0% found this document useful (0 votes)
138 views150 pages

Dataman Fixed-Mount Readers Reference Manual: 2019 November 15 Revision: 6.1.6Sr2.2

Uploaded by

Ivan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
138 views150 pages

Dataman Fixed-Mount Readers Reference Manual: 2019 November 15 Revision: 6.1.6Sr2.2

Uploaded by

Ivan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 150

DataMan® Fixed-Mount

Readers Reference Manual

2019 November 15
Revision: 6.1.6SR2.2
Legal Notices

Legal Notices
The software described in this document is furnished under license, and may be used or copied only in accordance with
the terms of such license and with the inclusion of the copyright notice shown on this page. Neither the software, this
document, nor any copies thereof may be provided to, or otherwise made available to, anyone other than the licensee.
Title to, and ownership of, this software remains with Cognex Corporation or its licensor. Cognex Corporation assumes
no responsibility for the use or reliability of its software on equipment that is not supplied by Cognex Corporation.
Cognex Corporation makes no warranties, either express or implied, regarding the described software, its
merchantability, non-infringement or its fitness for any particular purpose.
The information in this document is subject to change without notice and should not be construed as a commitment by
Cognex Corporation. Cognex Corporation is not responsible for any errors that may be present in either this document or
the associated software.
Companies, names, and data used in examples herein are fictitious unless otherwise noted. No part of this document
may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, nor
transferred to any other media or language without the written permission of Cognex Corporation.
Copyright © 2019. Cognex Corporation. All Rights Reserved.
Portions of the hardware and software provided by Cognex may be covered by one or more U.S. and foreign patents, as
well as pending U.S. and foreign patents listed on the Cognex web site at: cognex.com/patents.

The following are registered trademarks of Cognex Corporation:


Cognex, 2DMAX, Advantage, AlignPlus, Assemblyplus, Check it with Checker, Checker, Cognex Vision for Industry,
Cognex VSOC, CVL, DataMan, DisplayInspect, DVT, EasyBuilder, Hotbars, IDMax, In-Sight, Laser Killer, MVS-8000,
OmniView, PatFind, PatFlex, PatInspect, PatMax, PatQuick, SensorView, SmartView, SmartAdvisor, SmartLearn,
UltraLight, Vision Solutions, VisionPro, VisionView
The following are trademarks of Cognex Corporation:
The Cognex logo, 1DMax, 3D-Locate, 3DMax, BGAII, CheckPoint, Cognex VSoC, CVC-1000, FFD, iLearn, In-Sight
(design insignia with cross-hairs), In-Sight 2000, InspectEdge, Inspection Designer, MVS, NotchMax, OCRMax,
PatMax RedLine, ProofRead, SmartSync, ProfilePlus, SmartDisplay, SmartSystem, SMD4, VisiFlex, Xpand
Portions copyright © Microsoft Corporation. All rights reserved.
Portions copyright © MadCap Software, Inc. All rights reserved.

Other product and company trademarks identified herein are the trademarks of their respective owners.

2
Table of Contents

Table of Contents
Legal Notices 2
Table of Contents 3
About This Manual 7
Symbols 7
Safety Information 8
Warnings And Notices 8
Mechanical Information 9
DataMan 50 Reader Dimensions 9
DataMan 60 Reader Dimensions 10
DataMan 70 Series Reader Dimensions 11
DataMan 150 Reader Dimensions 12
DataMan 260 Reader Dimensions 13
DataMan 300 Series Reader Dimensions 14
DataMan 360 Series Reader Dimensions 16
DataMan 370 Series Reader Dimensions 17
DataMan 370 Series Reader with High Power Integrated Light (HPIL) 17
DataMan 370 Series Reader with High Power Illumination Accessory (HPIA) 18
DataMan 370 Series Reader with High Power Integrated Torch (HPIT) 18
DataMan 470 Series Reader Dimensions 19
DataMan 470 Reader with High Power Integrated Light (HPIL) 19
DataMan 470 Reader with High Power Illumination Accessory (HPIA) 19
DataMan 470 Reader with High Power Integrated Torch (HPIT) 20
DataMan 503 Reader Dimensions 21
Service Procedures 22
DataMan 50 Service Procedures 22
DataMan 60 Service Procedures 24
DataMan 70 Service Procedures 25
Service Procedures 27
DataMan 150 and 260 Series Service Procedures 27
DataMan 300 and 360 Series Service Procedures 37
DataMan 370 and 470 Series Service Procedures 43
DataMan 503 Service Procedures 56
Maintenance 57
Replacing the SD Card 57
Mounting Requirements 59
Mounting Your DataMan 70 Reader 59
Mounting Your DataMan 150 and 260 Reader 60
Mounting Your DataMan 370 and 470 Reader 64
Grounding 67
Thermal and Environmental Requirements 68
DataMan 50, 150, 260, 300, 360, and 503 IP Rating 68
DataMan 60 and 70 IP Rating 68
DataMan 370 and 470 IP Rating 68
Electrical Information 70
DataMan 50 and 60 Discrete I/O Connector 70

3
Table of Contents

DataMan 50 and 60 USB & Flying Leads I/O Cable 70


DataMan 50 and 60 RS-232 & Flying Leads I/O Cable 71
DataMan 50 and 60 Flying Leads Cable 71
DataMan 50 and 60 Digital Input Lines 72
DataMan 50 and 60 External Wiring Examples: Digital Input Lines 73
DataMan 50 and 60 Digital Output Lines 74
DataMan 50 and 60 External Wiring Examples: Digital Output Lines 75
DataMan 70 15 Pin Adapter Cable 76
DataMan 70 9 Pin Adapter Cable 77
DataMan 70 Serial IO Adapter (DMA-SERIALREST-ST) 78
DataMan 150 USB Cable 78
DataMan 70 and 150 Discrete I/O Connector 80
DataMan 70 and 150 RS-232 Cable 80
DataMan 150 Flying Leads Cable 81
DataMan 150 USB Connections 81
DataMan 150 RS-232 Connections 82
DataMan 150 Wiring the Basic I/O Module 82
Output Wiring Example 83
Input Wiring Example 84
DataMan 150 Digital Input Wiring Diagrams 84
Current Sink Configuration 84
Current Source Configuration 84
PNP Configuration 85
NPN Configuration 85
Dataman 150 Digital Output Wiring Diagrams 85
Sinking Outputs, Sourcing Inputs 86
Sinking Outputs, Sinking Inputs 86
Electrical Information 87
DataMan 260 Discrete I/O Connector 87
DataMan 260 Ethernet Cable 88
DataMan 150 and 260 Acquisition Triggering 89
DataMan 260 High-Speed Output Lines 90
DataMan 260 High-Speed Output Wiring 90
Dataman 300 5m RS-232 Connection Cable (CCB-M12XDB9Y-05) 91
DataMan 300, 360, 370, and 470 Series Readers Discrete I/O Connector 92
5m Breakout Cable (CCBL-05-01) 92
5m Breakout Cable (CCB-M12x12Fy-xx) 93
15m Breakout Cable (CCB-PWRIO-XX) 94
DataMan 300, 360, 370, and 470 Series Readers External Light Control 95
DataMan 300, 360, 370, and 470 Series Readers Power Requirements 95
DataMan 300, 360, 370, and 470 Series and DataMan 503 Readers Acquisition Triggering 95
DataMan 300, 360, 370, and 470 Series, and DataMan 503 Readers High-Speed Output Lines 96
DataMan 300, 360, 370, and 470 Series Readers High-Speed Output Wiring 98
DataMan 300 and 503 Ethernet M12 to RJ45 Cable (CCB-84901-y00x-xx) 99
DataMan 503 Discrete I/O Connector 100
5 m Breakout Cable (CCBL-05-01) 100
DataMan 503 RS-232 Serial Connector 100
DataMan 503 External Light Control 101
DataMan 503 High-Speed Output Wiring 101
DataMan 503 Power Requirements 102
Connecting the Encoder to a DataMan 103

