Motor valves

type ICM

Actuators
type ICAD

REFRIGERATION AND
AIR CONDITIONING Technical leaflet
Technical leaflet Motor valves, type ICM and actuators type ICAD

Contents Page
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
The ICM Concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Features (valve) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Design (valve) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Technical data (valve) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Function (valve) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Features (actuator) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Technical data (actuator) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Cable connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Function (actuator) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
ICAD-UPS for ICM 20-125 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Facts and features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
ICAD-UPS applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Material specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
ICM Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Recommended filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Nominal capacities:
Liquid line with/without phase change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Liquid line without phase change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Wet suction line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Dry suction line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Discharge line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Expansion capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
R 717 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
R 744 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
R 134a . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
R 404A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
R 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Ordering:
ICM 20 / ICAD 600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
ICM 25 / ICAD 600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
ICM 32 / ICAD 600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
ICM 40 / ICAD 900 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
ICM 50 / ICAD 900 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
ICM 65 / ICAD 900 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Dimensions:
ICM 20 / ICAD 600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
ICM 25 / ICAD 600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
ICM 32 / ICAD 600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
ICM 40 / ICAD 900 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
ICM 50 / ICAD 900 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
ICM 65 / ICAD 900 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Actuator setup:
General operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Parameter list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Reset to factory setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Introduction

ICM motor valves belong to the ICV (Industrial ICAD 600 / ICAD 900
Control Valve) family and are one of two product ICAD actuators can be controlled using the
groups. following signals:
ICV types 0-20 mA
– ICS - Industrial Control Servo 4-20 mA (default)
– ICM - Industrial Control Motor
0-10 V
The motor valve comprises three main 2-10 V
components: valve body, combined top cover /
function module and actuator. ICAD actuators can also operate an ICM valve as
an On/Off function supported by a digital input.
ICM are direct operated motorised valves
driven by actuator type ICAD (Industrial Control The ICM valve can be operated manually via the
Actuator with Display). ICAD actuator or the Multi-function tool for ICM
(see the ordering section).
ICM valves are designed to regulate an expansion
process in liquid lines with or without phase Fail Safe supply options
change or control pressure or temperature in In the event of a power failure, multiple fail safe
dry and wet suction lines and hot gas lines. options are possible, provided that a ICAD-UPS or
ICM valves are designed so that the opening similar is used.
and closing forces are balanced, therefore, only During power failure, ICM can be selected to:
two sizes of ICAD actuators are needed for the - Close ICM
complete range of ICM from DN 20 to DN 65. The - Open ICM
ICM motorised valve and ICAD actuator assembly - Stay in the same position, as when power
offers a very compact unit with small dimensions. failure occurs
- Go to a specific ICM valve opening degree
The ICM motorised valve and ICAD actuator See the section ICAD UPS for further information.
combinations are as follows:
Please note: a fail safe supply (battery or UPS) is
Actuator ICAD 600 ICAD 900 required.
ICM 20 ICM 40
Valve size ICM 25 ICM 50
ICM 32 ICM 65

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 


Technical leaflet Motor valves, type ICM and actuators type ICAD

The ICM Concept The ICM concept is developed around a modular


principle. This gives the possibility of combining
function modules and top covers with special
valve body size that is available in a variety of
connection possibilities.

There are six valve bodies available.

ICV 20 ICV 25 ICV 32 ICV 40 ICV 50 ICV 65

Each valve body is available with a range of


undersized through oversized connection
sizes and types.
D A J SOC SD SA FPT

Butt-weld DIN Butt-weld ANSI Butt-weld JIS Socket weld ANSI Solder DIN Solder ANSI Female Pipe Thread

Each body may be fitted with multiple Type Valve body Kv Cv


function / top cover to give different capacities. size
(m /h)
3
(USgal/min)
ICM20-A 0.6 0.7
ICM20-B 20 2.4 2.8
ICM20-C 4.6 5.3
ICM25-A 6 7.0
25
ICM25-B 12 13.9
ICM32-A 9 10.4
32
ICM32-B 17 20
ICM40-A 15 17
40
ICM40-B 26 30
ICM50-A 23 27
50
ICM50-B 40 46
ICM65-B 65 70 81

A magnetic coupled actuator is easily installed.


Only two actuators are needed to cover the entire
ICM program

ICAD 600 ICAD 900

 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Features (valve) Designed for Industrial Refrigeration Modular Concept


applications for a maximum working pressure – Each valve body is available with several
of 52 bar / 754 psig. different connection types and sizes.
Applicable to all common refrigerants – Valve overhaul is performed by replacing
including R717 and R744 (CO2) and non the function module.
corrosive gases/liquids. – Possible to convert ICM motor valve to ICS
servo valve.
Direct coupled connections.
Manual opening possible via ICAD or Multi-
Connection types include butt weld, socket function tool.
weld, solder and threaded connections.
PTFE seat provides excellent valve tightness.
Low temperature steel body.
Magnet coupling - real hermetic sealing.
Low weight and compact design.
V-port regulating cone ensures optimum
regulating accuracy particularly at part load.
Cavitation resistant valve seat.

Design (valve) Connections Valve body and top cover material


There is a very wide range of connection types Low temperature steel
available with ICM valves:
D: Butt weld, DIN (2448)
A: Butt weld, ANSI (B 36.10)
J: Butt weld, JIS (B S 602)
SOC: Socket weld, ANSI (B 16.11)
SD: Solder connection, DIN (2856)
SA: Solder connection, ANSI (B 16.22)
FPT: Female pipe thread (ANSI/ASME B 1.20.1)

Approvals
The ICV valve concept is designed to fulfil global
refrigeration requirements.
For specific approval information, please contact
Danfoss.

The ICM valves are approved in accordance with


the European standard specified in the Pressure
Equipment Directive and are CE marked.
For further details / restrictions - see Installation
Instruction.

ICM valves
Nominal bore DN≤ 25 (1 in.) DN 32-65 mm (11/4 - 21/2 in.)
Classified for Fluid group I
Category Article 3, paragraph 3 II

Technical data (valve) Refrigerants Pressure


Applicable to all common refrigerants The valve is designed for:
including R717 and R744 (CO2) and non- Max. working pressure: 52 bar g (754 psig)
corrosive gases/liquids. Surface protection
Use with flammable hydrocarbons cannot be ICM 20-65:
recommended. For further information please The external surface is zinc-chromated to
contact your local Danfoss sales company. provide good corrosion protection.
Temperature range: Max. openening pressure differential (MOPD)
Media: –60/+120°C (–76/+248°F). – ICM 20-32: 52 bar (750 psi)
– ICM 40: 40 bar (580 psi)
– ICM 50: 30 bar (435 psi)
– ICM 65: 20 bar (290 psi)

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 


Technical leaflet Motor valves, type ICM and actuators type ICAD

Function (valve)

ICM 20 ICM 25-65

ICM, Industrial Control Motor valves are designed There are two sizes of ICAD actuator that cover
for use with the ICAD, Industrial Control Actuator the range of valves from ICM 20 to ICM 65.
with Display. The actuators have a fully weather protected
enclosure with none of the moving parts exposed
The driving force from the actuator is transferred
to the environment. Spindle and electronic
via a magnetic coupling (a) through the stainless
heating elements are not required.
steel top housing (b) and thus eliminates
the need for a packing gland. The rotational The fast acting actuators and balanced valve
movement of the magnetic coupling (a) is design results in the valve being able to move
transferred to a spindle (c) which in turn provides from the fully closed to the fully open position
the vertical movement of the cone (d) and PTFE in between 3 to 13 seconds depending on valve
valve plate (e), to open and close the valve. The size.
closing force of the actuator, combined with the The cone (d) includes V-shaped grooves, which
PTFE valve plate (e) and cavitation resistant valve provides stable control regulation, particularly at
seat (f ), provides an effective seal to prevent low load conditions. Each valve size has at least
leakage across the valve port, when the valve two different function modules capacities to
is in the closed position. To prevent damage to select from.
the PTFE valve plate (e) and seat (f ) from system The function modules are designed for different
debris, it is recommended that a filter is installed capacities and are designated A and B, (and C in
upstream of the valve. Please refer to page 10 for the case of the ICM 20). In general, “A” modules
filter sizing and application recommendations. are for liquid applications. The “B” ( C ) modules
Valve inlet pressure (P1) acting on the underside have larger capacities than the “A” modules and
of the PTFE valve plate (e) also passes through are mainly for suction applications.
the hollow cone assembly (d) on to the top of
the piston (g) and balances the pressure acting
on the piston (g). Any trapped liquid across the
throttle cone (d) is allowed to equalise down
to the valve outlet without affecting the valve
performance.

 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

ICAD Actuator types ICAD 600 and 900 are dedicated


for use with ICM motorised valves. There are only
signal. ICAD incorporates an advanced MMI (Man
Machine Interface), including continuous display
two sizes of ICAD actuators that cover the range of Opening Degree, which gives the user a very
of valves from ICM 20 to ICM 65. advanced and flexible setup procedure that can
The ICAD is controlled via a modulating analogue meet many different applications.
signal (e.g. 4-20 mA/2-10 V) or a digital ON/OFF

Features (actuator) Specifically designed for industrial Position feed back : 0-20 mA, 4-20 mA (ICM)
refrigeration installations 3 Digital ON/OFF feedback
Advanced and high speed Digital Stepper Resolution: 20 micron/step
Motor Technology (0.02 mm stroke pr. step)
Seven segment LCD display and three Total steps: 250 – 1000 depending on size
programming keys included
Auto Calibration, Neutral zone
Valve opening degree can be observed
continuously. In the event of a power failure, multiple fail
safe options are possible. During power
Can easily be configured to different failure, ICM can be selected to:
applications on-site. (change speed, ON/OFF, Close ICM,
modulating valve) Open ICM,
Open – Close time: 3-13 seconds depending Stay in the same position, as when power
on valve size failure occurs
Modulating or ON/OFF operation Go to a specific ICM valve opening degree
Multiple speed selection during operation Hermetic magnetic motor - spindle heater not
required
Logging of old alarms
Enclosure: IP65 ~ NEMA 4
Password protection
Approvals: CE (EMC)
Control input signal :
4-20 mA, 0-20 mA, 0-10 V, 2-10 V

Technical data (actuator) ICAD 600 and ICAD 900 can be used together ICAD 600 ICAD 900
with following Danfoss valves. ICM 20 ICM 40
ICM 25 ICM 50
ICM 32 ICM 65

Materials Enclosure
Housing IP 65 (~NEMA 4)
Aluminium Cable connection
2 cable premounted of 1.8 m length (70.7 in.)
Top part of ICAD
PBT thermo plastic Supply cable
Weight 3 × 0.34 mm2 (3 × ~22 AWG)
ICAD 600: 1.2 kg (2.64 lb) Ø4.4 mm (diameter 0.17”)
ICAD 900: 1.8 kg (3.96 lb) Control cable
Temperature range (ambient) 7 × 0.25 mm2 (7 × ~24 AWG)
–30°C/+50°C (–22°F/122°F) Ø5.2 mm (diameter 0.20”)

Electrical data
Supply voltage is galvanic isolated from Input/ Analogue Output: 0/4-20 mA
Output. Load : ≤ 250 W
Supply voltage: 24 V d.c., + 10% / -15% Digital input - Digital ON/OFF input by means of
Load: ICAD 600: 1.2 A volt-free contact (Signal/Telecom relays with gold-
ICAD 900: 2.0 A plated contacts recommended) – Voltage input used
Fail safe supply: Min. 19 V d.c, max. 26.4 V d.c. ON: contact impedance < 50 W )
Load: ICAD 600: 1.2 A OFF: contact impedance > 100 k W
ICAD 900: 2.0 A Digital Output - 3 pcs. NPN transistor output
Battery capacity: External supply: 5-24 V d.c.
For each open/closed cycle (Same supply as for ICAD can
ICAD 600: 8.3 mAh be used, but please note that the
ICAD 900: 11.1 mAh galvanically isolated system will
then be spoiled)
Analogue Input - Current or Voltage Output load: 50 W
Current: 0/4-20 mA Load: Max. 50 mA
Load: 200 W
Voltage: 0/2-10 V d.c
Load : 10 kW

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 


Technical leaflet Motor valves, type ICM and actuators type ICAD

Technical data (cont.) Cable connection


Two 1.8 m (70.7 in.) cables premounted
Ref. Colour Description
A
B
C
D
White
Brown
Green
Yellow




Common Alarm
ICM fully open
ICM fully closed
GND ground
} Digital
Ouput

}
E Grey + 0/4 - 20 mA Input
Analogue
F Pink + 0/2 - 10 V Input
In/Output
G Blue + 0/4 - 20 mA Output

Fail safe supply


I White +
Battery / UPS* 19 V d.c.
II Brown + Supply voltage
III Green – 24 V d.c.
* Uninterruptable Power Supply

Figure 1

Approvals CE according to 89/336 EEC (EMC)


Emission : EN61000-6-3
Immunity: EN61000-6-2

Function (actuator) The design of ICAD is based on a digital stepper ICAD can manage and display different alarms.
motor technology combined with an advanced If an alam has been detected the display will
MMI (Man Machine Interface), that gives excellent alternate between showing: Actual alarm present
possibilities for having a high degree of flexibility and Opening Degree of ICM valve. If more than
with the same type of ICAD actuator. one alarm is active at the same time the alarm
with the highest priority will take preference. The
At the ICAD display the Opening Degree (0- alarm with the highest priority is shown on the
100 %) of the actual ICM valve installed can be display.
continuously observed. All alarms will automatically reset when
disappearing.
The advanced menu system will allow several
parameters to be ajusted to obtain the required Previous alarms can be recalled for traceability
function. Many different parameters can be and service purposes.
configurated, among these:
Modulating and ON/OFF control Any active alarm will activate the common digital
alarm output.
Analog input All alarms will automatically reset when
0- 20 mA or 4-20 mA disappearing.
0-10 V or 2-10 V
Analog output ICAD provides two digital output signals to 3rd
0- 20 mA or 4-20 mA party control equipment (e.g. PLC) indicating if
Automatic or manual control the ICM valve is completely open or completely
Change of ICM valve speed closed.
Automatic calibration The hermetic magnetic motor coupling makes it
Multiple Fail Safe set-up options during power easy to dismount the ICAD from ICM valve.
cut

For service all Input and Output signals can be


recalled and observed from the ICAD display.

A password protection has been linked to the


parameter of entering the correct ICM valve
to avoid unintentional and non-authorised
operation.

 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

ICAD-UPS for ICM 20-125 In the event of power failure, there is a need to
make sure that the ICM goes to a safe position.

ICAD-UPS can be connected to the ICAD 600/900.

The solution ICM with ICAD connected to ICAD-


UPS will give one of the following possibilities in
the event of power failure:
– close ICM
– open ICM
– stay
– go to a specefic ICM Opening Degree

ICAD-UPS is dedicated for use along with ICM When power supply has been re-established
sizes 20-125 installed with ICAD 600 and ICAD the system will automatically return to normal
900 actuators. operation.

Facts and features Industrial product. Check of battery every 60 sec.


Can support up to Adjustable buffer time*. (1, 2, 3, 5, 10, 15, 20,
– 5 pcs. of ICAD 900 or 30 or infinity) = Ensures longer life time of the
– 8 pcs. of ICAD 600 battery.
Integrated solution - battery and UPS. Forced remote shutdown in buffer mode via
Industrial approvals: digital input.
CE, UL, GL (Germanisher Lloyd). 3 digital volt free relay change over contacts
DIN rail mounting. for signals to PLC systems. (Power OK, Buffer
mode (failsafe supply to ICAD), Alarm).
LED indication
– Green (Power ON)
– Yellow (Flashing:charging, Constant:
* Buffer time is defined as the period where ICAD is only
Buffer mode (Failsafe supply to ICAD)) powered from the ICAD-UPS (i.e. not from main supply).
– Red (Battery fully discharged/Battery faulty) On ICAD-UPS there is an adjustable buffer time setting
(1, 2, 3, 5, 10, 15, 20, 30 min. or infinity). If set to 3, ICAD-UPS
24 V d.c supply → Same transformer as for will switch off power to connected ICAD 600/900, 3 minutes
ICAD can be used. Only +0,5 A extra load on after the power failure occurs. This ensures that the internal
the transformer. battery inside ICAD-UPS do not fully discharge.

Code number: 027H0182

For further information please see the instruction


PIHV0B.

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 


Technical leaflet Motor valves, type ICM and actuators type ICAD

ICAD-UPS applications
Seperate 24 V d.c tranformer for both ICAD-UPS and ICAD 600/900

max. 5 pcs. of ICAD 900 or


max. 8 pcs. of ICAD 600
ICAD-UPS
ICAD-UPS

Brown (+)
Brown (+)

White (+)
White (+)

Green (–)
Green (–)
Input
Input Output
Output
+- +-

25 V d.c. +
0.5 A -
+
24 V d.c.
-

One 24 V d.c tranformer for ICAD-UPS and ICAD 600/900


max. 5 pcs. of ICAD 900 or
max. 8 pcs. of ICAD 600

ICAD UPS
ICAD-UPS

Brown (+)
Brown (+)

White (+)
White (+)

Green (–)
Green (–)

Input
Input Output
Output
+- +-

+
24 V d.c.
-

10 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Material specification

Bolt sizes (pos. 5)


Type Screw
ICM 20 M10 × 55 A2-70 DIN 931
ICM 25 M12 × 30 A2-70 DIN 933
ICM 32 M14 × 35 A2-70 DIN 933
ICM 40 M14 × 35 A2-70 DIN 933
ICM 50 M16 × 40 A2-70 DIN 933
ICM 65 M16 × 40 A2-70 DIN 933

ICM 20 ICM 25-65

No. Part Material EN ASTM JIS


1 Housing Low temperature steel G20Mn5QT, EN 10213-3 LCC, A352 SCPL1, G5151
2 Top cover / Low temperature steel G20Mn5QT, EN 10213-3 LCC, A352 SCPL1, G5151
function module
2a O-ring Cloroprene (Neoprene)
2b O-ring Cloroprene (Neoprene)
2c O-ring Cloroprene (Neoprene)
4 Gasket Cloroprene (Neoprene)
4a Gasket Fiber, non-asbestos
5 Bolts Stainless steel A2-70, EN 1515-1 Grade B8 A320 A2-70, B 1054
11 Actuator
12 O-ring Cloroprene (Neoprene)
13 Screw Stainless steel
14 O-ring Cloroprene (Neoprene)
15 Seat High density polymer

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 11


Technical leaflet Motor valves, type ICM and actuators type ICAD

ICM Application

Hot gas bypass or defrost line

Dry suction line

Wet suction line

Discharge line

ICM can be used for pressure and temperature


regulation in dry and wet suction lines, in hot
gas lines and in liquid lines with or without
phase change (i.e. where no expansion occurs Liquid line without Liquid line with
in the valve). phase change phase change

Valve capacities for different refrigerants and As the ICM and ICS valves use a common body
applications are given in the following tables. it is possible to install the body without having
Selection of ICM / ICS valves will be available previously determined whether a servo or motor
with the DIRcalc ver. 1.3 selection program and function is required. A blank top cover complete
later. The resultant valve selections will be:- ICM- with fixing screws can be supplied to allow for
EXP for expansion valve functions and where pressure testing.
the selection criteria has been predefined for
expansion valve application: ICM will be for
control valve functions and will include for all
available function modules as valve pressure
drop is the main consideration for valve selection.

The process for identifying the ICM valve solution


can be determined from the ordering pages.
Initially select the nominal valve size, identify
the required valve body and connection types,
followed by the module insert and then the
correct actuator to suit the module insert and
valve body.

Recommended filters
Filter element for Filter element for
liquid line suction line
150 mesh 100 mesh 72 mesh 38 mesh
Filter Type Size D A FPT Soc 100 my 150 my 250 my 500 my
FIA Straightway 20 (3/4 in.) 148H3086 148H3098 148H3116 148H3110 148H3122 148H3124 148H3126 148H3128
FIA Straightway 25 (1 in.) 148H3087 148H3099 148H3117 148H3111 148H3123 148H3125 148H3127 148H3129
FIA Straightway 32 (11/4 in.) 148H3088 148H3100 148H3118 148H3112 148H3123 148H3125 148H3127 148H3129
FIA Straightway 40 (11/2 in.) 148H3089 148H3101 148H3113 148H3123 148H3125 148H3127 148H3129
FIA Straightway 50 (2 in.) 148H3090 148H3102 148H3114 148H3157 148H3130 148H3138 148H3144
FIA Straightway 65 (21/2 in.) 148H3091 148H3103 148H3131 148H3139 148H3145
FIA Straightway 80 (3 in.) 148H3092 148H3104 148H3119 148H3120 148H3121

12 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Liquid line with/without phase change
Location of valve in system (marked with grey)
Hot gas bypass & defrost line

Discharge
line
Dry suction line
Wet suction line

ICM

Liquid line without phase change Liquid line with or without phase change

SI units Calculation example (R717 capacities):

An application has following running conditions: Therefore the actual capacity must be corrected
to nominal condition by means of correction
Te = –20°C factors.
Qo = 250 kW Correction factor for ∆p 0.3 bar f∆p = 0.82
Tliq = 10°C Correction factor for liquid tempereature
Max. ∆p = 0.3 bar fTliq = 0.92
Connection: DN20
Qn = Qo × f∆p × fTliq = 250 × 0.82 × 0.92 = 189 kW
The capacity table is based on nominal condition
(pressure drop ∆p = 0.2 bar, Tliq = 30°C) From the capacity table a ICM 20-B with Qn
capacity 249 kW is selected.

US units Calculation example (R717 capacities):

An application has following running conditions: Therefore the actual capacity must be corrected
to nominal condition by means of correction
Te = –20°F factors.
Qo = 130 TR Correction factor for ∆p 3.5 psi f∆p = 0.91
Tliq = 50°F Correction factor for liquid tempereature
Max. ∆p = 3.5 psi fTliq = 0.92
Connection: 3/4"
Qn = Qo × f∆p × fTliq = 130 × 0.91 × 0.92 = 109 TR
The capacity table is based on nominal condition
(pressure drop ∆p = 3 psi, Tliq = 90°F) From the capacity table a ICM 20-C with Qn
capacity 134 TR is selected.

