Design Strategies:
Guidelines for
Horne Building
Jackson, Mississippi
Guidelines
Worksheets
Blank. Worksheets, Data Tables, and Worksheet Instructions. . . . . . . . . . . . . . . . . .39
Worked Example
Description of the Example Building. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ,47
Filled in Worksheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Annotated Worksheet Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
"Any'fown", USA • . . • . . • . . . . . • . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Appendix
Glossary of Tenns. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81
References. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Summary Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Technical Basis for the Builder Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . .87
JackBon, MiBBiBBippi
PASSIVE SOLAR DESIGN STRATEGIES
Jackson, Mississippi
Passive Solar
Design Strategies
GUIDELINES
Jackson, Mississippi
2 GUIDELINES PART ONE: INTRODUCTION
Jackson, Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 3
The Guidelines Part Three gives more The Base Case House is a
Some principles of passive solar specific advice about techniques reasonably energy-efficient
design remain the same in every for suntempering, direct gain house based on a 1987 National
climate. An important aspect of systems, thermal storage mass AsSOCiation of Home Builders
good passive solar design is that walls and sunspaces, and for study of housing characteristics,
it takes advantage of the natural cooling strategies to help for seven different regions. The
opportunities at the specific site. offset air-conditioning needs. Base Case used for Jackson.
So, many fundamental aspects The Example Tables in Part Mississippi is from the 1,000-
of passive solar design will Three are also related to 2,500 heating degree days
depend on the conditions in a Worksheet numbers. so that you region. The floor construction
small local area, and even on the can compare them to the is assumed to be slab-on-grade,
features of the building site. designs you are evaluating. For because this is typical in
Many of the suggestions in this example. the Passive Solar Mississippi.
section apply specifically to Sunspace Example Case which The examples show how to
Jackson, Mississippi. but there uses 40% less energy than the achieve 20%, 40% and 600A>
is also information which will be Base Case House (page 29) has: energy-\.lse reductions using
useful in any climate. • A ConseIVation Performance three basic strategies:
Part One introduces Passive Level of apprOximately 23,479 • Added Insulation:
Solar Design Strategies, and Btu/yr-sf. Increasing thermal resistance
presents the performance • An Auxiliary Heat insulation levels without adding
potential of several different Performance Level of solar features.
passive solar systems in the approximately 15,073 Btu/yr-sf, • Suntemperlng: Increasing
Jackson climate. Although in and south-faCing glazing to a
practice many factors will affect • A Summer Cooling maximum of 7% of the house's
actual energy performance. this Performance Level of 14,439 total floor area. without adding
information gives a general idea Btu/yr-sf. thermal mass (energy storage)
of how various systems might In this example. the energy beyond what is already in the
perform in Jackson. savings are achieved by framing, standard floor
Part Two discusses the basic increasing insulation about 7% coverings and gypsum wall-
concepts of passive solar design over the Base Case House, board and ceiling surfaces.
and construction: what the adding a sunspace with south Suntempertng is combined with
advantages of passive solar are. glazing area equal to 11% of the increased levels of thermal
how passive solar relates to house's floor area. and using a reSistance insulation.
other kinds of energy ceiling fan to cut some of the air
conseIVation measures. how the conditioning load.
primary passive solar systems A Base Case House is
work, and what the builder's compared with a series of
most important considerations example cases to illustrate
should be when evaluating and exactly how these increased
using different passive solar levels of energy-effiCiency might
strategies. be achieved.
Jackson, Mississippi
4 GUIDELINES PART ONE: INTRODUCTION
• Solar Architecture: Using The Worksheets from the Solar System Savings
three different design The Worksheets are specifically Fraction table or from the Heat
approaches: Direct Gain, tailored for Jackson, Mississippi, Gain Factor table.
Sunspace, and Thermal Storage and are a very important part of The Worksheets allow
Wall, with increased levels of this package because they allow calculation of the follOWing
thermal resistance insulation. you to compare different passive performance indicators:
For all strategies, the energy solar strategies or combinations • Worksheet I: Conservation
savings indicated are based on of strategies, and the effect that Performance Level: Determines
the assumption that the energy- changes will have on the overall how well the house's basic
efficient design and construction performance of the house. energy conservation measures
gUidelines have been followed, so The most effective way to use (insulation, sealing, caulking,
the houses are properly sited the Worksheets is to make etc.) are working to prevent
and tightly built with high- multiple copies before you fill unwanted heat loss or gains.
quality windows and doors. them out the first time. You can The bottom line of this
The Guidelines section has then use the Worksheets to Worksheet is a number
been kept as brief and calculate several different measuring heat loss in British
straightforward as possible, but designs. For instance, you could thermal units per square foot
more detailed information is first calculate the performance of per year (Btu/ sf-yr) - the lower
available if needed. Some the basic house you build now, the heat loss, the better.
references are indicated in the then fill out Worksheets for that • Worksheet U: AuxlUary
text, and a list of other house with a variety of energy Heat Performance Level:
information sources can be performance strategies such as Determines how much heat has
found in the References. Also increased insulation, to be supplied (that is, provided
included at the end of this book suntempering and specific by the heating system) after
are a brief glossary: a summary passive solar components. taking into account the heat
of the Example Tables for The Worksheets provide a contributed by passive solar.
Jackson, MisSissippi, and the way to calculate quickly and This worksheet arrives at a
Technical Basis for the Builder with reasonable accuracy how number estimating the amount
Guidelines which explains the well a design is likely to perform of heating energy the house's
background and assumptions in four key ways: how well it will non-solar heating system has to
behind the Guidelines and conserve heat energy: how much provide in Btu/yr-sf. Again, the
Worksheets. the solar features will contribute lower the value, the better.
to its total heating energy needs: • Worksheet m: Thermal
how comfortable the house will Mass/Comfort: Determines
be: and how much the annual whether the house has adequate
cooling load (need for air thermal mass to assure comfort
conditioning) will be. and good thermal performance.
The Worksheets are Worksheet III calculates the
supported by "look-up" tables number of degrees the
containing pre-calculated temperature inside the house is
numbers for the local area. likely to vary, or "swing", during
Some of the blanks in the a sunny winter day without the
Worksheets call for information heating system operating. A
about the house - for example, well-designed house should have
floor area and proJected area of a temperature swing of no more
passive solar glazing. Other than 13 degrees, and the less
blanks require a number from the better.
one of the tables - for example,
JacksOD, Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 5
• Worksheet IV: Summer 2. Passive Solar glass, and each passive solar
Cooling Performance Level: Performance system has 145 sf.
Indicates how much air The energy savings
conditioning the house will need Potential presented in this example
in the summer (It is riot, assume that all the systems are
however, intended for use in The energy performance of designed and built according to
sizing equipment, but as an passive solar strategies varies the suggestions in these
indication of the reductions in significantly, depending on Guidelines. It's also important
annual cooling load made climate, the specific design of to remember that the figures
possible by the use of natural the system, and the way it is below are for annual net heating
cooling). The natural cooling built and operated. Of course, benefits. The natural cooling
guidelines should make the energy performance is not the section in Part Three gives
house's total cooling load - the only consideration. A system advice about shading and other
bottom line of this Worksheet, in which will give excellent energy techniques which would make
Btu/yr-sf - smaller than in a performance may not be as sure the winter heating benefits
"conventional" house. The lower marketable in your area or as are not at the expense of higher
the cooling performance level, easily adaptable to your designs summer cooling loads.
the better the design. as a system which saves less Please note that throughout
So, the Worksheets provide energy but fits other needs. the Guidelines and Worksheets
four key numbers indicating the In the following table, several the glazing areas given are for
projected performance of the different passive solar systems the actual net area of the glass
various designs you are are presented along with two itself. A common rule of thumb
evaluating. numbers which indicate their is that the net glass area is 80
• The Worked Example: To performance. The Percent Solar percent.ofthe rough frame
assist in understanding how the Savings is a measure of how opening. For example, if a south
design strategies outlined in the much the passive solar system is glass area of 100 sf is desired,
Guidelines affect the overall reducing the need for purchased the required area of the rough
performance of a house, a energy. For example, the frame opening would be about
worked example is included. Percent Solar Savings for the 125 sf.
The example house is assumed Base Case House is 9.6%,
to be constructed of materials because even in a non-solar
and design elements typical of house, the south-facing windows
the area. Various design are contributing some heat
features, such as direct gain energy.
spaces, sunspaces, increased The Yield is the annual net
levels of insulation and thermal heating energy benefit of adding
mass, are included to illustrate the passive solar system,
the effects combined systems measured in Btu saved per year
have on the performance of a per square foot of additional
house. Also, many features are south glazing.
covered to demonstrate how The figures given are for a
various conditions and 1,500 sf, Single-story house with
situations are addressed in the a slab floor. The Base Case
worksheets. A description of the House has 45 sf of south-facing
design features, along with the glazing. For the purposes of this
house plans, elevations and example, the Suntempered
sections, is included for house has 100 sf of south-facing
additional support information.
Jackson, Mississippi
6 GUIDELINES PART ONE: INTRODUCTION
1. Night insulation is assumed to cover the south glass each night and
removed when sun is available. Experience has shown that many
homeowners find this inconvenient and so the potential energy savings
are often not achieved. Using low-e or other energy-efficient glazing is
more reliable.
3. The semi-enclosed sunspace has only the south wall exposed to the
out-of-doors. The glazing has a slope of 50· from the horizontal, or a
14:12 pitch. The side walls are adjacent to conditioned space in the
house. (See diagram SSD1 in the Worksheets.)
Jackson, Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 7
4. Mechanical Systems
5. South-Facing Glass
6. Thermal Mass
7. Orientation
Jackson, Mississippi
8 GUIDELINES PART TWO: BASICS OF PASSIVE SOLAR
1. Why Passive Solar? insulation is inviSible to the They just present their houses
More than a Question prospective home buyer. A as the state of the art in energy-
sunny. open living area lit by effiCiency and style. and they
of Energy south-faCing windows. on the use passive solar as a part of the
other hand. may be a key selling package.
Houses today are more energy- point. Windows in general are The U.S. Department of
efficient than ever before. popular with homebuyers. and Energy and the National Renew-
However. the vast majority of passive solar can make windows able Energy Laboratory (NREL)
new houses still ignore a lot of energy producers instead of conducted extensive national
energy saving opportunities - energy liabilities. surveys of passive solar homes.
opportunities available in the Another example: high- home owners and potential
sunlight falling on the house. in efficiency heating eqUipment can buyers. Some key findings:
the landscaping. breezes and account for significant energy • passive solar homes work
other natural elements of the savings - but it won't be as - they generally require an
site. and opportunities in the much fun on a winter morning average of about 300Al less
structure and materials of the as breakfast in a bright. energy for heating than
house itself. which. with attractive sunspace. "conventional" houses. with
thoughtful design. could be used The point is not that a some houses saving much more.
to collect and use free energy. buUder should choose passive • occupants of passive solar
Passive solar (the name solar instead of other energy- homes are pleased with the
distinguishes it from "active" or conserving measures. The performance of their homes (over
mechanical solar technologies) is important thing is that passive 90% "very satisfied"). but they
simply a way to take maximum solar strategies can add not only rank the comfort and pleasant
advantage of these energy-efficiency. but also very living environment as just as
opportunities. saleable amenities - style. important (in some regions.
Home buyers are also comfort. attractive interiOrs. more important) to their
increasingly sophisticated about curb appeal and resale value. satisfaction. and in their
energy issues. although the In fact. in some local decision to buy the house. as
average home buyer is probably markets. builders report that energy considerations.
much more familiar with they don·t even make specific • passive solar home owners
insulation than with passive reference to "passive solar". and lenders perceive the
solar. The "energy crisis" may resale value of passive solar
come and go. but very few people houses as high.
perceive their own household
Advantages of Passive Solar
energy bills as getting smaller -
quite the opposite. So a house • Energy perfonnance: Lower energy bills all year-round
with significantly lower monthly • Attractive living environment: large windows and views, sunny
energy costs year-round will interiors, open floor plans
have a strong market advantage • Comfort: quiet (no operating noise), solid construction, warmer in
over a comparable house down winter, cooler in summer (even during a power failure)
the street. no matter what • Value: high owner satisfaction, high resale value
international oU prices may be. • Low Maintenance: durable, reduced operation and repairs
There are many different
• Investment: independence from future rises in fuel costs, will continue
ways to reduce energy bills. and to save money long after any initial costs have been recovered
some are more marketable than
• Environmental Concerns: clean, renewable energy to combat
others. For instance. adding growing concerns over global warming, acid rain and
insulation can markedly improve ozone depletion
energy-efficiency - but added
Jackson. Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 9
Many of the measures that Although the concept is
2. Key Concepts: are often considered part of simple. in practice the
Energy Conservation, suntempering or passive solar - relationship between the
Suntempering, such as orienting to take amounts of glazing and mass is
advantage of summer breezes. or complicated by many factors.