4
Table of Contents

Optics and Lighting 104


DataMan 50 and 60 Reading Distances and Field of View 104
DataMan 70, 150 and 260 Reading Distances and Field of View 106
DataMan 300 and 360 Series Readers Reading Distances and Field of View 111
Scan Map for DataMan 300 and 360 Series Readers Using a 10.3 mm Lens 111
Scan Map for DataMan 300 and 360 Series Readers Using a 16 mm Lens 112
Scan Map for DataMan 300 and 360 Series Readers Using a 19 mm Lens 113
Scan Map for DataMan 300 and 360 Series Readers Using a 24 mm Lens with Liquid Lens 114
Scan Map for DataMan 300 and 360 Series Readers Using a 25 mm Lens 116
DataMan 370 Series Readers Reading Distances and Field of View 117
Reading Distance and Field of View for DataMan 370 Series Readers with a 10 mm High-Speed Liquid
Lens 117
Reading Distance and Field of View for DataMan 370 Series Readers with a 16 mm High-Speed Liquid
Lens 118
Reading Distance and Field of View for DataMan 370 Series Readers with a 24 mm High-Speed Liquid
Lens 119
DataMan 470 Series Readers Reading Distances and Field of View 120
Reading Distance and Field of View for DataMan 470 Series Readers with a 10 mm High-Speed Liquid
Lens 120
Reading Distance and Field of View for DataMan 470 Series Readers with a 16 mm High-Speed Liquid
Lens 121
Reading Distance and Field of View for DataMan 470 Series Readers with a 24 mm High-Speed Liquid
Lens 122
DataMan 503 Readers Reading Distances and Field of View 124
Scan Map for DataMan 503 Series Readers Using a 16 mm Lens Module 124
Scan Map for DataMan 503 Series Readers Using a 25 mm Lens Module 125
Scan Map for DataMan 503 Series Readers Using a 35 mm Lens Module 125
CS-Mount Lens Characteristics 126
DataMan 503 CS-Mount Lens Characteristics 126
Internal Lighting 127
DataMan 50 and 60 Internal Lighting 127
DataMan 70, 150 and 260 Internal Lighting 127
DataMan 300, 360, 370, and 470 Series Readers Internal Lighting 127
External Lighting 129
DataMan 50 and 60 External Lighting 129
DataMan 50 and 60 Illumination Strobe Output 129
DataMan 50 and 60 External Load Strobe Output 131
DataMan 300, 360, 370, and 470 Series Readers External Lighting 131
DataMan 50, 60, 300, 360, 370, and 470 External Lighting Duration 134
DataMan 503 External Lighting Duration 134
Operations Guide 135
Trigger Modes 135
Self-Trigger 135
Manual 135
Burst 135
Continuous 135
Single 135
Presentation 135
Package Detection Support 136
Test Mode 136

5
Table of Contents

Code Training 137


Automatic Code Training for DPM Symbols 137
Image Buffering and Image Recording 137
Retrieving Buffered Images 138
DataMan Multi-Reader Sync Configuration 138
Primary Reader 139
Secondary Readers 139
Data Formatting 139
Limitations 139
Synchronized Acquisition 139
Using C/CS-Mount Lenses 142
Aperture Setting 142
Selecting Optimum Focus 142
Optimizing Performance 142
Read Interval and Timeout Configuration 142
Optimizing Burst Trigger Parameters 142
Reducing DataMan Processing Requirements 143
Avoiding Reflections and Glare 143
Application Guide 144
Understanding Your Application Envelope 144
Tote Scanning 145
Side Scanning 146
Side Scanning (Large Field) 146
Print Verification (Carton Coding and Print & Apply) 147
Manual Presentation Scanning 148
Precautions 149

6
About This Manual

About This Manual


The DataMan Fixed-Mount Readers Reference provides detailed information on the configuration and operation of
DataMan fixed-mount readers. It includes the following sections:

l Safety Information
l Mechanical Information
l Electrical Information
l Optics and Lighting
l Operation

l Application Guide

Symbols
The following symbols indicate safety precautions and supplemental information:

WARNING: This symbol indicates a hazard that could cause death, serious personal injury or electrical shock.

CAUTION: This symbol indicates a hazard that could result in property damage.

Note: This symbol indicates additional information about a subject.

Tip: This symbol indicates suggestions and shortcuts that might not otherwise be apparent.

7
Safety Information

Safety Information
The DataMan 300, 360, 470, and 503 series readers have laser light.

If you need more information on the collection, reuse, and recycling systems, please contact your local or regional waste
administration.
You may also contact your supplier for more information on the environmental performance of this product.

Warnings And Notices


CAUTION: IP protection is ensured only when all connectors are attached to cables or shielded by a sealing cap.

Note: For product support, contact http://support.cognex.com.

CAUTION: Use of controls or adjustments or performance of procedures other than those specified herein may
result in hazardous radiation exposure.

l Do not attempt to service or repair this product - return it to Cognex for service.
l Do not permit anyone other than Cognex Corporation to service, repair, or adjust this product.
l Do not attempt to open or modify this device except as described in this document.
l Do not direct or reflect laser light toward people or reflective objects.
l Do not operate this device if it is damaged or if the covers or seals are missing or damaged.

This Laser Product is designated as Class 2 during all procedures of operation.

Wavelength 650 nm
Laser power for classification < 1 mW
Beam Diameter < 3 mm at aperture
Divergence < 1.5 mrad

8
Mechanical Information

Mechanical Information
This section provides information on various mechanical features of the DataMan 50, DataMan 60, DataMan 70,
DataMan 150, DataMan 260, DataMan 300, DataMan 360, DataMan 470, and DataMan 503 series readers, such as
dimensions, lens replacement, mounting information, as well as thermal and environmental requirements.

DataMan 50 Reader Dimensions

9
Mechanical Information

DataMan 60 Reader Dimensions

10
Mechanical Information

DataMan 70 Series Reader Dimensions

11
Mechanical Information

DataMan 150 Reader Dimensions


DataMan 150 dimensions in the straight configuration:

DataMan 150 dimensions in the angled configuration:

12
Mechanical Information

DataMan 260 Reader Dimensions


DataMan 260 dimensions in the straight configuration:

DataMan 260 dimensions in the angled configuration:

13
Mechanical Information

DataMan 300 Series Reader Dimensions

1 M3-5 (4x) mounting holes of the device


2 M3-6 (4x) mounting holes for external illumination
3 Illumination lights
4 Operating buttons
5 S-Mount (M12) Lens version
6 C-Mount Lens version

14
Mechanical Information

15
Mechanical Information

DataMan 360 Series Reader Dimensions


DataMan 360 dimensions without lens and with C-mount and S-mount lens options:

1 M3-5 (4x) mounting holes of the device


2 M3-6 (4x) mounting holes for external illumination
3 Illumination lights
4 Operating buttons

A C-Mount Lens version


B S-Mount (M12) Lens version

16
Mechanical Information

DataMan 370 Series Reader Dimensions

DataMan 370 Series Reader with High Power Integrated Light (HPIL)

17
Mechanical Information

DataMan 370 Series Reader with High Power Illumination Accessory (HPIA)

DataMan 370 Series Reader with High Power Integrated Torch (HPIT)

18
Mechanical Information

DataMan 470 Series Reader Dimensions

DataMan 470 Reader with High Power Integrated Light (HPIL)

DataMan 470 Reader with High Power Illumination Accessory (HPIA)

19
Mechanical Information

DataMan 470 Reader with High Power Integrated Torch (HPIT)

20
Mechanical Information

DataMan 503 Reader Dimensions

21
Mechanical Information

Service Procedures

DataMan 50 Service Procedures


DataMan 50 can operate in one of three distance ranges. Perform the following steps to set the focus position:

1. Remove the screws, washers, lens cover and rubber part.

2. Set focus by positioning a coin into the lens cap slit and turning the coin. Do not use a coin thicker than 2 mm. If
no coin is available, use the edge of the back cover

3. Make sure that the sealing and the sealing surface are clean before reassembling the lens cover.
4. Line up the holes with the icons, and attach the rubber part to the front window.