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 13


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Liquid line with/without phase change
R 717
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–50 –40 –30 –20 –10 0 10 20
Capacity table for nominal
ICM20-A 0.6 59.5 60.5 61.4 62.2 62.9 63.4 63.9 64.2
conditions, QN [kW],
ICM20-B 20 2.4 238 242 245 249 251 254 256 257
Tliq = 30°C,
∆P = 0.2 bar ICM20-C 4.6 457 464 471 477 482 486 490 493
ICM25-A 6 595 605 614 622 629 634 639 642
25
ICM25-B 12 1191 1210 1227 1243 1257 1269 1278 1285
ICM32-A 9 893 907 921 933 943 952 959 964
32
ICM32-B 17 1687 1714 1739 1761 1781 1797 1811 1820
ICM40-A 15 1489 1512 1534 1554 1571 1586 1598 1606
40
ICM40-B 26 2580 2622 2659 2694 2724 2749 2769 2784
ICM50-A 23 2283 2319 2353 2383 2409 2432 2450 2463
50
ICM50-B 40 3970 4033 4091 4145 4190 4229 4260 4283
ICM65-B 65 70 6947 7058 7160 7253 7333 7401 7455 7495

Correction factor for liquid


temperature (Tliq)
Liquid
Correction factor
temperature
Correction factor for ∆P (f∆P) –20°C 0.82
∆P (bar) Correction factor –10°C 0.86
0.05 2.00 0°C 0.88
0.1 1.41 10°C 0.92
0.2 1.00 20°C 0.96
0.3 0.82 30°C 1.00
0.4 0.71 40°C 1.04
0.5 0.63 50°C 1.09

R 717
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) -60 -40 -20 0 20 40 60 80


Capacity table for nominal
ICM20-A 0.7 17.1 17.4 17.7 17.9 18.1 18.3 18.4 18.5
conditions, QN [Tons of
Refrigeration], ICM20-B 20 2.8 68.3 69.5 70.7 71.7 72.5 73.2 73.7 74.0
Tliq = 90°F, ICM20-C 5.3 129 132 134 136 137 139 140 140
∆P = 3 psi ICM25-A
25
7 171 174 177 179 181 183 184 185
ICM25-B 14 342 348 353 358 363 366 369 370
ICM32-A 10 244 248 252 256 259 261 263 264
32
ICM32-B 20 488 497 505 512 518 523 527 529
ICM40-A 17 415 422 429 435 440 445 448 450
40
ICM40-B 30 732 745 757 768 777 784 790 793
ICM50-A 27 659 670 681 691 699 706 711 714
50
ICM50-B 46 1122 1142 1161 1177 1191 1203 1211 1216
ICM65-B 65 81 1976 2011 2044 2073 2098 2118 2133 2142

Correction factor for liquid


temperature (Tliq)
Liquid
Correction factor
temperature
Correction factor for ∆P (f∆P) –10°F 0.82
∆P (psi) Correction factor 10°F 0.85
0.75 1.97 30°F 0.88
1.5 1.39 50°F 0.92
3 1.00 70°F 0.96
3.5 0.91 90°F 1.00
4 0.85 110°F 1.04
4.5 0.81 130°F 1.09

14 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Liquid line with/without phase change
R 744
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m3/h) –50 –40 –30 –20 –10 0 10 20


Capacity table for nominal
ICM20-A 0.6 14.4 14.6 14.8 14.8 14.7 14.4 13.8 12.8
conditions, QN [kW],
ICM20-B 20 2.4 57.8 58.6 59.0 59.1 58.7 57.5 55.3 51.1
Tliq = 10°C,
ICM20-C 4.6 111 112 113 113 112 110 106 97.8
∆P = 0.2 bar
ICM25-A 6 144 146 148 148 147 144 138 128
25
ICM25-B 12 289 293 295 296 293 288 277 255
ICM32-A 9 217 220 221 222 220 216 207 191
32
ICM32-B 17 409 415 418 419 416 408 392 362
ICM40-A 15 361 366 369 369 367 360 346 319
40
ICM40-B 26 626 634 640 640 636 623 599 553
ICM50-A 23 554 561 566 566 562 551 530 489
50
ICM50-B 40 963 976 984 985 978 959 922 851
ICM65-B 65 70 1685 1708 1722 1724 1711 1678 1613 1489

Correction factor for liquid


Correction factor for ∆P (f∆P) temperature (Tliq)
∆P (bar) Correction factor Liquid
0.05 2.00 Correction factor
temperature
0.1 1.41 –20°C 0.52
0.2 1.00 –10°C 0.67
0.3 0.82 0°C 0.91
0.4 0.71 10°C 1.00
0.5 0.63 15°C 1.09

R 744
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60


Capacity table for nominal
conditions, QN [Tons of ICM20-A 0.7 4.2 4.2 4.3 4.3 4.2 4.1 3.9
Refrigeration], ICM20-B 20 2.8 16.7 17.0 17.1 17.1 16.9 16.5 15.5
Tliq = 50°F, ICM20-C 5.3 31.7 32.2 32.5 32.5 32.1 31.1 29.3
∆P = 3 psi ICM25-A 7 41.8 42.5 42.9 42.9 42.3 41.1 38.7
25
ICM25-B 14 83.7 85.0 85.7 85.7 84.7 82.3 77.3
ICM32-A 10 59.8 60.7 61.2 61.2 60.5 58.8 55.2
32
ICM32-B 20 120 121 122 122 121 118 110
ICM40-A 17 102 103 104 104 103 100 94
40
ICM40-B 30 179 182 184 184 181 176 166
ICM50-A 27 161 164 165 165 163 159 149
50
ICM50-B 46 275 279 282 282 278 270 254
ICM65-B 65 81 484 492 496 496 490 476 448

Correction factor for ∆P (f∆P) Correction factor for liquid


∆P (psi) Correction factor temperature (Tliq)
0.75 1.97 Liquid
Correction factor
1.5 1.39 temperature
3 1.00 –10°F 0.48
3.5 0.91 10°F 0.64
4 0.85 30°F 0.88
4.5 0.81 50°F 1.00

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 15


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Liquid line with/without phase change
R 134a
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–40 –30 –20 –10 0 10 20
Capacity table for nominal
ICM20-A 0.6 10.7 11.2 11.7 12.2 12.7 13.1 13.6
conditions, QN [kW],
ICM20-B 20 2.4 42.7 44.7 46.7 48.7 50.6 52.5 54.2
Tliq = 30°C,
∆P = 0.2 bar ICM20-C 4.6 81.9 85.8 89.6 93.3 97.0 101 104
ICM25-A 6 107 112 117 122 127 131 136
25
ICM25-B 12 214 224 234 243 253 262 271
ICM32-A 9 160 168 175 183 190 197 203
32
ICM32-B 17 303 317 331 345 358 372 384
ICM40-A 15 267 280 292 304 316 328 339
40
ICM40-B 26 463 485 506 527 548 568 588
ICM50-A 23 409 429 448 467 485 503 520
50
ICM50-B 40 712 746 779 811 843 874 904
ICM65-B 65 70 1246 1305 1363 1420 1476 1530 1582

Correction factor for liquid


temperature (Tliq)
Liquid
Correction factor
temperature
Correction factor for ∆P (f∆P) –20°C 0.66
∆P (bar) Correction factor –10°C 0.70
0.05 2.00 0°C 0.76
0.1 1.41 10°C 0.82
0.2 1.00 20°C 0.90
0.3 0.82 30°C 1.00
0.4 0.71 40°C 1.13
0.5 0.63 50°C 1.29

R 134a
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –40 –20 0 20 40 60 80


Capacity table for nominal
ICM20-A 0.7 3.0 3.2 3.3 3.5 3.7 3.8 3.9
conditions, QN [Tons of
Refrigeration], ICM20-B 20 2.8 12.1 12.7 13.4 14.0 14.6 15.2 15.8
Tliq = 90°F, ICM20-C 5.3 22.9 24.1 25.3 26.5 27.7 28.8 29.8
∆P = 3 psi ICM25-A
25
7 30.2 31.8 33.4 35.0 36.6 38.0 39.4
ICM25-B 14 60.4 63.7 66.9 70.1 73.1 76.0 78.8
ICM32-A 10 43.1 45.5 47.8 50.1 52.2 54.3 56.3
32
ICM32-B 20 86.3 91.0 95.6 100 104 109 113
ICM40-A 17 73.4 77.3 81.2 85.1 88.8 92.3 95.7
40
ICM40-B 30 129 136 143 150 157 163 169
ICM50-A 27 117 123 129 135 141 147 152
50
ICM50-B 46 198 209 220 230 240 250 259
ICM65-B 65 81 350 369 387 406 423 440 456

Correction factor for liquid


temperature (Tliq)
Liquid
Correction factor
temperature
Correction factor for ∆P (f∆P) –10°F 0.64
∆P (psi) Correction factor 10°F 0.68
0.75 1.97 30°F 0.74
1.5 1.39 50°F 0.81
3 1.00 70°F 0.89
3.5 0.91 90°F 1.00
4 0.85 110°F 1.15
4.5 0.81 130°F 1.35

16 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Liquid line with/without phase change
R 404A
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–50 –40 –30 –20 –10 0 10 20
Capacity table for nominal
ICM20-A 0.6 6.9 7.4 7.9 8.3 8.8 9.2 9.6 10.0
conditions, QN [kW],
ICM20-B 20 2.4 27.7 29.6 31.5 33.4 35.2 36.9 38.5 39.9
Tliq = 30°C,
∆P = 0.2 bar ICM20-C 4.6 53.0 56.7 60.4 64.0 67.5 70.8 73.8 76.5
ICM25-A 6 69.2 74.0 78.8 83.5 88.0 92.3 96.3 100
25
ICM25-B 12 138 148 158 167 176 185 193 200
ICM32-A 9 104 111 118 125 132 138 144 150
32
ICM32-B 17 196 210 223 237 249 262 273 283
ICM40-A 15 173 185 197 209 220 231 241 249
40
ICM40-B 26 300 321 341 362 381 400 417 432
ICM50-A 23 265 284 302 320 337 354 369 382
50
ICM50-B 40 461 493 525 557 587 615 642 665
ICM65-B 65 70 807 863 919 974 1027 1077 1123 1164

Correction factor for liquid


temperature (Tliq)
Liquid
Correction factor
temperature
Correction factor for ∆P (f∆P) –20°C 0.55
∆P (bar) Correction factor –10°C 0.60
0.05 2.00 0°C 0.66
0.1 1.41 10°C 0.74
0.2 1.00 20°C 0.85
0.3 0.82 30°C 1.00
0.4 0.71 40°C 1.23
0.5 0.63 50°C 1.68

R 404A
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60 80


Capacity table for nominal
ICM20-A 0.7 1.9 2.1 2.2 2.4 2.5 2.6 2.8 2.9
conditions, QN [Tons of
Refrigeration], ICM20-B 20 2.8 7.6 8.2 8.8 9.5 10.0 10.6 11.0 11.4
Tliq = 90°F, ICM20-C 5.3 14.4 15.6 16.8 17.9 19.0 20.0 20.9 21.7
∆P = 3 psi ICM25-A
25
7 19.0 20.6 22.1 23.6 25.1 26.4 27.6 28.6
ICM25-B 14 38.0 41.1 44.2 47.3 50.1 52.8 55.2 57.2
ICM32-A 10 27.2 29.4 31.6 33.8 35.8 37.7 39.4 40.9
32
ICM32-B 20 54.3 58.8 63.2 67.5 71.6 75.5 78.9 81.7
ICM40-A 17 46.2 50.0 53.7 57.4 60.9 64.1 67.1 69.5
40
ICM40-B 30 81.5 88.1 94.8 101 107 113 118 123
ICM50-A 27 73.3 79.3 85.3 91.2 96.7 102 107 110
50
ICM50-B 46 125 135 145 155 165 174 181 188
ICM65-B 65 81 220 238 256 274 290 306 320 331

Correction factor for liquid


temperature (Tliq)
Liquid
Correction factor
temperature
Correction factor for ∆P (f∆P) –10°F 0.52
∆P (psi) Correction factor 10°F 0.57
0.75 1.97 30°F 0.63
1.5 1.39 50°F 0.72
3 1.00 70°F 0.83
3.5 0.91 90°F 1.00
4 0.85 110°F 1.29
4.5 0.81 130°F 1.92

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 17


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Liquid line with/without phase change
R 22
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–50 –40 –30 –20 –10 0 10 20
Capacity table for nominal
ICM20-A 0.6 11.9 12.3 12.7 13.0 13.3 13.6 13.9 14.2
conditions, QN [kW],
ICM20-B 20 2.4 47.6 49.1 50.6 52.0 53.3 54.5 55.7 56.7
Tliq = 30°C,
∆P = 0.2 bar ICM20-C 4.6 91.3 94.2 97.0 100 102 105 107 109
ICM25-A 6 119 123 127 130 133 136 139 142
25
ICM25-B 12 238 246 253 260 267 273 278 283
ICM32-A 9 179 184 190 195 200 205 209 213
32
ICM32-B 17 337 348 358 368 378 386 394 401
ICM40-A 15 298 307 316 325 333 341 348 354
40
ICM40-B 26 516 532 548 563 578 591 603 614
ICM50-A 23 456 471 485 498 511 523 534 543
50
ICM50-B 40 794 819 843 866 889 909 928 945
ICM65-B 65 70 1389 1433 1476 1516 1555 1591 1624 1653

Correction factor for liquid


temperature (Tliq)
Liquid
Correction factor
temperature
Correction factor for ∆P (f ) ∆P –20°C 0.71
∆P (bar) Correction factor –10°C 0.75
0.2 1.00 0°C 0.80
0.25 0.89 10°C 0.86
0.3 0.82 20°C 0.92
0.4 0.71 30°C 1.00
0.5 0.63 40°C 1.09
0.6 0.58 50°C 1.22

R 22
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60 80


Capacity table for nominal
ICM20-A 0.7 3.4 3.5 3.6 3.7 3.8 3.9 4.0 4.1
conditions, QN [Tons of
Refrigeration], ICM20-B 20 2.8 13.5 14.0 14.4 14.9 15.3 15.7 16.0 16.3
Tliq = 90°F, ICM20-C 5.3 25.5 26.4 27.4 28.2 29.0 29.7 30.4 30.9
∆P = 3 psi ICM25-A
25
7 33.7 34.9 36.1 37.2 38.3 39.2 40.1 40.8
ICM25-B 14 67.4 69.8 72.2 74.5 76.6 78.5 80.2 81.6
ICM32-A 10 48.1 49.9 51.6 53.2 54.7 56.0 57.3 58.3
32
ICM32-B 20 96.3 100 103 106 109 112 115 117
ICM40-A 17 81.9 84.8 87.7 90.5 93.0 95.3 97.4 99.1
40
ICM40-B 30 144 150 155 160 164 168 172 175
ICM50-A 27 130 135 139 144 148 151 155 157
50
ICM50-B 46 221 229 237 245 252 258 264 268
ICM65-B 65 81 390 404 418 431 443 454 464 472

Correction factor for liquid


temperature (Tliq)
Liquid
Correction factor
temperature
Correction factor for ∆P (f∆P) –10°F 0.73
∆P (psi) Correction factor 10°F 0.77
3 1.00 30°F 0.82
4 0.87 50°F 0.87
5 0.79 70°F 0.93
6 0.72 90°F 1.00
7 0.66 110°F 1.09
8 0.62 130°F 1.20

18 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Liquid line without phase change
Location of valve in system (marked with grey)
Hot gas bypass & defrost line

Discharge
line
Dry suction line
Wet suction line

ICM

Liquid line without phase change Liquid line with or without phase change

SI units Calculation example (R717 capacities):

An application has following running conditions: Therefore the actual capacity must be corrected
to nominal condition by means of correction
Te = –20°C factors.
Qo = 180 kW Correction factor for ∆p 0.3 bar f∆p = 0.82
Circulation rate = 3 Correction factor for circulation rate frec = 0.75
Max. ∆p = 0.3 bar
Connection: DN20 Qn = Qo × f∆p × frec = 180 × 0.82 × 0.75 = 111 kW

The capacity table is based on nominal condition From the capacity table a ICM 20-C with Qn
(pressure drop ∆p = 0.2 bar, circulation rate = 4) capacity 153 kW is selected.

US units Calculation example (R717 capacities):

An application has following running conditions: Therefore the actual capacity must be corrected
to nominal condition by means of correction
Te = –20°F factors.
Qo = 130 TR Correction factor for ∆p 3.5 psi f∆p = 0.91
Circulation rate = 3 Correction factor for circulation rate frec = 0.75
Max. ∆p = 3.5 psi
Connection: 11/4" Qn = Qo × f∆p × frec = 130 × 0.91 × 0.75 = 89 TR

The capacity table is based on nominal condition From the capacity table a ICM 32-B with Qn
(pressure drop ∆p = 3 psi, circulation rate = 4) capacity 171 TR is selected.

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 19


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Liquid line without phase change
R 717
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–50 –40 –30 –20 –10 0 10 20
Capacity table at nominal
conditions, QN [kW], ICM20-A 0.6 21.9 21.3 20.7 20.0 19.3 18.5 17.8 16.9
Circulation rate = 4, ICM20-B 20 2.4 87.6 85.2 82.7 80.0 77.1 74.2 71.0 67.8
∆p = 0.2 bar ICM20-C 4.6 168 163 159 153 148 142 136 130
ICM25-A 6 219 213 207 200 193 185 178 169
25
ICM25-B 12 438 426 413 400 386 371 355 339
ICM32-A 9 329 320 310 300 289 278 266 254
32
ICM32-B 17 621 604 586 567 546 525 503 480
ICM40-A 15 548 533 517 500 482 464 444 424
40
ICM40-B 26 949 923 896 867 836 803 770 734
ICM50-A 23 840 817 793 767 739 711 681 650
50
ICM50-B 40 1460 1421 1378 1333 1286 1236 1184 1130
ICM65-B 65 70 2555 2486 2412 2333 2250 2163 2072 1977

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (bar) Correction factor Circulation rate Correction factor
0.05 2.00 2 0.5
0.1 1.41 3 0.75
0.2 1.00 4 1
0.3 0.82 6 1.5
0.4 0.71 8 2
0.5 0.63 10 2.5

R 717
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60 80


Capacity table at nominal
conditions, QN [Tons of ICM20-A 0.7 6.4 6.2 6.0 5.8 5.5 5.3 5.0 4.8
Refrigeration], ICM20-B 20 2.8 25.6 24.8 24.0 23.1 22.2 21.2 20.2 19.1
Circulation rate = 4, ICM20-C 5.3 48.4 46.9 45.3 43.7 41.9 40.1 38.1 36.1
∆p = 3 psi ICM25-A 7 64.0 62.0 59.9 57.7 55.4 53.0 50.4 47.7
25
ICM25-B 14 128 124 120 115 111 106 101 95.4
ICM32-A 10 91.4 88.5 85.6 82.5 79.1 75.7 72.0 68.1
32
ICM32-B 20 183 177 171 165 158 151 144 136
ICM40-A 17 155 150 145 140 135 129 122 116
40
ICM40-B 30 274 266 257 247 237 227 216 204
ICM50-A 27 247 239 231 223 214 204 194 184
50
ICM50-B 46 420 407 394 379 364 348 331 313
ICM65-B 65 81 740 717 693 668 641 613 583 552

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (psi) Correction factor Circulation rate Correction factor
0.75 1.97 2 0.5
1.5 1.39 3 0.75
3 1.00 4 1
3.5 0.91 6 1.5
4 0.85 8 2
4.5 0.81 10 2.5

20 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Liquid line without phase change
R 744
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–50 –40 –30 –20 –10 0 10
Capacity table at nominal
conditions, QN [kW], ICM20-A 0.6 6.7 6.3 5.9 5.4 4.8 4.2 3.4
Circulation rate = 4, ICM20-B 20 2.4 27.0 25.3 23.5 21.5 19.2 16.7 13.7
∆p = 0.2 bar ICM20-C 4.6 51.7 48.5 45.0 41.1 36.8 32.0 26.4
ICM25-A 6 67.5 63.3 58.7 53.7 48.0 41.7 34.4
25
ICM25-B 12 134.9 126.5 117.4 107.3 96.0 83.5 68.7
ICM32-A 9 101.2 94.9 88.1 80.5 72.0 62.6 51.6
32
ICM32-B 17 191 179 166 152 136 118 97.4
ICM40-A 15 169 158 147 134 120 104 85.9
40
ICM40-B 26 292 274 254 233 208 181 149
ICM50-A 23 259 242 225 206 184 160 132
50
ICM50-B 40 450 422 391 358 320 278 229
ICM65-B 65 70 787 738 685 626 560 487 401

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (bar) Correction factor Circulation rate Correction factor
0.05 2.00 2 0.77
0.1 1.41 3 0.90
0.2 1.00 4 1
0.3 0.82 6 1.13
0.4 0.71 8 1.20
0.5 0.63 10 1.25

R 744
US units Type Valve body
size
Cv Evaporating temperature [°F]

Capacity table at nominal (USgal/min) –60 –40 –20 0 20 40 60


conditions, QN [Tons of ICM20-A 0.7 2.0 1.8 1.7 1.5 1.3 1.1 0.9
Refrigeration], ICM20-B 20 2.8 7.9 7.4 6.8 6.1 5.4 4.5 3.4
Circulation rate = 4, ICM20-C 5.3 15.0 13.9 12.8 11.6 10.1 8.5 6.5
∆p = 3 psi ICM25-A 7 19.8 18.4 16.9 15.3 13.4 11.2 8.6
25
ICM25-B 14 39.5 36.8 33.9 30.5 26.8 22.5 17.2
ICM32-A 10 28.2 26.3 24.2 21.8 19.1 16.1 12.3
32
ICM32-B 20 56.4 52.6 48.4 43.6 38.3 32.1 24.6
ICM40-A 17 48.0 44.7 41.1 37.1 32.5 27.3 20.9
40
ICM40-B 30 84.7 78.9 72.6 65.4 57.4 48.2 37.0
ICM50-A 27 76.2 71.0 65.3 58.9 51.7 43.4 33.3
50
ICM50-B 46 130 121 111 100 88.0 73.9 56.7
ICM65-B 65 81 229 213 196 177 155 130 100

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (psi) Correction factor Circulation rate Correction factor
0.75 1.97 2 0.5
1.5 1.39 3 0.75
3 1.00 4 1
3.5 0.91 6 1.5
4 0.85 8 2
4.5 0.81 10 2.5