Passive Solar landscaping for natural cooling, and has been a subject of
or facing a long wall of the house conSiderable study and
The strategies for enhancing
south - can help a house experiment. From a comfort and
energy perfonnance which are conserve energy even if no energy standpOint. it would be
presented here fall into four "solar" features are planned. difficult to add too much mass.
general categories: The essential elements in a Thennal mass will hold warmth
• Energy Conservation: passive solar house are south- longer in winter and keep
insulation levels. control of air
facing glass and thermal mass. houses cooler in summer.
infiltration. glazing type and
In the simplest tenns. a The following sections of the
location. mechanical equipment
passive solar system collects Guidelines discuss the size and
and energy efficient appliances.
solar energy through south- location of glass and mass. as
• Suntemperlng: a limited use facing glass and stores solar well as other considerations
of solar techniques; modestly
energy in thennal mass - which are basic to both
increasing south-facing window
materials with a high capacity suntempered and passiye solar
area. usually by relocating
for storing heat (e.g .• brick, houses: improving conservation
windows from other sides of the
concrete masonry. concrete slab. performance; mechanical
house. but without adding
tile. water). The more south- systems; orientation; site
thennal mass.
facing glass is used in the planning for solar access;
• Solar Architecture: going house, the more thennal mass interior space planning; and
beyond conservation and
must be provided. or the house approaching to the house as a
suntempering to a complete
will overheat and the solar totally integrated system.
system of collection. storage and
system will not perfonn as
use of solar energy: using more
expected.
south glass. adding appropriate
Improperly done, passive
thennal mass. and taking steps
solar may continue to heat the
to control and distribute heat
house in the summer. causing
energy throughout the house.
discomfort or high air-
• Natural CooHng: using conditioning bills. or overheat
design and the environment to
the house in the winter and
cool the house and increase
require additional ventilation.
comfort. by increasing air
movement and employing
shading strategies.
What is immediately clear is
that these categories overlap. A
good passive solar design must
include an appropriate thennal
envelope. energy effiCient
mechanical systems. energy
effiCient appliances and proper
solar architecture. specifically
the appropriate amounts and
locations of mass and glass.
JacksOD, Mississippi
10 GUIDELINES PART TWO: BASICS OF PASSIVE SOLAR
Jackson, Mississippi
PASSIVE SOLAR DESIGN STRA TEGIES 11
Air Infiltration
Sealing the house carefully to Checklist for Minimizing Air Leakage
reduce air infiltration - air ./ Tighten seals around windows and doors, and weatherstripping
leakage - is as necessary to around all openings to the outside or to unconditioned rooms;
energy conservation as adding
./ Caulk around all windows and doors before drywall is hung; seal all
insulation. penetrations (plumbing, electrical, etc.);
The tightness of houses is
generally measured in the ./ Insulate behind wall outlets and/or plumbing lines in exterior walls;
number of air changes per hour ./ Caulk under headers and sills;
(ACH). A good, comfortable,
energy-efficient house, built ./ Chink spaces between rough openings and millwork with insulation, or
along the gUidelines in the table for a better seal, fill with foam;
on this page, will have ./ Seal larger openings such as ducts into attics or crawlspaces with
approximately 0.35 to 0.50 air taped polyethylene covered with insulation;
changes per hour under normal
./ Locate continuous vapor retardants located on the warm side of the
winter conditions. insulation (building wrap, continuous interior polyethylene, etc.);
Increasing the tightness of
the house beyond that may ./ Install dampers and/or glass doors on fireplaces; combined with
improve the energy performance, outside combustion air intake;
but it may also create problems ./ Install backdraft dampers on all exhaust fan openings;
with indoor air quality, moisture
build-up, and inadequately ./ Caulk and seal the joint between floor slabs and walls;
vented fireplaces and furnaces.
./ Remove wood grade stakes from slabs and seal;
Tighter houses may perform
effectively with appropriate ./ Cover and seal sump cracks;
mechanical ventilation systems.
The use of house sealing ./ Close core voids in top of concrete masonry foundation walls;
subcontractors to do the ./ Control concrete and masonry cracking;
tightening and check it with a
blower door can often save the ./ Use of air tight drywall methods are also acceptable;
builder time and problems, ./ Employ appropriate radon mitigation techniques.
especially when trying to achieve
particularly high levels of ./ Seal seams in exterior sheathing.
infiltration control.
JacksoD. Mississippi
12 GUIDELINES PART TWO: BASICS OF PASSIVE SOLAR
Non-Solar Glazing account for the glass. the frame. West windows may be the
South-faCing windows are the air gap and any special (low- most problematic. and there are
considered solar glazing. The e) coatings. few shading systems that will be
south windows in any house are North windows should be effective enough to offset the
contributing some solar heat used with care. Sometimes potential for overheating from a
energy to the house's heating views or the diffuse northern large west-faCing window. Glass
needs - whether it's a light are desirable. but in with a low shading coeffiCient
significant. usable amount or general north-faCing windows may be one effective approach -
hardly worth measuring will should not be large. Very large for example. tinted glass or some
depend on design. location and north-facing windows should types oflow-e glass which
other factors which are dealt have high insulation value. or provide some shading while
with later under the discussions R-value. Since north windows allOwing almost clear views. The
of suntempering and passive receive relatively little direct sun cost of properly shading both
solar systems. in sununer. they do not present east and west windows should
North windows in almost much of a shading problem. So be balanced against the benefits.
every climate lose significant if the choice were between an As many windows as
heat energy and gain very little average-sized north-facing possible should be kept operable
useful sunlight in the winter. window and an east or west- for easy natural ventilation in
East and west windows are likely facing window. north would summer. (See also Orientation.
to increase air conditioning actually be a better chOice. page 16. Reconunended Non-
needs unless heat gain is considering both sununer and South Glass Guidelines. page
minimized with careful attention winter perfonnance. 34. and Shading. page 35)
to shading. East windows catch the
But most of the reasons morning sun. Not enough to
people want windows have very provide significant energy. but.
little to do with energy. so the unfortunately. usually enough to
best design will probably be a cause potential overheating
good compromise between problems in summer. If the
energy effiCiency and other views or other elements in the
benefits. such as bright living house's design dictate east
spaces and views. windows. shading should be
Double-glazing of all non- done with particular care.
solar glazing is advisable. Low-e
glazing on all non-solar windows
may be an especially useful
solution because some low-e
coatings can insulate in winter
and shield against unwanted
heat gain in sununer.
A chart is provided with the
worksheets that gives typical
window R-values for generic
window types. When possible.
however. manufacturer's data
based on National Fenestration
Rating Council procedures
should be used. The R-values
that result from procedures
Jackson. Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 13
4. Mechanical • Night Setback: Clock In the National AsSOCiation of
Systems thermostats for automatic Home Builders' Energy-Efficient
setback are usually very effective House Project, all the rooms
The passive solar features in the - but in passive solar systems were fed with low, central air
house and the mechanical with large amounts of thermal supplies, as opposed to the
heating, ventilating and air mass (and thus a large capacity usual placement of registers
conditioning systems (HVAC) will for storing energy and releasing under windows at the end of
it during the night), setback of long runs. This resulted in good
interact all year round, so the
most effective approach will be the thermostat may not save comfort and energy performance.
to design the system as an very much energy unless set The performance of even the
integrated whole. HVAC design properly to account for the time most beautifully designed
is, of course, a complex subject, lag effects resulting from the passive solar house can easily be
but four areas are particularly thermal mass. undermined by details like
worth noting in energy-efficient • Ducts: One area often uninsulated ducts, or by
houses: neglected but of key importance overlooking other basic energy
• System Sizing: Mechanical to the house's energy conservation measures.
systems are often oversized for performance is the design and
the relatively low heating loads location of the ducts. Both the
in well-insulated passive solar supply and return ducts should
houses. Oversized systems will be located within insulated
cost more in the first place, and areas, or be well insulated if they
will cycle on and off more often, run in cold areas of the house.
wasting energy. The back-up All segments of ducts should be
systems in passive solar houses sealed at the jOints. The joints
should be sized to provide 100% where the ducts turn up into
of the heating or cooling load on exterior walls or penetrate the
the design day, but no larger. ceiling should be particularly
Comparing estimates on system tight and sealed.
sizes from more than one • System Efficiency: Heating
contractor is probably a good system efficiency is rated by the
idea. annual fuel utilization efficiency
(AFUE). Cooling system
efficiency is rated by the
seasonal efficiency is rating
(SEER). The higher the number,
the better the performance.
JacksoD, Mississippi
14 GUIDELINES PART TWO: BASICS OF PASSIVE SOLAR
5. South-Facing Glass The third limit on south- When the solar glazing is
facing glass is the total of all tilted, its winter effectiveness as
South-facing solar glass is a key passive solar systems combined, a solar collector usually
component of any passive solar which should not exceed 20% of increases. However, tilted
system. The system must total floor area. Using more glazing can cause serious
include enough solar glazing for south glass than this limit could overheating in the summer if it.
good performance in winter, but lead to overheating even in is not properly shaded.
not so much that cooling winter. Ordinazy vertical glazing is
performance in summer will be For example, a passive solar easier to shade, less likely to
compromised. The amount of system for a 1.500 sf house overheat, less susceptible to
solar glazing must also be might combine 150 sf of direct damage and leaking, and so is
carefully related to the amount gain glazing with 120 sf of almost always a better year-
of thermal mass. Suntempered sunspace glazing for a total of round solution.
houses use no additional 270 sf of solar glazing, or 18% of
thermal mass beyond that the total floor area, well within
already in the wallboard, the direct gain limit of 12% and
framing and furnishings of a the overall limit of 20%. For a
typical house. Houses with design like this, thermal mass
solar architecture must have would be required both in the
additional thennal mass. house and within the sunspace.
There are three types of The Natural Cooling
limits on the amount of south- guidelines in Part Three include
facing glass that can be used recommendations on the window
effectively in a house. The first area that should be operable to
is a limit on the amount of allow for natural ventilation.
glazing for suntempered houses,
7% of the house's total floor
area. Above this 7% limit, mass
must be added.
For direct gain systems in
passive solar houses, the
maximum amount of south-
facing glazing is 12% of total
floor area, regarcUess of how
much additional thennal mass is
provided. This limit will reduce
the problems associated with
visual glare or fabriC fading.
Further details about the most
effective sizing of south glass
and thermal mass for direct gain
systems are provided in Part
Three.
Jackson, Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 15
6. Thermal Mass The thermal storage The design issues related to
capabilities of a given material thermal mass depend on the
Some heat storage capacity, or depend on the material's passive system type. For
thermal mass, is present in all conductivity, specific heat and sunspaces and thermal storage
houses. in the framing. gypsum density. Most of the concrete wall systems. the required mass
wallboard, typical furnishings and masollty materials typically of the system is included in the
and floor coverings. In used in passive solar have design itself. For direct gain, the
suntempered houses, this similar specific heats. added mass must be within the
modest amount of mass is Conductivity tends to increase rooms receiving the sunlight.
suffiCient for the modest amount with increasing density. So the The sections on Direct Gain
of south-facing glass. But more major factor affecting Systems, Sunspaces and
thermal mass is required in performance is density. Thermal Storage Walls contain
passive solar houses, and the Generally, the higher the density more information on techniques
question is not only how much, the beUer. for sizing and locating thermal
but what kind and where it mass in those systems.
should be located.
The thermal mass in a
passive solar system is usually a
conventional construction
material such as brick, poured
concrete. concrete masollty, or Heat Storage Properties of Materials
Specific
tile, and is usually placed in the Heat Density Heat Capacity
floor or interior walls. Other Material (Btu/lb OF) (lb/ft3) (Btu/in-sf- OF)
materials can also be used for
thermal mass, such as water or Poured Concrete 0.16-0.20 120 - 150 2.0 - 2.5
"phase change" materials. Phase Clay Masonry 0.19-0.21
change materials store and Molded Brick 120 -130 2.0 - 2.2
release heat through a chemical Extruded Brick 125 -135 2.1 - 2.3
Pavers 130 - 135 2.2 - 2.3
reactions. Water actually has a
higher unit thermal storage Concrete Masonry 0.19-0.22
capacity than concrete or Concrete Masonry Units 80 - 140 1.3 - 2.3
masollty. Water tubes and units Brick 115 - 140 1.9 - 2.3
Pavers 130 - 150 2.2 - 2.5
called "water walls" are
commercially available (general Gypsum Wallboard 0.26 50 1.1
recommendations for these
systems are included in the Water 62.4 5.2
section on Thermal Storage Wall
systems).
Jackson, Mississippi
16 GUIDELINES PART TWO: BASICS OF PASSIVE SOLAR
Magnetic Deviation
Magnetic Diviation is the angle between true
north and magnetic north.
JacksOD, Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 17
~~-
8. Site Planning for also the figure on page 35
Solar Access showing landscaping for
summer shade.
The basic objective of site
planning for maximum energy
.~
.................•...............• .....
Jackson, Mississippi
18 GUIDELINES PART TWO: BASICS OF PASSIVE SOLAR
Jackson, Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 19
r/ 2. Upgraded levels of Insulation: It is possible, of course, to achieve very high energy-efficiency with a
"superinsulated" design. But in many cases, one advantage of passive solar design is that energy-efficiency
can be achieved with more economical increases in insulation.
On the other hand, if very high energy performance is a priority - for example, in areas where the cost of
fuel is high - the most cost-effective way to achieve it is generally through a combination of high levels of
insulation and passive solar features.
r/ 3. Reduced air Infiltration: Air tightness is not only critical to energy performance, but it also makes the
house more comfortable.