5. Attach both to the housing and add the washers and screws.

22
Mechanical Information

6. Tighten screws in the order shown below. The maximum torque for the cover screws is 5 N-cm (0.4 pound-inch).
The yellow arrow on the cover indicates the selected focus position.

23
Mechanical Information

DataMan 60 Service Procedures


DataMan 60 can operate in one of three distance ranges. Perform the following steps to set the focus position:

1. Remove the lens cover.

2. Set the focus position to 45, 70, or 110: turn the lens cap clockwise (45->70->110) to focus to a larger distance;
turn the lens cap counter-clockwise (110->70->45) to focus to a shorter distance.
3. Reattach the front cover.

24
Mechanical Information

DataMan 70 Service Procedures


DataMan 70 can operate in one of three distance ranges. Follow the steps below to set the focus position.

1. Remove the screws and the front cover.

DM70 with 6.2 mm lens DM70 with 16 mm lens

2. Using a flathead screwdriver, set the focus position from the front. Always turn clockwise to focus to a larger
distance and counterclockwise to focus to a shorter distance.

DM70 with 6.2 mm lens DM70 with 16 mm lens

Note: If an optical filter has been mounted, first disconnect the DataMan 70 reader from power and remove
the illumination module with the filter before adjusting the focus.

25
Mechanical Information

3. Remount the front cover. Observing the tightening sequence below, tighten all four screws to 9 Ncm using a
torque wrench.

DM70 with 6.2 mm lens DM70 with 16 mm lens

Note: The rib in the front cover must be oriented to the top side.

26
Mechanical Information

Service Procedures

DataMan 150 and 260 Series Service Procedures


Setting the Focus Position of a DataMan 150 or DataMan 260 Reader
DataMan 150 and 260 can operate in one of three distance ranges. Follow the steps below to set the focus position.

Note: The following steps describe service procedures for both the DataMan 150 and the 260 readers, but the
images show only the DataMan 260.

1. Remove the screws and the front cover.

2. Using a flathead screwdriver, set the focus position from the front. Always turn clockwise to focus to a larger
distance and counterclockwise to focus to a shorter distance.

Note: If an optical filter has been mounted, first disconnect the DataMan 150 or 260 reader from power and
remove the illumination module with the filter before adjusting the focus.

3. Remount the front cover. Observing the tightening sequence below, tighten all four screws to 9 Ncm using a
torque wrench.

Note: If you use an optical filter and the illumination was removed, remount the illumination module first and
then remount the front cover.

Note: The rib in the front cover must be oriented to the top side.

27
Mechanical Information

Changing from a 6.2 mm Lens to a 16 mm Lens on a DataMan 150 or DataMan 260


Reader
Perform the following steps to change a 6.2 mm lens to a 16 mm lens on your DataMan 150 or 260 reader.

Note: Disconnect the DataMan 150 or 260 reader from power before changing lenses.

WARNING: This modification must be made in a dust-free and ESD safe area.

Note: The following steps describe service procedures for both the DataMan 150 and the 260 readers, but the
images show only the DataMan 260.

1. Remove the front cover: unscrew the four screws and take off the LED cover.

2. Remove the illumination module.

3. Unscrew the two Phillips head screws and remove the 6.2 mm lens mount.

4. Attach the 16 mm lens mount.

5. Fasten the two Phillips head screws to 0.06 Nm using a torque wrench.

28
Mechanical Information

6. In the case of a manual focus lens, press the 16 mm lens cap onto the lens. The lens has 12 cutouts so it can be
locked in steps of 30 degrees.

7. Attach the illumination board.

Note: Take care to attach the illumination with the right orientation.

8. Attach the extended front cover. Observing the tightening sequence below, tighten all four screws to 9 Ncm using
a torque wrench.

Note: The rib in the front cover must be oriented to the top side.

Installing an Optical Filter


Perform the following steps to install an optical filter in the optics module of your DataMan 150 or DataMan 260 reader.

Note: Disconnect the reader from power before installing an optical filter.

Observe the following constraints on the filter:

l Diameter (Ø): 12.3 mm<Ø<12.7 mm


l Thickness (t): 1.6 mm<t<2 mm filter

29
Mechanical Information

Note: The following steps describe service procedures for both the DataMan 150 and the 260 readers, but the
images show only the DataMan 260.

1. Remove the front cover: unscrew the four M2x12 mm Phillips Pan head screws and take off the LED cover.

2. Insert the filter at the bottom side of the round opening in the transparent plastic part.

3. Push the top side of the filter firmly until it is sitting flat against the PCB.

Note: Use finger to push the filter in and then a q-tip to clean the filter, or use a q-tip to push the filter into
place.

30
Mechanical Information

4. Attach the front cover. Observing the tightening sequence below, tighten all four M2x12 mm Phillips Pan head
screws to 9 Ncm using a torque wrench.

Note: The rib in the front cover must be oriented to the top side.

Installing a Liquid Lens


Perform the following steps to install a liquid lens on your DataMan 150 or DataMan 260 reader.

Note: Disconnect the reader from power before installing the liquid lens.

Note: The following steps describe service procedures for both the DataMan 150 and the 260 readers, but the
images show only the DataMan 260.

31
Mechanical Information

1. Remove the front cover: unscrew the four M2x12 mm Phillips Pan screws and take off the LED cover.

2. Remove the illumination module.

3. Turn the lens cap to the 105 mm position.

4. Remove the lens cap from the imager lens by pulling it.

Note: Do not rotate the imager lens while the lens cap is removed. Otherwise, focus calibration will be lost.

32
Mechanical Information

5. Attach the liquid lens accessory by aligning the 2x2 connectors of the liquid lens with the 2x2 sockets on the
optics mount.

6. Press the liquid lens onto the imager lens until you reach the stop.

7. Reattach the illumination.

33
Mechanical Information

8. Attach the front cover. Observing the tightening sequence below, tighten all four M2x12 mm Phillips Pan screws
to 9 Ncm using a torque wrench.

Note: The rib in the front cover must be oriented to the top side.

Note: The DataMan 150 and the DataMan 260 liquid lens must be calibrated after field exchange. This can
be done under Focus Settings in the DataMan Setup Tool. For more information, see the DataMan
Questions and Answers document. A reboot is required for the lens to operate with the new settings.

Changing to an Illumination with a Different Color


Perform the following steps to change the illumination.

Note: Disconnect the reader from power before changing to an illumination with a different color.

Note: The following steps describe service procedures for both the DataMan 150 and the 260 readers, but the
images show only the DataMan 260.

34
Mechanical Information

1. Remove the front cover: unscrew the four screws and take off the LED cover.

2. Remove the illumination module.

3. Attach a new color illumination module.

Note: Make sure you attach the illumination with the right orientation.

35
Mechanical Information

4. Attach the front cover. Observing the tightening sequence below, tighten all four screws to 9 Ncm using a torque
wrench.

Note: The rib in the front cover must be oriented to the top side.

36
Mechanical Information

DataMan 300 and 360 Series Service Procedures


Replacing a 10.3 mm Lens
To remove and replace a 10.3 mm lens of a DataMan 300 or 360 series reader, perform the following steps:

WARNING: Disconnect the DataMan reader from power before continuing.

