Load Calculation of RCC
Load Calculation of RCC
So, if we assume a column size of 230 mm x 600 mm with 1% steel and 3 meters standard
height, the self-weight of the column is around 1000 kg per floor, that id equal to 10 kN.
While doing calculations, we assume the self weight of columns is between 10 to 15 kN per
floor.
we assume each meter of the beam has dimensions of 230 mm x 450 mm excluding slab
thickness.
For a 6 inch thick Brick wall of 3-meter height and a length of 1 meter,
The load / running meter to be equal to 0.150 x 1 x 3 x 2000 = 900 kg,
This method can be adopted for load calculations of Brick per running meter for any brick
type using this technique.
For aerated concrete blocks and autoclaved concrete blocks, like Aerocon or Siporex, the
weight per cubic meter is between 550 to 700 kg per cubic meter.
if your are using these blocks for construction, the wall loads per running meter can be as
low as 4 kN/meter, use of this block can significantly reduce the cost of the project.
Now, If we consider the Finishing load to be 1 kN per meter and superimposed live load to
be 2 kN per meter.
So, from the above data, we can estimate the slab load to be around 6 to 7 kN per square
meter.
In the end, after calculating the entire load on a column, do not forget to add in the factor of
safety, which is most important for any building design for the safe and convenient
performance of the building during his design life duration.