Indoor air quality is an important issue, and too complex for a complete discussion here, but in general,
the suntempered and passive solar houses built according to the GUidelines provide an alternative approach to
achieving improved energy efficiency without requiring air quality controls such as air to air heat exchangers,
which would be needed if the house were made extremely airtight.
r/ 4. Proper window sizing and location: Even if the total amount of glazing is not changed, rearranging the
location alone can often lead to significant energy savings at little or no added cost. Some energy-conserving
designs minimize window area on all sides of the house - but it's a fact of human nature that people like
windows, and windows can be energy producers if located correctly.
r/ 5. Selection of glazing: Low-emissivity (low-e) glazing types went from revolutionary to commonplace in a
very short time, and they can be highly energy-efficient choices. But the range of glazing possibilities is
broader than that, and the choice will have a significant impact on energy performance. Using different types
of glazing for windows with different orientations is worth considering for maximum energy performance; for
example, using heat-rejecting glazing on west windows, high R-value glazing for north and east windows, and
clear double-glazing on solar glazing.
r/ 6. Proper shading of windows: If windows are not properly shaded in summer - either with shading
devices, or by high-performance glazing with a low shading coefficient - the air conditioner will have to work
overtime and the energy savings of the winter may be canceled out. Even more important, unwanted solar
gain is uncomfortable.
r/ 7. Addition of thennal mass: Adding thermal mass - tiled or paved concrete slab, masonry walls, brick
fireplaces, tile floors, etc. - can greatly improve the comfort in the house, holding heat better in winter and
keeping rooms cooler in summer. In a passive solar system, of course, properly sized and located thermal
mass is essential.
r/ 8. Interior design for easy air distribution: If the rooms in the house are planned carefully, the flow of heat
in the winter will make the passive solar features more effective, and the air movement will also enhance
ventilation and comfort during the summer. Often this means the kind of open floor plan which is highly
marketable in most areas. Planning the rooms with attention to use patterns and energy needs can save
energy in other ways, too - for instance, using less-lived-in areas like storage rooms as buffers on the north
side.
r/ 9. Selection and proper sizing of mechanical systems, and selection of energy-efficient appliances:
High-performance heating, cooling and hot water systems are extremely energy-efficient, and almost always a
good investment. Mechanical equipment should have at least a 0.80 Annual Fuel Utilization Efficiency (AFUE).
Well-insulated passive solar homes will have much lower energy loads than conventional homes, and
should be sized accordingly. Oversized systems will cost more and reduce performance.
JacksOD, Mississippi
20 GUIDELINES PART TWO: BASICS OF PASSIVE SOLAR
Jackson, Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 21
2. Suntempering
3. Direct Gain
4. Sunspaces
6. Combined Systems
Jackson, Mississippi
22 GUIDELINES PART THREE: STRATEGIES FOR IMPROVING ENERGY PERFORMANCE
Jackson, Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 23
2. Suntempering
Examples of Heat Energy Savings
Suntempered
Both suntempered and passive
1,500 sf Single Story House (in a specific location)
solar houses:
• begin with good basic Base
energy-conservation, Case 20% 40% 60%
R-Values
• take maximum advantage of Ceiling/Roof 26 26 34 45
the building site through the Walls 14 13 18 25
right orientation for year-round Slab Edge 0 0 0 2
energy savings, and Glass .9 1.8 1.8 1.8
• have increased south-facing Air Changes/Hour 0.75 0.50 0.66 0.50
glass to collect solar energy.
Suntempertng refers to Glass Area (percent of total floor area)
West 3.0% 2.0% 2.0% 2.0%
modest increases in windows on North 3.0% 4.0% 4.0% 4.0%
the south side. East 3.0% 4.0% 4.0% 4.0%
No additional thermal mass South 3.0% 6.7% 6.7% 6.7%
is used, only the "free mass" in
Solar System Size (square feet)
the house - the framing, South Glass 45 100 100 100
gypsum wall-board and
furnishings. Percent Solar Savings
In a "conventional" house, 10% 19% 22% 28%
about 25% of the windows face Performance (Btu/yr-sf)
south, which amounts to about Conservation 27,212 24,941 19,581 14,281
3% of the house's total floor Auxiliary Heat 24,599 20,024 15,098 10,164
Cooling 15,575 13,079 10,293 8,051
area. In a suntempered house,
the percentage is increased to a Summary: Insulation values and tightness of the house (as measured in
maximum of about 7% of,the ACH) have been increased. The window area has been slightly
floor area. decreased on the west, increased slightly on the east and north, and
increased significantly on the south.
The energy savings are more
modest with this system, but Note: These examples should not be construed as recommendations - the
suntempering is a very low-cost numbers represent the effect of changes in design required to achieve the
strategy. exact savings in annual auxiliary heat. In practice, the designer has great
latitude in selecting values to use.
Of course, even though the
necessity for precise sizing of
glazing and thermal mass does
not apply to suntempertng (as
long as the total south-facing
glass does not exceed 7% of the
total house floor area), all other
recommendations about energy-
effiCient design such as the basic
energy conselVation measures,
room lay-out. siting, glazing type
and so on are still important for
perlormance and comfort in
suntempered homes.
Jackson, Mississippi
24 GUIDELINES PART THREE: STRATEGIES FOR IMPROVING ENERGY PERFORMANCE
3. Direct Gain houses) and 12%. depending on where the winter sun will fall
how much thennal mass will be directly on it.
The most common passive solar used in the design. as discussed Effective materials for floors
strategy system is called direct below. include painted. colored or vinyl-
gain: sunlight through south- covered concrete. brick (face
facing glazing falls directly into Glazing brick or pavers have even higher
the space to be heated. and is Double glazing is recommended density than ordinary building
stored in thennal mass for direct gain glazing in brick). quarry tile. and dark-
incorporated into the floor or Jackson. The Performance colored ceramic tile lead directly
interior walls. The south Potential table on page 6 shows on the slab.
window area is increased above the relative performance of For houses built with
the 7% limit of a suntempered different types of direct gain crawlspaces or basements. the
house. and additional thennal glazing. You will note from this incorporation of significant
mass is added to store the table that yield increases by 11% amounts of heavy thennal mass
additional solar gains and thus between double and triple or is a little more difficult. Thermal
prevent overheating. low-e glazing. Night insulation mass floor coverings over
also improves energy basements. crawlspaces and
perfonnance dramatically. In lower stories would generally be
fact. as the Perfonnance limited to thin set tile or other
Potential table shows. covering thin mass floors.
the windows at night or on When more mass is reqUired.
cloudy days with the equivalent the next best option is for
of R-4 shades or other material interior walls interior finishes or
will save almost as much energy exterior walls or interior
as with R-9 material. But masonry fireplaces. When
studies have shown that only evaluating costs. the dual
relatively few homeowners will function of mass walls should be
be diligent enough about remembered. They often seIVe
operating their night insulation as structural elements or for fire
to achieve those savings. protection as well as for thennal
Direct Ga/n Energy-efficient glazing. on the storage. Another option is to
Direct gain is the most common passive solar other hand, needs no operation, switch to another passive solar
system in residential applications
and therefore is a more system type such as attached
Sizing Limit convenient and reliable option. slab-on-grade sunspaces or
Total direct gain glass area thermal storage walls built
should not exceed about 12% of Thennal Mass directly on exterior foundation
the house's floor area. Beyond Thennal mass can be walls.
that. problems with glare or incorporated easily into houses Sunlit thennal mass floors
fading of fabriCS are more likely with slab-on-grade floors by should be relatively dark in
exposing the mass. The mass is color. to absorb and store energy
to occur. and it becomes more
much more effective if sunlight more effectively. However. mass
difficult to provide enough
falls directly on it. Covering the walls and ceilings should be
thennal mass for year-round
mass with any insulation light in color to help distribute
comfort.
material. such as carpet. greatly both heat and light more evenly.
So the total south-facing
glass area in a direct gain reduces its effectiveness. A good
strategy is to expose a narrow Ratio of Mass to Glass. The
system should be between 7%
strip about 8 ft. wide along the simplest rule of thumb states:
(the maximum for suntempered
south wall next to the windows
Jackson. Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 25
For each added sqjt oj sunlight, as long as it is in the The effectiveness of thermal
direct-gain glass (above the same room, with no other walls mass is relative to the density
7% sW1tempering ltmit), 6 between the mass and the area and thickness. The vertical axis
sqjt oj exposed mass where the sunlight is falling. shows how many square feet of
surface should be added (The 8.3 value is typical, but the mass area are needed for each
within the direct-gain true value does depend on mass added square foot of direct gain.
space. density and thiclmess. Refer to As you can see, performance
the mass thiclmess graph for increases start leveling off after a
The following procedure can be more specific values to use.) few inches of thermal mass.
used to determine a somewhat More south-facing glazing
more accurate estimate. This than the maximum as 4O+-~~----------------~
procedure gives the maximum determined here would tend to 5O#/cI
JacksOD, Mississippi
26 GUIDELINES PART THREE: STRATEGIES FOR IMPROVING ENERGY PERFORMANCE
Base
Case 20% 40% 60%
R-values
Ceiling/Roof 26 25 32 39
Walls 14 13 17 21
Slab Edge 0 0 0 1
Glass .9 1.8 1.8 1.8
Performance (Btu/yr-sf)
Conservation 27,212 25,405 21,152 16,703
Auxiliary Heat 24,599 20,020 15,158 10,112
Cooling 15,575 13,606 12,003 11,514
Jackson, Missiuippi
PASSIVE SOLAR DESIGN STRATEGIES 27
4. Sunspaces sunspace to be considered truly glass-to-mass ratio. on a clear
thermally isolated. winter day a temperature swing
The sunspace is a very popular The sunspace should not be of about 30'F should be
passive solar feature. adding an on the same heating system as expected.
attractive living space as well as the rest of the house. A well The sunspace floor is a good
energy performance. There are designed sunspace will probably location for thermal mass. The
many variations on the basic need no mechanical heating mass floors should be dark in
theme of the sunspace. and the system. but if necessary. a small color. No more than 15-25% of
possibilities for sunspace design fan or heater may be used to the floor slab should be covered
are extraordinarily diverse protect plants on extremely cold with rugs or plants. The lower
(References 17 through 20 winter nights. edge of the south-facing
include specific design ideas). The sunspace should be just windows should be no more
As used in this gUide. a as tightly constructed and than six inches from the floor to
sunspace is a separate direct- insulated as the rest of the make sure the mass in the floor
gain room on the south side of house. receives suffiCient direct
the house. The wall that sunlight. If the windows sills are
separates the house from the higher than that. additional
sunspace is called a common mass may have to be located in
wall. The common wall should the walls.
include operable windows and Another good location for
doors that may be closed so that thermal mass is the common
when the sunspace is not wall (the wall separating the
providing heat to the house it is sunspace from the rest of the
not draining heat from the house). Options for the common
house. wall are discussed in more detail
The sunspace concept used later.
in these Guidelines can be used Water in various types of
year-round. will provide most or containers is another form of
all of its own energy needs. and energy storage often used in
will contribute to the energy Sunspaces sunspaces.
Sunspaces provide useful passive solar
needs of the rest of the house as heating and also provide a valuable amenity
well. to homes. Glazing
Sunspaces are referred to as Clear. double-glazing is
"isolated gain" passive solar Thermal Mass recommended for sunspaces.
systems. because the SUnlight is A sunspace has extensive south- Adding the second pane makes a
collected in an area which can facing glass. so sufficient large improvement in energy
be closed off from the rest of the thermal mass is very important. savings. Triple-glazing or low-e
house. During the day. the Without it. the sunspace is liable coatings. on the other hand. will
doors or windows between the to be uncomfortably hot during further improve comfort. but will
sunspace and the house can be the day. and too cold for plants have little effect on energy
opened to Circulate collected or people at night. savings.
heat. and then closed at night. However. the temperature in Windows on the east and
and the temperature in the the sunspace can vary more west walls should be small (no
sunspace allowed to drop. It than in the house itself. so more than 10% of the total
should be noted that the about three square feet of four sunspace floor area) but they are
common wall is often mass. and inch thick thermal mass for each useful for cross-ventilation.
not necessarily suffiCient for the square foot of sunspace glazing
should be adequate. With this
Jackson. Mississippi
28 GUIDELINES PART THREE: STRATEGIES FOR IMPROVING ENERGY PERFORMANCE
Jackson. Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 29
Summer ventilation
The sunspace must be vented to Examples of Heat Energy Savings
Passive Solar-Sunspace
the outside to avoid overheating
1,500 sf Single Story House
in the summer or on warm days
in spring and fall. A properly Base
vented and shaded sunspace Case 20% 40% 60%
R·Values
can function much like a Ceiling/Roof 26 24 29 34
screened-in porch in late spring, Walls 14 12 15 18
summer, and early fall. Slab Edge 0 0 0 0
Glass .9 1.8 1.8 1.8
Operable windows and/ or
vent openings should be located Air Changes/Hour 0.75 0.59 0.70 0.62
for effective cross-ventilation.
and to take advantage of the Glass Area (percent of total floor area)
West 3.0% 2.0% 2.0% 2.0%
prevailing summer wind. Low
North 3.0% 4.0% 4.0% 4.0%
inlets and high outlets can be East 3.0% 4.0% 4.0% 4.0%
used in a "stack effect". since South (windows) 3.0% 3.0% 3.0% 3.0%
warm air wUl rise. These Sunspace 0.0% 6.7% 11.0% 17.0%
ventilation areas should be at Solar System Size (square feet)
least 15% of the total sunspace South Glass 45 45 45 45
south glass areas. Sunspace Glass 0 100 165 255
Where natural ventilation is Sunspace Thermal Mass 0 302 495 765
insufficient. or access to natural Percent Solar Savings
breezes is blocked. a small. 10% 25% 35% 49%
thermostat-controlled fan set at
Performance (Btu/yr-sf)
about 76'F will probably be a
Conservation 27,212 26,782 23,479 19,989
useful addition. Auxiliary Heat 24,599 20,012 15,073 10,119
Cooling 15,575 14,875 14,439 1.5,546
Summary: Insulation (for the 40 and 60% savings) and tightness have
been increased. North and east-facing glazing have been increased
slightly. The sunspace assumed here is semi-enclosed (surrounded on
three sides by conditioned rooms of the house, as in Figure SSC1 of the
worksheets), with vertical south glazing. The common wall is a thermal
mass wall made of masonry. Sunspace glazing is assumed to be double.