CAUTION: Do not leave the image sensor exposed to the environment.

Note: The following steps describe service procedures for both the DataMan 300 and the 360 readers, but the
images show only the DataMan 360.

1. Remove and retain the four screws at the corners of the front cover.

2. Remove the front cover. The first image shows a reader with a liquid lens attached to the 10.3 mm lens. The
second image shows a reader with a 10.3 mm lens only.

3. If you have a liquid lens module attached to your 10.3 mm lens, carefully disconnect the liquid lens module cable.
If you only have a 10.3 mm lens inserted, jump to step 5 of this procedure.

WARNING: Do not pinch or pull the cable.

37
Mechanical Information

4. Loosen the lens locking ring and withdraw the module.

When reinstalling the module, observe the following precautions:


l Make sure that the liquid lens cable is not pinched, pulled or crimped during installation.
5. Loosen the locking ring and withdraw the lens.

When reattaching the front cover, tighten the screws in


the sequence shown below and observe a torque limit
of 9 N-cm (0.8 Lb-In).

Installing the 24 mm Liquid Lens Module


The possible hardware configurations using a 24 mm liquid lens module with a DataMan 300 or 360 series reader is the
following: DM3xx-system + DM300-LENS-24LL + DM360-HPIL-RE-01 / DM360-HPIL-RE-P-01.
To install a 24 mm liquid lens module of a DataMan 300 or 360 series reader, perform the following steps:

WARNING: Disconnect the DataMan reader from power before continuing.

CAUTION: Do not leave the image sensor exposed to the environment.

Note: The following steps describe service procedures for both the DataMan 300 and the 360 readers, but the
images show only the DataMan 360.

38
Mechanical Information

1. Attach the 24 mm Lens to the device by using the screw thread on the metal ring.

1. Insert the Liquid Lens cable into the connector of the device.

2. Attach the Liquid Lens to the front side of the 24mm Lens.

39
Mechanical Information

3. Place the DM360-HPIL-RE-01 or DM360-HPIL-RE-P-01 unit on the front of the device.

CUSTOMIZED CAPTIVE SCREW, PHILLIPS PAN HEAD, M3x28mm

Note: The minimum peak current capacity of the power supply for the device and the DM360-HPIL-RE-01 /
DM360-HPIL-RE-P-01 is 2 A per unit for the DataMan 300 and 2.2 A per unit for the DataMan 360.

Note: The DM360-HPIL-RE-01 or DM360-HPIL-RE-P-01 is also compatible with the 10.3 mm Liquid Lens.
For the 10.3 mm Liquid Lens, use CUSTOMIZED CAPTIVE SCREW, PHILLIPS PAN HEAD, M3x28mm.

4. Screw in the four screws.

Note: Use 0.2 Nm torque on the screws and tighten in sequence.

Replacing a 16 mm (SHD) Lens


To remove and replace a 16 mm (SHD) lens of a DataMan 300 or 360 series reader, perform the following steps:

WARNING: Disconnect the DataMan reader from power before continuing.

CAUTION: Do not leave the image sensor exposed to the environment.

Note: The following steps describe service procedures for both the DataMan 300 and the 360 readers, but the
images show only the DataMan 360.

40
Mechanical Information

1. Remove and retain the four screws at the corners of the front cover.

2. Remove the front cover.

3. Remove the rubber lens-locking cone from the lens.

4. Remove the lens.

When replacing the lens, observe the following precaution:


l Avoid rotating the lens when you insert it. Press the rubber lens-locking cone into the reader until it snaps
into place inside the C-mount threads and around the nose of the 16 mm lens.
When reattaching the front cover, tighten the screws in the sequence shown and observe a torque limit of 9 N-cm
(0.8 Lb-In).

41
Mechanical Information

Replacing a C-Mount Lens


To remove and replace a C-Mount lens of a DataMan 300 or 360 series reader, perform the following steps:

WARNING: Disconnect the DataMan reader from power before continuing.

CAUTION: Do not leave the image sensor exposed to the environment.

Note: The following steps describe service procedures for both the DataMan 300 and the 360 readers, but the
images show only the DataMan 360.

1. Remove the front cover.

Note: Do not unscrew the front-most part of the nose of the cover to avoid risking the glass lens falling out.

2. Remove the screws from the C-mount cover base.

3. Remove the C-Mount cover base.

4. Remove the lens.

When replacing the lens, observe the following precaution:

l When you attach the front cover, align the peg on the reader and the slot on the cover so that the cover locks in
place.

When reattaching the C-mount cover base, tighten the screws in the sequence shown and observe a torque limit of 9 N-
cm (0.8 Lb-In).

42
Mechanical Information

DataMan 370 and 470 Series Service Procedures


You can choose between a variety of different (High Speed) Liquid Lenses and C-Mount lens options to be installed on
your DataMan 370 or 470 series reader.

Assembly Instructions
DataMan 374 + HPIL Installing the Liquid Lens Module with High Power
Integrated Light (HPIL) on page 43

DataMan 474 + HPIL

DataMan 37x + HPIA Installing a Lens with High Power Illumination Accessory
(HPIA) on page 47

DataMan 47x + HPIA

DataMan 37x + HPIT Installing High Power Integrated Torch (HPIT) on page 49

DataMan 47x + HPIT

DataMan 37x + C-Mount Installing a C-Mount Lens on page 51

DataMan 47x + C-Mount

The following sections describe service procedures for both the DataMan 370 and the 470 series readers, but the
images show only the DataMan 370.

Installing the Liquid Lens Module with High Power Integrated Light (HPIL)
For possible hardware configurations using a liquid lens module with HPIL for DataMan 374 or 474, see the DataMan
370 Series Reference Manual and the DataMan 470 Series Reference Manual, respectively.
Tools needed:

l Wrench for lens locking ring (10.3 mm LL only - delivered by Cognex with Liquid Lens module)
l Phillips screwdriver

To install a 10.3 mm or a 24 mm liquid lens module of a DataMan 374 or 474 reader, perform the following steps:

WARNING: Disconnect the DataMan reader from power before continuing.

CAUTION: Do not leave the image sensor exposed to the environment.

43
Mechanical Information

Note: The following steps describe service procedures for both the DataMan 374 and the 474 readers, but the
images show only the DataMan 374.

1. Remove the adhesive protective film covering the threaded lens opening.

2. Attach the 24 mm Lens to the device by using the screw thread on the metal ring.

Insert an S-Mount adapter, thread the 10.3 mm Lens into the reader, and tighten the locking ring.

44
Mechanical Information

3. Insert the Liquid Lens cable into the connector of the reader.

WARNING: To avoid equipment damage, the cables must be routed as shown in the figure.

4. Attach the Liquid Lens to the front side of the 24 mm Lens.

In case of the 10.3 mm Lens, attach the liquid lens module onto the nose of the lens.

45
Mechanical Information

5. Place the HPIL unit on the front of the device.

CUSTOMIZED CAPTIVE SCREW, PHILLIPS PAN HEAD, M3x28 mm


6. Screw in the four screws.

Note: Use 0.2 Nm torque on the screws and tighten in sequence.

Replacing a 10.3 mm Lens


To remove and replace a 10.3 mm lens of a DataMan 370 or 470 series reader, perform the following steps:

WARNING: Disconnect the DataMan reader from power before continuing.

CAUTION: Do not leave the image sensor exposed to the environment.

Note: The following steps describe service procedures for both the DataMan 370 and the 470 series readers, but
the images show only the DataMan 470.

1. If you have a liquid lens module attached to your 10.3 mm lens, carefully disconnect the liquid lens module cable.
If you only have a 10.3 mm lens inserted, jump to step 3 of this procedure.

