network).
Its basic principle is to provide the AVR with an auxiliary control signal to
make the generator produce an electrical torque in phase with the deviation
of rotor speed.
Mathematical Model of Power System Stabilizer
There are several forms of PSS. Here we give a commonly used block diagram of
a PSS transfer function as shown in Fig
30
1) Is the gain of PSS;‚
2) Is the measurement unit with a time Constant T6 (usually very small and
can be ignored);
3) ƒIs a wash-out unit or low frequency filter to block steady-state input signal
to disable PSS at steady-state operation.T5usually is as large as about 5 s.„
;
4) and (5)… ; are two lead-lag networks. PSS should consist of at least one lead-
lag network.† ;
(6) Is a limiter.
Input signal to PSS,VIS , usually is generator speed, terminal voltage, power,
system frequency, or combination of some of them. Output signal Vs is
superimposed on the AVR input signal.
For PSS to play an effective role, its installing location must be selected and
parameters be set properly.
31
32
Inclusion of Limits
There are two types of limiters
1. Windup Limiter
2. Non-Windup Limiter
As the behavior of these limiters are different, it is necessary to indicate the
type of the limiter in the block diagram using the convention shown in Figure
Windup limiter
Non-windup limiter
In the case of the windup limiter, the output variable (y) of the transfer
function is not limited and is free to vary. In this case the limiter can be treated
as a separate block whose input is y and the output is z. If
33
the equations with the windup limiter are
If
In the case of the non-windup limiter, the output of the transfer function is
limited and there is no separate block for the limiter. The equations in this case
are
Note that
1. Windup limiter can result in slow response as the output z of the limiter
does not change until y comes within the limits.
2. Generally, all integrator blocks have non-windup limits.
34
Excitation Systems-Standard Block Diagram
The second IEEE committee report published in 1981. distinguished
between the excitation systems based on their power source.
This classification is more logical and can avoid gross approximations in the
representation of different excitation systems.
1 DC Excitation System
Usually used for small generation units (100 MW or below) 35
The type DC 1 which represents field controlled DC commutator exciters
with continuously acting voltage regulators, is shown in Figure.
Figure : Type DC1-DC commutator exciter
This is similar to the IEEE Type 1 excitation system. The block with the
transfer function (1 + sTc)/(1 + sTB) represents Transient Gain Reduction
(TGR) as TB > TC·
TB and TC are time constants of the excitation regulator itself.
They are usually very small and considered to be zero.
This has the similar function as Excitation System Stabilizer (ESS)
which is used in the feedback path. Normally, either TGR (in the forward
path) or ESS is used. By choosing TB = TC, the TGR is neglected. Similarly by
36
choosing KF = 0, ESS is avoided.
2. AC Excitation System
Excitation system with an AC exciter is widely used for 100 MW or above
generation units.
Type AC 1 (Field controlled alternator rectifier, with non-controlled rectifiers)
excitation system is shown in Figure .
This signal VFE is proportional to the exciter field current. This signal is also used
as input to the Excitation System Stabilizer (ESS).
40
3 Static Excitation System
In these systems, transformers are used to convert voltage (and also current in
compounded systems) to the required level of the field voltage.
Controlled or uncontrolled rectifiers are used to provide the dc voltage for the generator
field.
Although negative field voltage forcing is used, many of the excitation systems used do
not permit negative field current.
This aspect is normally ignored in computer simulation but can be significant
sometimes (particularly in asynchronous operation).
As the exciter ceiling voltage tends to be high in static exciters, field current limiters
are used to protect the exciter and field circuit.
However, this protection is also not modelled except in special cases.
The block diagram of the potential source, controlled-rectifier excitation system is shown
in Figure
41
The internal limiter following the summing junction can be neglected, but field
voltage limits which are dependent on both VT and IFD must be considered.
For transformer fed systems Kc is small and can be neglected.
Figure depicts the general structure of a detailed excitation system model having
a one-to-one correspondence with the physical equipment.
While this model structure has the advantage of retaining a direct relationship
between model parameters and physical parameters, such detail is considered
too great for general system studies.