Jackson. Mississippi
30 GUIDELINES PART THREE: STRATEGIES FOR IMPROVING ENERGY PERFORMANCE
Jackson. Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 31
Jackson. Mississippi
32 GUIDELINES PART THREE: STRATEGIES FOR IMPROVING ENERGY PERFORMANCE
Jackson, Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 33
The potential of some
natural and low-energy cooling Cooling Potential
8asecase 15,575 8tu/yr-sf
strategies is shown in the
following table for Jackson. Energy
Worksheet IV: CooRng· Savings Percent
Performance Level indicates Strategy (8tu/yr -sf) Savings
the total annual cooling load. No Night Ventilation 1
and so can give an idea of how without ceiling fans 0 0%
the passive solar features with ceiling fans 4,270 27%
increase the cooling load and
Night Ventilation 1
how much reduction is possible without ceiling fans 1,930 12%
when natural cooling techniques with ceiling fans 6,100 39%
are used.
High Mass2
It should be noted that the
without ceiling fans 410 3%
Cooling Performance numbers with ceiling fans 200 1%
presented in the Examples for
each passive solar strategy 1 With night ventilation, the house is ventilated at night when
temperature and humidity conditions are favorable.
assume that the design also
includes the recommended 2 A "high mass" building is one with a thermal mass area at least equal
natural cooling techniques. This to the house floor area.
is especially true of the higher
percentage reductions; these
assume better heating
performance. but also better
shading and other natural
cooling strategies.
Jackson. Mississippi
34 GUIDELINES PART THREE: STRATEGIES FOR IMPROVING ENERGY PERFORMANCE
Jackson. Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 35
Shading Roof Overhangs. Fixed
Shading strategies generally fall overhangs are an inexpensive
into three categories: feature. and require no
landscaping. roof overhangs and operation by the home owner.
exterior or interior shading They must be carefully designed.
devices. however. Otherwise. an
overhang that blocks summer
Landscaping. The ideal site for sun may also block sun in the
summer shading has deciduous Landscaping for Summer Shade spring. when solar heating is
trees to shade the east and west Trees and other landscaping features may be desired. and. by the same token.
effectively used to shade east and west
windows. Even small trees such windows from summer solar gains. an overhang sized for maximum
as fruit trees can help block sun solar gain in winter will allow
hitting the first story of a house. Other landscaping ideas for solar gain in the fall on hot days.
Trees on the south side can summer shade: The following figure may be used
present a difficult choice. Even • Trellises on east and west to determine the optimum
deciduous trees will shadow the covered with vines. overhang size.
solar glazing during the winter • Shrubbery or other plantings In Jackson. an ideal
and interfere with solar gain. In to shade paved areas. overhang projection for a four
fact. trees on the south side can • Use of ground cover to foot high window would be 14
all but eliminate passive solar prevent glare and heat inches and the bottom of the
performance. unless they are absorption. overhang would be 12 inches
very close to the house and the • Trees, fences. shrubbery or above the top of the window.
low branches can be removed. other plantings to "channel"
allowing the winter sun to summer breezes into the house.
penetrate under the tree canopy. • DeCiduous trees on the east
However. in many cases the and west sides of the house. as
trees around the house are shown above. to balance solar
bigger selling points than the gains in all seasons.
energy efficiency and the builder
must make a choice.
If a careful study of the
shading patterns is done before
construction. it should be
possible to accomodate the
south-facing glazing while
leaving in as many trees as
possible (see page 17. Site
Planning for Solar Access).
South Overhang Sizinfl
In Jackson, an ideally SIZed south overhang
should allow full exposure of the window
when the sun has a noon altitude of 39
degrees (angle A) and fully shade the window
when the sun has a noon altitude of 76
degrees (angle B).
Jackson. Mississippi
36 GUIDELINES PART THREE: STRATEGIES FOR IMPROVING ENERGY PERFORMANCE
Jackson, Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 37
Ventilation The best possible
When possible. the house should performance of a whole-house
be positioned on the site to take fan results when a timer. a
advantage of prevailing winds. thermostat and a "humidistat"
During the cooling season. the are used. so that the fan would
prevailing wind is from the only operate when there is less
south. Windows. stairwells. than 60% relative hUmidity and
transoms and other elements a temperature of less than 76'F.
should be located for maximum Natural ventilation and
cross-ventilation in each room. whole-house fans are effective at
The free vent area (unobstructed Ventllstlon for Summer Cooling removing heat. but not at
Natural ventilation is often impaired by
openings like open windows) vegetation and topography. Ventilation fans moving air. Ceiling fans. on the
do not depend on surroundings to be
should be between 6-7.5% of effective. other hand. can often create
total floor area. half located on enough of a breeze to maintain
the leeward and half on the In cooling climates. a whole- comfort at higher temperatures.
windward side of the building. house fan is a good idea for and still use less power than
Insect screens can reduce the aSSisting ventilation. especially required by air conditioning. By
effective free vent area by as in houses with ~ites or designs using natural cooling strategies
much as 50%. Casement or that make natural ventilation and low-energy fans. the days.
awning windows have a 90% difficult. On the other hand. when air-conditioning is needed
open area: double hung windows when the temperature is higher can be reduced substantially.
have only 50%. Casement than about 76'F. a whole-house
windows extend outward from fan will not be very effective.
the house. tending to channel Research indicates that a
breezes through the opening if whole-house fan should pull
properly placed. Improperly approximately 10 ACR. A rule of
placed casements might deflect thumb: for rooms with eight foot
breezes. Double-hung windows ceilings. total floor area
do not have this advantage. multiplied by 1.34 will equal the
Natural ventilation can help necessary CFM of the fan. For
keep houses cool and 10 foot ceilings. multiply floor
comfortable at the beginning and area by 1.67.
end of the cooling season and
thus shorten the time when air
conditioning is required. But
natural ventilation can seldom
do the entire coolingjob.
especially for less than ideal
sites with little natural air
movement.
JacksoD. Mississippi
38 GUIDELINES PART THREE: STRATEGIES FOR IMPROVING ENERGY PERFORMANCE
Jackson, Mississippi
Passive Solar
Design Strategies
WORKSHEETS
Blank
Worksheets
Jackson
Mississippi
(A+B+C)
Total Heat
X
Heating Degree
X
Heating Degree
= BtuIyr-sf
CompueLmeEtoLmeF
41
Worksheet II: Auxiliary Heat Performance Level
Total
+
Floor
= Total Projected
Projected Area Area per
Area Square Foot
[ 1-
Solar
X
Conservation
= Btu/yr-sf
Savings Performance
Fraction Level [Worksheet I,
Step E]
E. Comparative AuxlUary Heat Performance (From Previous Calculation or from Table G) Btutyr-sf
JackSOD, Mlnissippi
42
Worksheet m: Thermal Mass/Comfort
C. Heat Capacity of Mass Surfaces Enclosing Spaces Connected to Direct Gain Spaces
Unit Heat
Mass Description
(include thickness) Area C~ci~
IT Ie ]
Total Heat
Capacity
Trombe Walls X 3.8 =
Water Walls X 4.2 =
X =
X =
X =
BtufOF
Total
Jackson, Mlsslulppl
43
Worksheet IV: Summer Cooling Performance Level
A. Opaque Surfaces
Radiant Barrier Absorp- Heat Gain
Heat Loss Factor tance Factor
Description [Worksheet I) [TableJ) [Table K) [Table L) Load
Ceilings/roofs X X X =
X X X =
X X X =
Walls X na X =
X na X =
Doors X na X =
kBtu/yr
Total
B. Non-solar Glazing
Rough Frame Net Area Shade Factor Heat Gain
Description Area Factor [Table M) Factor [Table L) Load
North Glass X 0.80 X X =
East Glass X 0.80 X X
JackSDD, Miaalsslppl
45
F3-Water Walls Table H-Umt Heat Capacities Table L-Heat Gain Facton
Load WWA3 WWB4 WWC2 (Btu/F-sf) Ceiling/roofs 63.4
Collector No Night Night Selective Walls and Doors 28.6
Ratio Insulation Insulation Surface North Glass SO.2
H1-Mase Surfaces Enclosing Direct Gain East Glass 96.3
400 0.09 0.06 0.07 Spaces West Glass 104.7
300 0.12 0.10 0.11 Skylights 191.1
200 0.17 0.18 0.18 Thickness (inches) Direct Gain Glazing SO.3
lSO 0.21 0.24 0.25 Material 2 3 4 6 8 12 Trombe Walls and 23.6
100 0.29 0.35 0.35 Poured Conc. 1.8 4.3 6.7 8.8 11.311.5 10.3 Water Walls
SO 0.34 0.42 0.42
60 0.41 0.52 0.51
Cone. Masonry 1.8 4.2 6.5 8.4 10.210.0 9.0 suns~ces
Face Brick 2.0 4.7 7.1 9.0 10.4 9.9 9.0 SSl 54.9
SO 0.46 0.58 0.57 2.1 4.8 7.1 8.5 8.6 8.0 7.6 SSBl 54.9
45 0.49 0.62 0.60 Flarc Stone
Buider Brick 1.5 3.7 5.4 6.5 6.6 6.0 5.8 SSCl 23.6
40 0.52 0.66 0.64 Adobe 1.3 3.2 4.8 5.5 5.4 4.9 4.8 SSDl 54.9
35 0.57 0.70 0.69 Hardwood 0.4 1.4 1.8 1.7 1.5 1.5 1.5 SSEl 54.9
30 0.61 0.75 0.74 Water 5.2 10.415.6 20.8 31.2 41.6 62.4
25 0.67 0.81 0.79
20 0.73 0.87 0.85
15 0.81 0.93 0.92
H2-Rooms with no Direct Solar Gain Table M-8bading Facton
Thickness (inches) Projection
F4-Sunspaces Material 1 2 3 4 6 8 12 Factor South East North West
Load Poured Cone. 1.7 3.0 3.6 3.8 3.7 3.6 3.4 0.00 1.00 1.00 1.00 1.00
Collector Sunspace Type Cone. Masonry 1.6 2.9 3.5 3.6 3.6 3.4 3.2 0.20 0.89 0.95 0.92 0.95
Ratio SSAl SSBl SSCl SSDl SSEl Face Brick 1.8 3.1 3.6 3.7 3.5 3.4 3.2 0.40 0.72 0.84 0.84 0.85
400 0.15 0.12 0.08 0.15 0.13 Fla~ Stone 1.9 3.1 3.4 3.4 3.2 3.1 3.0 0.60 0.57 0.73 0.76 0.73
0.17 0.14 0.11 0.19 Buider Brick 1.4 2.6 3.0 3.1 2.9 2.7 2.7 O.SO O.SO 0.62 0.68 0.62
300 0.16 Adobe 1.2 2.4 2.8 2.8 2.6 2.4 2.4
200 0.22 0.18 0.15 0.24 0.21 1.00 0.45 0.53 0.59 0.53
150 0.26 0.22 0.19 0.30 0.25 Hardwood 0.5 1.1 1.3 1.2 1.1 1.0 1.1 1.20 0.41 0.45 0.51 0.45
100 0.33 0.28 0.26 0.38 0.33 Multiply by 0.8 for low-e glass, 0.7 for tinted glass and
SO 0.37 0.32 0.30 0.43 0.38 0.6 for low-e tinted glass.