WARNING: Do not pinch or pull the cable.

46
Mechanical Information

2. Loosen the lens locking ring and withdraw the module.

When reinstalling the module, observe the following precautions:


l Make sure that the liquid lens cable is not pinched, pulled or crimped during installation.

3. Loosen the locking ring and withdraw the lens.

Installing a Lens with High Power Illumination Accessory (HPIA)


For a list of lenses compatible with the HPIA, see the DataMan 370 Series Reference Manual and the DataMan 470
Series Reference Manual, respectively.
Tools needed:

l Wrench for lens locking ring (10.3 mm LL only - delivered by Cognex with Liquid Lens module)
l Phillips screwdriver (PH0)
l Phillips screwdriver (PH1)

Note: The following steps describe service procedures for both the DataMan 370 and the 470 series readers, but
the images show only the DataMan 370.

To install a lens module of a DataMan 370 or 470 reader with HPIA, perform the following steps:

1. To install the lens, see:


l Installing a C-Mount Lens on page 51
l Installing the Liquid Lens Module with High Power Integrated Light (HPIL) on page 43
l Installing High Power Integrated Torch (HPIT) on page 49

47
Mechanical Information

2. Place the HPIA on the front of the reader.

3. Insert the lens cover mounting plate into the HPIA and secure them to the reader using the four M3 screws.

M3 x 16 mm screws

Note: Use a 3 mm hex wrench to torque the screws to 0.34 Nm (3 in-lb). Tighten in sequence.

48
Mechanical Information

4. Attach the C-mount lens cover to the front of the plate and secure it using the four M2 screws.

Note: For lenses that do not fit under the DM500-CMTLC-000 lens cover, you are required to use the
DM500-LNSEXT-000 lens cover extension.

M2 x 5 mm screws

Note: Use a Phillips Screwdriver (PH0) to torque the screws to 0.09 Nm (0.8 in-lb). Tighten in sequence.

Installing High Power Integrated Torch (HPIT)


For possible hardware configurations using HPIT with a DataMan 370 or 470 series reader, see the DataMan 370 Series
Reference Manual and the DataMan 470 Series Reference Manual, respectively.
Tools needed:

l 2 mm Allen wrench
l Phillips screwdriver (PH0)

Note: The following steps describe service procedures for both the DataMan 370 and the 470 series readers, but
the images show only the DataMan 370.

Perform the following steps to mount the HPIT to your DataMan 370 or 470 series reader:

1. Remove the adhesive protective film covering the threaded lens opening.

2. Add the small PCB into the light connector.

49
Mechanical Information

3. Attach the DM470 HPIT adapter plate.

M3 x 6 mm screws

Note: Use a 2 mm hex wrench to torque the screws to 0.34 Nm (3 in-lb). Tighten in sequence.

4. Attach the lens module and fix the lens with the captive screws.

Note: Use a Phillips screwdriver (PH0) to torque the screws to 0,08 Nm (0.7 in-lb). Tighten in sequence.
l Do not push or pull the lens at its barrel – push or pull on the metal housing.
l Be careful not to touch the gear ring with the screwdriver.

5. Attach the light module.

50
Mechanical Information

M3 x 6.35 mm captive screws

Note: Use a 2 mm hex wrench to torque the captive screws to 0.34 Nm (3 in-lb). Tighten in sequence.

6. Attach the front cover.

M3 x 12mm captive screws

Note: Use a Phillips Screwdriver (PH0) to torque the captive screws to 0.31 Nm (2.75 in-lb). Tighten in
sequence.

Note: Remove the adhesive protective film from the front cover after attaching it.

Installing a C-Mount Lens


Note: The following steps describe service procedures for both the DataMan 370 and the 470 series readers, but
the images show only the DataMan 370.

51
Mechanical Information

Possible hardware configurations using a C-Mount lens with a DataMan 370 or 470 series reader:

System Lens Lens Part Number C-Mount Cover Short C-Mount Cover
(DM300-CMCOV) (DM300-CMCOV-SH)
DM370 12 mm F8 LEC-CFF12-F8
DM470
16 mm F8 LEC-CFF16-F8

25 mm F8 LEC-CFF25-F8

35 mm F8 LEC-CFF35-F8

40 mm F8 LEC-CFF40-F8

50 mm F8 LEC-CFF50-F8

1. Remove the adhesive protective film.

2. Thread the lens into the reader.

3. Place the reader at the desired working distance from focus target.

Note: Make sure to set focus for the reader before fitting the lens cover.

a. Connect the reader to the DataMan Setup Tool.


b. Navigate to the Optimize Image pane, and on the Basic tab, click the triangle on the Live button to
access the drop-down list, and check the Focus Feedback option.
c. Use the DataMan Focus Target template, available through the Windows Start menu or the DataMan
Setup Tool Help menu, to align the edge of the reader body to the line marked with the target distance
used in your application.

52
Mechanical Information

d. Adjust focus for maximum sharpness. Enhance image quality in the DataMan Setup Tool for better
guidance.

4. Attach the C-Mount cover base.

53
Mechanical Information

5. Add the screws to the C-Mount cover base.

PHILLIPS PAN HEAD M2 X 6 mm

Note:
Tighten in sequence. Torque limit: 9 Ncm (0.8 in-lbs).

6. Attach the front cover.

Note: Do not unscrew the front-most part of the nose of the cover to avoid risking the glass lens falling out.

7. Align the peg on the reader and the slot on the cover so that the cover locks in place.

54
Mechanical Information

Replacing a C-Mount Lens


To remove and replace a C-Mount lens of a DataMan 370 or 470 series reader, perform the following steps:

WARNING: Disconnect the DataMan reader from power before continuing.

CAUTION: Do not leave the image sensor exposed to the environment.

Note: The following steps describe service procedures for both the DataMan 370 and the 470 series readers, but
the images show only the DataMan 470.

1. Remove the front cover.

Note: Do not unscrew the front-most part of the nose of the cover to avoid risking the glass lens falling out.

2. Remove the screws from the C-mount cover base.

3. Remove the C-Mount cover base.

4. Remove the lens.

When replacing the lens, observe the following precaution:

l When you attach the front cover, align the peg on the reader and the slot on the cover so that the cover locks in
place.

55
Mechanical Information

DataMan 503 Service Procedures


Installing a C-Mount Lens
DataMan 503 ships with no lens installed. You must install a standard C-mount lens before using your reader.
For reading distances and field of view charts, see the DataMan Fixed-Mount Reference, available through the Windows
Start menu or the DataMan Setup Tool Help menu.

1. Remove the front cover, if attached, and lens cover.

Note: Remove the protective cover from the lens mount.

CAUTION: Do not leave the DataMan sensor exposed to the environment!

2. Insert and thread lens into the reader.

3. Align the peg on the reader and the slot on the cover, and re-attach it.

56
Mechanical Information

4. Lock the cover in place.

Maintenance

Replacing the SD Card


The DataMan 370 and 470 series readers are equipped with a Micro SD card slot and an SD card is pre-installed for
saving backup and configuration files. In the unlikely event when a reader breaks down and needs to be replaced,
complete the following steps to clone the reader by replacing the SD card.

Note: The reader supports SD cards with a maximum capacity of 8 GB, formatted with a FAT32 file system.

CAUTION:
l Hot-plugging the SD card is not supported and may damage the SD card and/or lead to unexpected
behavior. The SD card has to be present already at the boot phase. Do not pull out the SD card during
operation.
l Observe ESD precautions when installing or removing an SD card or other accessories.

1. Disconnect the reader from the power source.


2. Unscrew the screw(s) in the Micro SD card cover to open the card slot.
3. Remove the existing SD card from the Micro SD card slot.
4. Insert the SD card from the broken reader into the Micro SD card slot to clone the old reader. Ensure the card is
properly oriented.