Therefore, model reduction techniques are used to simplify and obtain a
practical model appropriate for the type of study for which it is intended.
43
The parameters of the reduced model are selected such that the gain and phase
characteristics of the reduced model match those of the detailed model over the
frequency range of 0 to 3 Hz. In addition, all significant nonlinearities that
impact on system stability are accounted for. With a reduced model, however,
direct correspondence between the model parameters and the actual system
parameters is generally lost.
44
The type DC1A exciter model represents field controlled dc commutator
exciters, with continuously acting voltage regulators. The exciter may be
separately excited or self excited, the latter type being more common.
When self excited, KE is selected so that initially VR=0, representing
operator action of tracking the voltage regulator by periodically trimming
the shunt field rheostat set point.
The type AC4A exciter model represents an alternator supplied controlled rectifier
excitation system - a high initial response excitation system utilizing full wave thyristor
bridge circuit. Excitation system stabilization is usually provided in the form of a series
lag-lead network (transient gain reduction). The time constant associated with the
regulator and firing of thyristors is represented by TA. The overall gain is represented by
KA. The rectifier operation is confined to mode 1 region. Rectifier regulation effects on
exciter output limits are accounted for by constant KC.
47
4. Type ST1A exciter model
The type ST1A exciter model represents potential-source controlled-rectifier
systems.
The excitation power is supplied through a transformer from generator terminals;
therefore, the exciter ceiling voltage is directly proportional to generator terminal
voltage. The effect of rectifier regulation on ceiling voltage is represented by KC. The
model provides flexibility to represent series lag-lead or rate feedback stabilization.
Because of very high field forcing capability of the system, a field current limiter is
sometimes employed; the limit is defined by lLR and the gain by KLR.
48
49
Prime-Mover Control System
The regulation of frequency in the system requires the speed control of
prime-mover using governor. However, parallel operation of generators
requires a droop characteristic incorporated in the speed-governing system
to ensure stability and proper division of load. Hence, to maintain
constant frequency, an auxiliary control is required which responds to a
load unbalance.
Also, it is necessary for the prime-mover control to adjust the generation
according to economic dispatch.
52
Mathematical Model of Hydro-turbine and
Governing System
(1) Mathematical Model of Hydraulic Turbine
When the opening position of the wicket gate increases suddenly, water
volume at the wicket gate increases.
However, due to the water inertia, speed of water flow at other points inside the
pipe cannot increase immediately.
This results in input water pressure of the hydraulic turbine decreasing instead
of increasing for a short of period of time after the change, leading to a decrease
of input power of the hydraulic turbine instead of an increase.
On the other hand, when the opening position of the wicket gate decreases
suddenly, input water pressure and input power will increase temporarily and
then decrease. This phenomenon is usually called the water hammer effect.
54
Additionally we shall only consider an ideal hydraulic turbine, i.e.,
(1) Neglecting the mechanical power loss caused by the resistance against water
flow from the penstock wall;
(2) Power output of the hydraulic turbine being proportional to the product of net
water head and water flow volume; and
(3) Speed of water flow being proportional to the product of the opening position of
the wicket gate and square root of the stationary water head.
Hence we can obtain the hydraulic equations as follows:
Where
………….(1)
U = water velocity;
KU = proportional constant;
………….(2) H = net water head of hydraulic turbine;
µ= opening position of wicket gate;
………….(3) Pm = mechanical power output of hydraulic
turbine;
KP = proportional constant; g the gravity
acceleration constant;
L = length of penstock; and
H0 = steady-state value of H.
55
Taking the initial value of various variables as their base value, the above
hydraulic equations can be converted into the following per unit form
………….(4)
………….(5)
………….(6)
Where
………….(7)
………….(9)
………….(10)
The model above is called the classical model of a hydraulic turbine. Its
transfer function block diagram is shown in Fig
58
Assuming that the output steam flow is proportional to steam pressure in the
vessel, we have
𝑃𝑜
P= 𝑄
𝑄𝑜 𝑜𝑢𝑡
59
TV is called the time constant of steam volume effect.