60 0.43 0.38 0.37 0.51 0.45
SO 0.48 0.42 0.41 0.56 0.50 Table l-Comfort Facton (Btu/sf)
45 0.50 0.44 0.44 0.59 0.53
40 0.53 0.47 0.47 0.62 0.56 Direct Gain 870 Table N-lDtemal Gala Facton
35 0.57 0.51 0.51 0.66 0.60 Sunspaces and 290 Constant Component 2,9SO kBtulyr
30 0.61 0.55 0.56 0.70 0.64 Vented Trombe Walls
25 0.66 0.60 0.61 0.75 0.69 Variable Component 1,250 kBtu/yr-BR
20 0.72 0.66 0.68 0.81 0.76
15 O.SO 0.74 0.76 0.88 0.83
Jackson, Mississippi
46
General Should the estimated conservation reduced by about 50 percent to account
The Worksheets provide a calculation perfonnance level be greater than for throw rugs and furnishings.
procedure to estimate the perfonnance desired. the designer should consider As a rule-of-thumb. exposed slab area
level of passive solar building designs. It additional building insulation or should be considered to be in the sun
is recommended that the results be reducing non-south glass area. only when it is located directly behind
compared to Worksheet calculations for south glazing. The maximum slab area
the builder's typical house. Perfonnance Worksheet n-AuzWary Heat that is assumed to be in the sun should
levels for the NAHB Base Case House Performance Level not exceed 1.5 times the adjacent south
used in the Guidelines are also provided This is an estimate of the amount of heat glass area.
for comparison. that must be provided each year from In Step F. the projected area of solar
A separate worksheet is provided for the auxiliary heatlog system. It glazing calculated on Worksheet II is
the four separate performance levels and accounts for savings due to solar energy. used to calculate the comfort
associated base cases. In Step A •the user may enter the perfonnance level. The projected area of
The worksheets are supported by a rough frame area of solar glazing. since it water walls and unvented Trombe walls
number of data tables. The tables are is generally easier to measure the rough is excluded in this step.
given a letter designation and are frame area than it is the net glazing area. A high temperature swing indicates
referenced next to each worksheet entJy. The worksheet includes a net area factor inadequate thermal mass or too much
when applicable. of 0.80 to account for window frames direct gain solar glazing. If the comfort
The floor area used in the and mullions. If the designer enters the performance level is greater than desired
calculations should not include net glass area, then the net area factor is (13°F recommended). additional thermal
suns paces. garages or other 1.00. mass should be added to the building or
unconditioned spaces. The projected area of the solar energy direct gain glazing should be reduced.
systems may be calculated using the
Worksheet I--COnservatlon adjustment factors in Table E or by Worksheet IV-8ummer CooUng
Performance Level making a scaled elevation drawing of the Performance Level
This is an estimate of the amount of heat building facing exactly south and This is an estimate of the annual cooling
energy needed by the building each year measuring the glazing area from the load of the building-the heat that needs
from both the solar system and the scaled drawing. to be removed from the building by an
auxiliary heatlog system. The projected area per square foot is air conditioner in order to maintain
For Step A. it is necessary to measure calculated as the last part of Step A. comfort during the summer.
the net area of surfaces that enclose This is used to determine the heatlog In Step A. only the envelope surfaces
conditioned space. For walls. the net degree days adjustment used on that are exposed to sunlight are to be
surface area is the gross wall area less Worksheet I. Step E. included. For instance. floors over
the window and door area. The load collector ratio is calculated crawlspaces and walls or doors adjacent
Rough frame dimensions are in Step B. This is used to determine the to garages are excluded.
generally used to measure window area. solar savings fractions in Step C. Steps B and C of the worksheet
The R-values in Table A4 are for the The solar energy systems used in Step account for solar gains. They use the
rough frame window area. C should be identical to those used in rough frame area since this is easier to
Heat loss from passive solar systems Step A. The first and last columns of measure. The worksheets include a net
is excluded. The surface area of direct Step A are simply carried down. area factor of 0.80 to account for window
gain glazing. Trombe walls. water walls The solar savings fraction is frames and mullions. If the net window
and the walls that separate sunspaces determined separately for each type of area is used. the net area factor is 1.00.
from the house are ignored. passive solar system by looking up Table M gives the shade factor for
Step A includes consideration of values in Tables Fl through F4. The windows with overhangs based on a
insulated floors over crawlspaces. sunspace system types are shown projection factor. The projection factor is
unheated basements or garages. beneath Table F4. the ratio between the horizontal
R-values are provided in Table A3 that If the auxiliary heat perfonnance level projection of the overhang from the
account for the buffering effect of these calculated in Step D is larger than surface of window and the distance from
unconditioned spaces. When insulation desired. the designer should consider the bottom of the window to the bottom
is not installed in the floor assembly. but increasing the size of the solar energy of the overhang. When windows have
rather around the perimeter of a systems or adding additional solar sunscreens. tlots or films. the shade
crawlspace or unheated basement. Step energy systems. i.e. thermal storage factors in Table M should not be used.
B should be used. walls. Instead. a shading coefficient should be
The perimeter method of Step B is determined from manufacturers'
used for slabs-on-grade. the below-grade Worksheet III-Comfort literature.
portion of heated basements. unheated Performance Level
basements (when the floor is not This is the temperature swing expected
insulated). and perimeter insulated on a clear winter day with the auxiliary
crawls paces (when the floor is not heating system not operatlog.
insulated). Heated basement walls that This worksheet requires that two sub-
are above grade should be considered in areas be defined within the building:
Step A. those areas that receive direct solar
Slab edge perimeter. unheated gains and those areas that are connected
basements or perimeter insulated to rooms that receive direct solar gains.
crawlspaces adjacent to sunspaces Rooms that are separated from direct
should not be included. gain spaces by more than one door
The conservation perfonnance level is should not be included in either
calculated as the product of the heat loss category.
per degree day per square foot [Step D\ Thermal mass elements located in
and the heating degree days. adjusted for unconditioned spaces such as suns paces
the heat loss and solar glazing per are not included.
square foot The adjustment is taken An exposed slab is one finished with If the cooling perfonnance level is
from Table C. based on data calculated vinyl tile. ceramic tile or other highly greater than desired. the designer should
on Worksheet I. Step D and Worksheet H. conductive materials. Carpeted slabs consider reducing non-south glass.
Step A. should not be considered exposed. The providing additional shading or
exposed slab area should be further ~creasing thermal mass.
Jackson, Mississippi
Passive Solar
Design Strategies
EXAMPLE
The Worked Example The house has a semi- The house is equipped with a
enclosed sunspace with vertical ceiling fan to help reduce the
Description of glazing. The sunspace floor has air-conditioning load. North
Example Bullding a four-inch thick slab-on-grade windows have an overhang with
A 1.504 square foot passive with quarry tile set in a mortar a projection factor of 0.30. East
solar. single-family home is used bed. The sunspace is separated and west windows are small and
to illustrate how to fill in the from the conditioned portion of have no effective overhang
worksheets. See sketches for the house by sliding glass doors because of the gable roof. South
the building layout. A variety of and a masomy fireplace wall. windows. including the
design features have been Sunspace ventilation is provided sunspace windows. have an
incorporated into the house to to the outside by awning overhang with a projection factor
help illustrate how to handle windows located at the top and of 0.20.
different situations in the bottom of the south wall. Take-offs from the house are
worksheets. South facing windows given in the worksheets. Refer
The building selected has provide direct gain solar heating to the circled values in the
good insulation as described on to the dining area. kitchen and worksheet tables to locate where
Worksheet I. master bedroom. The south the various values which show
The east portion of the house glazing in the kitchen and dining up in the worksheets come from.
is slab on grade. The great room area provides heat to an exposed Performance is found to be
and master bedroom are slab-on-grade finished with satisfactory on all four
constructed over a crawlspace. ceramic tile to provide direct worksheets.
gain heat storage.
The house faces 10 degrees
to the east of true south.
N Garage
C\J
3040 3040
~
4040
Bedroom Bedroom
Great Room
0C')
~ 0
C\J
'"
0
Master '"
Bedroom
4050 5030
8020
8088 8068 8088
28'
III
South Elevation
··
I:t :::
North Elevation
Gt'oeat Room
Section
JackSOD, Mississippi
50 WORKED EXAMPLE
JacksOD, Mississippi
51
Jackson, Mississippi
52
General Project Information
(A+B+C)
F. Comparison Conservation Performance (From Previous Calculation or from Table 0) 1-11(L Btu/yr-sf
Jackson, Mississippi
53
Worksheet II: Auxiliary Heat Performance Level
[1 - o.'-t"Z-
Solar
X \~~,q
Conservation
= , '''05::> Btu/yr-sf
Savings Performance
Fraction Level [Worksheet I.
Step E]
E. Comparative AuxlUary Heat Performance (From Previous Calculation or from Table G) U1~"S Btu/yr-sf
Jackson, Mississippi
54
Worksheet ITI: Thermal Mass/Comfort
C. Heat Capacity of Mass Surfaces Enclosing Spaces Connected to Direct Gain Spaces
Unit Heat
Mass Description Ca~ci~ Total Heat
Capacity
(include thickness) Area ITa Ie )
Trombe Walls X 3.8 =
Water Walls X 4.2
>..,
=
fAc..e.. llL-W:4-. ~~. \ \I X = 411
X =
X = Btu/OF
'-\ II
Total
Heat
Capacity
JacksOD, Mississippi
55
Worksheet IV: Summer Cooling Performance Level
A. Opaque Surfaces
Radiant Barrier Absorp- Heat Gain
Heat Loss Factor , tance Factor
Description [Worksheet I) [TableJ) [Table K) [Table L) Load
Ceilings/roofs 1:1 X \.C'o X o.::f1 X 61·:1 = 1t (,2-
'2..1 X 1·00 X 0.",1 X b~.~ = ~S2
X X X =
Walls B~ X na D."O X U., = "62.-
X na X =
Doors 9 X na 2·"]0 X 1.IiI. (, = :l:I
J2S~ kBtu/yr
Total
B. Non-solar Glazing
Rough Frame Net Area Shade Factor Heat Gain
Description Area Factor [Table M) Factor [Table L) Load
North Glass 4.0 X 0.80 X 0.68 X ~().2..
= \'-\\C:t
Skylights X 0.80 X X =
'l-)'~ kBtu/yr
Total
C. Solar Glazing
Solar System Rouih Frame Net Area Shade Factor Heat Gain
iI.,
Description rea Factor [Table M) Factor [Table L) Load
Direct Gain B6 X 0.80 X o. X BO.} = so'S!
E. CooUng Load per Square Foot 1,000 X "2..\ 1.2-\ + '5:0'-\ \"'L\~ Btu/yr-sf
(A+B+C+D) Floor Area
H. Comparison CooUng Performance (From Previous Calculation or from Table P) \7'5'<' Btu/yr-sf
Compare Line G to Line H
Jackson, Mississippi
56
Table A.-condnued ••
Table A-Equivalent Thermal Table D-Base Case Conservation
Performance of Assemblies Performance (Btu/yr-s1l
R-values (hr-F-sf/Btu) AS-Doors Base Case 27,212
Solid wood with
Weatherstripping
A1-CeilingsiRoofs
Metal with rigid 5.9 Table E-Projected Area
Attic Insulation R-value foam core Adjustment Facto"
Construction R-38 R-49 R-SO
@
27.9 35.9 46.9 57.9
Table B-Perimeter Heat Loss
Degrees off ~ Solar System Type
True
South
D 1..IlL..
,~
SSA
SSD
SSB,
SSE
Framed Insulation R-value
Construction R-19 R-22 R-3O R-38 Facto" for Slabs-Gn-Grade and o 1.00 o. n 0.75
Basements (Btu/h-F-ft)
2x6 at 16"oc 14.7 15.8 16.3 5 ~ 0.76 0.75
2x6 at 24"oc 15.3 16.5 17.1 Heated Unheated Insulated 10 0.98 0.75 0.74
2x8 at 16"oc 17.0 18.9 20.6 21.1 Perimeter Siabs-on- Base- Base- Crawl- 15 . 0.74 0.73
2x8 at 24"oc 19.6 21.6 22.2 Insulation ments ments spaces 20 0.94 0.72 0.70
2xl 0 at 16"oc
2xl 0 at 24"oc W> 20.1
20.7
24.5
25.5
25.7
26.8
None
R-5
CQ5
0.8 1.3
0.8
1.1
0.7
1.1
0.6
25
30
0.91
0.87
0.69
0.66
0.68
0.65
2x12 at 16"oc 18.8 21.0 25.5 30.1 R-7 0.3 0.7 0.6 0.5
2x12 at 24"oc 19.0 21.4 27.3 31.4 R-l1 0.3 0.6 0.5 0.4
R-19 0.2 0.4 0.5 0.3
R-30 0.1 0.3 0.4 0.2
Table F-8olar System Saving
A2-Framed Walls FnctioDS
Single
Wall Insulation R-value
Framing R-l1 R-13 R-19 R-25 Table C-Hea~ Degree Days Fl-Dlrect Gain
2x4 at 16"oc
2x4 at 24"oc
2x6 at 16"oc
9fr
14.1
13.6
13.9
15.4 17.7 19.2
(F-day)
Load
Collector
Ratio
DGCl
Double
Glazing
DGC2
Low-e
Glazing
DGC3
R-9 Night
Insulation
2x6 at 24"oc 14.3 15.6 18.2 19.8 Cl-Heatlng Degree Days (Baa. 65oF)~ 400 0.08 0.09 0.10
Double Jackson 2, 300 0.11 0.11 0.13
Wall Total Thickness (inches) Belzoni , 7 200 0.15 0.16 0.18
Framing 8 10 12 14 Brookhaven 2,065 150 0.19 0.20 0.23
25.0 31.3 37.5 43.8 Canton 2,570 100 0.25 0.27 0.31
The R-value of insulating sheathing should be added to
the values in this table.