57
Mechanical Information

5. Replace the SD card cover and reinsert the screw(s).

Note: Torque the screw(s) to 0.18 Nm (25 in-oz). Tighten in sequence.

DataMan 370 DataMan 470

6. Restore power to the reader.

58
Mechanical Information

Mounting Requirements
The DataMan 150, 260, 300, 360, 370, 470, and 503 series readers provide four threaded attachment points, located as
shown in the previous sections:

l DataMan 70 Series Reader Dimensions


l DataMan 150 Series Reader Dimensions
l DataMan 260 Series Reader Dimensions
l DataMan 300 Series Reader Dimensions
l DataMan 360 Series Reader Dimensions
l DataMan 370 Series Reader Dimensions

l DataMan 470 Series Reader Dimensions


l DataMan 503 Reader Dimensions

The attachment points have the following characteristics:

l M3 thread
l 5 mm thread depth
l 9 N-cm (0.8 Lb-In) maximum torque

CAUTION: Use all four attachment points when mounting your DataMan reader.

Mounting Your DataMan 70 Reader


Mounting the DataMan 70 at a slight angle (15°) can reduce reflections and improve reader performance. Having a
recess for screw heads on the top and the bottom, the DataMan 70 allows for upside down mounting. Recommended
fasteners and nuts:

59
Mechanical Information

l Fastener: 2 x DIN 7985 M3x30 mm or DIN 912/ISO 4762 M3x30 mm


l Nut: 2 x DIN 985 M3

Mounting Your DataMan 150 and 260 Reader


Mounting the DataMan 150 and the DataMan 260 at a slight angle (15°) can reduce reflections and improve reader
performance.

60
Mechanical Information

Right-Angle Configuration

Changing Orientation
Perform the following steps to change between in-line and right-angle configuration.

Note:
l Switching between in-line and right-angle configuration is recommended only up to 10 times in the lifetime
of your DataMan device.
l Disconnect the DataMan device from power before changing the orientation.

WARNING: Make sure that no electrostatic charges are applied to the PCB. (For example, wear ESD shoes.) If the
main module is separated from the I/O connector module, take care to assemble them correctly. Otherwise, the IP
rating can be compromised.

61
Mechanical Information

1. Carefully remove the screw covers, threaded nuts and washers.

DataMan 150 DataMan 260

M2 Torx 10 CAP NUT

DIN 6798A M2 LOCKWASHER


2. Detach the main module and the I/O connector module by firmly pulling them apart.

DataMan 150 DataMan 260

3. Change the orientation.

Note: Make sure that the gasket is properly seated on the main module. Ensure that the flat gasket side is
facing away from the module

DataMan 150 DataMan 260

Place the bottom edge of the gasket onto the underside of the main module. Press on the top edge to fully seat
the gasket:

62
Mechanical Information

Note: The flat side of the gasket (marked as "Front" in the image above) has to face outside.

WARNING: Do not touch any electrical component.

3. Reattach the I/O connector module to the main module.

DataMan 150 DataMan 260

4. Reinstall the washers and loosely fasten the modules together with the two T10 cap nuts, but do not tighten.

DataMan 150 DataMan 260

63
Mechanical Information

5. After each cap nut has been fastened, torque to 0.12 Nm (1.06 in-lb) and reinstall the screw covers.

Note: There are unique left and right screw covers. Take care to attach them correctly.

DataMan 150 DataMan 260

Mounting Your DataMan 370 and 470 Reader


The accessory mounting bracket kit (DMBK-370-MNT for the DataMan 370 and DMBK-470-MNT for the DataMan 470)
includes the mounting bracket, four Phillips flat head M3 DIN 965 screws for attaching the reader to the mounting bracket
and four M6 DIN 912 (ISO 4762) screws for securing the bracket to a mounting surface.

CAUTION: It is recommended the reader be grounded, either by mounting the reader to a fixture that is electrically
grounded or by attaching a wire from the reader’s mounting fixture to frame ground or Earth ground. If a ground wire
is used, it should be attached to one of the four mounting points on the back plate of the reader; not to the mounting
points on the front of the reader.

64
Mechanical Information

1. Align the holes on the mounting surface with the mounting holes on the reader.

DataMan 370 DataMan 470

2. Insert the M3x5, DIN 965 (4x) screws into the mounting holes.

Note: Use a 2.5 mm hex wrench to torque the captive screws to 0.60 Nm (5 in-lb). Tighten in sequence.

DataMan 370 DataMan 470

3. Align the mounting holes on the mounting plate with the M6 drop-in nuts and the M6, DIN 912 (ISO 4762) socket
head screw in the mounting surface.

65
Mechanical Information

4. Attach the mounting bracket to the mounting surface using M6, DIN 912 (ISO 4762) socket head screws with M6
drop-in nuts for OTS aluminum profiles.

Mounting the DataMan reader at a slight angle (15°) can reduce reflections and improve performance.

DataMan 370 DataMan 470

66
Mechanical Information

Grounding
If you want to mount a DataMan fixed-mount reader to a bracket or a plate, make sure that those parts make a proper
connection to ground (PE). Cognex recommends that you use lock-washers between the mounting screws and the
bracket to ensure permanent ground conductivity.

If you want to mount your reader to an electrically isolated bracket, the reader needs to be individually grounded.
For this purpose, Cognex recommends that you connect at least one of the 4 mounting holes on the bottom of the device
with a minimum 22 gauge grounding wire to system ground (PE). Use lock-washers to ensure a permanent and robust
connection.

67
Mechanical Information

Thermal and Environmental Requirements


See the following table for thermal and environmental requirements:

Operating temperature 0 ºC — 40 ºC (32 ºF — 104 ºF)


Storage temperature -10 ºC — 60 ºC (-14 ºF — 140 ºF)
Maximum humidity 95% (non-condensing)

DataMan 50, 150, 260, 300, 360, and 503 IP Rating


The DataMan 50, 150, 260, 300, 360 series and 503 readers provide IP65 protection against dust and water intrusion. In
order to meet this rating, the following conditions must be met:

l All connectors must have cables connected or be sealed with protective plugs.
l The reader front cover and lens cover must be correctly installed.

l The requirements for temperature, vibration, and shock must be met.

DataMan 60 and 70 IP Rating


The DataMan 60 and 70 readers provide IP40 protection against dust and water intrusion. In order to meet this rating, the
following conditions must be met:

l All connectors must have cables connected or be sealed with protective plugs.
l The reader front cover and lens cover must be correctly installed.
l The requirements for temperature, vibration, and shock must be met.

DataMan 370 and 470 IP Rating


The DataMan 370 and 470 series readers provide IP67 protection against dust and water intrusion. In order to meet this
rating, the following conditions must be met:

68
Mechanical Information

l All connectors must have cables connected or be sealed with protective plugs.
l The reader front cover and lens cover must be correctly installed.
l The requirements for temperature, vibration, and shock must be met.

69
Electrical Information

Electrical Information
DataMan 50 and 60 Discrete I/O Connector
The I/O cable provides access to trigger and high-speed outputs. Unused wires can be clipped short or tied back using a
tie made of non-conductive material. For RS-232, use the Power Supply return path for ground.

Note: GND (Pin 4) is connected to the reader housing, cable shield, and DB15 shell.

PIN Color Signal


1 Brown Reserved
2 Green TxD
3 Green/Black RxD
4 Red and Brown/White GND
5 Red/Black DC+ (system power, 5-24 VDC)
6 Blue RTS
7 Blue/White Output-0
8 White Input-0
9 White/Black Input-1
10 Light Blue CTS
11 Light Blue/Black Output-1
12 Light Blue/Yellow Output-Common
This is a male connector/plug. 13 Light Blue/Green Output-Strobe
14 Yellow Reserved
15 Yellow/Black Reserved

DataMan 50 and 60 USB & Flying Leads I/O Cable


You can connect a cable with USB & flying leads (DM-USBIO-00) to the cable that is attached to the device. The
following table shows the pinout and color description of the flying leads.