From TV equation we can see that the bigger the volume of the vessel, the
higher is the time constant of volume effect.
From Qout equation we can see that when the input steam flow increases (or
decreases) suddenly, the output steam flow will not increases (or decreases)
immediately because the pressure inside the vessel cannot increase (or
decrease) instantly. Change of output steam flow lags that of input steam
flow. This is the steam volume effect phenomena
60
There are many types of configuration of steam turbines. Modern steam turbine
units consist of multiple-stage steam turbines to drive a single generator.
According to the difference in rated operating steam pressure, multiple-stage
turbines can be classified as high pressure (HP), intermediate pressure (IP),
and low pressure (LP) turbines.
Medium and small steam turbine units may have only a one-stage turbine. To
increase thermal efficiency, modern steam turbine units usually have an
intermediate reheater (RH).
Fig. Illustration of a
multistage steam turbine
61
From Illustration of a multistage steam turbine
we can see that the high-pressure high-temperature steam from the boiler
enters the HP stage through a main valve and steam chest.
We should note the existence of a certain volume of steam in the pipe and
chest from the main valve to the nozzle of the HP stage.
Exhaust steam from the HP stage is sent into the reheater section to raise
temperature before entering the IP stage.
Similarly we should to note that there exists a certain volume of steam
between the output point of the HP stage and input point of IP stage.
Exhaust steam from IP stage enters the LP stage through crossover that also
has a certain volume.
Volume effects of the three volumes mentioned above can be described by time
constant TCH, TRH, and TCO, respectively. Usually TCH is between 0.2 and 0.3 s,
time constant of reheater TRH is large, between 5 and 10 s, and TCO is about
0.5 s.
Output mechanical torque of the steam turbine is proportional to the steam
flow at the nozzle.
In addition, we assume that input steam flow to the HP stage is
approximately proportional to the opening position of the main steam valve µ.
We denote the proportionality coefficient of mechanical power of HP, IP, and
LP stages to be FHP,FIP ,FLP. Usually FHP, FIP, FLPis 0.3, 0.3, 0.4 and their
62
summation is one.
From the analysis above and taking proper base values for per unit expressions,
we can obtain the mathematical model of the steam turbine in per unit to be
Where TmH, TmI, TmLi s the output mechanical torque of HP, IP, and LP
turbines, respectively, flows Q0–Q3 are shown in Fig.
63
There are six common steam turbine systems given below
(i) Nonreheat
(ii) Tandem Compound, Single Reheat
(iii) Tandem Compound, Double Reheat
(iv) Cross Compound, Single Reheat with two LP turbines
(v) Cross Compound, Single Reheat with single LP turbine
(vi) Cross Compound, Double Reheat
Tandem compound has only one shaft on which all the turbines, High
Pressure (HP), Intermediate Pressure (IP) and Low Pressure (LP) turbines
are mounted. Sometimes there is a Very High Pressure (VHP) turbine also.
Cross compound systems have two shafts driving two independent
generators.
64
The configurations corresponding to (ii) Tandem Compound, Single Reheat and
(iii) Cross Compound, Single Reheat are shown in Figure
65
(b) Steam system configurations for Cross compound, single reheat
66
(b) Steam turbine models for Cross compound, single reheat
67
All compound steam turbines use governor controlled valves at the inlet to the
high pressure turbine, to control the steam flow. The steam chest, reheater and
crossover piping all introduces delays.
The time constants TCH and TRH and TCO represent these delays. The fractions
FHP, FIP, FLP represent fractions of the total turbine power developed, in the
HP,IP and LP turbines respectively. Typical values for TCH, TRH and TCO are
The typical values of FHP, FIP and FLP are 0.3, 0.3 and 0.4 respectively, the
sum adding to unity.
68
The stop valves (MSV and RSV) are primarily emergency
trip valves.
The CVs modulate steam flow during normal operation.
69
The CVs as well as the IVs limit overspeed.
70
71
72
73