Columbia
Greenville
Greenwood
Kosciusko
Moorhead
1,881
2,635
2,716
2,893
2,634
I. 80
60
50
-n15
40
0.30
0.36
0.44
0.48
0.32
0.40
"-"4 ,,-\1.- 0.45
0.49
0.53
0.37
0.46
0.53
0.57
0.61
A3-lnsulated Floors Natchez 1,941 35 0.52 0.57 0.66
Pickens 2,584 30 0.57 0.63 0.72
Insulation R-value Port Gibson 2,532 25 0.62 0.69 0.79
Framing R-ll R-19 R-3O R-38 Vicksbu!1l 2,201 20 0.68 0.76 0.85
2x6s at 16"oc 18.2 23.8 29.9 Yazoo City 2,480 15 0.75 0.83 0.91
2x6s at 24"oc 18.4 24.5 31.5
2x8s at 16"oc 18.8 24.9 31.7 36.0
2x8s at 24"oc 18.9 25.4 33.1 37.9 C2-Heatlng Degree Day Multiplier F2-Trombe Walla
2xl 0 at 16"oc 19.3 25.8 33.4 38.1
2xl0 at 24"oc 19.3 26.1 34.4 39.8 Passive Solar TWF3 TWA3 TWJ2 TWI4
2x12 at 16"oc 19.7 26.5 34.7 39.8 Heat Loss Glazing Area per Load Unvented Vented Unvented Unvented
2x12 at 24"oc 19.6 26.7 per Square per Square Foot Collector Non- Non- Selec- Night
35.5 41.2 Fool .00 .05 .10 .15 .20 Ratio selective selective tive Insulation
These R-values include the buffering effect of a 12.00 1.17 1.18 1.19 1.20 1.20 400 0.06 0.09 0.08 0.05
ventilated crawlspace or unconditioned basement. 11.50 1.16 1.17 1.18 1.19 1.20 300 0.09 0.11 0.12 0.08
11.00 1.15 1.16 1.17 1.18 1.19 200 0.13 0.16 0.19 0.14
10.50 1.13 1.15 1.16 1.17 1.18 150 0.16 0.19 0.25 0.20
A4-Wlndows 10.00 1.12 1.14 1.15 1.16 1.17 100 0.23 0.26 0.35 0.29
9.50 1.11 1.12 1.14 1.15 1.17 80 0.27 0.30 0.42 0.35
Ai'j.,Gap
1/4 in. 1I' in. 112 in. argon ~:~ t~ 1.09 1.11 1.13
1.11
1.14
1.13
1.15
1.14
60
50
0.33
0.38
0.37
0.41
0.51
0.57
0.43
0.49
Ao...!.OO 1.04 1.07 1.09 45 0.40 0.44 0.60 0.53
~
Standard Metal Frame 1.13
Single .9 ~·"-I.50 1.01 1.04 1.07 1.12 40 0.43 0.47 0.64 0.57
Double 1.1 1.2 1.2 7.00 0.99 1.02 1.05 1.10 35 0.47 0.51 0.69 0.61
Low-e (e<=O.40) 1.2 1.3 1.3 6.50 0.96 0.99 1.02 1.05 1.08 30 0.52 0.56 0.74 0.66
Metal frame with thermal break 6.00 0.93 0.97 1.00 1.03 1.06 25 0.57 0.61 0.79 0.72
Double 1.5 c1S) 1.7 5.50 0.89 0.94 0.97 1.01 1.03 20 0.64 0.68 0.85 0.79
Low-e (e<=O.40) 1.6 1.8 1.8 5.00 0.84 0.90 0.94 0.98 1.01 15 0.73 0.76 0.91 0.87
Low-e (e<=O.20) 1.7 1.9 2.0 4.50 0.78 0.85 0.90 0.95 0.98
Wood frame with vinyl cladding 4.00 0.71 0.80 0.86 0.91 0.95
Double 2.0 2.1 2.2 3.50 0.65 0.73 0.81 0.87 0.92
Low-e 1e<=o.401 2.1 2.4 2.5 3.00 0.56 0.67 0.74 0.82 0.88
Low-e e<=O.20 2.2 2.6 2. 7 2.50 0.44 0.58 0.68 0.76 0.83
Low-e e<=0.10 2.3 2.6 2.9 2.00 0.29 0.47 0.60 0.69 o.n
These R-values are based on a 3 mph wind speed and
are typical for the entire rough framed opening.
Manufacture's data, based on National Fenestration
Rating Council procedures, should be used when
available. One half the R-value of movable insulation
should be added, when appropriate.
Jackson, Mississippi
57
~
Bare Concrete
Red Brick
Medium Red 0.80
Medium Brown 0.84
Dark Blue-Grey 0.88 Table P-Baae Case Cooling
Dark Brown 0.88 Performance (Btu/sf-yr)
Base Case 15,575
Jackson, Mississippi
58 WORKED EXAMPLE
JacksOD, Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 59
Anytown ,
USA
Anytown, USA
60 INTRODUCTION
Anytown, USA
PASSIVE SOLAR DESIGN STRATEGIES 61
Description of The building has an South facing windows
attached sunspace. The provide direct gain solar heating
Example Building
( ) sunspace floor has a four-inch
thick slab-on-grade with quarry
to the dining area. kitchen and
master bedroom. The south
A 1.504 square foot passive tile set in a mortar bed. The glazing in the kitchen and
solar. single-family home with sunspace is separated from the dining area provides heat to an
an 8.3 ft. average ceiling height conditioned portion of the house exposed slab-on-grade.
is used to illustrate how to use by sliding glass doors and a The east portion of the
the worksheets. A floor plan. masonry fireplace wall. Awning house is slab-on-grade
building elevations. building windows located at the top and construction. The great room
sections and details are shown bottom of the south wall provide and master bedroom suite are
below. outside ventilation for the raised floor construction. The
sunspace. slab-on-grade floor in the
kitchen and dining area is
finished with ceramic tile so that
the floor may function as
thermal mass.
The exterior doors are metal
with a foam core center.
Garage
4040
Bedroom
Great Room
Master
;.. Bedroom
.,...
Suns pace
8088 8088
14'
FLOOR PLAN
----
o2 4 8 12
AnytOWD, USA
62 INTRODUCTION
SOUTH ELEVATION
NORTH ELEVATION
'........
----
024 B 12
.........................::::::::::::::J
"r
ABOVE GRADE SECTION
02 4
...... B 12
)
Insulation,.---i''ti"*t:=;::::::l I
. .,
. .... . .. ' : .r'''<:'.:l.-m~'-'-:!
""""!1rf"'_'11IT'nl-.LA .' .' •
§ 1111 § III I;, : .....: . ini~),i~,
§1I11 § 1111 ., ..•• ". 1I11§1Il1t='
•.• ' :." .•• 1I11§1II"
.• : .' ~'. 1111"
", • "II .~. ", 111'
.... . ....
'"
",
-... ... ." . .. . ..
..... .. .•....
.. '
'. -
"
",'.'
,'
'
• ' II' . ' II'
TYPES OF FOUNDATIONS /
Anytown, USA
PASSIVE SOLAR DESIGN STRATEGIES 63
General pro~ect Information
1504 sf
~:Area
Anytown, USA
64 CONSERVATION PERFORMANCE LEVEL
27.9 35
R-49 R-60
46.9 57.9
house from the sunspace. There are actually five separate Framed Insulation R-value
If the example building had tables labeled AI, A2, A3, A4 Construction R-19 R-22 R-30 R-38
Trombe walls or water walls, and A5. A separate table is 2x6 at 16"oc 14.7 15.8 16.3 -
2x6 at 24'oc
2x8 at 16"oc
15.3 16.5 17.1
17.0 18.9 20.6 21.1
-
heat loss through these passive provided fQr ceilings/roofs, 2x8 at 24"oc 17.6 19.6~ 22.2
solar systems would also be walls, floors, windows and 2x10 at 16"oc 18.1 20.1 24. 25.7
2x10 at 24"oc 18.4 20.7 . 26.8
excluded from the calculation. doors. The R-values' in these 2x12 at 16"oc 18.8 21.0 25.5 30.1
2x12 at 24 'oc 19.0 21.4 27.3 31.4
Heat loss from the passive tables include the thermal
solar energy systems is excluded resistance of both the insulation The area and R-value of the )
since the solar savings fractions and other materials that two different types of
in Worksheet II take these losses typically make up the construction are entered on two
into account. construction assembly such as lines of the table under
exterior sheathing and "ceilings/roofs" and the heat
sheetrock. They also account loss is calculated by dividing the
for framing members that surface area by the total .
penetrate the insulation and R-value. Note that the ceiling
reduce the effectiveness. over the sunspace is not
included in this calculation.
Anytown, USA
PASSIVE SOLAR DESIGN STRATEGIES 65
Walls The R-value of each wall The total R-value is selected
There are two types of wall type is detennined from Table from Table A3, which considers
'\ construction in the example A2 in the Worksheets booklet. the buffering effect of the
)
building. The typical exterior The R-value of both wall types is crawlspace as well as framing
wall is of 2x6 wood frame 17.7 from the table, but since and the floor materials. The
construction with R-19 mineral the first wall type has R-7 area and R-value is entered on
insulation in the cavity. An insulating sheathing, this is one line of the table and the
insulating sheathing with an R- added to the value from the heat loss is calculated by .
7 rating is attached to the table so that 24.7 is used in the dividing the area by the R-value.
exterior surface of the framing. calculations. These R-values
A3-lnsulated Floors
The wall is finished with 1/2 along with the associated areas
Insulation R·value
inch sheetrock on the inside are entered on two lines of the Framing R-11 R-19 R-30 R-38
2x6s at 16"oc 18.2 23.8 29.9
and a brick veneer on the table and the heat loss is 2x6s at 24"oc 18.4 24.5 31.5
outside.
The second type of wall
calculated by dividing each
surface area by the
2x8s at 16"oc
2x8s at 24"oc
2x10 at 16"oc
2x10 at 24"oc
18.9 4W
18.8 24.9 31.7 36.0
33.1 37.9
19.3 25.8 33.4 38.1
19.3 .1 34.4 39.8
construction separates the corresponding R-value. 2x12 at 16"oc 19.7 26.5 34.7 39.8
2x12 at 24"oc 19.6 26.7 35.5 41.2
house from the garage. This These R·values include the buffering effect of a
A2-Framed Walls
wall is also of 2x6 wood frame ventilated crawlspace or unconditioned basement.
Single Wall Insulation R·value
construction With R-19 in the Framing R-11 R-13 R-19 R-25 Had there been different
2x4 at 16"oc 12.0 13.6 insulation conditions for the
cavity, but it does not have the 2x4 at 24"oc 12.7 13.9 ~ -
insulating sheathing or the 2x6 at 16"oc 14.1 15.4 17. 19.2 raised floor, an additional line of
2x6 at 24"oc 14.3 15.6 . 19.8
brick veneer. Note that the Double the table would be completed for
Wall Total Thickness (inches) each condition.
walls that separate the house Framing 8 10 12 14
from the sunspace are not 25.0 31.3 37.5 43.8 If the example building had
included. ..... The R·value of insulating. sheathing should be
insulated floors over a garage or
\
/ It is necessary to measure added to the values in this table. unheated basement, these
the surface area of each type of components would also be
wall construction. The surface Floors included in this step.
area may be determined by Only the raised floor is As an alternative to
multiplying the length of wall by considered in this step of the insulating between the floor
the average height and heat loss calculation; heat loss joists, the perimeter walls of the
subtracting the area of doors from the slab-on-grade floor is crawlspace could have b~en
and windows. conSidered in Step B. There is insulated and floor insulation
one type of raised floor eliminated. When this
construction in the example technique is used, the perimeter
building. R-19 mineral heat loss method in Step B
insulation is placed between should be used. Step A only
2xlO floor joists at 16 inches on includes floors when insulation
center; the crawlspace beneath is placed in the floor assembly.
is ventilated.
Anytown, USA
66 CONSERVATION PERFORMANCE LEVEL
Anytown, USA
PASSIVE SOLAR DESIGN STRATEGIES 67
Table B-Perimeter Heat Loss Factors
Step B. Foundation for Slabs·on·Grade and Unheated The building volume is
Perimeter Heat Loss . Basements (Btuth·F·ft) calculated by multiplying the
Heated Unheated Insulated
Foundation heat loss from average ceiling height by the
) slabs-on-grade. basements and
Perimeter Siabs-on- Base·
Insulation Grade ments
Base- Crawl·
ments spaces
conditioned floor area. In this
None 0.8 1.3 1.1 1.1
insulated crawispaces is R5 ~ 0.8 0.7 0.6 example the average ceiling
R:7 0.3 0.7 0.6 0.5
estimated by multiplying the R·11 . 0.6 0.5 0.4 height is 8.3 ft. The conditioned
R-19 0.2· 0.4 0.5 0.3
length of perimeter times an R-30 0.1 0.3 0.4 0.2 floor area is 1,504 sf which does
appropriate heat loss factor When a raised floor assembly is not include the garage or the
taken from Table B. not insulated, for instance, over sunspace. The resulting
The dining area, kitchen and crawlspaces insulated at the building volume is 12,483 cubic
secondary bedrooms in the perimeter or basements, heat feet.
example house have slab-on- loss occurs primarily at the The units of infiltration heat
grade construction. R-7 perimeter. loss are Btu;oF-h, the same as
insulation is installed around The example house does not for the building envelope and
the perimeter. have a basement or a heated the foundation perimeter.