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 21


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Liquid line without phase change
R 134a
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–40 –30 –20 –10 0 10 20
Capacity table at nominal
conditions, QN [kW], ICM20-A 0.6 4.9 4.8 4.6 4.4 4.2 4.0 3.7
Circulation rate = 4, ICM20-B 20 2.4 19.8 19.1 18.3 17.6 16.7 15.9 14.9
∆p = 0.2 bar ICM20-C 4.6 37.9 36.6 35.2 33.6 32.1 30.4 28.7
ICM25-A 6 49.5 47.7 45.9 43.9 41.8 39.7 37.4
25
ICM25-B 12 98.9 95.5 91.7 87.8 83.7 79.4 74.7
ICM32-A 9 74.2 71.6 68.8 65.8 62.7 59.5 56.1
32
ICM32-B 17 140 135 130 124 119 112 106
ICM40-A 15 124 119 115 110 105 99.2 93.4
40
ICM40-B 26 214 207 199 190 181 172 162
ICM50-A 23 190 183 176 168 160 152 143
50
ICM50-B 40 330 318 306 293 279 265 249
ICM65-B 65 70 577 557 535 512 488 463 436

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (bar) Correction factor Circulation rate Correction factor
0.2 1.00 2 0.5
0.25 0.89 3 0.75
0.3 0.82 4 1
0.4 0.71 6 1.5
0.5 0.63 8 2
0.6 0.58 10 2.5

R 134a
US units Type Valve body
size
Cv Evaporating temperature [°F]

Capacity table at nominal (USgal/min) –40 –20 –0 20 40 60 80


conditions, QN [Tons of ICM20-A 0.7 1.4 1.4 1.3 1.3 1.2 1.1 1.0
Refrigeration], ICM20-B 20 2.8 5.8 5.5 5.3 5.0 4.8 4.5 4.2
Circulation rate = 4, ICM20-C 5.3 10.9 10.5 10.0 9.5 9.0 8.5 7.9
∆p = 3 psi ICM25-A 7 14.4 13.8 13.2 12.6 11.9 11.2 10.4
25
ICM25-B 14 28.8 27.7 26.4 25.1 23.8 22.4 20.8
ICM32-A 10 20.6 19.8 18.9 18.0 17.0 16.0 14.9
32
ICM32-B 20 41.1 39.5 37.8 35.9 34.0 32.0 29.8
ICM40-A 17 35.0 33.6 32.1 30.5 28.9 27.2 25.3
40
ICM40-B 30 61.7 59.3 56.7 53.9 51.0 48.0 44.6
ICM50-A 27 55.5 53.3 51.0 48.5 45.9 43.2 40.2
50
ICM50-B 46 94.6 90.9 86.9 82.6 78.2 73.5 68.4
ICM65-B 65 81 167 160 153 146 138 130 121

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (psi) Correction factor Circulation rate Correction factor
3 1.00 2 0.5
4 0.87 3 0.75
5 0.79 4 1
6 0.72 6 1.5
7 0.66 8 2
8 0.62 10 2.5

22 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Liquid line without phase change
R 404A
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–50 –40 –30 –20 –10 0 10 20
Capacity table at nominal
conditions, QN [kW], ICM20-A 0.6 4.4 4.2 4.0 3.8 5.3 3.4 3.1 2.9
Circulation rate = 4, ICM20-B 20 2.4 17.5 16.7 15.9 15.1 21.2 13.5 12.5 11.5
∆p = 0.2 bar ICM20-C 4.6 33.4 32.1 30.4 29.0 40.6 25.8 24.0 21.9
ICM25-A 6 43.6 41.8 39.7 37.8 53.0 33.7 31.3 28.6
25
ICM25-B 12 87.3 83.7 79.4 75.6 105.9 67.4 62.6 57.3
ICM32-A 9 65.4 62.7 59.5 56.7 79.5 50.5 46.9 42.9
32
ICM32-B 17 124 119 112 107 150 95.4 88.6 81.1
ICM40-A 15 109 105 99.2 94.5 132.4 84.2 78.2 71.6
40
ICM40-B 26 189 181 172 164 230 146 136 124
ICM50-A 23 167 160 152 145 203 129 120 110
50
ICM50-B 40 291 279 265 252 353 225 209 191
ICM65-B 65 70 509 488 463 441 618 393 365 334

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (bar) Correction factor Circulation rate Correction factor
0.05 2.00 2 0.5
0.1 1.41 3 0.75
0.2 1.00 4 1
0.3 0.82 6 1.5
0.4 0.71 8 1.2
0.5 0.63 10 2.5

R 404A
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60 80


Capacity table at nominal
conditions, QN [Tons of ICM20-A 0.7 1.3 1.2 1.1 1.1 1.0 1.0 0.9 0.8
Refrigeration], ICM20-B 20 2.8 5.1 4.9 4.6 4.4 4.1 3.8 3.5 3.1
Circulation rate = 4, ICM20-C 5.3 9.7 9.2 8.7 8.2 7.7 7.2 6.6 5.9
∆p = 3 psi ICM25-A 7 12.7 12.2 11.5 10.9 10.2 9.5 8.7 7.8
25
ICM25-B 14 25.5 24.4 23.0 21.8 20.4 19.0 17.4 15.5
ICM32-A 10 18.2 17.4 16.4 15.6 14.6 13.6 12.4 11.1
32
ICM32-B 20 36.4 34.8 32.8 31.1 29.2 27.2 24.8 22.2
ICM40-A 17 31.0 29.6 27.9 26.4 24.8 23.1 21.1 18.8
40
ICM40-B 30 54.6 52.2 49.3 46.7 43.8 40.7 37.2 33.3
ICM50-A 27 49.2 47.0 44.3 42.0 39.4 36.7 33.5 29.9
50
ICM50-B 46 83.8 80.1 75.5 71.6 67.2 62.5 57.1 51.0
ICM65-B 65 81 148 141 133 126 118 110 101 89.8

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (psi) Correction factor Circulation rate Correction factor
0.75 1.97 2 0.5
1.5 1.39 3 0.75
3 1.00 4 1
3.5 0.91 6 1.5
4 0.85 8 2
4.5 0.81 10 2.5

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 23


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Liquid line without phase change
R 22
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–50 –40 –30 –20 –10 0 10 20
Capacity table at nominal
conditions, QN [kW], ICM20-A 0.6 5.3 5.2 5.0 4.8 4.6 4.3 4.1 3.9
Circulation rate = 4, ICM20-B 20 2.4 21.4 20.6 19.9 19.1 18.2 17.3 16.4 15.4
∆p = 0.2 bar ICM20-C 4.6 40.9 39.6 38.1 36.5 35.0 33.3 31.5 29.6
ICM25-A 6 53.4 51.6 49.7 47.7 45.6 43.4 41.1 38.6
25
ICM25-B 12 107 103 99.4 95.3 91.2 86.7 82.1 77.1
ICM32-A 9 80.1 77.4 74.6 71.5 68.4 65.1 61.6 57.9
32
ICM32-B 17 151 146 141 135 129 123 116 109
ICM40-A 15 134 129 124 119 114 108 103 96
40
ICM40-B 26 231 224 215 207 198 188 178 167
ICM50-A 23 205 198 191 183 175 166 157 148
50
ICM50-B 40 356 344 331 318 304 289 274 257
ICM65-B 65 70 623 602 580 556 532 506 479 450

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (bar) Correction factor Circulation rate Correction factor
0.2 1.00 2 0.5
0.25 0.89 3 0.75
0.3 0.82 4 1
0.4 0.71 6 1.5
0.5 0.63 8 2
0.6 0.58 10 2.5

R 22
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60 80


Capacity table at nominal
conditions, QN [Tons of ICM20-A 0.7 1.6 1.5 1.4 1.4 1.3 1.2 1.2 1.1
Refrigeration], ICM20-B 20 2.8 6.2 6.0 5.8 5.5 5.2 4.9 4.6 4.3
Circulation rate = 4, ICM20-C 5.3 11.8 11.4 10.9 10.4 9.9 9.3 8.7 8.1
∆p = 3 psi ICM25-A 7 15.6 15.0 14.4 13.7 13.1 12.3 11.6 10.7
25
ICM25-B 14 31.2 30.1 28.8 27.5 26.1 24.7 23.1 21.4
ICM32-A 10 22.3 21.5 20.6 19.6 18.7 17.6 16.5 15.3
32
ICM32-B 20 44.6 43.0 41.2 39.3 37.3 35.2 33.0 30.6
ICM40-A 17 37.9 36.5 35.0 33.4 31.7 29.9 28.1 26.0
40
ICM40-B 30 66.9 64.4 61.7 58.9 56.0 52.9 49.5 45.9
ICM50-A 27 60.2 58.0 55.6 53.0 50.4 47.6 44.6 41.3
50
ICM50-B 46 103 98.8 94.7 90.4 85.8 81.0 75.9 70.4
ICM65-B 65 81 181 174 167 159 151 143 134 124

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (psi) Correction factor Circulation rate Correction factor
3 1.00 2 0.5
4 0.87 3 0.75
5 0.79 4 1
6 0.72 6 1.5
7 0.66 8 2
8 0.62 10 2.5

24 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Wet suction line
Location of valve in system (marked with grey)
Hot gas bypass & defrost line

High-pressure
line
Dry suction line
Wet suction line
ICM

Liquid line without phase change Liquid line with or without phase change

SI units Calculation example (R717 capacities):

An application has following running conditions: Therefore the actual capacity must be corrected
to nominal condition by means of correction
Te = –20 C factors.
Qo = 80 kW Correction factor for ∆p 0.3 bar f∆p = 0.82
Circulation rate = 3 Correction factor for circulation rate frec = 0.9
Max. ∆p = 0.3 bar
Connection: DN32 Qn = Qo × f∆p × frec = 80 × 0.82 × 0.9 = 59 kW

The capacity table is based on nominal condition From the capacity table a ICM 32-B with Qn
(pressure drop ∆p = 0.2 bar, recirculation rate = 4) capacity 60.1 kW is selected.

US units Calculation example (R717 capacities):

An application has following running conditions: Therefore the actual capacity must be corrected
to nominal condition by means
Te = –20 F of correction factors.
Qo = 8 TR Correction factor for ∆p 3.5 psi f∆p = 0.91
Circulation rate = 3 Correction factor for circulation rate frec = 0.9
Max. ∆p = 3.5 psi
Connection: 1” Qn = Qo × f∆p × frec = 8 × 0.91 × 0.9 = 6.6 TR

The capacity table is based on nominal condition From the capacity table a ICM 25-B with Qn
(pressure drop ∆p = 3 psi, recirculation rate = 4) capacity 10.2 TR is selected.

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 25


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Wet suction line
R 717
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–50 –40 –30 –20 –10 0 10 20
Capacity table at nominal
conditions, QN [kW], ICM20-A 0.6 0.9 1.3 1.7 2.1 2.5 3.0 3.4 3.9
Circulation rate = 4, ICM20-B 20 2.4 3.4 5.2 6.8 8.5 10.2 11.9 13.7 15.6
∆p = 0.2 bar ICM20-C 4.6 6.6 10.0 13.1 16.3 19.5 22.9 26.4 29.9
ICM25-A 6 8.6 13.0 17.1 21.2 25.5 29.8 34.4 39.0
25
ICM25-B 12 17.2 26.0 34.2 42.4 50.9 59.7 68.7 78.0
ICM32-A 9 12.9 19.5 25.7 31.8 38.2 44.7 51.6 58.5
32
ICM32-B 17 24.4 36.8 48.5 60.1 72.1 84.5 97.4 111
ICM40-A 15 21.5 32.5 42.8 53.0 63.6 74.6 85.9 97.5
40
ICM40-B 26 37.3 56.3 74.1 91.9 110 129 149 169
ICM50-A 23 33.0 49.8 65.6 81.3 97.6 114 132 150
50
ICM50-B 40 57.4 86.6 114 141 170 199 229 260
ICM65-B 65 70 101 152 200 248 297 348 401 455

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (bar) Correction factor Circulation rate Correction factor
0.05 2.00 2 0.77
0.1 1.41 3 0.90
0.2 1.00 4 1
0.3 0.82 6 1.13
0.4 0.71 8 1.20
0.5 0.63 10 1.25

R 717
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60 80


Capacity table at nominal
conditions, QN [Tons of ICM20-A 0.7 0.2 0.4 0.5 0.6 0.8 0.9 1.1 1.2
Refrigeration], ICM20-B 20 2.8 0.9 1.5 2.0 2.6 3.1 3.7 4.3 4.9
Circulation rate = 4, ICM20-C 5.3 1.8 2.8 3.9 4.9 5.9 7.0 8.1 9.3
∆p = 3 psi ICM25-A 7 2.3 3.8 5.1 6.4 7.8 9.3 10.8 12.3
25
ICM25-B 14 4.6 7.5 10.2 12.9 15.7 18.5 21.5 24.5
ICM32-A 10 3.3 5.4 7.3 9.2 11.2 13.2 15.4 17.5
32
ICM32-B 20 6.6 10.7 14.6 18.4 22.4 26.5 30.7 35.0
ICM40-A 17 5.6 9.1 12.4 15.6 19.0 22.5 26.1 29.8
40
ICM40-B 30 9.9 16.1 21.9 27.6 33.5 39.7 46.1 52.5
ICM50-A 27 8.9 14.5 19.7 24.8 30.2 35.8 41.5 47.3
50
ICM50-B 46 15.2 24.7 33.5 42.3 51.4 60.9 70.7 80.5
ICM65-B 65 81 26.8 43.5 59.0 74.5 90.6 107 125 142

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (psi) Correction factor Circulation rate Correction factor
0.75 1.97 2 0.77
1.5 1.39 3 0.90
3 1.00 4 1
3.5 0.91 6 1.13
4 0.85 8 1.20
4.5 0.81 10 1.25

26 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Wet suction line
R 744
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–50 –40 –30 –20 –10 0 10
Capacity table at nominal
conditions, QN [kW], ICM20-A 0.6 1.8 2.1 2.4 2.6 2.8 2.9 2.9
Circulation rate = 4, ICM20-B 20 2.4 7.3 8.4 9.4 10.4 11.2 11.7 11.8
∆p = 0.2 bar ICM20-C 4.6 14.0 16.1 18.1 19.9 21.5 22.5 22.6
ICM25-A 6 18.3 21.0 23.6 26.0 28.0 29.3 29.5
25
ICM25-B 12 36.5 41.9 47.1 51.9 56.0 58.6 59.0
ICM32-A 9 27.4 31.4 35.4 39.0 42.0 44.0 44.2
32
ICM32-B 17 51.7 59.4 66.8 73.6 79.3 83.1 83.5
ICM40-A 15 45.6 52.4 58.9 64.9 70.0 73.3 73.7
40
ICM40-B 26 79.1 90.8 102 113 121 127 128
ICM50-A 23 70.0 80.3 90.4 100 107 112 113
50
ICM50-B 40 122 140 157 173 187 195 197
ICM65-B 65 70 213 245 275 303 327 342 344

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (bar) Correction factor Circulation rate Correction factor
0.05 2.00 2 0.77
0.1 1.41 3 0.90
0.2 1.00 4 1
0.3 0.82 6 1.13
0.4 0.71 8 1.20
0.5 0.63 10 1.25

R 744
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60


Capacity table at nominal
conditions, QN [Tons of ICM20-A 0.7 0.5 0.6 0.7 0.8 0.8 0.9 0.8
Refrigeration], ICM20-B 20 2.8 2.1 2.4 2.8 3.1 3.3 3.4 3.3
Circulation rate = 4, ICM20-C 5.3 4.0 4.6 5.3 5.8 6.3 6.5 6.3
∆p = 3 psi ICM25-A 7 5.2 6.1 7.0 7.7 8.3 8.6 8.4
25
ICM25-B 14 10.5 12.2 13.9 15.4 16.6 17.2 16.7
ICM32-A 10 7.5 8.7 9.9 11.0 11.9 12.3 11.9
32
ICM32-B 20 14.9 17.4 19.9 22.0 23.7 24.6 23.9
ICM40-A 17 12.7 14.8 16.9 18.7 20.1 20.9 20.3
40
ICM40-B 30 22.4 26.1 29.8 33.0 35.6 36.9 35.8
ICM50-A 27 20.2 23.5 26.8 29.7 32.0 33.2 32.2
50
ICM50-B 46 34.4 40.1 45.7 50.7 54.5 56.6 54.9
ICM65-B 65 81 60.5 70.6 80.5 89.2 96.0 100 97

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (psi) Correction factor Circulation rate Correction factor
0.75 1.97 2 0.77
1.5 1.39 3 0.90
3 1.00 4 1
3.5 0.91 6 1.13
4 0.85 8 1.20
4.5 0.81 10 1.25

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 27


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Wet suction line
R 134a
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–40 –30 –20 –10 0 10 20
Capacity table at nominal
conditions, QN [kW], ICM20-A 0.6 0.4 0.5 0.7 0.8 1.0 1.1 1.2
Circulation rate = 4, ICM20-B 20 2.4 1.6 2.2 2.7 3.3 3.8 4.3 4.9
∆p = 0.2 bar ICM20-C 4.6 3.1 4.2 5.3 6.3 7.3 8.3 9.4
ICM25-A 6 4.0 5.5 6.8 8.2 9.5 10.9 12.2
25
ICM25-B 12 8.0 11.0 13.7 16.4 19.1 21.7 24.4
ICM32-A 9 6.0 8.2 10.3 12.3 14.3 16.3 18.3
32
ICM32-B 17 11.4 15.5 19.4 23.2 27.0 30.8 34.6
ICM40-A 15 10.1 13.7 17.1 20.5 23.9 27.2 30.5
40
ICM40-B 26 17.4 23.7 29.7 35.5 41.3 47.1 52.9
ICM50-A 23 15.4 21.0 26.3 31.4 36.6 41.6 46.8
50
ICM50-B 40 26.8 36.5 45.7 54.6 63.6 72.4 81.4
ICM65-B 65 70 47.0 63.9 79.9 95.5 111 127 142

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (bar) Correction factor Circulation rate Correction factor
0.2 1.00 2 0.77
0.25 0.89 3 0.90
0.3 0.82 4 1
0.4 0.71 6 1.13
0.5 0.63 8 1.20
0.6 0.58 10 1.25

R 134a
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –40 –20 0 20 40 60 80


Capacity table at nominal
conditions, QN [Tons of ICM20-A 0.7 0.1 0.2 0.2 0.3 0.3 0.3 0.4
Refrigeration], ICM20-B 20 2.8 0.5 0.7 0.8 1.0 1.2 1.4 1.5
Circulation rate = 4, ICM20-C 5.3 0.9 1.2 1.6 1.9 2.2 2.6 2.9
∆p = 3 psi ICM25-A 7 1.2 1.6 2.1 2.5 2.9 3.4 3.8
25
ICM25-B 14 2.3 3.3 4.1 5.0 5.9 6.8 7.6
ICM32-A 10 1.7 2.3 3.0 3.6 4.2 4.8 5.4
32
ICM32-B 20 3.3 4.7 5.9 7.2 8.4 9.7 10.9
ICM40-A 17 2.8 4.0 5.0 6.1 7.2 8.2 9.2
40
ICM40-B 30 5.0 7.0 8.9 10.8 12.6 14.5 16.3
ICM50-A 27 4.5 6.3 8.0 9.7 11.4 13.0 14.7
50
ICM50-B 46 7.6 10.7 13.6 16.5 19.4 22.2 25.0
ICM65-B 65 81 13.4 18.9 24.0 29.1 34.1 39.1 44.0

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (psi) Correction factor Circulation rate Correction factor
3 1.00 2 0.77
4 0.87 3 0.90
5 0.79 4 1
6 0.72 6 1.13
7 0.66 8 1.20
8 0.62 10 1.25

28 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Wet suction line
R 404A
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–50 –40 –30 –20 –10 0 10 20
Capacity table at nominal
conditions, QN [kW], ICM20-A 0.6 0.5 0.7 0.8 0.9 1.0 1.2 1.3 1.4
Circulation rate = 4, ICM20-B 20 2.4 2.1 2.6 3.1 3.7 4.2 4.7 5.2 5.6
∆p = 0.2 bar ICM20-C 4.6 4.0 5.0 6.0 7.0 8.0 9.0 10.0 10.8
ICM25-A 6 5.2 6.5 7.8 9.1 10.5 11.7 13.0 14.1
25
ICM25-B 12 10.4 13.0 15.6 18.3 20.9 23.5 26.0 28.2
ICM32-A 9 7.8 9.8 11.7 13.7 15.7 17.6 19.5 21.1
32
ICM32-B 17 14.7 18.5 22.1 25.9 29.6 33.3 36.8 39.9
ICM40-A 15 12.9 16.3 19.5 22.8 26.1 29.4 32.5 35.2
40
ICM40-B 26 22.4 28.3 33.7 39.6 45.3 50.9 56.3 61.1
ICM50-A 23 19.8 25.0 29.8 35.0 40.1 45.0 49.8 54.0
50
ICM50-B 40 34.5 43.5 51.9 60.9 69.7 78.3 86.6 93.9
ICM65-B 65 70 60.4 76.1 90.8 107 122 137 152 164

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (bar) Correction factor Circulation rate Correction factor
0.05 2.00 2 0.77
0.1 1.41 3 0.90
0.2 1.00 4 1
0.3 0.82 6 1.13
0.4 0.71 8 1.20
0.5 0.63 10 1.25

R 404A
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60 80


Capacity table at nominal
conditions, QN [Tons of ICM20-A 0.7 0.1 0.2 0.2 0.3 0.3 0.4 0.4 0.4
Refrigeration], ICM20-B 20 2.8 0.6 0.8 0.9 1.1 1.3 1.4 1.6 1.7
Circulation rate = 4, ICM20-C 5.3 1.1 1.4 1.7 2.1 2.4 2.7 3.0 3.2
∆p = 3 psi ICM25-A 7 1.5 1.9 2.3 2.7 3.2 3.6 4.0 4.3
25
ICM25-B 14 2.9 3.8 4.6 5.5 6.3 7.2 7.9 8.6
ICM32-A 10 2.1 2.7 3.3 3.9 4.5 5.1 5.7 6.1
32
ICM32-B 20 4.2 5.4 6.6 7.8 9.1 10.2 11.3 12.2
ICM40-A 17 3.5 4.6 5.6 6.7 7.7 8.7 9.6 10.4
40
ICM40-B 30 6.2 8.1 9.9 11.7 13.6 15.4 17.0 18.3
ICM50-A 27 5.6 7.3 8.9 10.6 12.2 13.8 15.3 16.5
50
ICM50-B 46 9.6 12.4 15.2 18.0 20.8 23.6 26.1 28.1
ICM65-B 65 81 16.9 21.9 26.7 31.7 36.7 41.5 45.9 49.5