PIN Color Signal

4 Black GND

7 Blue/White Output-0

8 White Input-0

9 White/Black Input-1

11 Light Blue/Black Output-1

12 Light Blue/Yellow Output-Common

13 Light Blue/Green Output-Strobe

70
Electrical Information

DataMan 50 and 60 RS-232 & Flying Leads I/O Cable


You can connect a cable with RS-232 & flying leads (DM-RS232IO-00) to the cable that is attached to the device. The
following table shows the pinout and color description of the flying leads.

PIN Color Signal

4 Black GND

5 Brown/White VDC

7 Blue/White Output-0

8 White Input-0

9 White/Black Input-1

11 Light Blue/Black Output-1

12 Light Blue/Yellow Output-Common

13 Light Blue/Green Output-Strobe

DataMan 50 and 60 Flying Leads Cable


You can connect a cable with flying leads (DM50-PWRIO-05) to the cable that is attached to the device. The following
table shows the pinout and color description of the flying leads.

This is a female connector/socket.


IN Color Signal
2 Green TxD
3 Green/Black RxD
4 Red GND
5 Brown/White DC+ (system power, 5-24 VDC)
6 Blue RTS
7 Blue/White Output-0
8 White Input-0
9 White/Black Input-1
10 Light Blue CTS
11 Light Blue/Black Output-1
12 Light Blue/Yellow Output-Common
13 Light Blue/Green Output-Strobe

71
Electrical Information

DataMan 50 and 60 Digital Input Lines


Inputs are not galvanic isolated but need to be referenced to ground.

72
Electrical Information

DataMan 50 and 60 External Wiring Examples: Digital Input


Lines
The following figures show external wiring examples for digital input lines for the DataMan 50. The DataMan 60 has the
same characteristics.

73
Electrical Information

DataMan 50 and 60 Digital Output Lines


The digital outputs can be used as either NPN (pull-down) or PNP (pull-up) lines. For NPN lines, the external load
should be connected between the output and the positive supply voltage (<26 V). The outputs pull down to less than 3 V
when ON, which causes current to flow through the load. When the outputs are OFF, no current flows through the load.
Outputs are not galvanic isolated but need to be referenced to ground.

NPN (pull down) output type characteristics


Applied voltage 26 VDC or less
Residual voltage 0.85 V or less
Maximum sink current 25 mA
Short-circuit current 100 mA or less
Short-circuit protection multifuse – 50 mA

PNP (pull up) output type characteristics


Applied voltage 26 VDC or less
Residual voltage 0.8 V or less
Maximum sink current 25 mA
Short-circuit current 50 mA or less
Short-circuit protection multifuse – 50 mA

Note: For information about the Illumination Strobe Output, see DataMan 50 and 60 Illumination Strobe Output on
page 129

74
Electrical Information

DataMan 50 and 60 External Wiring Examples: Digital Output


Lines
The following figures show external wiring examples for digital input lines for the DataMan 50. The DataMan 60 has the
same characteristics.

75
Electrical Information

DataMan 70 15 Pin Adapter Cable

P1 Pin Number Signal Name


1 Reserved
2 Reserved
3 Reserved
4 Reserved
5 Reserved
6 Ground
7 TXD
8 RXD
9 Reserved
10 Reserved
11 Adapter Power
12 CTS
13 RTS
14 External Trigger
15 External Illumination

76
Electrical Information

DataMan 70 9 Pin Adapter Cable


The following table shows the pinouts.

Pin Number Signal Name


1 Trigger
2 TXD Output TTL Only
3 RXD Input TTL Only
4 NC
5 Ground
6 +5 V Power
7 CTS Input TTL Only
8 RTS Output TTL Only
9 Beeper/Download

77
Electrical Information

DataMan 70 Serial IO Adapter (DMA-SERIALREST-ST)

This is a male connector/plug.


Pin Number Signal Name
1 Reserved
2 TxD
3 RxD
4 GND
5 DC+ (system power, 5-24 VDC)
6 NC
7 Output-0
8 Input-0
9 NC
10 NC
11 NC
12 Output-Common
13 NC
14 Reserved
15 Reserved

DataMan 150 USB Cable


The DataMan 150 is available with USB and RS-232 communication options.

The I/O module with USB has all signals on a SUB-D 15 connector with the following pinouts:

PIN Color Signal


1 Brown Reserved
2 Green TxD (RS-232)

78
Electrical Information

PIN Color Signal


3 Green/Black RxD (RS-232)
4 Red & Red/Black GND
5 Brown/White DC+ (system power, 5-24 VDC)
6 Blue RTS
7 Blue/White Output-0
8 White Input-0
9 White/Black Input-1
10 Light Blue CTS
11 Light Blue/Black Output-1
12 Light Blue/Yellow Output-Common
13 Light Blue/Green Input-Common
14 Yellow Reserved
15 Yellow/Black Reserved

Note: Pin numbers are shown for cable connector, not I/O module.

79
Electrical Information

DataMan 70 and 150 Discrete I/O Connector


You can connect a cable with USB & flying leads (DM-USBIO-00) to the cable that is attached to the device. The
following table shows the pinout and color description of the flying leads.

Note: GND (Pin 4) is connected to the reader housing, cable shield, and DB15 shell.

PIN Color Signal

4 Black GND

7 Blue/White Output-0

8 White Input-0

9 White/Black Input-1

11 Light Blue/Black Output-1

12 Light Blue/Yellow Output-Common

13 Light Blue/Green Input-Common

DataMan 70 and 150 RS-232 Cable


You can connect a cable with RS-232 & flying leads (DM-RS232IO-00) to the cable that is attached to the device. The
following table shows the pinout and color description of the flying leads.

PIN Color Signal

4 Black GND

5 Brown/White VDC

7 Blue/White Output-0

8 White Input-0

9 White/Black Input-1

11 Light Blue/Black Output-1

12 Light Blue/Yellow Output-Common

13 Light Blue/Green Input-Common

80
Electrical Information

DataMan 150 Flying Leads Cable


You can connect a cable with flying leads (DM50-PWRIO-05) to the cable that is attached to the device. The following
table shows the pinout and color description of the flying leads.

PIN Color Signal


2 Green TxD
3 Green/Black RxD
4 Red GND
5 Brown/White DC+ (system power, 5-24 VDC)
6 Blue RTS
7 Blue/White Output-0
8 White Input-0
9 White/Black Input-1
10 Light Blue CTS
11 Light Blue/Black Output-1
12 Light Blue/Yellow Output-Common
13 Light Blue/Green Input-Common

DataMan 150 USB Connections


When connected to a PC over USB, the DataMan 150 appears as a COM port.
You can connect your device to the computer in the following ways:

Connect directly to the PC: Connect to the PC through a basic I/O module:

If the reader is configured as an HID device and you want to return to USB serial, scan the USB serial connection code:

81
Electrical Information

Note: The DataMan PC software must be installed for this connection type.

DataMan 150 RS-232 Connections


You can connect the DataMan 150 reader to a PC or other device over a standard RS-232 serial connection.

Note: You must supply external power to use this connection type.

You can make a connection in the following ways:

Connect directly to the PC: Connect to the PC through a basic I/O module:

DataMan 150 Wiring the Basic I/O Module

82
Electrical Information

1. Power: 5-24 VDC, 2.5 W peak. Connect either ground pin to chassis ground.
2. Discrete output: Opto-isolated, current source or sink, depending on wiring; must connect logical ground to
common. Outputs are opto-isolated and protected against reverse polarity. Max current is 50 mA @ 24 VDC.
Output 1 is used for external illumination control by default.
3. Trigger input: Opto-isolated, polarity-independent, current source or sink; have reference to a separated
common signal. Work with ±15-30 V. Input 0 is dedicated trigger line.
4. Communication: RS-232 serial port and USB port.