The heat loss factor for the crawlspace, but if it did, the
slab edge is 0.3, selected from Step D. Total Heat Loss per
foundation heat loss would be
Table B. The heat loss factor is Square Foot
calculated by multip1ying the
multiplied by the perimeter to The total building heat loss is
perimeter of these elements by a
calculate the heat loss. The the sum of the heat loss for the
heat loss factor selected from
units of heat loss, using the building envelope (Step A), the
Table B.
perimeter method, are the same foundation perimeter (Step B)
When houses have heated
as for the building envelope and infiltration (Step C). For
basements, heat loss from ,
calculated in the previous step. residences this value will range
basement walls located above
Note that sunspace slab is not between 200 and 500. It
grade would be included in
included in this calculation. represents the Btu of heat loss
Step A.
The slab edge perimeter from the building envelope over
adjacent to the crawlspace and Step C. Infiltration Heat Loss the period of an hour when it is
the sunspace is also excluded. The heat loss from infiltration or one OF colder outside than
air leakage is estimated by inside. This total heat loss, of
multiplying the building volume course, does not include heat
times the air changes per hour loss from the solar systems,
times a heat loss factor of 0.018. including direct gain glazing.
The example building is The result of Step D,
estimated to have an infiltration however, is the annual heat loss
rate of 0.50 based on local per degree day per square foot.
building experience. This value is calculated by
mUltiplying the total heat loss
by 24 hours/ day and dividing
by the conditioned floor area.
Anytown, USA
68 CONSERVATION PERFORMANCE LEVEL
~
0.90 0.94 0.98~. 1.03
.00 0.86 0.91 0.95 . 1.01 completed for the typical design
~5 Q~ Q~ Q~ Q9 Q~
. 0 0.77 0.83 0.88 . 2 0.96 and the results of these
3.50 0.72 0.78 0.83 0.88 0.93
calculations would be entered in
The conservation Step F.
perfonnance level for the If the conservation
example building is compared to per.(onnance level of the
the base case conservation proposed building (Step E) is
perfonnance level in the next greater than the base case or
step. typical-design conservation
)
perfonnance level. the designer
should conSider additional
building insulation or reduced
non-solar glass area.
Anytown; USA
PASSIVE SOLAR DESIGN STRATEGIES 69
Worksheet II: Auxili Heat Performance Level
A. Projected Area of Passive Solar Glazing
/
I. )
Solar System Rough Frame Net Area Adjustment Projected
Reference Code Area Factor Factor [Table E] Area
Q~QI ee X 0.80 X ~e fl~
SSQI 2Qe X 0.80 X ~e jfl~
X 0.80 X
X 0.80 X =
X 0.80 X =
X
X
0.80
0.80
X
X
=
=
2~fl 2~2 sf
Total Area Total
Projected
Area
Anytown, USA
70 AUXILIARY HEA T PERFORMANCE LEVEL
,
./
Anytown, USA
PASSIVE SOLAR DESIGN STRATEGIES 71
Step B. Load Collector Ratio A reference code, for The solar savings fraction for
The load collector ratio is instance "DGC 1", is also each system is multiplied by the
calculated by taking the total provided for each solar system projected area and totaled at the
heat loss from Worksheet I, Step variation. These references are bottom of the table. This total is
D and multiplying this value entered on the worksheet "Solar then divided by the total
times 24 (hours/ day) and System Reference Code". They projected area from Step A to
dividing by the total projected are also a key to additional calculate the weighted average
area of the solar glazing information about each solar solar savings fraction for the
calculated in the previous step. system as provided in Passive whole building.
Solar Heating Analysis and The solar savings fractions
Step C. Solar Savings Fraction other reference manuals. are based on reference designs.
The next step is to calculate the The assumptions made about
solar savings fraction for the F1-Direct Gain
Load DGC3
these reference designs are
DGCI DGC2
building. This is calculated as a Collector Double Low-e R-9 Night summarized below.
Ratio Glazing Glazing Insulation
weighted average of the solar 200 0.10 0.11 0.13
savings fraction for the separate 155 0.13 0.14 0.17 Direct Gain
100 0.18 0.20 0.24
passive solar systems. The 80 0.22 0.25 0.30 The direct gain reference
60 0.28 0.31 0.38
weightings are based on 50 0.32 0.36 0.44 designs are all assumed to have
projected area. 45 0.34 0.39 0.47
40 0.37 0.43 0.51 double-pane glass and sufficient
The solar systems used in
this step should be identical to
those used above in Step A. The
ar 20
15
~ .9
0.55
0.62
0.47
0.52
0.58
0.65
0.74
0.56
0.62
0.69
0.77
0.85
heat storage to limit the clear
day temperature swing to 13°F.
For the case with night
first two columns are simply insulation, the thermal
carried down from the first and F4-Sunspaces resistance is assumed to be R-9.
last columns in· Step A. Load
Collector sunsEace Type
) The solar savings fraction for Ratio SSAI SSBI SCI SSDI SSEI Trombe Walls
200 '0.17 0.14 0.11 0.19 0.15
e9-ch individual system is taken 155 0.20 0.17 0.14 0.23 0.19 The Trombe wall reference
100 0.26 0.22 0.19 0.30 0.26
from Tables F1 through F4 80 0.30 0.25 0.23 0.35 0.30 designs are all assumed to have
based on the load collector ratio 60 0.35 0.30 0.28 0.42 0.36 double-pane glass. The mass
50 0.39 0.34 0.32 0.46 0.40
calculated in Step B and the 45 0.42 0.36 0.35 0.49 0.43 wall is assumed to be 12 inches
40 0.44 0.39 0.38 0.52 0.46
type of solar system. Table F1 is 0.49 thick and constructed of
~ ~
0.48 0.42 0.56
0.52 0.46 0.60 0.54
for direct gain systems, Table F2 0.56 0.50 .0 0.65 0.59 masonry or concrete.
for thermal storage walls, Table 20 0.62 0.56 0.57 0.72 0.65
15 0.70 0.64 0.65 0.79 0.73
F3 for water walls and Table F4 Water Walls
for sunspaces. There are The water wall reference designs
multiple columns in each table are all assumed to have double-
that account for system design pane glass. The water tank is
features such as night assumed to be nine inches
insulation or selective surfaces. thick, extending continuously in
front of the glazing surface. The
space between the water tank
and the glazing is assumed to be
sealed.
Anytown l USA
72 AUXILIARY HEA T PERFORMANCE LEVEL
\)
I
Alternatively, the
performance level may be
compared to a previous
worksheet calculation made for
a typical builder house.
If the auxiliary heat
performance level calculated in
Step D were larger than the base
case auxiliary heat performance,
the designer should conSider
increasing the size of the solar
Sunspace Reference Designs systems, adding additional solar
Data is provided for five types of sunspaces. systems or increasing insulation
levels.
\
/
Anytown, USA
PASSIVE SOLAR DESIGN STRATEGIES 73
Worksheet III: Thermal Mass/Comfort
(
'\
\ A. Heat Capacity of Sheetrock and Interior Furnishings
) Unit Total
Heat Heat
Floor Area Capacity Capacity
BQQIDl! lIlli!b Qi[~Q! !:aiilie 424 X 4.7 2H~1
QRiilQ~l! QQee~Q!~g !Q Qi~Q! !:aiilie QRiilQ~l! ~4~ X 4.5 = 42Z1
2452 Btu/OF
Total
B. Heat Capacity of Mass Surfaces Enclosing Direct Gain Spaces
Unit Heat
Mass Description capaci~ Total Heat
(include thickness) Area [Table ] Capacity
nQIDb~ WslIIl! X 8.8
, wm~[Wiillll! X 10.4 =
E~RQl!~g Qliilb ie Que lQa X 13.4 = laaQ
E~RQl!~g Qliilb IlIQ! ie Que laZ X 1.8 = 24Z
X =
X =
X =
122Z Btu/OF
Total
C. Heat Capacity of Mass Surfaces Enclosing Spaces Connected to Direct Gain Spaces
Unit Heat
Mass Description Capacity Total Heat
(include thickness) Area [Table H] Capacity
I[QIDb~ WslIIl! X 3.8
W~[WiillIl!
. X 4.2 =
) EiilQ~ 6[iQis 4" III X 3,Z = 4ll
X =
X =
4ll Btu/OF
Total
Anytown, USA
74 COMFORT PERFORMANCE LEVEL
Suns pace
Anytown, USA
PASSIVE SOLAR DESIGN STRATEGIES 75
Step B. Heat Capacity of Mass Exposed slabs-on-grade Step C. Heat Capacity of Mass
Surfaces Enclosing include those with a surface of Surfaces Enclosing Spaces
() Direct Gain Spaces
The heat capacity of thermal
vinyl tile. ceramic tile or other
materials that are highly
Connected to Direct Gain
Spaces
mass elements (other than conductive. Slabs that are The same type of calculation is
sheetrock and furnishings) that covered with carpet should not performed for mass surfaces
enclose the direct gain spaces is be considered to be exposed. that enclose spaces connected
conSidered in this step. The The exposed slab area should be to direct gain spaces. The
surface area of each element is further reduced. when primary difference is the unit
measured from the building appropriate. to account for heat capacity figures taken from
plans and multiplied by the unit throw rugs and furnishings. Table H2 instead of Table H 1.
heat capacity. The unit heat The exposed slab area is In the example building. the
capacity is printed directly in then subdivided into two areas: fireplace wall and hearth are
the table for Trombe walls. water that which is expected to be in considered in this category.
walls. and exposed slabs-on- the sun and that which is not. This area and the unit heat
grade. The unit heat capacity As a rule-of-thumb. slab area capacity is entered in the table
for other mass elements is should be considered in the sun and multiplied by each other.
selected from Table H 1. Note only when it is located directly This represents the total
that thermal mass located in the behind south glazing. In any effective heat capacity of mass
sunspace is not included in this event. the slab area assumed to elements that enclose the
calculation. be in the sun should not exceed spaces connected to direct gain
1.5 times the south glass area. spaces.
H1-Mass Surfaces Enclosing
Direct Gain Spaces . In the example building. the
H2-Rooms with no Direct Solar Gain
Thickness (inches) slabs-on-grade located in the Thickness (inches)
Material 1 2 3' 4 6 8 12
Poured Conc. 1.8 4.3 6.7 8.8 11.311.5 10.3 kitchen and dining room are Material 1 2 ~ 4 6 8 12
) Conc. Masonry 1.8 4.2 6.5 8.4 10.210.0 9.0
Face Brick 2.0 4.7 7.1 9.0 10.49.9 9.0
located within direct gain Poured Conc. 1.7 3.0 3.6 3.8 3.7 3.6 3.4
Conc. Masonry 1.6 2.9 3.5 ~.6 3.4 3.2
Flag Stone 2.1 4.8 7.1 8.5 8.6 8.0 7.6 spaces. Some of this area is Face Brick 1.8 3.1 3.6 3.7 .5 3.4 3.2
Builder Brick 1.5 3.7 5.4 6.5 6.6 6.0 5.8 Fla~Stone 1.9 3.1 3.4 . 3.2 3.1 3.0
Adobe 1.3 3.2 4.8 5.5 5.4 4.9 4.8 considered to De in the sun and Builder Brick 1.4 2.6 3.0 3.1 2.9 2.7 2.7
Hardwood 0.4 1.4 1.8 1.7 1.5 1.5 1.5 Adobe 1.2 2.4 2.8 2.8 2.6 2.4 2.4
Water 5.2 10.415.6 20.8 31.241.6 62.4 the remainder not. These Hardwood 0.5 1.1 1.3 1.2 1.1 1.0 1.1
surface areas are entered in the
table and multiplied by the
appropriate unit heat capacity.
The products are then summed
at the bottom of the table.
Anytown, USA
76 COMFORT PERFORMANCE LEVEL
Step D. Total Heat Capacity Step F. Clear Winter Day Step G. Recommended
The total heat capacity is the Temperature Swing Maximum Temperature Swing
sum of the heat capacity from The clear winter day The comfort performance target ' \
Steps A, B and C. This temperature swing is calculated for all locations is 13°F. If the )
represents the effective heat in Step F. The projected area of comfort performance level
capacity of all thermal mass all direct gain glazing is entered calculated in Step F had been
within the building. in the first row. This includes greater than 13°F, additional
all direct gain systems either thermal mass should be added
Step E. Total Heat Capacity with or without night insulation. to the building or direct gain
per Square Foot In the second row, the projected glazing should be reduced.
The total heat capacity area of sunspace glazing and
calculated in Step D is divided Trombe walls vented to the
by the total floor area of the indoors is entered. Unvented
building to get the total heat Trombe walls and water walls
capacity per square foot. The are not included in this
floor area used in this calculation since solar gain from
calculation should not include these systems does not
the sunspace or other contribute to the temperature
unconditioned spaces. This swing of the conditioned space.
value is calculated here for The appropriate comfort
convenience, but it is not used factor is entered in the second
until Worksheet IV is completed. column, selected from Table I.