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (psi) Correction factor Circulation rate Correction factor
0.75 1.97 2 0.77
1.5 1.39 3 0.90
3 1.00 4 1
3.5 0.91 6 1.13
4 0.85 8 1.20
4.5 0.81 10 1.25

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 29


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Wet suction line
R 22
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–50 –40 –30 –20 –10 0 10 20
Capacity table at nominal
conditions, QN [kW], ICM20-A 0.6 0.5 0.6 0.8 0.9 1.1 1.2 1.3 1.5
Circulation rate = 4, ICM20-B 20 2.4 1.9 2.5 3.1 3.7 4.2 4.8 5.4 5.9
∆p = 0.2 bar ICM20-C 4.6 3.7 4.8 5.9 7.0 8.1 9.2 10.3 11.4
ICM25-A 6 4.8 6.3 7.7 9.1 10.6 12.0 13.5 14.9
25
ICM25-B 12 9.6 12.6 15.4 18.3 21.2 24.1 26.9 29.7
ICM32-A 9 7.2 9.4 11.6 13.7 15.9 18.1 20.2 22.3
32
ICM32-B 17 13.6 17.8 21.9 25.9 30.0 34.1 38.1 42.1
ICM40-A 15 12.0 15.7 19.3 22.8 26.5 30.1 33.6 37.2
40
ICM40-B 26 20.7 27.2 33.4 39.6 45.9 52.2 58.3 64.4
ICM50-A 23 18.3 24.1 29.6 35.0 40.6 46.2 51.6 57.0
50
ICM50-B 40 31.9 41.9 51.4 60.9 70.6 80.3 89.7 99.1
ICM65-B 65 70 55.8 73.3 90.0 107 124 141 157 173

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (bar) Correction factor Circulation rate Correction factor
0.2 1.00 2 0.77
0.25 0.89 3 0.90
0.3 0.82 4 1
0.4 0.71 6 1.13
0.5 0.63 8 1.20
0.6 0.58 10 1.25

R 22
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60 80


Capacity table at nominal
conditions, QN [Tons of ICM20-A 0.7 0.1 0.2 0.2 0.3 0.3 0.4 0.4 0.5
Refrigeration], ICM20-B 20 2.8 0.5 0.7 0.9 1.1 1.3 1.5 1.7 1.8
Circulation rate = 4, ICM20-C 5.3 1.0 1.4 1.7 2.1 2.4 2.8 3.1 3.5
∆p = 3 psi ICM25-A 7 1.3 1.8 2.3 2.8 3.2 3.7 4.1 4.6
25
ICM25-B 14 2.7 3.6 4.6 5.5 6.4 7.4 8.3 9.2
ICM32-A 10 1.9 2.6 3.3 3.9 4.6 5.3 5.9 6.5
32
ICM32-B 20 3.8 5.2 6.5 7.9 9.2 10.5 11.9 13.1
ICM40-A 17 3.2 4.4 5.6 6.7 7.8 9.0 10.1 11.1
40
ICM40-B 30 5.7 7.8 9.8 11.8 13.8 15.8 17.8 19.6
ICM50-A 27 5.1 7.0 8.8 10.6 12.4 14.2 16.0 17.7
50
ICM50-B 46 8.7 12.0 15.0 18.1 21.2 24.2 27.3 30.1
ICM65-B 65 81 15.4 21.1 26.5 31.9 37.3 42.7 48.0 53.0

Correction factor for


Correction factor for ∆P (f∆P) circulation rate (frec)
∆P (psi) Correction factor Circulation rate Correction factor
3 1.00 2 0.77
4 0.87 3 0.90
5 0.79 4 1
6 0.72 6 1.13
7 0.66 8 1.20
8 0.62 10 1.25

30 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Dry suction line
Location of valve in system (marked with grey)
Hot gas bypass & defrost line

Discharge
line
Dry suction line ICM
Wet suction line

Liquid line without phase change Liquid line with or without phase change

SI units Calculation example (R717 capacities):

An application has following running conditions: Therefore the actual capacity must be corrected
to nominal condition by means of correction
Te = –20°C factors.
Qo = 90 kW Correction factor for ∆p 0.3 bar f∆p = 0.82
Tliq = 10°C Correction factor for liquid temperature fTliq = 0.92
Max. ∆p = 0.3 bar
Connection: DN32 Qn = Qo × f∆p × fTliq = 90 × 0.82 × 0.92 = 68 kW

The capacity table is based on nominal condition From the capacity table a ICM 32-B with Qn
(pressure drop ∆p = 0.2 bar, Tliq = 30°C) capacity 92.3 kW is selected.

US units Calculation example (R717 capacities):

An application has following running conditions: Therefore the actual capacity must be corrected
to nominal condition by means of correction
Te = 0°F factors.
Qo = 20 TR Correction factor for ∆p 3.5 psi f∆p = 0.91
Tliq = 50°F Correction factor for liquid temperature fTliq = 0.92
Max. ∆p = 3.5 psi
Connection: 11/4” Qn = Qo × f∆p × fTliq = 20 × 0.91 × 0.92 = 16.7 TR

The capacity table is based on nominal condition From the capacity table a ICM 32-B with Qn
(∆p = 3 psi, Tliq = 90°F) capacity 28.2 TR is selected.

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 31


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Dry suction line
R 717
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–50 –40 –30 –20 –10 0 10 20
Capacity table at nominal
conditions, QN [kW], ICM20-A 0.6 1.6 2.0 2.6 3.3 4.0 4.9 5.9 6.9
Tliq = 30°C, ICM20-B 20 2.4 6.2 8.0 10.3 13.0 16.1 19.5 23.4 27.7
∆p = 0.2 bar ICM20-C 4.6 11.9 15.3 19.8 25.0 30.9 37.5 44.9 53.0
Superheating = 8°C ICM25-A 6 15.5 20.0 25.8 32.6 40.3 48.9 58.5 69.2
25
ICM25-B 12 31.0 40.0 51.6 65.1 80.6 97.7 117 138
ICM32-A 9 23.3 30.0 38.7 48.9 60.4 73.3 87.8 104
32
ICM32-B 17 44.0 56.7 73.1 92.3 114 138 166 196
ICM40-A 15 38.8 50.0 64.5 81.4 101 122 146 173
40
ICM40-B 26 67.2 86.7 112 141 175 212 254 300
ICM50-A 23 59.5 76.7 98.9 125 154 187 224 265
50
ICM50-B 40 103 133 172 217 269 326 390 461
ICM65-B 65 70 181 234 301 380 470 570 683 807

Correction factor for liquid


temperature (Tliq)
Liquid
Correction factor
temperature
Correction factor for ∆P (f∆P) –20°C 0.82
∆P (bar) Correction factor –10°C 0.86
0.05 2.00 0°C 0.88
0.1 1.41 10°C 0.92
0.2 1.00 20°C 0.96
0.3 0.82 30°C 1.00
0.4 0.71 40°C 1.04
0.5 0.63 50°C 1.09

R 717
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60 80


Capacity table at nominal
conditions, QN [Tons of ICM20-A 0.7 0.5 0.6 0.8 1.0 1.2 1.5 1.9 2.2
Refrigeration], ICM20-B 20 2.8 1.9 2.3 3.1 3.9 5.0 6.1 7.4 8.8
Tliq = 90°F, ICM20-C 5.3 3.5 4.4 5.8 7.5 9.4 11.6 14.0 16.8
∆p = 3 psi ICM25-A 7 4.7 5.8 7.6 9.9 12.4 15.3 18.5 22.1
25
Superheating = 12°F ICM25-B 14 9.3 11.6 15.3 19.7 24.8 30.6 37.1 44.2
ICM32-A 10 6.7 8.3 10.9 14.1 17.7 21.9 26.5 31.6
32
ICM32-B 20 13.3 16.5 21.9 28.2 35.5 43.8 53.0 63.2
ICM40-A 17 11.3 14.0 18.6 23.9 30.1 37.2 45.0 53.7
40
ICM40-B 30 20.0 24.8 32.8 42.3 53.2 65.6 79.4 94.8
ICM50-A 27 18.0 22.3 29.5 38.0 47.9 59.1 71.5 85.3
50
ICM50-B 46 30.7 38.0 50.3 64.8 81.6 101 122 145
ICM65-B 65 81 54.0 66.9 88.5 114 144 177 215 256

Correction factor for liquid


temperature (Tliq)
Liquid
Correction factor
temperature
Correction factor for ∆P (f∆P) –10°F 0.82
∆P (psi) Correction factor Correction factor for 10°F 0.85
0.75 1.97 superheat (TS) 30°F 0.88
1.5 1.39 Τs Correction factor 50°F 0.92
3 1.00 10°F 1.00 70°F 0.96
3.5 0.91 14°F 1.00 90°F 1.00
4 0.85 18°F 1.00 110°F 1.04
4.5 0.81 20°F 1.00 130°F 1.09

32 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Dry suction line
R 744
SI units Type Valve body
size
Kv Evaporating temperature [°C]

Capacity table at nominal (m3/h) –50 –40 –30 –20 –10 0 10


conditions, QN [kW], ICM20-A 0.6 2.1 2.6 3.1 3.7 4.3 4.9 5.6
Tliq = 10°C, ICM20-B 20 2.4 8.4 10.3 12.4 14.6 17.1 19.6 22.3
∆p = 0.2 bar ICM20-C 4.6 16.1 19.7 23.7 28.1 32.7 37.7 42.8
Superheating = 8°C ICM25-A 6 21.0 25.8 30.9 36.6 42.7 49.1 55.8
25
ICM25-B 12 42.1 51.5 61.9 73.2 85.4 98.2 112
ICM32-A 9 31.6 38.6 46.4 54.9 64.0 73.7 83.7
32
ICM32-B 17 59.6 73.0 87.7 104 121 139 158
ICM40-A 15 52.6 64.4 77.4 91.5 107 123 140
40
ICM40-B 26 91.2 112 134 159 185 213 242
ICM50-A 23 80.7 98.7 119 140 164 188 214
50
ICM50-B 40 140 172 206 244 285 327 372
ICM65-B 65 70 246 301 361 427 498 573 651

Correction factor for liquid


Correction factor for ∆P (f∆P) temperature (Tliq)
∆P (bar) Correction factor Liquid
Correction factor
0.05 2.00 temperature
0.1 1.41 –20°C 0.52
0.2 1.00 –10°C 0.67
0.3 0.82 0°C 0.91
0.4 0.71 10°C 1.00
0.5 0.63 15°C 1.09

R 744
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60


Capacity table at nominal
conditions, QN [Tons of ICM20-A 0.7 0.6 0.7 0.9 1.1 1.3 1.5 1.7
Refrigeration], ICM20-B 20 2.8 2.4 3.0 3.7 4.4 5.2 6.0 6.9
Tliq = 50°F, ICM20-C 5.3 4.5 5.7 6.9 8.3 9.8 11.4 13.0
∆p = 3 psi ICM25-A 7 6.0 7.5 9.1 11.0 13.0 15.1 17.2
25
Superheating = 12°F ICM25-B 14 11.9 14.9 18.3 22.0 26.0 30.2 34.5
ICM32-A 10 8.5 10.7 13.1 15.7 18.5 21.5 24.6
32
ICM32-B 20 17.0 21.3 26.1 31.4 37.1 43.1 49.2
ICM40-A 17 14.5 18.1 22.2 26.7 31.5 36.6 41.8
40
ICM40-B 30 25.5 32.0 39.2 47.1 55.6 64.6 73.9
ICM50-A 27 23.0 28.8 35.3 42.4 50.1 58.2 66.5
50
ICM50-B 46 39.1 49.1 60.1 72.2 85.3 99.1 113
ICM65-B 65 81 68.9 86.4 106 127 150 175 199

Correction factor for ∆P (f∆P) Correction factor for liquid


∆P (psi) Correction factor Correction factor for temperature (Tliq)
0.75 1.97 superheat (TS) Liquid
Correction factor
1.5 1.39 Τs Correction factor temperature
3 1.00 10°F 1.00 –10°F 0.48
3.5 0.91 14°F 1.00 10°F 0.64
4 0.85 18°F 1.00 30°F 0.88
4.5 0.81 20°F 1.00 50°F 1.00

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 33


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Dry suction line
R 134a
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–40 –30 –20 –10 0 10 20
Capacity table at nominal
conditions, QN [kW], ICM20-A 0.6 0.5 0.7 0.9 1.2 1.4 1.8 2.1
Tliq = 30°C, ICM20-B 20 2.4 2.1 2.8 3.6 4.6 5.7 7.0 8.5
∆p = 0.2 bar ICM20-C 4.6 4.1 5.4 7.0 8.8 11.0 13.5 16.3
Superheating = 8°C ICM25-A 6 5.3 7.0 9.1 11.5 14.4 17.6 21.3
25
ICM25-B 12 10.6 14.1 18.2 23.1 28.7 35.2 42.6
ICM32-A 9 8.0 10.5 13.6 17.3 21.5 26.4 32.0
32
ICM32-B 17 15.1 19.9 25.7 32.7 40.7 49.9 60.4
ICM40-A 15 13.3 17.6 22.7 28.8 35.9 44.0 53.3
40
ICM40-B 26 23.1 30.5 39.4 50.0 62.2 76.3 92.3
ICM50-A 23 20.4 26.9 34.8 44.2 55.0 67.5 81.7
50
ICM50-B 40 35.5 46.9 60.6 76.9 95.7 117 142
ICM65-B 65 70 62.1 82.0 106 135 168 206 249

Correction factor for liquid


temperature (Tliq)
Liquid
Correction factor
temperature
Correction factor for ∆P (f∆P) –20°C 0.66
∆P (bar) Correction factor –10°C 0.70
0.05 2.00 0°C 0.76
0.1 1.41 10°C 0.82
0.2 1.00 20°C 0.90
0.3 0.82 30°C 1.00
0.4 0.71 40°C 1.13
0.5 0.63 50°C 1.29

R 134a
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –40 –20 0 20 40 60 80


Capacity table at nominal
conditions, QN [Tons of ICM20-A 0.7 0.2 0.2 0.3 0.4 0.4 0.6 0.7
Refrigeration], ICM20-B 20 2.8 0.6 0.8 1.1 1.4 1.8 2.2 2.7
Tliq = 90°F, ICM20-C 5.3 1.1 1.6 2.1 2.7 3.4 4.2 5.2
∆p = 3 psi ICM25-A 7 1.5 2.1 2.7 3.5 4.5 5.6 6.9
25
Superheating = 12°F ICM25-B 14 3.0 4.1 5.4 7.1 9.0 11.2 13.7
ICM32-A 10 2.2 2.9 3.9 5.0 6.4 8.0 9.8
32
ICM32-B 20 4.3 5.9 7.8 10.1 12.8 16.0 19.6
ICM40-A 17 3.7 5.0 6.6 8.6 10.9 13.6 16.6
40
ICM40-B 30 6.5 8.8 11.7 15.1 19.2 23.9 29.4
ICM50-A 27 5.8 7.9 10.5 13.6 17.3 21.5 26.4
50
ICM50-B 46 9.9 13.5 17.9 23.2 29.4 36.7 45.0
ICM65-B 65 81 17.4 23.8 31.5 40.8 51.8 64.6 79.3

Correction factor for liquid


temperature (Tliq)
Liquid
Correction factor
temperature
Correction factor for ∆P (f∆P) –10°F 0.64
∆P (psi) Correction factor Correction factor for 10°F 0.68
0.75 1.97 superheat (TS) 30°F 0.74
1.5 1.39 Τs Correction factor 50°F 0.81
3 1.00 10°F 1.00 70°F 0.89
3.5 0.91 14°F 1.00 90°F 1.00
4 0.85 18°F 1.00 110°F 1.15
4.5 0.81 20°F 1.00 130°F 1.35

34 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Dry suction line
R 404A
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–50 –40 –30 –20 –10 0 10 20
Capacity table at nominal
conditions, QN [kW], ICM20-A 0.6 0.5 0.6 0.8 1.1 1.3 1.6 2.0 2.4
Tliq = 30°C, ICM20-B 20 2.4 1.9 2.5 3.3 4.2 5.3 6.5 8.0 9.6
∆p = 0.2 bar ICM20-C 4.6 3.6 4.9 6.3 8.1 10.2 12.5 15.2 18.3
Superheating = 8°C ICM25-A 6 4.8 6.4 8.3 10.6 13.2 16.3 19.9 23.9
25
ICM25-B 12 9.5 12.7 16.5 21.1 26.5 32.7 39.8 47.8
ICM32-A 9 7.1 9.5 12.4 15.9 19.9 24.5 29.8 35.9
32
ICM32-B 17 13.5 18.0 23.4 29.9 37.5 46.3 56.3 67.8
ICM40-A 15 11.9 15.9 20.7 26.4 33.1 40.8 49.7 59.8
40
ICM40-B 26 20.6 27.5 35.8 45.8 57.4 70.8 86.2 104
ICM50-A 23 18.2 24.3 31.7 40.5 50.8 62.6 76.2 91.7
50
ICM50-B 40 31.7 42.3 55.1 70.5 88.3 109 133 159
ICM65-B 65 70 55.5 74.1 96.5 123 155 191 232 279

Correction factor for liquid


temperature (Tliq)
Liquid
Correction factor
temperature
Correction factor for ∆P (f∆P) –20°C 0.55
∆P (bar) Correction factor –10°C 0.60
0.05 2.00 0°C 0.66
0.1 1.41 10°C 0.74
0.2 1.00 20°C 0.85
0.3 0.82 30°C 1.00
0.4 0.71 40°C 1.23
0.5 0.63 50°C 1.68

R 404A
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60 80


Capacity table at nominal
conditions, QN [Tons of ICM20-A 0.7 0.1 0.2 0.2 0.3 0.4 0.5 0.6 0.8
Refrigeration], ICM20-B 20 2.8 0.5 0.7 1.0 1.2 1.6 2.0 2.5 3.0
Tliq = 90°F, ICM20-C 5.3 1.0 1.3 1.8 2.4 3.0 3.8 4.7 5.7
∆p = 3 psi ICM25-A 7 1.3 1.8 2.4 3.1 4.0 5.0 6.2 7.6
25
Superheating = 12°F ICM25-B 14 2.6 3.5 4.8 6.2 8.0 10.0 12.4 15.2
ICM32-A 10 1.8 2.5 3.4 4.5 5.7 7.2 8.9 10.8
32
ICM32-B 20 3.7 5.1 6.8 8.9 11.4 14.3 17.8 21.7
ICM40-A 17 3.1 4.3 5.8 7.6 9.7 12.2 15.1 18.4
40
ICM40-B 30 5.5 7.6 10.2 13.4 17.1 21.5 26.6 32.5
ICM50-A 27 4.9 6.8 9.2 12.0 15.4 19.4 24.0 29.3
50
ICM50-B 46 8.4 11.6 15.7 20.5 26.2 33.0 40.8 49.9
ICM65-B 65 81 14.8 20.5 27.6 36.1 46.2 58.1 71.9 87.8

Correction factor for liquid


temperature (Tliq)
Liquid
Correction factor
temperature
Correction factor for ∆P (f∆P) –10°F 0.52
∆P (psi) Correction factor Correction factor for 10°F 0.57
0.75 1.97 superheat (TS) 30°F 0.63
1.5 1.39 Τs Correction factor 50°F 0.72
3 1.00 10°F 1.00 70°F 0.83
3.5 0.91 14°F 1.00 90°F 1.00
4 0.85 18°F 1.00 110°F 1.29
4.5 0.81 20°F 1.00 130°F 1.92

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 35


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Dry suction line
R 22
SI units Type Valve body
size
Kv Evaporating temperature [°C]

(m /h)
3
–50 –40 –30 –20 –10 0 10 20
Capacity table at nominal
conditions, QN [kW], ICM20-A 0.6 0.6 0.8 1.0 1.3 1.5 1.9 2.2 2.6
Tliq = 30°C, ICM20-B 20 2.4 2.5 3.2 4.1 5.0 6.2 7.4 8.8 10.4
∆p = 0.2 bar ICM20-C 4.6 4.7 6.1 7.8 9.7 11.8 14.2 16.9 19.9
Superheating = 8°C ICM25-A 6 6.2 8.0 10.1 12.6 15.4 18.6 22.1 26.0
25
ICM25-B 12 12.3 16.0 20.3 25.2 30.8 37.1 44.1 51.9
ICM32-A 9 9.3 12.0 15.2 18.9 23.1 27.8 33.1 39.0
32
ICM32-B 17 17.5 22.6 28.7 35.7 43.6 52.6 62.5 73.6
ICM40-A 15 15.4 20.0 25.4 31.5 38.5 46.4 55.2 64.9
40
ICM40-B 26 26.7 34.6 43.9 54.6 66.7 80.4 95.6 113
ICM50-A 23 23.7 30.6 38.9 48.3 59.0 71.1 84.6 100
50
ICM50-B 40 41.1 53.3 67.6 84.0 103 124 147 173
ICM65-B 65 70 72.0 93.2 118 147 180 217 258 303

Correction factor for liquid


temperature (Tliq)
Liquid temperature Correction factor
Correction factor for ∆P (f∆P) –20°C 0.71
∆P (bar) Correction factor –10°C 0.75
0.2 1.00 0°C 0.80
0.25 0.89 10°C 0.86
0.3 0.82 20°C 0.92
0.4 0.71 30°C 1.00
0.5 0.63 40°C 1.09
0.6 0.58 50°C 1.22

R 22
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60 80


Capacity table at nominal
conditions, QN [Tons of ICM20-A 0.7 0.2 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Refrigeration], ICM20-B 20 2.8 0.7 0.9 1.2 1.5 1.9 2.3 2.8 3.3
Tliq = 90°F, ICM20-C 5.3 1.3 1.7 2.2 2.9 3.6 4.3 5.2 6.2
∆p = 3 psi ICM25-A 7 1.7 2.3 3.0 3.8 4.7 5.7 6.9 8.2
25
Superheating = 12°F ICM25-B 14 3.4 4.6 5.9 7.5 9.4 11.5 13.8 16.4
ICM32-A 10 2.4 3.3 4.2 5.4 6.7 8.2 9.9 11.7
32
ICM32-B 20 4.9 6.5 8.5 10.8 13.4 16.4 19.8 23.5
ICM40-A 17 4.1 5.5 7.2 9.2 11.4 13.9 16.8 20.0
40
ICM40-B 30 7.3 9.8 12.7 16.1 20.1 24.6 29.6 35.2
ICM50-A 27 6.6 8.8 11.4 14.5 18.1 22.1 26.7 31.7
50
ICM50-B 46 11.2 15.0 19.5 24.8 30.8 37.7 45.4 54.0
ICM65-B 65 81 19.7 26.4 34.3 43.6 54.3 66.4 80.0 95.1

Correction factor for liquid


temperature (Tliq)
Liquid temperature Correction factor
Correction factor for ∆P (f∆P) –10°F 0.73
∆P (psi) Correction factor Correction factor for 10°F 0.77
3 1.00 superheat (TS) 30°F 0.82
4 0.87 Τs Correction factor 50°F 0.87
5 0.79 10°F 1.00 70°F 0.93
6 0.72 14°F 1.00 90°F 1.00
7 0.66 18°F 1.00 110°F 1.09
8 0.62 20°F 1.00 130°F 1.20

36 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Discharge line
Location of valve in system (marked with grey)
Hot gas bypass & defrost line

Discharge
line
Dry suction line ICM
Wet suction line

Liquid line without phase change Liquid line with or without phase change

SI units Calculation example (R717 capacities):

An application has following running conditions: Therefore the actual capacity must be corrected
to nominal condition by means of correction
Te = –20°C factors.
Qo = 90 kW Correction factor for ∆p 0.4 bar f∆p = 0.72
Tliq = 10°C Correction factor for liquid temperature fTliq = 0.92
Max. ∆p = 0.4 bar Correction factor for Tdisch. 60°C, fdisch. = 0.97
Tdisch. = 60°C
Connection: DN25 Qn = Qo × f∆p × fTliq × fTdisch. =
90 × 0.72 × 0.92 × 0.97 = 58 kW
The capacity table is based on nominal condition
(∆p = 0.2 bar, Tliq = 30°C, Pdisch. = 12 bar, Tdisch. = From the capacity table a ICM 25-A with Qn
80°C) capacity 73.2 kW is selected.