,(he projected areas are
multiplied by the appropriate
comfort factors and summed.
This sum is then divided by the '!\
total heat capacity from Step D
to yield the clear winter day
temperature Swing.
Anytown, USA
PASSIVE SOLAR DESIGN STRATEGIES 77
Worksheet IV: Summer Coolin Performance Level
A. Opaque Surfaces
'\ Radiant Barrier Absorp- Heat Gain
j Heat Loss Factor tance Factor
Description [Worksheet I] [Table J] [Table K] [table L] Load
Anytown, USA
78 SUMMER COOLING PERFORMANCE LEVEL
a heat gain factor (from Table L). -... Multiply by O.B for low-e glass, 0.7 for tinted glass
and 0.6 for low-e tinted Qlass.
The end product of this
The rough frame area is
calculation is an estimate of the
generally entered in the table
annual cooling load that is
and adjusted by the net area
associated with each suIface in
factor. If the net glazing area is
thousands of Btu per year
entered instead, then the net
(kBtu/yr).
area factor is 1.00.
Anytown, USA
PASSIVE SOLAR DESIGN STRATEGIES 79
Table M gives the shade If the example building had Step C. Solar Glazing
factor for overhangs. The tinted glazing. glazing films or The solar systems addressed on
overhang shade factor depends external shading devices. the Worksheet II reduce heating
on the orientation of the window shade factors from Table M energy. but they also can
and the projection factor. The should not be used. Sunscreen increase cooling energy. The
proj ection factor is the overhang and glass manufacturers cooling energy impact of the
projection divided by the usually rate the shading effect of solar systems is calculated in
distance from the bottom of the their devices by publishing a this step. Each solar system
window to the bottom of the shading coefficient. The listed on Worksheet II should be
overhang. as illustrated below. shading coefficient is a number carried over to this worksheet.
between zero and one that The cooling energy for each
A indicates how much solar heat system is calculated by
makes it through the window multiplying the total surface
compared to an unshaded 1/8 area (not the projected area)
inch clear pane. This shading times the net area factor. the
coefficient may be used in the appropriate shade factor (as
calculation instead of the value discussed above) and a heat
from Table M. gain factor (from Table L). This
The overhang on the east calculation gives the annual
and west is at the eave. well cooling load for each passive
above the window. and does not solar system.
Overhang Projection Factor provide any useful shading. For A shade factor of 0.83 is
The projection factor is the overhang
projection divided by the distance between the
these windows. the shade factor used because of south
bottom of the window and the bottom of the is 1.00. overhangs. This is based on a
overhang. Each glazing area is projection factor of about 0.2 as
\ The north windows have a multiplied by the net area factor discussed above.
height of four feet and the and the appropriate shade The annual cooling load
bottom of the overhang is about factor. The products are associated with all the passive
six inches above the window summed at the bottom of the solar systems is summed at the
head. The overhang projection table. bottom of the table.
is 1.5 feet. The projection factor
is calculated by dividing the
overhang projection by the
distance from the bottom of the
window to the bottom of the
overhang. This is about 0.33. A
shade factor of 0.84 is used in
the calculations. which is
interpolated between the values
for a projection factor of 0.2 and
0.4
Anytown, USA
80 SUMMER COOLING PERFORMANCE LEVEL
Anytown, USA
Passive Solar
Design Strategies
APPENDIX
Jackson. Mississippi
82 APPENDIX
JacksoD, Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 83
Site Planning Sunspaces
15. Builder's Guide to Passive Solar 17. Jones, Robert W. and Robert D.
Home Design and Land Development, McFarland. The Sunspace Primer. A
National Fenestration Council. Available Guide for Passive Solar Heating, available
for $12.00 from NFC, 3310 Harrison, for $32.50 from Van Nostrand Reinhold,
White Lakes Professional Building, 115 5th Avenue, New York, N.Y. 10003
Topeka, KS. 66611
18. Greenlwusesfor Uving, from Steven
16. Site PlanningJor Solar Access, U.S. Winter Associates, Attn: Publications,
Department of Housing and Urban 6100 Empire State Building, New York,
Development/American Planning N.Y. WOOl, $6.95.
Association. Available for $6.50 from
Superintendent of Documents, U.S. 19. ConceptN, from Andersen
Government Printing Office, Washington Corporation, Bayport, MN. 55003, $6.95.
D.C. 20402
20. Passive Solar Greenhouse Design and
Construction. Ohio Department of
Energy/John Spears, 8821 Silver Spring,
Md., 20910.
JackBon, MiBBiBBippi
86 SUMMARY FOR JACKSON, MISSISSIPPI
'~.
"J
Jacksoo, Mississippi
PASSIVE SOLAR DESIGN STRATEGIES 87
Technical Basis for Los Alamos National Laboratory with and heat losses through the solar
funding from the U.S. Department of aperture and, thus. correct for omitting
the Builder Energy Solar Buildings Program. See the the solar components from the
references for more information. calculation of annual heat loss.
Guidelines
1. J. Douglas Balcomb. Robert W. Jones,
Annual Heat Loss Robert D. McFarland. and William O.
How the Builder (Worksheet I) Wray, "Expanding the SIR MethDd",
Passive Solar Journal. Vol. 1, No.2,
Guidelines Were The heat-loss calculation is based on a 1982, pp. 67-90. Available from the
Produced straightforward summation of the American Solar Energy Society. 2400
traditional elements that make up the Central Ave. Unit B-1, Boulder. CO
The text of the Builder Guidelines book building heat-loss coefficient (excluding 80301.
is generated by merging two computer the solar components). The worksheet
meso The first is a word-processor file procedure estimates the annual heat loss 2. J. Douglas Balcomb, Robert W. Jones,
containing the text; it does not change by multiplying the heat-loss coefficient Robert D. McFarland. and William O.
from location to location. The second by annual degree days (times 24 to Wray. Passive Solar Heating Analysis,
contains numbers and text and is convert from days to hours). Degree days American Society of Heating.
location dependent. This second file is for each month were determined using Refrigerating, and Air-Conditioning
produced by running a computer an appropriate base temperature that Engineers, 1984. Available from
program that calculates performance accounts for an assumed thermostat ASHRAE, 1719 Tullie Circle. NE, Atlanta,
numbers based on long-term monthly setting of 70 degrees. an assumed GA 30329.
weather and solar data compiled by the internal heat generation of 36 Btu/day
National Oceanic and AtmospheriC per sq ft of floor area. and the total 3. J. Douglas Balcomb and William O.
Administration for a particular location. building loss coefficient. This forms the Wray, Passive Solar Heating Analysis,
The merge operation slots the numbers basis of the table of heating degree day SupplemeDt ODe, Thermal Mass
and text in the second file into their multipliers. The result of the worksheet Effects aDd Additional SLK
correct locations in the first me. This is is an estimate of the annual heat CorrelatioDs, American Society of
then laser printed to produce the required to maintain comfort. excluding Heating. Refrigerating. and Air-
camera-ready manuscript. both positive and negative effects Conditioning Engineers, 1987. See
resulting from the solar components. In ASHRAE address above.
this estimate. no solar heating credit is
More than a Decade of given to east, west. and north windows,
Experience because it is assumed that these will be Temperature Swing
protected by vegetation or other shading (Worksheet III)
The concentrated effort of research, in accordance with the Builder Guideline
design. construction. monitoring. and recommendations. This is a conservative The temperature swing estimate on
evaluation of actual buildings that assumption because there will always be worksheet III is based on the diurnal
started at the First Passive Solar some solar gain through these windows. heat capacity (dhc) method (reference 3).
Conference in Albuquerque in 1976 has The method is an analytic procedure in
continued up to the present. It is which the total heat stored in the
estimated that more than 200.000 Annual Auxiliary Heat building during one day is estimated by
passive solar homes have been built in (Worksheet II) summing the effective heat storage
the United States during this time. This potential of the all the various materials
wealth of experience has been reviewed The tables of passive solar savings in the building for a 24-hour periodic
by NREL, the Technical Committee of fractions are calculated using the solar cycle of solar input. Rooms with direct
PSIC, and by the Standing Committee on load ratio (SLR) method (references 1 and gain are assumed to have radiative
Energy of the National Association of 2). Monthly solar savings fraction (SS1'1 coupling of the solar heat to the mass.
Home Builders and is distilled into these values are determined using correlation Rooms connected to rooms with direct
Guidelines. fits to the results of hourly computer gain are assumed to have convective
simulation calculations for a variety of coupling, which is rather les!;! effective,
climates. These 12 values are converted especially for massive elements. The dhc
Analysis Procedures into an annual value and entered into of the sheetrock, framing, and furniture
worksheet Tables FI-F4. The SLR is approximated as 4.5 or 4.7 Btuf"F per
The analysis procedures used method gives answers that agree within
throughout the GUidelines were sq ft of floor area. Worksheet Tables H 1
about 5% of the hourly computer and H2 list the increased value of
developed using simple. well-established
simulations and within 11% of the diurnal heat capacity for various
methods for estimating the performance
measured passive solar performance of conventional materials that are often
of passive solar heating and natural 55 bUildings monitored under the Solar
cooling strategies. These procedures used to provide extra heat storage,
Buildings Program. The SSF estimates assuming these materials replace
(described below) were developed at the account properly for both solar gains sheetrock.
JackSOD, Mississippi
88 APPENDIX
The only numbers in worksheet III underestimates very large cooling loads worksheet can be used anywhere within
that are location dependent are the in poorly designed buildings. 4 degrees of latitude of the parent
comfort factors, taken from Table I. The The adjustment factors for location.
direct-gain comfort factor is 61% of the ventilation properly account for The cooling estimate obtained from
solar gain transmitted through vertical, maintaining comfort in hot and humid worksheet IV is specific to the location.
south-facing double glazing on a clear climates. Ventilation is restricted to Within the same viCinity and within plus
January day. The driving effect of times when the outside dew-point or minus 20%, the result could be
suns paces and vented Trombe walls is temperature is less than 62 OF. This adjusted, based on a ratio of cooling
assumed to result in one-third this restriction avoids ventilation when high degree days. However, this adjustment is
value, based on data from monitored hUmidity might cause discomfort not done automatically within the
buildings. The origin of the 61 % factor is worksheet.
described in the references. 4. Robert D. McFarland and Gloria
Lazarus, Monthly AwdIlary CooUng
Estimation for Residential Buildings,
Getting Data
Annual Auxiliary Cooling lA-11394-MS, Los Alamos National
(Worksheet IV) Laboratory, NM 87545, 1989.
Heating and cooling degree-day data can
be obtained from the National Climatic
The purpose of including the summer Center, Asheville, NC. Refer to
cooling estimates in the Builder Notfor Sizing Equipment Climatography of the United States No.
Guidelines is to (1) determine if design 81 which lists monthly normals for the
elements added to promote passive solar All heating and cooling values given in period 1951-1980 on a state-by-state
heating will cause excessive summer the Builder Guidelines Tables and basis. More than 2400 locations are
cooling loads and (2) provide a rough numbers calculated using the listed in this data base.
estimate of the effectiveness of solar worksheets are for annual heat delivered
shading and natural cooling strategies. or removed by the mechanical heating or
The analysis method is based on a cooling system. You cannot directly use
modified monthly degree-day procedure these numbers for sizing the capacity of
in which the day is divided into day and this equipment. The methods developed
night periods (reference 4). All estimates by the American Society of Heating,
are derived from correlations based on Refrigerating, and Air Conditioning
hourly computer simulations. Solar, Engineers for sizing equipment are well-
conduction, and internal gains are established and are recommended. The
estimated for each half-day period in purpose of the guidance provided in
each month. Delay factors are used to these booklets is to minimize the
account for heat carryover from day to operating time and resources consumed
night and night to day. The results are by this eqUipment.
estimates of annual sensible cooling
delivered by the air conditioner and do Using the Worksheets in
not include latent loads.
Because the the original Los Alamos
Nearby Locations
monthly procedure is too complex to be
The applicability of worksheets I and II
implemented in a worksheet, a Simplified
can be extended somewhat by using the
procedure is adopted on worksheet IV.
base-65 OF degree-day value for a site
Heat Gain Factors and Internal Gain
which is close to the location for which
Factors in Tables L and N are the
the worksheet tables were generated. We
calculated annual incremental cooling
recommend limiting such applications to
loads resulting from a one-unit
sites where the annual heating degree-
incremental change in the respective
days are within plus or minus 10% of the
heat input parameter (that is, a one-unit
parent location and where it is
change in UA, glazing area, or number of
reasonable to assume that the solar
bedrooms). The combined heat load
radiation is about the same as in the
resulting from all inputs is summed and
parent location. The procedure 1s simple:
then adjusted for thermal mass and
Use the measured base-65 OF degree-day
ventilation. This correction includes a
value in worksheet I, line F, instead of
constant required to match the
the degree-day value for the parent
calculated cooling load of the base-case
location.
building. This linearized procedure gives
Worksheet III depends only slightly
accurate estimates for cooling loads that
on location. The only variables are the
are less than about 150% of the base-
Comfort Factors in Table I, which only
case building: however, it
change with latitude. Thus, this
Jackson, Mississippi