US units Calculation example (R717 capacities):

An application has following running conditions: Therefore the actual capacity must be corrected
to nominal condition by means of correction
Te = 0°F factors.
Qo = 8 TR Correction factor for ∆p 4.5 psi f∆p = 0.81
Tliq = 50°F Correction factor for liquid temperature fTliq = 0.92
Max. ∆p = 4.5 psi Correction factor for Tdisch. 120°F, fdisch. = 0.95
Tdisch. = 120°F
Connection: 3/4” Qn = Qo × f∆p × fTliq × fTdisch. =
8 × 0.81 × 0.92 × 0.95 = 5.7 TR
The capacity table is based on nominal condition
(∆p = 3 psi, Tliq = 90°F, Pdisch. = 185 psi, Tdisch. = From the capacity table a ICM 20-B with Qn
180°F) capacity 8.4 TR is selected.

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 37


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Discharge line
R 717
SI units Type Valve body
size
Kv Evaporating temperature [°C]

Capacity table at nominal (m3/h) –50 –40 –30 –20 –10 0 10 20


conditions, QN [kW], ICM20-A 0.6 7.0 7.1 7.2 7.3 7.4 7.5 7.5 7.6
Tliq = 30°C, ICM20-B 20 2.4 28.0 28.5 28.9 29.3 29.6 29.9 30.1 30.3
∆p = 0.2 bar, ICM20-C 4.6 53.7 54.5 55.4 56.1 56.8 57.3 57.8 58.1
Pdisch. = 12 bar, ICM25-A 6 70.0 71.1 72.3 73.2 74.1 74.7 75.3 75.8
Tdisch. = 80°C 25
ICM25-B 12 140 142 145 146 148 149 151 152
Superheating = 8°C ICM32-A 9 105 107 108 110 111 112 113 114
32
ICM32-B 17 198 202 205 207 210 212 213 215
ICM40-A 15 175 178 181 183 185 187 188 189
40
ICM40-B 26 303 308 313 317 321 324 326 328
ICM50-A 23 268 273 277 281 284 287 289 290
50
ICM50-B 40 467 474 482 488 494 498 502 505
ICM65-B 65 70 817 830 843 854 864 872 879 884

Correction factor for liquid


Correction factor for discharge temperature (Tliq)
temperature (Tdisch). Liquid
Correction factor
Discharge temperature
Correction factor
Correction factor for ∆P (f∆P) temperature –20°C 0.82
∆P (bar) Correction factor 50°C 0.96 –10°C 0.86
0.05 2.00 60°C 0.97 0°C 0.88
0.1 1.41 80°C 1.00 10°C 0.92
0.2 1.00 90°C 1.01 20°C 0.96
0.3 0.82 100°C 1.03 30°C 1.00
0.4 0.71 110°C 1.04 40°C 1.04
0.5 0.63 120°C 1.06 50°C 1.09

R 717
US units Type Valve body Cv Evaporating temperature [°F]
size
Capacity table at nominal (USgal/min) –60 –40 –20 0 20 40 60 80
conditions, QN [Tons of ICM20-A 0.7 2.0 2.0 2.1 2.1 2.1 2.2 2.2 2.2
Refrigeration], ICM20-B 20 2.8 8.0 8.2 8.3 8.4 8.5 8.6 8.7 8.7
Tliq = 90°F, ICM20-C 5.3 15.2 15.4 15.7 15.9 16.1 16.3 16.4 16.5
∆p = 2.9 psi, ICM25-A 7 20.0 20.4 20.7 21.0 21.3 21.5 21.7 21.8
Pdisch. = 185 psi, 25
ICM25-B 14 40.1 40.8 41.5 42.0 42.6 43.0 43.4 43.6
Tdisch. = 180°F ICM32-A 10 28.6 29.1 29.6 30.0 30.4 30.7 31.0 31.2
Superheating = 12°F ICM32-B
32
20 57.3 58.3 59.3 60.0 60.9 61.5 62.0 62.3
ICM40-A 17 48.7 49.5 50.4 51.0 51.7 52.3 52.7 53.0
40
ICM40-B 30 85.9 87.4 88.9 90.0 91.3 92.2 93.0 93.5
ICM50-A 27 77.3 78.7 80.0 81.0 82.2 83.0 83.7 84.2
50
ICM50-B 46 132 134 136 138 140 141 143 143
ICM65-B 65 81 232 236 240 243 247 249 251 253

Correction factor for liquid


Correction factor for discharge temperature (Tliq)
temperature (Tdisch). Liquid
Correction factor
Discharge temperature
Correction factor
Correction factor for ∆P (f∆P) temperature –10°F 0.82
∆P (psi) Correction factor 120°F 0.95 10°F 0.85
0.75 1.97 140°F 0.97 30°F 0.88
1.5 1.39 180°F 1.00 50°F 0.92
3 1.00 200°F 1.02 70°F 0.96
3.5 0.91 210°F 1.02 90°F 1.00
4 0.85 230°F 1.04 110°F 1.04
4.5 0.81 250°F 1.05 130°F 1.09

38 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Discharge line
R 744
SI units Type Valve body
size
Kv Evaporating temperature [°C]

Capacity table at nominal (m3/h) –50 –40 –30 –20 –10 0 10


conditions, QN [kW], ICM20-A 0.6 4.4 4.5 4.5 4.6 4.6 4.5 4.4
Tliq = 10°C, ICM20-B 20 2.4 17.7 17.9 18.1 18.2 18.2 18.0 17.7
∆p = 0.2 bar, ICM20-C 4.6 33.8 34.4 34.8 34.9 34.9 34.6 33.9
Pdisch. = 10 bar, ICM25-A 6 44.1 44.8 45.3 45.5 45.5 45.1 44.2
Tdisch. = 80°C 25
ICM25-B 12 88.3 89.7 90.7 91.0 91.0 90.2 88.5
Superheating = 8°C ICM32-A 9 66.2 67.2 68.0 68.3 68.3 67.6 66.3
32
ICM32-B 17 125 127 128 129 129 128 125
ICM40-A 15 110 112 113 114 114 113 111
40
ICM40-B 26 191 194 196 197 197 195 192
ICM50-A 23 169 172 174 174 174 173 170
50
ICM50-B 40 294 299 302 303 303 301 295
ICM65-B 65 70 515 523 529 531 531 526 516

Correction factor for discharge


temperature (Tdisch).
Discharge
Correction factor
Correction factor for liquid
Correction factor for ∆P (f∆P) temperature temperature (Tliq)
∆P (bar) Correction factor 50°C 0.96 Liquid
Correction factor
0.05 2.00 60°C 0.97 temperature
0.1 1.41 80°C 1.00 –20°C 0.52
0.2 1.00 90°C 1.01 –10°C 0.67
0.3 0.82 100°C 1.03 0°C 0.91
0.4 0.71 110°C 1.04 10°C 1.00
0.5 0.63 120°C 1.06 15°C 1.09

R 744
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60


Capacity table at nominal
conditions, QN [Tons of ICM20-A 0.7 1.2 1.3 1.3 1.3 1.3 1.2 1.2
Refrigeration], ICM20-B 20 2.8 4.9 5.0 5.1 5.1 5.1 5.0 5.0
Tliq = 90°F, ICM20-C 5.3 9.3 9.5 9.6 9.7 9.6 9.5 9.5
∆p = 3 psi, ICM25-A 7 12.3 12.6 12.7 12.8 12.7 12.5 12.5
25
Pdisch. = 120 psi, ICM25-B 14 24.7 25.1 25.4 25.5 25.4 25.0 25.0
Tdisch. = 180°F ICM32-A 10 17.6 18.0 18.1 18.2 18.1 17.8 17.8
Superheating = 12°F 32
ICM32-B 20 35.3 35.9 36.3 36.5 36.3 35.7 35.7
ICM40-A 17 30.0 30.5 30.9 31.0 30.9 30.3 30.3
40
ICM40-B 30 52.9 53.9 54.4 54.7 54.4 53.5 53.5
ICM50-A 27 47.6 48.5 49.0 49.2 49.0 48.2 48.2
50
ICM50-B 46 81.1 82.6 83.5 83.9 83.5 82.1 82.1
ICM65-B 65 81 143 145 147 148 147 145 145

Correction factor for discharge


temperature (Tdisch).
Discharge
Correction factor
Correction factor for ∆P (f∆P) temperature Correction factor for liquid
∆P (psi) Correction factor 120°F 0.95 temperature (Tliq)
0.75 1.97 140°F 0.97 Liquid
Correction factor
1.5 1.39 180°F 1.00 temperature
3 1.00 200°F 1.02 –10°F 0.48
3.5 0.91 210°F 1.02 10°F 0.64
4 0.85 230°F 1.04 30°F 0.88
4.5 0.81 250°F 1.05 50°F 1.00

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 39


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Discharge line
R 134a
SI units Type Valve body
size
Kv Evaporating temperature [°C]

Capacity table at nominal (m3/h) –40 –30 –20 –10 0 10 20


conditions, QN [kW], ICM20-A 0.6 5.7 6.0 6.3 6.5 6.8 7.0 7.3
Tliq = 30°C, ICM20-B 20 2.4 22.9 24.0 25.1 26.1 27.2 28.2 29.1
∆p = 0.2 bar, ICM20-C 4.6 43.8 45.9 48.0 50.1 52.0 54.0 55.9
Pdisch. = 8 bar, ICM25-A 6 57.2 59.9 62.7 65.3 67.9 70.5 72.9
Tdisch. = 80°C 25
ICM25-B 12 114 120 125 131 136 141 146
Superheating = 8°C ICM32-A 9 85.8 89.9 94.0 98.0 102 106 109
32
ICM32-B 17 162 170 178 185 192 200 206
ICM40-A 15 143 150 157 163 170 176 182
40
ICM40-B 26 248 260 272 283 294 305 316
ICM50-A 23 219 230 240 250 260 270 279
50
ICM50-B 40 381 399 418 435 453 470 486
ICM65-B 65 70 667 699 731 762 792 822 850

Correction factor for liquid


Correction factor for discharge temperature (Tliq)
temperature (Tdisch). Liquid
Correction factor
Discharge temperature
Correction factor for ∆P (f∆P) Correction factor
temperature –20°C 0.66
∆P (bar) Correction factor 50°C 0.96 –10°C 0.70
0.05 2.00 60°C 0.97 0°C 0.76
0.1 1.41 80°C 1.00 10°C 0.82
0.2 1.00 90°C 1.01 20°C 0.90
0.3 0.82 100°C 1.03 30°C 1.00
0.4 0.71 110°C 1.04 40°C 1.13
0.5 0.63 120°C 1.06 50°C 1.29

R 134a
US units Type Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –40 –20 0 20 40 60 80


Capacity table at nominal
conditions, QN [Tons of ICM20-A 0.7 0.5 0.5 0.6 0.6 0.6 0.6 0.7
Refrigeration], ICM20-B 20 2.8 2.0 2.1 2.3 2.4 2.5 2.6 2.7
Tliq = 90°F, ICM20-C 5.3 3.9 4.1 4.3 4.5 4.7 4.9 5.0
∆p = 3 psi, ICM25-A 7 5.1 5.4 5.6 5.9 6.2 6.4 6.7
25
Pdisch. = 120 psi, ICM25-B 14 10.2 10.7 11.3 11.8 12.3 12.8 13.3
Tdisch. = 180°F ICM32-A 10 7.3 7.7 8.0 8.4 8.8 9.2 9.5
Superheating = 12°F 32
ICM32-B 20 14.5 15.3 16.1 16.9 17.6 18.3 19.0
ICM40-A 17 12.4 13.0 13.7 14.3 15.0 15.6 16.2
40
ICM40-B 30 21.8 23.0 24.1 25.3 26.4 27.5 28.5
ICM50-A 27 19.6 20.7 21.7 22.8 23.8 24.7 25.7
50
ICM50-B 46 33.4 35.3 37.0 38.8 40.5 42.1 43.7
ICM65-B 65 81 58.9 62.1 65.2 68.3 71.3 74.2 77.0

Correction factor for liquid


Correction factor for discharge temperature (Tliq)
temperature (Tdisch). Liquid
Correction factor
Discharge temperature
Correction factor for ∆P (f∆P) Correction factor
temperature –10°F 0.64
∆P (psi) Correction factor 120°F 0.95 10°F 0.68
0.75 1.97 140°F 0.97 30°F 0.74
1.5 1.39 180°F 1.00 50°F 0.81
3 1.00 200°F 1.02 70°F 0.89
3.5 0.91 210°F 1.02 90°F 1.00
4 0.85 230°F 1.04 110°F 1.15
4.5 0.81 250°F 1.05 130°F 1.35

40 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Discharge line
R 404A
SI units Type Valve body
size
Kv Evaporating temperature [°C]

Capacity table at nominal (m3/h) –50 –40 –30 –20 –10 0 10 20


conditions, QN [kW], ICM20-A 0.6 5.3 5.7 6.0 6.4 6.7 7.1 7.4 7.6
Tliq = 30°C, ICM20-B 20 2.4 21.2 22.6 24.1 25.5 26.9 28.2 29.5 30.5
∆p = 0.2 bar, ICM20-C 4.6 40.6 43.4 46.2 48.9 51.5 54.1 56.4 58.6
Pdisch. = 12 bar, ICM25-A 6 53.0 56.6 60.3 63.8 67.2 70.5 73.6 76.4
Tdisch. = 80°C 25
ICM25-B 12 106 113 121 128 134 141 147 153
Superheating = 8°C ICM32-A 9 79.5 84.9 90.4 95.7 101 106 110 115
32
ICM32-B 17 150 160 171 181 190 200 209 216
ICM40-A 15 132 141 151 159 168 176 184 191
40
ICM40-B 26 230 245 261 276 291 306 319 331
ICM50-A 23 203 217 231 244 258 270 282 293
50
ICM50-B 40 353 377 402 425 448 470 491 509
ICM65-B 65 70 618 660 703 744 784 823 859 891

Correction factor for liquid


Correction factor for discharge temperature (Tliq)
temperature (Tdisch). Liquid
Correction factor
Discharge temperature
Correction factor
Correction factor for ∆P (f∆P) temperature –20°C 0.55
∆P (bar) Correction factor 50°C 0.96 –10°C 0.60
0.05 2.00 60°C 0.97 0°C 0.66
0.1 1.41 80°C 1.00 10°C 0.74
0.2 1.00 90°C 1.01 20°C 0.85
0.3 0.82 100°C 1.03 30°C 1.00
0.4 0.71 110°C 1.04 40°C 1.23
0.5 0.63 120°C 1.06 50°C 1.68

R 404A
US units Typ Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60 80


Capacity table at nominal
ICM20-A 0.7 0.5 0.5 0.5 0.6 0.6 0.6 0.7 0.7
conditions, QN [Tons of
ICM20-B 20 2.8 1.8 2.0 2.1 2.3 2.4 2.5 2.7 2.8
Refrigeration],
Tliq = 90°F, ICM20-C 5.3 3.5 3.7 4.0 4.3 4.6 4.8 5.0 5.2
∆p = 3 psi, ICM25-A
25
7 4.6 5.0 5.3 5.7 6.0 6.4 6.6 6.9
Pdisch. = 120 psi, ICM25-B 14 9.2 9.9 10.6 11.4 12.0 12.7 13.3 13.8
Tdisch. = 180°F ICM32-A 10 6.5 7.1 7.6 8.1 8.6 9.1 9.5 9.9
32
Superheating = 12°F ICM32-B 20 13.1 14.1 15.2 16.2 17.2 18.1 19.0 19.7
ICM40-A 17 11.1 12.0 12.9 13.8 14.6 15.4 16.1 16.8
40
ICM40-B 30 19.6 21.2 22.8 24.3 25.8 27.2 28.5 29.6
ICM50-A 27 17.7 19.1 20.5 21.9 23.2 24.5 25.6 26.6
50
ICM50-B 46 30.1 32.5 35.0 37.3 39.6 41.7 43.7 45.4
ICM65-B 65 81 53.0 57.3 61.6 65.7 69.7 73.5 76.9 79.9

Correction factor for liquid


Correction factor for discharge temperature (Tliq)
temperature (Tdisch). Liquid
Correction factor
Discharge temperature
Correction factor
Correction factor for ∆P (f∆P) temperature –10°F 0.52
∆P (psi) Correction factor 120°F 0.95 10°F 0.57
0.75 1.97 140°F 0.97 30°F 0.63
1.5 1.39 180°F 1.00 50°F 0.72
3 1.00 200°F 1.02 70°F 0.83
3.5 0.91 210°F 1.02 90°F 1.00
4 0.85 230°F 1.04 110°F 1.29
4.5 0.81 250°F 1.05 130°F 1.92

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 41


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Discharge line
R 22
SI units Type Valve body
size
Kv Evaporating temperature [°C]

Capacity table at nominal (m3/h) –50 –40 –30 –20 –10 0 10 20


conditions, QN [kW], ICM20-A 0.6 2.3 2.3 2.4 2.5 2.5 2.6 2.7 2.7
Tliq = 30°C, ICM20-B 20 2.4 9.1 9.3 9.6 9.9 10.1 10.4 10.6 10.8
∆p = 0.2 bar, ICM20-C 4.6 17.3 17.9 18.4 19.0 19.5 19.9 20.4 20.8
Pdisch. = 12 bar, ICM25-A 6 22.6 23.4 24.0 24.7 25.4 26.0 26.6 27.1
Tdisch. = 80°C 25
ICM25-B 12 45.3 46.7 48.1 49.5 50.7 51.9 53.1 54.2
Superheating = 8°C ICM32-A 9 33.9 35.0 36.1 37.1 38.1 39.0 39.9 40.6
32
ICM32-B 17 64.1 66.2 68.1 70.1 71.9 73.6 75.3 76.7
ICM40-A 15 56.6 58.4 60.1 61.8 63.4 64.9 66.4 67.7
40
ICM40-B 26 98.1 101 104 107 110 113 115 117
ICM50-A 23 86.7 89.5 92.2 94.8 97.3 100 102 104
50
ICM50-B 40 151 156 160 165 169 173 177 181
ICM65-B 65 70 264 273 281 289 296 303 310 316

Correction factor for liquid


Correction factor for discharge temperature (Tliq).
temperature (Tdisch). Liquid
Correction factor
Discharge temperature
Correction factor
Correction factor for ∆P (f ) ∆P temperature –20°C 0.71
∆P (bar) Correction factor 50°C 0.96 –10°C 0.75
0.2 1.00 60°C 0.97 0°C 0.80
0.25 0.89 80°C 1.00 10°C 0.86
0.3 0.82 90°C 1.01 20°C 0.92
0.4 0.71 100°C 1.03 30°C 1.00
0.5 0.63 110°C 1.04 40°C 1.09
0.6 0.58 120°C 1.06 50°C 1.22

R 22
US units Typ Valve body
size
Cv Evaporating temperature [°F]

(USgal/min) –60 –40 –20 0 20 40 60 80


Capacity table at nominal
ICM20-A 0.7 0.6 0.7 0.7 0.7 0.7 0.7 0.8 0.8
conditions, QN [Tons of
ICM20-B 20 2.8 2.6 2.6 2.7 2.8 2.9 3.0 3.0 3.1
Refrigeration],
Tliq = 90°F, ICM20-C 5.3 4.8 5.0 5.2 5.3 5.5 5.6 5.8 5.9
∆p = 3 psi, ICM25-A
25
7 6.4 6.6 6.8 7.1 7.3 7.4 7.6 7.8
Pdisch. = 120 psi, ICM25-B 14 12.8 13.2 13.7 14.1 14.5 14.9 15.2 15.6
Tdisch. = 180°F ICM32-A 10 9.1 9.5 9.8 10.1 10.4 10.6 10.9 11.1
32
Superheating = 12°F ICM32-B 20 18.2 18.9 19.6 20.2 20.7 21.3 21.8 22.2
ICM40-A 17 15.5 16.1 16.6 17.1 17.6 18.1 18.5 18.9
40
ICM40-B 30 27.4 28.4 29.3 30.3 31.1 31.9 32.7 33.3
ICM50-A 27 24.6 25.5 26.4 27.2 28.0 28.7 29.4 30.0
50
ICM50-B 46 42.0 43.5 45.0 46.4 47.7 49.0 50.1 51.1
ICM65-B 65 81 73.9 76.6 79.2 81.7 84.0 86.2 88.2 90.0

Correction factor for liquid


Correction factor for discharge temperature (Tliq).
temperature (Tdisch). Liquid
Correction factor
Discharge temperature
Correction factor
Correction factor for ∆P (f ) ∆P temperature –10°F 0.73
∆P (psi) Correction factor 120°F 0.95 10°F 0.77
3 1.00 140°F 0.97 30°F 0.82
4 0.87 180°F 1.00 50°F 0.87
5 0.79 200°F 1.02 70°F 0.93
6 0.72 210°F 1.02 90°F 1.00
7 0.66 230°F 1.04 110°F 1.09
8 0.62 250°F 1.05 130°F 1.20

42 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Nominal capacities
Expansion - ICM
Location of valve in system (marked with grey)
Hot gas bypass & defrost line Pump
Discharge
line
Dry suction line
Wet suction line

Liquid line without phase change Expansion

Location of valve in system (marked with grey)


Hot gas bypass & defrost line
DX

Dry suction Discharge


line line

Expansion

Correction factors
When dimensioning, multiply the evaporator
capacity by a correction factor k dependent on
the subcooling ∆tsub just ahead of the valve.
The corrected capacity* can then be found in the
capacity table.

Correction factors for subcooling


Subcooling K 2 4 10 15 20 25 30 35 40
R717 1.01 1 0.98 0.96 0.94 0.92 0.91 0.89 0.87
R744 1.02 1 0.95 0.90 0.86 0.82 0.79 0.75 0.73
R134a 1.03 1 0.93 0.88 0.84 0.80 0.76 0.73 0.70
R404A 1.04 1 0.91 0.83 0.78 0.73 0.68 0.65 0.61
R22 1.03 1 0.94 0.90 0.87 0.83 0.80 0.77 0.74
* The capacity table is based on nominal conditions of subcooling just ahead of the valve of 4°K.

Calculation example:
An application has the following operating Correction factor for subcooling: 0.94
conditions:
Pressure drop across the valve:
Refrigerant R717 11.7 bar - 2.9 bar = 8.8 bar
Te = –10°C
Tc = +30°C Corrected capacity: 1500 x 0.94 = 1410 kW
Q0 = 1500 kW
∆tsub = 20°K From the R717 capacity table ICM 20-C is selected
with Qnom capacity 1990 kW at 8 bar.

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 43


Technical leaflet Motor valves, type ICM and actuators type ICAD

Expansion
Capacities for nominal conditions, Qn (kW)
R 717
Pressure drop across valve ∆p bar Pressure drop across valve ∆p bar
Type
1 2 4 8 12 16 1 2 4 8 12 16
Evaporating temperature 10°C Evaporating temperature 0°C
ICM20-A DN20 0.6 85.9 119 163 217 253 279 90 123 167 221 256 282
ICM20-B DN20 2.4 498 686 930 1230 1435 1587 515 705 950 1245 1450 1594
ICM20-C DN20 4.6 824 1124 1507 1990 2310 2550 850 1145 1525 2000 2320 2560
ICM25-A DN25 6 1274 1739 2337 3080 3575 3970 1310 1773 2370 3100 3600 3980
ICM32-A DN32 9 1834 2515 3400 4490 5220 5775 1890 2580 3450 4530 5250 5790
ICM40-A DN40 15 3410 4630 6200 8150 9450 10450 3500 4700 6250 8170 9480 10450
ICM50-A DN50 23 5960 8050 10750 14100 16300 18100 6100 8150 10800 14100 16300 18100
Evaporating temperature –10°C Evaporating temperature –20°C
ICM20-A DN20 0.6 92 127 170 224 258 284 94.5 129 172 225 258 284
ICM20-B DN20 2.4 527 715 955 1253 1452 1594 535 718 957 1250 1450 1594
ICM20-C DN20 4.6 859 1152 1520 1990 2310 2550 860 1140 1505 1975 2290 2525
ICM25-A DN25 6 1332 1780 2360 3090 3590 3960 1332 1770 2345 3070 3570 3940
ICM32-A DN32 9 1930 2600 3450 4520 5240 5780 1935 2590 3440 4510 5220 5750
ICM40-A DN40 15 3550 4715 6220 8140 9450 10430 3520 4650 6140 8050 9350 10350
ICM50-A DN50 23 6150 8150 10700 14000 16300 18000 6070 8000 10550 13850 16100 17800
Evaporating temperature –30°C Evaporating temperature –40°C
ICM20-A DN20 0.6 96 130 173 225 258 282 97 131 173 224 256 280
ICM20-B DN20 2.4 532 716 950 1240 1435 1580 527 705 940 1230 1420 1555
ICM20-C DN20 4.6 840 1111 1480 1950 2270 2505 815 1085 1450 1920 2230 2470
ICM25-A DN25 6 1310 1740 2310 3030 3530 3880 1270 1690 2270 2990 3480 3830
ICM32-A DN32 9 1920 2560 3400 4460 5150 5700 1870 2500 3350 4400 5100 5630
ICM40-A DN40 15 3430 4530 6030 7950 9250 10200 3300 4400 5900 7820 9120 10100
ICM50-A DN50 23 5900 7800 10350 13650 15900 17600 5670 7550 10150 13400 15700 17400
Evaporating temperature –50°C
ICM20-A DN20 0.6 97.5 131 172 222 253 276
ICM20-B DN20 2.4 512 690 925 1210 1400 1535
ICM20-C DN20 4.6 780 1055 1425 1890 2200 2430
ICM25-A DN25 6 1220 1650 2220 2950 3420 3780
ICM32-A DN32 9 1810 2450 3280 4325 5030 5540
ICM40-A DN40 15 3170 4280 5800 7710 8950 9900
ICM50-A DN50 23 5430 7350 9900 13200 15400 17100

Expansion
Capacities for nominal conditions, Qn (TR)
R 717
Pressure drop across valve ∆p psi Pressure drop across valve ∆p psi
Type
15 30 60 120 180 240 15 30 60 120 180 240
Evaporating temperature 60°F Evaporating temperature 40°F
ICM20-A DN20 0.7 24.5 33.9 46.3 61.8 72 79.3 25.3 35 47.6 63 73 80.4
ICM20-B DN20 2.8 142 196 265 352 410 451 147 201 271 358 415 458
ICM20-C DN20 5.3 235 321 432 570 660 730 243 328 438 574 665 735
ICM25-A DN25 7 363 497 670 880 1025 1130 375 510 680 888 1030 1140
ICM32-A DN32 10 523 720 970 1280 1490 1645 539 735 985 1294 1500 1655
ICM40-A DN40 17 975 1325 1780 2330 2705 3000 1000 1350 1800 2344 2715 3010
ICM50-A DN50 27 1695 2310 3070 4030 4690 5170 1745 2350 3100 4050 4700 5200
Evaporating temperature 20°F Evaporating temperature 0°F
ICM20-A DN20 0.7 26.3 36.2 48.8 64 74 81.4 27.1 37 49.5 64.5 74.3 81.5
ICM20-B DN20 2.8 151 206 275 360 416 459 154 207 276 360 416 458
ICM20-C DN20 5.3 248 332 439 574 665 734 249 330 435 570 660 728
ICM25-A DN25 7 383 515 681 888 1030 1135 385 513 678 884 1025 1130
ICM32-A DN32 10 553 746 993 1299 1510 1657 560 747 990 1293 1500 1650
ICM40-A DN40 17 1020 1360 1795 2346 2715 3005 1022 1345 1775 2325 2700 2970
ICM50-A DN50 27 1770 2350 3100 4040 4680 5170 1770 2320 3050 4000 4650 5130
Evaporating temperature –20°F Evaporating temperature –40°F
ICM20-A DN20 0.7 27.7 37.5 50 64.5 74 81 28 37.8 50 64.3 73.5 79.9
ICM20-B DN20 2.8 154 206 274 357 413 454 152 203 270 353 408 446
ICM20-C DN20 5.3 244 323 428 560 653 720 235 313 418 553 642 710
ICM25-A DN25 7 380 503 665 875 1015 1120 366 488 653 860 1000 1100
ICM32-A DN32 10 555 740 978 1285 1485 1635 540 723 965 1265 1465 1610
ICM40-A DN40 17 995 1315 1740 2290 2660 2945 955 1270 1700 2250 2615 2900
ICM50-A DN50 27 1720 2255 2985 3930 4570 5050 1640 2180 2920 3870 4500 4990
Evaporating temperature –60°F
ICM20-A DN20 0.7 28.1 37.6 49.5 63.7 72.5 79
ICM20-B DN20 2.8 147 199 266 347 400 440
ICM20-C DN20 5.3 225 304 410 544 630 695
ICM25-A DN25 7 352 475 640 845 980 1080
ICM32-A DN32 10 520 703 943 1246 1440 1585
ICM40-A DN40 17 910 1230 1660 2210 2570 2850
ICM50-A DN50 27 1560 2110 2850 3800 4430 4900

44 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Expansion
Capacities for nominal conditions, Qn (kW)
R 744
Pressure drop across valve ∆p bar Pressure drop across valve ∆p bar
Type
1 2 4 8 12 16 1 2 4 8 12 16
Evaporating temperature 10°C Evaporating temperature 0°C
ICM20-A DN20 0.6 18.7 26.2 36.1 48.3 56 61 22.4 31 42.5 56.8 66 72
ICM20-B DN20 2.4 109 152 209 280 324 353 130 179 246 329 381 417
ICM20-C DN20 4.6 180 251 347 465 535 583 215 297 408 542 630 686
ICM25-A DN25 6 277 389 535 718 826 900 333 460 630 838 975 1065
ICM32-A DN32 9 400 560 770 1030 1190 1300 478 660 905 1210 1400 1530
ICM40-A DN40 15 743 1040 1435 1920 2215 2400 890 1230 1680 2250 2600 2830
ICM50-A DN50 23 1295 1810 2500 3340 3850 4180 1550 2140 2940 3900 4530 4750
Evaporating temperature –10°C Evaporating temperature –20°C
ICM20-A DN20 0.6 24.7 34.5 47.5 63.6 74 81 27.1 37.8 52 69.6 81 88.5
ICM20-B DN20 2.4 143 200 275 368 428 470 157 219 302 402 468 512
ICM20-C DN20 4.6 238 331 455 608 705 770 260 363 497 665 770 840
ICM25-A DN25 6 368 513 705 940 1090 1195 402 563 770 1025 1190 1300
ICM32-A DN32 9 528 735 1015 1355 1570 1720 580 810 1110 1480 1715 1880
ICM40-A DN40 15 980 1370 1880 2510 2910 3180 1075 1500 2060 2740 3160 3470
ICM50-A DN50 23 1710 2380 3280 4380 5050 5550 1870 2620 3580 4750 5500 6030
Evaporating temperature –30°C Evaporating temperature –40°C
ICM20-A DN20 0.6 29.7 41 56.3 75 86.8 95 32.1 44 60 79 91.2 99.5
ICM20-B DN20 2.4 172 238 325 432 500 545 186 256 345 455 525 571
ICM20-C DN20 4.6 285 395 536 710 820 895 308 422 570 745 855 930
ICM25-A DN25 6 440 610 828 1100 1270 1380 478 655 880 1155 1325 1444
ICM32-A DN32 9 632 880 1195 1585 1830 2000 685 940 1270 1670 1915 2090
ICM40-A DN40 15 1175 1630 2220 2920 3370 3680 1275 1750 2350 3060 3530 3830
ICM50-A DN50 23 2050 2850 3850 5080 5850 6400 2220 3050 4080 5330 6100 6650
Evaporating temperature –50°C
ICM20-A DN20 0.6 33.3 46 62.5 82.5 94.8 103
ICM20-B DN20 2.4 193 266 359 472 540 588
ICM20-C DN20 4.6 319 438 587 765 880 955
ICM25-A DN25 6 494 678 910 1190 1360 1480
ICM32-A DN32 9 710 980 1320 1720 1980 2155
ICM40-A DN40 15 1320 1810 2420 3150 3610 3940
ICM50-A DN50 23 2300 3150 4210 5450 6250 6800

Expansion
Capacities for nominal conditions, Qn (TR)
R 744
Pressure drop across valve ∆p psi Pressure drop across valve ∆p psi
Type
15 30 60 120 180 240 15 30 60 120 180 240
Evaporating temperature 60°F Evaporating temperature 40°C
ICM20-A DN20 0.7 4.8 6.7 9.2 12.3 14.2 15.3 5.8 8.2 11.3 15.2 17.6 19.2
ICM20-B DN20 2.8 27.8 39 53.7 71.5 82 88.8 33.9 47.6 66 88.3 102 111
ICM20-C DN20 5.3 46 64.5 89 118 136 146 56 79 109 146 169 184
ICM25-A DN25 7 71.1 100 137 183 210 226 87 122 169 226 261 285
ICM32-A DN32 10 102 144 198 264 303 327 125 176 242 325 376 410
ICM40-A DN40 17 191 267 368 490 561 605 232 326 450 603 699 760
ICM50-A DN50 27 332 465 640 855 976 1055 405 570 785 1050 1215 1320
Evaporating temperature 20°F Evaporating temperature 0°C
ICM20-A DN20 0.7 6.8 9.6 13.2 17.7 20.5 22.4 7.7 10.7 14.7 19.7 22.8 25
ICM20-B DN20 2.8 39.9 55.7 76.5 102 118 130 44.7 62.3 85.5 114 132 144
ICM20-C DN20 5.3 66 92 126 169 195 214 74.3 103 141 188 217 237
ICM25-A DN25 7 102 142 196 261 303 330 115 159 218 290 335 367
ICM32-A DN32 10 147 205 281 376 437 476 165 230 315 418 485 528
ICM40-A DN40 17 273 381 524 699 805 880 307 426 585 775 895 975
ICM50-A DN50 27 475 663 910 1215 1400 1535 535 745 1015 1350 1555 1700
Evaporating temperature –20°F Evaporating temperature –40°C
ICM20-A DN20 0.7 8.4 11.7 16 21.4 24.7 27 9.1 12.6 17.2 22.7 26.2 28.5
ICM20-B DN20 2.8 48.9 68 93 123 142 155 53 73.3 99 131 150 164
ICM20-C DN20 5.3 81 112 153 203 233 255 87.8 121 163 214 245 267
ICM25-A DN25 7 125 174 237 313 362 395 135 187 253 331 380 414
ICM32-A DN32 10 180 250 341 453 523 570 195 270 365 480 549 600
ICM40-A DN40 17 335 464 633 835 960 1050 362 500 675 878 1010 1100
ICM50-A DN50 27 584 810 1100 1450 1670 1820 633 870 1170 1530 1750 1900
Evaporating temperature –60°F
ICM20-A DN20 0.7 9.6 13.3 18.1 23.7 27.3 29.5
ICM20-B DN20 2.8 56 77 104 136 156 169
ICM20-C DN20 5.3 92.8 127 170 221 253 275
ICM25-A DN25 7 143 197 263 342 391 425
ICM32-A DN32 10 206 284 380 496 568 618
ICM40-A DN40 17 383 524 700 907 1040 1130
ICM50-A DN50 27 667 915 1215 1570 1800 1950

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 45


Technical leaflet Motor valves, type ICM and actuators type ICAD

Expansion
Capacities for nominal conditions, Qn (kW)
R 134a
Pressure drop across valve ∆p bar Pressure drop across valve ∆p bar
Type
1 2 4 8 12 16 1 2 4 8 12 16

Evaporating temperature 10°C Evaporating temperature 0°C


ICM20-A DN20 0.6 19.4 26 33.6 40.5 42.7 42.5 20.1 26.8 34.3 40.8 42.5 42.1
ICM20-B DN20 2.4 112 149 192 230 243 242 116 153 194 231 242 240
ICM20-C DN20 4.6 184 243 310 370 392 391 189 247 311 370 389 388
ICM25-A DN25 6 285 377 480 575 607 606 292 383 482 575 604 602
ICM32-A DN32 9 410 545 699 835 885 883 422 555 703 835 880 875
ICM40-A DN40 15 760 1000 1270 1520 1610 1605 775 1015 1270 1515 1596 1590
ICM50-A DN50 23 1320 1730 2200 2620 2770 2785 1350 1750 2200 2610 2750 2740

Evaporating temperature –10°C Evaporating temperature –20°C


ICM20-A DN20 0.6 20.7 27.4 34.5 40.5 42 41.5 21.1 27.6 34.5 40 41.1 40.1
ICM20-B DN20 2.4 118 154 194 229 238 235 119 154 193 225 233 228
ICM20-C DN20 4.6 191 247 310 365 381 379 190 244 305 357 372 365
ICM25-A DN25 6 296 383 481 568 593 587 295 380 474 555 575 568
ICM32-A DN32 9 430 559 702 826 865 855 430 555 695 810 840 826
ICM40-A DN40 15 785 1013 1265 1490 1565 1550 775 995 1240 1460 1520 1495
ICM50-A DN50 23 1360 1740 2180 2570 2700 2670 1340 1710 2130 2510 2620 2590

Evaporating temperature –30°C Evaporating temperature –40°C


ICM20-A DN20 0.6 21.3 27.6 34.2 39.1 40 38.7 21.4 27.5 33.6 38 38.3 36.8
ICM20-B DN20 2.4 118 152 189 219 225 218 116 149 184 211 216 208
ICM20-C DN20 4.6 186 238 297 347 357 350 180 231 288 335 342 333
ICM25-A DN25 6 290 372 463 540 555 545 280 361 448 520 532 516
ICM32-A DN32 9 425 545 680 790 812 792 415 532 660 760 780 755
ICM40-A DN40 15 760 970 1210 1415 1465 1430 730 940 1175 1360 1410 1358
ICM50-A DN50 23 1305 1670 2080 2440 2530 2480 1260 1610 2010 2350 2420 2350

Expansion
Capacities for nominal conditions, Qn (TR)
R 134a
Pressure drop across valve ∆p psi Pressure drop across valve ∆p psi
Type
15 30 60 120 180 240 15 30 60 120 180 240

Evaporating temperature 60°F Evaporating temperature 40°F


ICM20-A DN20 0.7 5.5 7.3 9.5 11.4 12 11.9 5.7 7.6 9.7 11.6 12.1 11.9
ICM20-B DN20 2.8 31.5 42 54.1 65 68.5 68.2 32.7 43.5 55.3 65.8 68.8 68
ICM20-C DN20 5.3 52 69 88 105 111 111 53.6 70.5 89 106 111 110
ICM25-A DN25 7 80.3 106 136 163 172 171 83 109 138 164 172 170
ICM32-A DN32 10 116 154 198 237 250 249 120 158 201 238 250 248
ICM40-A DN40 17 214 284 360 431 455 454 222 289 364 432 455 452
ICM50-A DN50 27 373 493 625 745 787 787 385 500 630 745 785 780

Evaporating temperature 20°F Evaporating temperature 0°F


ICM20-A DN20 0.7 5.9 7.8 9.9 11.6 12 11.8 6 7.9 9.9 11.4 11.7 11.4
ICM20-B DN20 2.8 33.6 44.3 55.5 65.5 68 66.7 34.1 44.4 55.4 64.2 66.2 64.5
ICM20-C DN20 5.3 54.8 71 88.5 105 109 108 54.8 70.2 87.5 102 106 104
ICM25-A DN25 7 85 110 138 162 169 167 85 109 136 159 164 161
ICM32-A DN32 10 123 160 201 237 247 243 124 160 199 232 240 235
ICM40-A DN40 17 225 291 363 428 447 442 224 287 357 418 433 425
ICM50-A DN50 27 390 503 625 737 770 760 387 495 615 720 747 735

Evaporating temperature –20°F Evaporating temperature –40°F


ICM20-A DN20 0.7 6.1 7.9 9.8 11.2 11.3 10.9 6.1 7.8 9.6 10.8 10.8 10.3
ICM20-B DN20 2.8 34 43.9 54.3 62.6 64 61.8 33.3 42.7 52.8 60.1 61 58.5
ICM20-C DN20 5.3 53.5 68.5 85.3 99 102 99 51.7 66.6 82.5 95 97 93.7
ICM25-A DN25 7 83.5 107 132 154 158 154 80.7 103.3 128 148 151 145
ICM32-A DN32 10 122 157 195 225 231 224 119 153 189 217 220 212
ICM40-A DN40 17 219 280 347 405 416 405 211 270 336 388 397 383
ICM50-A DN50 27 377 480 597 695 720 710 362 463 575 667 685 660

46 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Expansion
Capacities for nominal conditions, Qn (kW)
R 404A
Pressure drop across valve ∆p bar Pressure drop across valve ∆p bar
Type
1 2 4 8 12 16 1 2 4 8 12 16

Evaporating temperature 10°C Evaporating temperature 0°C


ICM20-A DN20 0.6 15.7 21.3 27.8 33.8 35.3 34.5 16.6 22.5 29.3 35.2 36.8 35.9
ICM20-B DN20 2.4 91 123 160 194 203 198 96.5 130 168 201 210 205
ICM20-C DN20 4.6 150 203 263 315 330 322 159 213 273 327 341 333
ICM25-A DN25 6 233 313 406 490 510 500 246 329 423 508 528 518
ICM32-A DN32 9 335 452 589 710 740 723 354 475 612 733 766 750
ICM40-A DN40 15 621 835 1080 1300 1360 1323 659 876 1123 1340 1400 1370
ICM50-A DN50 23 1085 1455 1880 2250 2350 2300 1145 1525 1950 2330 2430 2380
Evaporating temperature –10°C Evaporating temperature –20°C
ICM20-A DN20 0.6 17.4 23.5 30.3 36.1 37.5 36.5 18.2 24.3 31 36.5 37.7 36.5
ICM20-B DN20 2.4 101 135 173 206 214 209 105 139 176 207 214 208
ICM20-C DN20 4.6 166 220 280 333 345 338 172 225 283 333 345 335
ICM25-A DN25 6 257 340 435 515 535 525 265 348 439 515 535 520
ICM32-A DN32 9 370 493 629 748 778 760 384 506 640 750 778 755
ICM40-A DN40 15 685 904 1150 1360 1420 1390 706 920 1160 1360 1410 1375
ICM50-A DN50 23 1190 1570 1990 2350 2450 2400 1230 1600 2000 2350 2435 2380
Evaporating temperature –30°C Evaporating temperature –40°C
ICM20-A DN20 0.6 18.7 24.7 31.3 36.5 37.3 35.8 19.2 25 31.3 35.8 36.3 34.7
ICM20-B DN20 2.4 107 140 176 205 211 204 109 140 174 202 205 197
ICM20-C DN20 4.6 173 225 281 329 338 328 173 221 276 320 328 316
ICM25-A DN25 6 269 349 437 510 525 508 269 345 428 499 510 490
ICM32-A DN32 9 389 508 637 745 765 742 393 503 628 730 745 715
ICM40-A DN40 15 711 922 1150 1345 1385 1340 711 902 1130 1310 1340 1295
ICM50-A DN50 23 1235 1590 1980 2320 2390 2320 1225 1555 1940 2255 2320 2240
Evaporating temperature –50°C
ICM20-A DN20 0.6 19.5 25 30.9 35 35.1 33.2
ICM20-B DN20 2.4 108 138 171 196 198 188
ICM20-C DN20 4.6 170 215 268 310 315 301
ICM25-A DN25 6 265 335 418 484 490 468
ICM32-A DN32 9 388 493 613 705 715 680
ICM40-A DN40 15 695 875 1090 1270 1290 1230
ICM50-A DN50 23 1195 1505 1880 2180 2230 2130

Expansion
Capacities for nominal conditions, Qn (TR)
R 404A
Pressure drop across valve ∆p psi Pressure drop across valve ∆p psi
Type
15 30 60 120 180 240 15 30 60 120 180 240
Evaporating temperature 60°F Evaporating temperature 40°F
ICM20-A DN20 0.7 4.4 5.9 7.7 9.3 9.7 9.3 4.7 6.3 8.2 9.9 10.2 9.9
ICM20-B DN20 2.8 25.2 34.1 44.5 53.5 55.5 53.8 27.2 36.5 47.3 56.5 58.8 57
ICM20-C DN20 5.3 41.8 56.3 73 87.5 91 87.5 45 60 77 92 95.5 92.5
ICM25-A DN25 7 64.5 87 113 135 141 136 69.5 93 119 143 148 144
ICM32-A DN32 10 93 125 163 196 204 197 100 134 173 207 215 208
ICM40-A DN40 17 173 233 300 360 373 360 186 248 318 377 393 381
ICM50-A DN50 27 300 405 522 625 647 625 325 431 550 655 680 660
Evaporating temperature 20°F Evaporating temperature 0°F
ICM20-A DN20 0.7 4.9 6.6 8.6 10.2 10.6 10.2 5.2 6.9 8.8 10.4 10.6 10.3
ICM20-B DN20 2.8 28.7 38.4 49.1 58.2 60.5 58.5 29.9 39.5 50.3 59 60.6 58.5
ICM20-C DN20 5.3 47.3 62.6 79.8 94.5 97.5 94.7 49 64.3 81 95 98 94.5
ICM25-A DN25 7 73 97 123 146 151 147 76 99.5 125 147 152 147
ICM32-A DN32 10 105 140 179 212 220 213 109 144 183 214 221 214
ICM40-A DN40 17 195 259 327 387 402 389 202 264 332 389 401 389
ICM50-A DN50 27 340 448 567 670 694 675 352 457 573 672 694 672
Evaporating temperature –20°F Evaporating temperature –40°F
ICM20-A DN20 0.7 5.4 7.1 8.9 10.4 10.5 10.1 5.5 7.2 8.9 10.2 10.3 9.7
ICM20-B DN20 2.8 30.8 40.2 50.5 58.7 60 57.5 31.2 40.2 50 57.5 58 55.3
ICM20-C DN20 5.3 50 64.5 80.5 93.5 96 92.5 50 63.6 79 91.5 93 89
ICM25-A DN25 7 77.5 100 125 145 149 143 77.5 99 123 142 144 138
ICM32-A DN32 10 112 146 183 212 217 209 113 144 180 207 211 201
ICM40-A DN40 17 205 265 330 383 394 380 204 259 323 373 380 363
ICM50-A DN50 27 355 457 567 660 678 655 353 447 555 643 657 630
Evaporating temperature –60°F
ICM20-A DN20 0.7 5.6 7.1 8.8 9.9 9.9 9.3
ICM20-B DN20 2.8 31.1 39.5 48.8 55.6 55.6 52.2
ICM20-C DN20 5.3 49 61.5 76.7 87.8 89 84
ICM25-A DN25 7 76.3 96 119 137 138 130
ICM32-A DN32 10 111 141 175 200 201 190
ICM40-A DN40 17 200 250 312 360 363 343
ICM50-A DN50 27 344 430 535 620 628 595

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 47


Technical leaflet Motor valves, type ICM and actuators type ICAD

Expansion
Capacities for nominal conditions, Qn (kW)
R 22
Pressure drop across valve ∆p bar Pressure drop across valve ∆p bar
Type
1 2 4 8 12 16 1 2 4 8 12 16
Evaporating temperature 10°C Evaporating temperature 0°C
ICM20-A DN20 0.6 20.1 27.6 36.8 46.7 51.7 54.2 21.1 28.8 38.1 48 53 55.4
ICM20-B DN20 2.4 117 160 212 268 297 312 122 166 218 274 303 316
ICM20-C DN20 4.6 193 263 346 435 482 505 201 271 355 443 490 513
ICM25-A DN25 6 299 406 535 675 746 785 312 420 550 687 760 795
ICM32-A DN32 9 430 585 777 980 1085 1140 448 606 798 998 1100 1155
ICM40-A DN40 15 798 1080 1420 1790 1980 2080 830 1115 1460 1820 2005 2110
ICM50-A DN50 23 1390 1880 2470 3100 3430 3600 1450 1940 2530 3150 3480 3650
Evaporating temperature –10°C Evaporating temperature –20°C
ICM20-A DN20 0.6 21.9 29.8 39 48.8 53.7 55.8 22.7 30.5 39.8 49.3 53.7 55.7
ICM20-B DN20 2.4 126 170 223 278 305 318 130 174 225 279 305 317
ICM20-C DN20 4.6 208 277 360 448 493 514 212 280 361 447 490 510
ICM25-A DN25 6 321 430 557 695 764 796 328 435 559 693 760 792
ICM32-A DN32 9 463 621 809 1010 1110 1157 475 630 815 1012 1105 1151
ICM40-A DN40 15 855 1140 1472 1830 2012 2112 870 1150 1475 1830 2005 2100
ICM50-A DN50 23 1490 1970 2550 3170 3480 3650 1510 1980 2550 3150 3460 3630
Evaporating temperature –30°C Evaporating temperature –40°C
ICM20-A DN20 0.6 23.2 31 40 49.3 53.5 55.3 23.6 31.3 40.1 48.8 52.8 54.3
ICM20-B DN20 2.4 132 175 225 277 302 313 133 174 223 274 298 308
ICM20-C DN20 4.6 212 279 357 443 485 505 210 275 353 436 475 495
ICM25-A DN25 6 329 433 556 685 752 783 327 428 550 676 740 765
ICM32-A DN32 9 478 631 812 1000 1095 1140 478 626 805 990 1075 1120
ICM40-A DN40 15 873 1140 1465 1810 1980 2070 860 1120 1440 1780 1940 2020
ICM50-A DN50 23 1510 1970 2520 3110 3420 3560 1480 1930 2480 3070 3350 3500
Evaporating temperature –50°C
ICM20-A DN20 0.6 23.8 31.3 39.8 48 51.8 53
ICM20-B DN20 2.4 131 172 220 269 291 300
ICM20-C DN20 4.6 205 269 346 427 465 480
ICM25-A DN25 6 320 418 540 663 720 747
ICM32-A DN32 9 470 615 789 970 1055 1090
ICM40-A DN40 15 835 1095 1410 1740 1900 1970
ICM50-A DN50 23 1435 1880 2430 3000 3270 3400

Expansion
Capacities for nominal conditions, Qn (TR)
R 22
Type Pressure drop across valve ∆p psi Pressure drop across valve ∆p psi
15 30 60 120 180 240 15 30 60 120 180 240
Evaporating temperature 60°F Evaporating temperature 40°F
ICM20-A DN20 0.7 5.6 7.7 10.3 13.1 14.5 15.2 6 8.2 10.8 13.6 15 15.6
ICM20-B DN20 2.8 32.5 44.6 59.5 75.5 83.6 87.5 34.5 47 62 77.8 85.5 89.5
ICM20-C DN20 5.3 54 73.5 97.5 123 136 142 57 77 101 126 139 145
ICM25-A DN25 7 83.2 114 151 190 210 220 88 119 156 196 216 226
ICM32-A DN32 10 120 164 218 275 305 320 127 172 226 283 313 327
ICM40-A DN40 17 223 303 400 505 560 585 236 317 415 517 570 596
ICM50-A DN50 27 388 528 695 878 970 1015 410 550 720 895 990 1035
Evaporating temperature 20°F Evaporating temperature 0°F
ICM20-A DN20 0.7 6.3 8.5 11.2 13.9 15.2 15.9 6.5 8.7 11.4 14.1 15.3 15.9
ICM20-B DN20 2.8 36 48.7 63.6 79 87 90.6 37.3 49.8 64.5 80 87 90.2
ICM20-C DN20 5.3 59.5 79.5 103 128 140 146 60.7 80.5 104 128 140 146
ICM25-A DN25 7 92 123 160 198 218 227 94 125 161 199 217 226
ICM32-A DN32 10 133 178 232 289 317 329 136 181 234 289 316 329
ICM40-A DN40 17 245 326 423 525 575 600 250 330 424 524 575 599
ICM50-A DN50 27 427 565 730 905 995 1038 435 570 730 905 993 1035
Evaporating temperature –20°F Evaporating temperature –40°F
ICM20-A DN20 0.7 6.7 8.9 11.5 14.1 15.2 15.7 6.8 9 11.5 13.9 15 15.4
ICM20-B DN20 2.8 37.9 50.3 64.5 79.2 86.2 89.1 38.1 50.2 64 78.5 85 87.6
ICM20-C DN20 5.3 61.3 80.1 103 127 138 144 60.5 79 101 125 136 140
ICM25-A DN25 7 95 125 160 197 215 223 94 123 157 193 211 218
ICM32-A DN32 10 138 182 233 287 314 325 138 180 231 283 307 318
ICM40-A DN40 17 251 329 421 518 567 590 248 323 413 510 555 575
ICM50-A DN50 27 435 565 725 895 980 1020 428 555 710 875 960 995
Evaporating temperature –60°F
ICM20-A DN20 0.7 6.9 9 11.4 13.7 14.7 15
ICM20-B DN20 2.8 37.7 49.5 63 76.8 83 85
ICM20-C DN20 5.3 59 77 99 122 132 136
ICM25-A DN25 7 92 120 154 189 205 212
ICM32-A DN32 10 135 177 227 276 300 309
ICM40-A DN40 17 240 314 403 498 540 560
ICM50-A DN50 27 412 540 695 855 935 965

48 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

ICM 20 / ICAD 600


Ordering from the parts programme

Example (select from table I, II and III)

+ + =
Top cover/function module
Valve body 22 SD (7/8 in.) ICM 20-B Actuator
027H1154 027H1181 027H1200
Table I Table II Table III

ICM 20 function module /


ICV 20 valve body w/different connections Table I top cover Table II ICAD 600 actuator Table III

20 D (3/4 in.) 25 D (1 in.) 20 A (3/4 in.) 20 SOC (3/4 in.) Description Code Number Description Code Number
027H1145 027H1163 027H1148 027H1151 ICM 20-A 027H1180 *) ICAD 600 027H1200
ICM 20-B 027H1181 *)
16 SA (5/8 in.) 22 SA (7/8 in.) 16 SD (5/8 in.) 22 SD (7/8 in.)
ICM 20-C 027H1182 *)
027H1129 027H1160 027H1132 027H1154
*) Including gasket, bolts and O-rings
20 FPT (3/4 in.) 25 A (1 in.)
027H1157 027H1166
D = Butt-weld DIN ; A = Butt-weld ANSI ; J = Butt-weld JIS ; SOC = Socket weld ANSI ;
SD = Solder DIN ; SA = Solder ANSI ; FPT = Female Pipe Thread

Ordering complete factory assembled valve without actuator Spare parts and accessories
(body, function module/top cover) Table A Spare parts

Available connections Spare Parts Code Number


20 D (3/4 in.) 25 D (1 in.) 20 A (3/4 in.) 20 SOC (3/4 in.) 16 SA (5/8 in.) 22 SA (7/8 in.) 16 SD (5/8 in.) 22 SD (7/8 in.) 20 FPT (3/4 in.)
ICM 20 Service kit 027H1190
ICM 20-A 027H1030 027H1020 027H1035 027H1040 027H1050 027H1045
ICM 20-B 027H1031 027H1021 027H1036 027H1041 027H1051 027H1046 Accessories
ICM 20-C 027H1032 027H1022 027H1052 027H1047

25 A (1 in.)
ICM 20-A
ICM 20-B
ICM 20-C 027H1025

Select from parts programme ICAD-UPS for ICM 20-125 Multi-function tool for ICM 20-32

Accessories Code Number


ICV 20
027H1174 *)
top cover blind

*) Including bolts and gaskets


027H0182 027H0180

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 49


Technical leaflet Motor valves, type ICM and actuators type ICAD

ICM 25 / ICAD 600


Ordering from the parts programme

Example (select from table I, II and III)

+ + =
Function module/top cover
Valve body 32 D (11/4 in.) ICM 25-B Actuator
027H2129 027H2181 027H1200
Table I Table II Table III

ICM 25 function module /


ICV 25 valve body w/different connections Table I top cover Table II ICAD 600 actuator Table III

20 D (3/4 in.) 25 D (1 in.) 32 D (11/4 in.) 40 D (11/2 in.) Description Code Number Description Code Number
027H2128 027H2120 027H2129 027H2135 ICM 25-A 027H2180 *) ICAD 600 027H1200
ICM 25-B 027H2181 *)
35 SD (1 /8 in. SA)
3
28 SA (1 /8 in.)
1
22 SA ( /8 in.)
7
28 SD (1 /8 in.)
1

027H2134 027H2126 027H2125 027H2124 *) Including gasket and O-rings

22 SD (7/8 in.) 20 A (3/4 in.) 25 A (1 in.) 32 A (11/4 in.)


027H2123 027H2131 027H2121 027H2130

20 SOC (3/4 in.) 25 SOC (1 in.) 20 FPT (3/4 in.) 25 FPT (1 in.)
027H2132 027H2122 027H2133 027H2127
D = Butt-weld DIN ; A = Butt-weld ANSI ; J = Butt-weld JIS ; SOC = Socket weld ANSI ; SD = Solder DIN ; SA = Solder ANSI ; FPT = Female Pipe Thread

Ordering complete factory assembled valve without actuator Spare parts and accessories
(body, function module/top cover) Table A Spare parts

Available connections Spare Parts Code Number


20 D (3/4 in.) 25 D (1 in.) 32 D (11/4 in.) 40 D (11/2 in.) 35 SD (13/8 in. SA) 28 SA (11/8 in.) 22 SA (7/8 in.) 28 SD (11/8 in.) ICM 25 Service kit 027H2220
ICM 25-A 027H2000 027H2016 027H2014 027H2012 027H2010 027H2008
ICM 25-B 027H2001 027H2015 027H2013 027H2011 027H2009
Accessories

22 SD (7/8 in.) 20 A (3/4 in.) 25 A (1 in.) 32 A (11/4 in.) 20 SOC (3/4 in.) 25 SOC (1 in.) 20 FPT (3/4 in.) 25 FPT (1 in.)
ICM 25-A 027H2006 027H2002 027H2004
ICM 25-B 027H2007 027H2003 027H2005

Select from parts programme


ICAD-UPS for ICM 20-125 Multi-function tool for ICM 20-32

Accessories Code Number


ICV 25
027H2174 *)
top cover blind
027H0182 027H0180
*) Including bolts and gaskets

50 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

ICM 32 / ICAD 600


Ordering from the parts programme

Example (select from table I, II and III)

+ + =
Valve body 40 D (11/2 in.) Top cover ICM 32-A Actuator
027H3125 027H3180 027H1200
Table I Table II Table III

ICM 32 function module /


ICV 32 valve body w/different connections Table I top cover Table II ICAD 600 actuator Table III

32 D (11/4 in.) 40 D (11/2 in.) 42 SA (15/8 in.) 42 SD (15/8 in.) Description Code Number Description Code Number
027H3120 027H3125 027H3127 027H3128 ICM 32-A 027H3180 *) ICAD 600 027H1200
ICM 32-B 027H3181 *)
35 SD (13/8 in. SA) 32 A (11/4 in.) 32 SOC (11/4 in.) 40 A (11/2 in.)
*) Including gasket and O-rings
027H3123 027H3121 027H3122 027H3126
D = Butt-weld DIN ; A = Butt-weld ANSI ; J = Butt-weld JIS ; SOC = Socket weld ANSI ;
SD = Solder DIN ; SA = Solder ANSI ; FPT = Female Pipe Thread

Ordering complete factory assembled valve without actuator Spare parts and accessories
(body, function module/top cover) Table A Spare parts

Available connections Spare Parts Code Number


32 D (11/4 in.) 40 D (11/2 in.) 42 SA (15/8 in.) 42 SD (15/8 in.) 35 SD (13/8 in. SA) 32 A (11/4 in.) 32 SOC (11/4 in.) 40 A (11/2 in.) ICM 32 Service kit 027H3220
ICM 32-A 027H3000 027H3012 027H3008 027H3006 027H3002 027H3004
ICM 32-B 027H3001 027H3009 027H3007 027H3003 027H3005
Accessories
Select from parts programme

ICAD-UPS for ICM 20-125 Multi-function tool for ICM 20-32

Accessories Code Number


ICV 32
027H3174 *)
027H0182 027H0180 top cover blind
*) Including bolts and gaskets

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 51


Technical leaflet Motor valves, type ICM and actuators type ICAD

ICM 40 / ICAD 900


Ordering from the parts programme

Example (select from table I, II and III)

+ + =
Valve body A 40 (11/2 in.) Top cover ICM 40-A Actuator
027H4121 027H4180 027H1201
Table I Table II Table III

ICM 40 function module /


ICV 40 valve body w/different connections Table I top cover Table II ICAD 900 actuator Table III

40 D (11/2 in.) 50 D (2 in.) 42 SA (15/8 in.) 42 SD (15/8 in.) Description Code Number Description Code Number
027H4120 027H4126 027H4124 027H4123 ICM 40-A 027H4180 *) ICAD 900 027H1201
ICM 40-B 027H4181 *)
40 A (11/2 in.) 40 SOC (11/2 in.) 50 A (2 in.)
*) Including gasket and O-rings
027H4121 027H4122 027H4127
D = Butt-weld DIN ; A = Butt-weld ANSI ; J = Butt-weld JIS ; SOC = Socket weld ANSI ;
SD = Solder DIN ; SA = Solder ANSI ; FPT = Female Pipe Thread

Ordering complete factory assembled valve without actuator Spare parts and accessories
(body, function module/top cover) Table A Spare parts

Available connections Spare Parts Code Number


40 D (11/2 in.) 50 D (2 in.) 42 SA (15/8 in.) 42 SD (15/8 in.) 40 A (11/2 in.) 40 SOC (11/2 in.) 50 A (2 in.) ICM 40 Service kit 027H4220
ICM 40-A 027H4000 027H4010 027H4006 027H4008 027H4002 027H4004
ICM 40-B 027H4001 027H4007 027H4009 027H4003 027H4005
Accessories
Select from parts programme

ICAD-UPS for ICM 20-125 Multi-function tool for ICM 40-65

Accessories Code Number


ICV 40
027H4174 *)
027H0182 027H0181 top cover blind
*) Including bolts and gaskets

52 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

ICM 50 / ICAD 900


Ordering from the parts programme

Example (select from table I, II and III)

+ + =
Valve body 65 D (21/2 in.) Top cover ICM 50-A Actuator
027H5124 027H5180 027H1201
Table I Table II Table III

ICM 50 function module /


ICV 50 valve body w/different connections Table I top cover Table II ICAD 900 actuator Table III

50 D (2 in.) 65 D (21/2 in.) 54 SD (21/8 in. SA) 50 A (2 in.) Description Code Number Description Code Number
027H5120 027H5124 027H5123 027H5121 ICM 50-A 027H5180 *) ICAD 900 027H1201
ICM 50-B 027H5181 *)
50 SOC (2 in.) 65 A (21/2 in.)
*) Including gasket and O-rings
027H5122 027H5125
D = Butt-weld DIN ; A = Butt-weld ANSI ; J = Butt-weld JIS ; SOC = Socket weld ANSI ;
SD = Solder DIN ; SA = Solder ANSI ; FPT = Female Pipe Thread

Ordering complete factory assembled valve without actuator Spare parts and accessories
(body, function module/top cover) Table A Spare parts

Available connections Spare Parts Code Number


50 D (2 in.) 65 D (21/2 in.) 54 SD (21/8 in. SA) 50 A (2 in.) 50 SOC (2 in.) 65 A (21/2 in.) ICM 50 Service kit 027H5220
ICM 50-A 027H5000 027H5008 027H5006 027H5002 027H5004
ICM 50-B 027H5001 027H5007 027H5003 027H5005
Accessories
Select from parts programme

ICAD-UPS for ICM 20-125 Multi-function tool for ICM 40-65

Accessories Code Number


ICV 50
027H5174 *)
027H0182 027H0181 top cover blind
*) Including bolts and gaskets

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 53


Technical leaflet Motor valves, type ICM and actuators type ICAD

ICM 65 / ICAD 900


Ordering from the parts programme

Example (select from table I, II and III)

+ + =
Valve body 65 J (21/2 in.) Top cover ICM 65-B Actuator
027H6122 027H6181 027H1201
Table I Table II Table III

ICM 65 Function module /


ICV 65 valve body w/different connections Table I top cover Table II ICAD 900 actuator Table III

65 D (21/2 in.) 65 A (21/2 in.) 65 J (21/2 in.) 80 D (3 in.) Description Code Number Description Code Number
027H6120 027H6121 027H6122 027H6126 ICM 65-B 027H6181 *) ICAD 900 027H1201
*) Including gasket and O-rings
80 A (3 in.) 67 SA (25/8 in.) 76 SD (3 in.) 65 SOC (21/2 in.)
027H6127 027H6125 027H6124 027H6123

D = Butt-weld DIN ; A = Butt-weld ANSI ; J = Butt-weld JIS ; SOC = Socket weld ANSI ;
SD = Solder DIN ; SA = Solder ANSI ; FPT = Female Pipe Thread

Ordering complete factory assembled valve without actuator Spare parts and accessories
(body, function module/top cover) Table A Spare parts

Available connections Spare Parts Code Number


65 D (21/2 in.) 65 A (21/2 in.) 65 J (21/2 in.) 80 D (3 in.) 80 A (3 in.) 67 SA (25/8 in.) 76 SD (3 in.) 65 SOC (21/2 in.) ICM 65 Service kit 027H6220
ICM 65-B 027H6001 027H6003 027H6007 027H6009 027H6005

Select from parts programme Accessories

ICAD-UPS for ICM 20-125 Multi-function tool for ICM 40-65

Accessories Code Number


ICV 65
027H6174 *)
027H0182 027H0181 top cover blind
*) Including bolts and gaskets

54 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

ICM 20 / ICAD 600


Dimensions

ICM 20 / ICAD 600

Connection H H1 H2 L L1 L2 Weight ICM incl. ICAD


mm 40 146 85 107 87 65 3 kg
20 D ( /4 in.)
3
in. 1.58 5.75 3.35 4.21 3.43 2.56 6.6 lb.
mm 40 146 85 107 87 65 3 kg
25 D (1 in.)
in. 1.58 5.75 3.35 4.21 3.43 2.56 6.6 lb.
mm 40 146 85 107 87 65 3 kg
25 A (1 in.)
in. 1.58 5.75 3.35 4.21 3.43 2.56 6.6 lb.
mm 40 146 85 107 87 65 3 kg
20 A (3/4 in.)
in. 1.58 5.75 3.35 4.21 3.43 2.56 6.6 lb.
mm 40 146 85 107 87 65 3 kg
20 SOC (3/4 in.)
in. 1.58 5.75 3.35 4.21 3.43 2.56 6.6 lb.
mm 40 146 85 107 87 65 3 kg
16 SD (5/8 in.)
in. 1.58 5.75 3.35 4.21 3.43 2.56 6.6 lb.
mm 40 146 85 107 87 65 3 kg
22 SD (7/8 in.)
in. 1.58 5.75 3.35 4.21 3.43 2.56 6.6 lb.
mm 40 146 85 107 87 65 3 kg
16 SA (5/8 in.)
in. 1.58 5.75 3.35 4.21 3.43 2.56 6.6 lb.
mm 40 146 85 107 87 65 3 kg
22 SA (7/8 in.)
in. 1.58 5.75 3.35 4.21 3.43 2.56 6.6 lb.
mm 40 146 85 107 87 65 3 kg
20 FPT (3/4 in.)
in. 1.58 5.75 3.35 4.21 3.43 2.56 6.6 lb.

D = Butt-weld DIN ; A = Butt-weld ANSI ; J = Butt-weld JIS ; SOC = Socket weld ANSI ; SD = Solder DIN ; SA = Solder ANSI ; FPT = Female Pipe Thread

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 55


Technical leaflet Motor valves, type ICM and actuators type ICAD

ICM 25 / ICAD 600


Dimensions (continued)

ICM 25 / ICAD 600

Connection H H1 H2 L L1 L2 Weight ICM incl. ICAD


mm 40 153 99 135 87 84 4.1 kg
20 D ( /4 in.)
3
in. 1.58 6.02 3.90 5.31 3.43 3.31 8.8 lb.
mm 40 153 99 135 87 84 4.1 kg
25 D (1 in.)
in. 1.58 6.02 3.90 5.31 3.43 3.31 8.8 lb.
mm 40 153 99 135 87 84 4.1 kg
32 D (1 /4 in.)
1
in. 1.58 6.02 3.90 5.31 3.43 3.31 8.8 lb.
mm 40 153 99 135 87 84 4.1 kg
40 D (11/2 in.)
in. 1.58 6.02 3.90 5.31 3.43 3.31 8.8 lb.
mm 40 153 99 135 87 84 4.1 kg
20 A ( /4 in.)
3
in. 1.58 6.02 3.90 5.31 3.43 3.31 8.8 lb.
mm 40 153 99 135 87 84 4.1 kg
25 A (1 in.)
in. 1.58 6.02 3.90 5.31 3.43 3.31 8.8 lb.
mm 40 153 99 135 87 84 4.1 kg
32 A (1 /4 in.)
1
in. 1.58 6.02 3.90 5.31 3.43 3.31 8.8 lb.
mm 40 153 99 135 87 84 4.1 kg
20 SOC (3/4 in.)
in. 1.58 6.02 3.90 5.31 3.43 3.31 8.8 lb.
mm 40 153 99 148 87 84 4.1 kg
25 SOC (1 in.)
in. 1.58 6.02 3.90 5.83 3.43 3.31 8.8 lb.
mm 40 153 99 135 87 84 4.1 kg
22 SD (7/8 in.)
in. 1.58 6.02 3.90 5.31 3.43 3.31 8.8 lb.
mm 40 153 99 147 87 84 4.1 kg
28 SD (1 /8 in.)
1
in. 1.58 6.02 3.90 5.79 3.43 3.31 8.8 lb.
mm 40 153 99 135 87 84 4.1 kg
22 SA (7/8 in.)
in. 1.58 6.02 3.90 5.31 3.43 3.31 8.8 lb.
mm 40 153 99 147 87 84 4.1 kg
28 SA (11/8 in.)
in. 1.58 6.02 3.90 5.79 3.43 3.31 8.8 lb.
mm 40 153 99 147 87 84 4.1 kg
35 SD (1 /8 in. SA)
3
in. 1.58 6.02 3.90 5.79 3.43 3.31 8.8 lb.
mm 40 153 99 135 87 84 4.1 kg
20 FPT (3/4 in.)
in. 1.58 6.02 3.90 5.31 3.43 3.31 8.8 lb.
mm 40 153 99 135 87 84 4.1 kg
25 FPT (1 in.)
in. 1.58 6.02 3.90 5.31 3.43 3.31 8.8 lb.
D = Butt-weld DIN ; A = Butt-weld ANSI ; J = Butt-weld JIS ; SOC = Socket weld ANSI ; SD = Solder DIN ; SA = Solder ANSI ; FPT = Female Pipe Thread

56 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

ICM 32 / ICAD 600


Dimensions (continued)

ICM 32 / ICAD 600

Connection H H1 H2 L L1 L2 Weight ICM incl. ICAD


mm 40 146 117 145 87 102 5.8 kg
32 D (11/4 in.)
in. 1.58 5.75 4.61 5.71 3.43 4.02 11.0 lb.
mm 40 146 117 145 87 102 5.8 kg
40 D (11/2 in.)
in. 1.58 5.75 4.61 5.71 3.43 4.02 11.0 lb.
mm 40 146 117 145 87 102 5.8 kg
32 A (11/4 in.)
in. 1.58 5.75 4.61 5.71 3.43 4.02 11.0 lb.
mm 40 146 117 145 87 102 5.8 kg
40 A (11/2 in.)
in. 1.58 5.75 4.61 5.71 3.43 4.02 11.0 lb.
mm 40 146 117 147 87 102 5.8 kg
32 SOC (11/4 in.)
in. 1.58 5.75 4.61 5.79 3.43 4.02 11.0 lb.
mm 40 146 117 148 87 102 5.8 kg
35 SD (13/8 in. SA)
in. 1.58 5.75 4.61 5.83 3.43 4.02 11.0 lb.
mm 40 146 117 148 87 102 5.8 kg
42 SD (15/8 in.)
in. 1.58 5.75 4.61 5.83 3.43 4.02 11.0 lb.
mm 40 146 117 148 87 102 5.8 kg
42 SA (15/8 in.)
in. 1.58 5.75 4.61 5.83 3.43 4.02 11.0 lb.

D = Butt-weld DIN ; A = Butt-weld ANSI ; J = Butt-weld JIS ; SOC = Socket weld ANSI ; SD = Solder DIN ; SA = Solder ANSI ; FPT = Female Pipe Thread

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 57


Technical leaflet Motor valves, type ICM and actuators type ICAD

ICM 40 / ICAD 900


Dimensions (continued)

ICM 40 / ICAD 900

Connection H H1 H2 L L1 L2 Weight ICM incl. ICAD


mm 45 184 131 160 87 107 7.8 kg
40 D (1 /2 in.)
1
in. 1.77 7.24 5.16 6.30 3.43 4.21 17.2 lb
mm 45 184 131 180 87 107 7.8 kg
50 D (2 in.)
in. 1.77 7.24 5.16 7.09 3.43 4.21 17.2 lb
mm 45 184 131 160 87 107 7.8 kg
40 A (11/2 in.)
in. 1.77 7.24 5.16 6.30 3.43 4.21 17.2 lb
mm 45 184 131 180 87 107 7.8 kg
50 A (2 in.)
in. 1.77 7.24 5.16 7.09 3.43 4.21 17.2 lb
mm 45 184 131 180 87 107 7.8 kg
40 SOC (11/2 in.)
in. 1.77 7.24 5.16 7.09 3.43 4.21 17.2 lb
mm 45 184 131 180 87 107 7.8 kg
42 SD (15/8 in.)
in. 1.77 7.24 5.16 7.09 3.43 4.21 17.2 lb
mm 45 184 131 180 87 107 7.8 kg
42 SA (15/8 in.)
in. 1.77 7.24 5.16 7.09 3.43 4.21 17.2 lb

D = Butt-weld DIN ; A = Butt-weld ANSI ; J = Butt-weld JIS ; SOC = Socket weld ANSI ; SD = Solder DIN ; SA = Solder ANSI ; FPT = Female Pipe Thread

58 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

ICM 50 / ICAD 900


Dimensions (continued)

ICM 50 / ICAD 900

Connection H H1 H2 L L1 L2 Weight ICM incl. ICAD


mm 45 176 159 200 87 125 11.1
50 D (2 in.)
in. 1.77 6.93 6.26 7.87 3.43 4.92 24.4
mm 45 176 159 210 87 125 11.1
65 D (21/2 in.)
in. 1.77 6.93 6.26 8.27 3.43 4.92 24.4
mm 45 176 159 200 87 125 11.1
50 A (2 in.)
in. 1.77 6.93 6.26 7.87 3.43 4.92 24.4
mm 45 176 159 210 87 125 11.1
65 A (21/2 in.)
in. 1.77 6.93 6.26 8.27 3.43 4.92 24.4
mm 45 176 159 216 87 125 11.1
50 SOC (2 in.)
in. 1.77 6.93 6.26 8.50 3.43 4.92 24.4
mm 45 176 159 216 87 125 11.1
54 SD (21/8 in. SA)
in. 1.77 6.93 6.26 8.50 3.43 4.92 24.4

D = Butt-weld DIN ; A = Butt-weld ANSI ; J = Butt-weld JIS ; SOC = Socket weld ANSI ; SD = Solder DIN ; SA = Solder ANSI ; FPT = Female Pipe Thread

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 59


Technical leaflet Motor valves, type ICM and actuators type ICAD

ICM 65 / ICAD 900


Dimensions (continued)

ICM 65 / ICAD 900

Connection H H1 H2 L L1 L2 Weight ICM incl. ICAD


mm 45 176 188 230 87 139 16.6 kg
65 D (2 /2 in.)
1
in. 1.77 6.93 7.40 9.06 3.43 5.47 36.5 lb
mm 45 176 188 245 87 139 16.6 kg
80 D (3 in.)
in. 1.77 6.93 7.40 9.65 3.43 5.47 36.5 lb
mm 45 176 188 230 87 139 16.6 kg
65 A (2 /2 in.)
1
in. 1.77 6.93 7.40 9.06 3.43 5.47 36.5 lb
mm 45 176 188 245 87 139 16.6 kg
80 A (3 in.)
in. 1.77 6.93 7.40 9.65 3.43 5.47 36.5 lb
mm 45 176 188 230 87 139 16.6 kg
65 J (2 /2 in.)
1
in. 1.77 6.93 7.40 9.06 3.43 5.47 36.5 lb
mm 45 176 188 230 87 139 16.6 kg
65 SOC (21/2 in.)
in. 1.77 6.93 7.40 9.06 3.43 5.47 36.5 lb
mm 45 176 188 245 87 139 16.6 kg
76 SD (3 in.)
in. 1.77 6.93 7.40 9.65 3.43 5.47 36.5 lb
mm 45 176 188 245 87 139 16.6 kg
67 SA (2 /8 in.)
5
in. 1.77 6.93 7.40 9.65 3.43 5.47 36.5 lb
D = Butt-weld DIN ; A = Butt-weld ANSI ; J = Butt-weld JIS ; SOC = Socket weld ANSI ; SD = Solder DIN ; SA = Solder ANSI ; FPT = Female Pipe Thread

60 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006


Technical leaflet Motor valves, type ICM and actuators type ICAD

Connections Size Size OD T OD T


mm in. mm mm in. in.
D: Butt-weld DIN (2448) 20 (3/4) 26.9 2.3 1.059 0.091
25 (1) 33.7 2.6 1.327 0.103
32 (11/4) 42.4 2.6 1.669 0.102
40 (11/2) 48.3 2.6 1.902 0.103
50 (2) 60.3 2.9 2.37 0.11
65 (21/2) 76.1 2.9 3 0.11
80 (3) 88.9 3.2 3.50 0.13

A: Butt-weld ANSI (B 36.10) Size Size OD T OD T


Schedule
mm in. mm mm in. in.
(20) 3
/4 26.9 4.0 1.059 0.158 80
(25) 1 33.7 4.6 1.327 0.181 80
(32) 11/4 42.4 4.9 1.669 0.193 80
(40) 11/2 48.3 5.1 1.902 0.201 80
(50) 2 60.3 3.9 2.37 0.15 40
(65) 21/2 73.0 5.2 2.87 0.20 40
(80) 3 88.9 5.5 3.50 0.22 40

J: Butt-weld JIS Size Size OD T OD T


mm in. mm mm in. in.
(20) 3
/4 26.9 4.0 1.059 0.158
(25) 1 33.7 4.6 1.327 0.181
(32) 11/4 42.4 4.9 1.669 0.193
(40) 11/2 48.3 5.1 1.902 0.201
(50) 2 60.3 3.9 2.37 0.15
(65) 21/2 76.3 5.2 3.0 0.20
(80) 3 88.9 5.5 3.50 0.22

SOC: Size Size ID T ID T L L


Socket welding ANSI (B 16.11) mm in. mm mm in. in. mm in.
(20) 3
/4 27.2 4.6 1.071 0.181 13 0.51
(25) 1 33.9 7.2 1.335 0.284 13 0.51
(32) 11/4 42.7 6.1 1.743 0.240 13 0.51
(40) 11/2 48.8 6.6 1.921 0.260 13 0.51
(50) 2 61.2 6.2 2.41 0.24 16 0.63
(65) 21/2 74 8.8 2.91 0.344 16 0.63

SD: Soldering (DIN 2856) Size Size ID ID L L


mm in. mm in. mm in.
16 16.07 15
22 22.08 16.5
28 28.08 26
35 35.07 25
42 42.07 28
54 54.09 33
76 76.1 33

SA: Soldering (ANSI B 16.22) 5


/8 0.625 0.591
7
/8 0.875 0.650
11/8 1.125 1.024
13/8 1.375 0.984
15/8 1.625 1.102
21/8 2.125 1.300
25/8 2.625 1.300

FPT: Size Size


Inside pipe thread
Female pipe thread, mm in.
(ANSI/ASME B 1.20.1) (20) 3
/4 (3/4 x 14 NPT)
(25) 1 (1 x 11.5 NPT)
(32) 11/4 (11/4 x 11.5 NPT)

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 61


Technical leaflet Motor valves, type ICM and actuators type ICAD

General operation

1. "Down" arrow push button


2. Enter
3. "Up" arrow push button
4. Display

Fig. 2

ICAD is equipped with an MMI (Man Machine – To exit from the Parameter list and return
Interface) from which it is possible to monitor to the display of Opening Degree (OD) keep
and change the setting of parameters to adapt the push button activated for 2 seconds.
the ICAD and the corresponding ICM to the Display (fig. 2, pos. 4)
actual refrigeration application. – Normally the Opening Degree (OD) 0 - 100 %
of the ICM valve is displayed. No activation of
The setting of parameters is managed by means push buttons for 20 seconds means that the
of the integrated ICAD MMI (see fig. 2 and fig. 3) display will always show OD (see fig. 5).
and consists of:

Fig. 5

"Down" arrow Enter "Up" arrow Displays the parameter.


Fig. 3 Displays the actual value of a parameter.
Displays the function status by means of text
"Down" arrow push button (fig. 2, pos. 1) (fig. 2, pos. 4)
– Decreases parameter number by 1 at each – Mod represents that ICAD is positioning the
activation ICM valve according to an analog input
"Up" arrow pushbutton (fig. 2, pos. 3) signal (Current or Voltage)
– Increases parameter number by 1 at each – Low represents that ICAD is operating the
activation ICM valve like an ON/OFF solenoid valve
with low speed according to a digital input
Enter push button (fig. 2, pos. 2) signal.
– Gives access to the Parameter list by – Med represents that ICAD is operating the
keeping the push button activated for 2 ICM valve like an ON/OFF solenoid valve
seconds. A Parameter list example is with medium speed according to a digital
shown below (parameter ¡08, fig. 4). input signal.
– High represents that ICAD is operating the
ICM valve like an ON/OFF solenoid valve
with high speed according to a digital input
signal (see fig. 6).

Fig. 4

– Gives access to change a value once the


Parameter list has been accessed.
– Acknowledge and save change of value of a
Fig. 6
parameter.
62 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006
Technical leaflet Motor valves, type ICM and actuators type ICAD

Alarms ICAD can handle and display different alarms. If an alarm has been detected the ICAD display
(fig. 2) will alternate between showing
ICM
Description
alarm text
Comments Actual alarm and present Opening Degree.
No valve type A1 At start-up A1 and CA will be If more than one alarm is active at the same
selected displayed time the alarm with the highest priority will take
Controller fault A2 Internal fault inside electronics preference. A1 has the highest priority, A5 the
AIl input error A3 Not active if ¡01 = 2 or ¡02 = 2 lowest.
When ¡03 = 1 and AI A > 22 mA Any active alarm will activate the Common
When ¡03 = 2 and AI A > 22 mA
or AI A < 2 mA
Digital Alarm output (Normally Open).
When ¡03 = 3 and AI A >12 V All alarms will automatically reset them-selves
When ¡03 = 4 and AI A >12 V
when they physically disappear.
or AI A < 1 V
Low voltage of A4 If 5 V d.c. < Fail safe supply Old alarms (alarms that have been active, but
fail safe supply < 18 V d.c. have physically disappeared again) can be found
Check Supply A5 If supply voltage < 18 V d.c. in parameter ¡11.
to ICAD

Parameter list
Display Factory
Description Min. Max. Unit Comments
name setting
ICM OD (Opening ICM valve Opening Degree is displayed during normal operation.
- 0 100 - %
Degree) Running display value (see ¡01, ¡05).
Internal main switch
1: Normal operation
Main Switch ¡01 1 2 1 -
2: Manual operation. Valve Opening Degree will be flashing. With the down arrow
and the up arrow push buttons the OD can be entered manually.
Operation mode
1: Modulating – ICM positioning according to Analogue Input (see ¡03)
Mode ¡02 1 2 1 -
2: ON/OFF - operating the ICM valve like an ON/OFF solenoid valve controlled via
Digital Input. See also ¡09.
Type of Analogue Input signal from external controller
1: 0 - 20 mA
Analogue Input signal ¡03 1 4 2 - 2: 4 - 20 mA
3: 0 - 10 V
4: 2 - 10 V
Speed can be decreased. Max. speed is 100 %
Not active when ¡01 = 2
If ¡02 = 2 the display will indicate speed in display. Low, Med and High also
Speed at ON/OFF and
¡04 1 100 100 % means ON/OFF operation.
Modulating Mode
If ¡04 < = 33, Low is displayed
33 < If ¡04 < = 66, Med is displayed
If ¡04 > = 67 High is displayed
Not active before ¡26 has been operated.
Always auto reset to 0.
Automatic calibration ¡05 0 1 0 -
CA” will flash in the display during calibration, if Enter push button has been
activated for two seconds.
Type of A0 signal for ICM valve position
0: No signal
Analogue Output signal ¡06 0 2 2 -
1: 0 - 20 mA
2: 4 - 20 mA
Define condition at power cut when fail safe is installed.
1: Close valve
Fail safe ¡07 1 4 1 - 2: Open valve
3: Maintain valve position
4: Go to OD given by ¡12
Define function when DI is ON (short circuited DI terminals) when ¡02 = 2
Digital Input function ¡09 1 2 1 1: Open ICM valve (DI = OFF = > Close ICM valve)
2: Close ICM valve (DI = OFF = > Open ICM valve)
Enter number to access password protected parameters:
Password ¡10 0 199 0 -
¡26
Old alarms will be listed with the latest shown first. Alarm list can be reset by
Old Alarms ¡11 A1 A99 - -
means of activating down arrow and up arrow at the same time for 2 seconds.
Only active if ¡07 = 4
OD at powercut ¡12 0 100 50 -
If fail safe supply is connected and powercut occurs ICM will go to entered OD.
NB: Password protected. Password = 11
At first start up A1 will flash in display. Enter valve type
0: No valve selected. Alarm A1 will become active.
1: ICM20 with ICAD 600
ICM configuration ¡26 0 6 0 2: ICM25 with ICAD 600
3: ICM32 with ICAD 600
4: ICM40 with ICAD 900
5: ICM50 with ICAD 900
6: ICM65 with ICAD 900

 Danfoss A/S (RC-CMS / MWA), 01-2006 DKRCI.PD.HT0.A2.02 / 520H0646 63


Technical leaflet Motor valves, type ICM and actuators type ICAD

Parameter list (continued)


Service
Display Factory
Description name
Min. Max.
setting
Unit Comments

OD % ¡50 0 100 - % ICM valve Opening Degree


AI [mA] ¡51 0 20 - mA Analog Input signal
AI [V] ¡52 0 10 - V Analog Input signal
AO [mA] ¡53 0 20 - mA Analog Output signal
DI ¡54 0 1 - - Digital Input signal
DO Close ¡55 0 1 - - Digital Output Closed status. ON when OD < 3 %
DO Open ¡56 0 1 - - Digital Output Open status. ON when OD > 97 %
DO Alarm ¡57 0 1 - - Digital Output alarm status. ON when an alarm is detected
MAS mP SW ver. ¡58 0 100 - - Software version for MASTER Microprocessor
SLA mP SW ver. ¡59 0 100 - - Software version for SLAVE Microprocessor

Reset to factory setting : 1. Remove the power supply.


2. Activate down arrow and up arrow push buttons
at the same time.
3. Connect the power supply.
4. Release down arrow and up arrow push buttons.
5. When the display on ICAD (fig. 2) is alternating
between showing: CA and A1 the factory
resetting is complete.

64 DKRCI.PD.HT0.A2.02 / 520H0646  Danfoss A/S (RC-CMS / MWA), 01-2006