Note: You must use a null modem cable when connecting the Basic I/O Module to a PC’s RS-232 serial port.

Output Wiring Example

83
Electrical Information

Input Wiring Example

DataMan 150 Digital Input Wiring Diagrams

Current Sink Configuration

Current Source Configuration

84
Electrical Information

PNP Configuration

NPN Configuration

Dataman 150 Digital Output Wiring Diagrams


The digital outputs can be used as either NPN (pull-down) or PNP (pull-up) lines. For NPN lines, the external load
should be connected between the output and the positive supply voltage (<26 V). The outputs pull down to less than 3 V
when ON, which causes current to flow through the load. When the outputs are OFF, no current flows through the load.

NPN (pull down) output type characteristics are the following:

Applied voltage 26 VDC or less


Residual voltage 0.85 V or less
Maximum sink current 100 mA
Overcurrent protection multifuse - 160 mA

PNP (pull up) output type characteristics are the following:

Output voltage range 26 VDC or less


Residual voltage 0.85 V or less
Maximum source current 100 mA
Overcurrent protection multifuse - 160 mA

85
Electrical Information

Sinking Outputs, Sourcing Inputs

Sinking Outputs, Sinking Inputs

86
Electrical Information

Electrical Information

DataMan 260 Discrete I/O Connector


The I/O breakout cable (CCBL-05-01) provides access to trigger and high-speed outputs. You can clip unused wires
short or use a tie made of non-conductive material to tie them back. For RS-232, use the Power Supply return path for
ground.
The figure on the left shows the plug on the device.

Signal: 24 VDC Ethernet Model

87
Electrical Information

Signal: PoE Ethernet Model

DataMan 260 Ethernet Cable


The Ethernet cable (CCB-84901-2001-05) provides Ethernet connection for network communications. The Ethernet
cable can be connected to a single device or provide connections to multiple devices via a network switch or router.

Note: Cables are sold separately.The wiring for this cable follows standard industrial Ethernet M12 specifications. It
differs from the 568B standard.

88
Electrical Information

X-coded to RJ45 Cable

P1 Pin Number Wire Color Signal Name P2 Pin Number


1 White/Orange TxRx A + 1
2 Orange TxRx A - 2
3 White/Green TxRx B + 3
4 Blue TxRx C + 8
5 White/Blue TxRx C - 7
6 Green TxRx B - 4
7 White/Brown TxRx D + 5
8 Brown TxRx D - 6

DataMan 150 and 260 Acquisition Triggering


The acquisition trigger input on the reader is opto-isolated.
To trigger from an NPN (pull-down) type photo-detector or PLC output, connect In 0 to +24 V and connect Common In to
the output of the detector. When the output turns on, it pulls Common In down to 0 V, turning the opto-coupler on.
To trigger from a PNP (pull-up) photo-detector or PLC output, connect In 0 to the output of the detector and connect
Common In to 0 V. When the output turns on, it pulls In 0 up to 24 V, turning the opto-coupler ON.

28 V maximum across input pins - Transition approximately 12 V (Min).

89
Electrical Information

DataMan 260 High-Speed Output Lines


The high-speed outputs can be used as either NPN (pull-down) or PNP (pull-up) lines.

Specification Description
Voltage 28 V maximum through external load
Current 50 mA maximum sink current
OFF state leakage current 100 µA
External load resistance 240 Ohms to 10K Ohms
Each line rated at a maximum 50 mA, protected against over-current, short circuits and
transients from switching inductive loads. High current inductive loads require external
protection diode.

For NPN lines, the external load should be connected between the output and the positive supply voltage (<28 V). The
outputs pull down to less than 3 VDC when ON, which causes current to flow through the load. When the outputs are
OFF, no current flows through the load.

For PNP lines, the external load should be connected between the output and the negative supply voltage (0 VDC).
When connected to a 24 VDC power supply, the outputs pull up greater than 21 VDC when ON, and current flows
through the load. When the outputs are OFF, no current flows through the load.

DataMan 260 High-Speed Output Wiring


To connect to an NPN-compatible PLC input, connect Output 0, Output 1, Output 2 or Output 3 directly to the PLC input.
When enabled, the output pulls the PLC input down to less than 3 VDC.

90
Electrical Information

To connect to a PNP-compatible PLC input, connect Output 0, Output 1, Output 2 or Output 3 directly to the PLC input.
When enabled, the output pulls the PLC input up to greater than 21 VDC.

To connect the high-speed outputs to a relay, LED or similar load, connect the negative side of the load to the output and
the positive side to +24 VDC. When the output switches on, the negative side of the load is pulled down to less than 3
VDC, and 24 VDC appears across the load. Use a protection diode for a large inductive load, with the anode connected
to the output and the cathode connected to +24 VDC.

Dataman 300 5m RS-232 Connection Cable (CCB-M12XDB9Y-05)


You can clip unused wires short or use a tie made of non-conductive material to tie them back.
The figure on the left shows the plug on the device.

91
Electrical Information

DataMan 300, 360, 370, and 470 Series Readers Discrete I/O
Connector
The Breakout cable provides access to trigger and high-speed outputs. You can clip unused wires short or use a tie
made of non-conductive material to tie them back. For RS-232, use the Power Supply return path for ground.

5m Breakout Cable (CCBL-05-01)


The figure on the left shows the plug on the device.

92
Electrical Information

5m Breakout Cable (CCB-M12x12Fy-xx)


The figure on the left shows the plug on the device.

93
Electrical Information

15m Breakout Cable (CCB-PWRIO-XX)


The figure on the left shows the plug on the device.

94
Electrical Information

DataMan 300, 360, 370, and 470 Series Readers External Light
Control
The External Light cable is used to connect to an external lighting device, providing power and strobe control.
A 4-pin cable is provided for the external light control. The drawing on the left shows the socket on the device. This
socket does not work if the external light is connected to one of the outputs on the breakout cable.

Output Voltage 24 V+/-5% (20 V – 27 V) Voltage may drop depending on the length of the cable.
Max avg Current 1A
Peak Operating Current 1.5 A up to 100 µs, avg to not exceed 1 A
Max Inrush Current 5 A not exceeding 0.4 As

DataMan 300, 360, 370, and 470 Series Readers Power


Requirements
For the DataMan 300, 360, 370, and 470 series readers, 24 VDC power is provided through the I/O+RS232+24 V cable.
Maximum power consumption is 5 W (internal illumination) or 18 W (internal and external lights).

DataMan 300, 360, 370, and 470 Series and DataMan 503
Readers Acquisition Triggering
The acquisition trigger input on the reader is opto-isolated.
To trigger from an NPN (pull-down) type photo-detector or PLC output, connect Common In to +24 VDC and connect In
to the output of the detector. When the output turns on, it pulls In down to 0 VDC, turning the opto-coupler on.
To trigger from an PNP (pull-up) photo-detector or PLC output, connect In 0 to the output of the detector and connect
Common In to 0 VDC. When the output turns on, it pulls In 0 up to 24 VDC, turning the opto-coupler ON.

95
Electrical Information

The DataMan 300, 360, 370, and 470 series readers support 26.4 V maximum across input pins – Transition
approximately 12 V (Min.). The DataMan 503 reader supports 28 V maximum across input pins - Transition
approximately 12 V (Min.).

DataMan 300, 360, 370, and 470 Series, and DataMan 503
Readers High-Speed Output Lines
The high-speed outputs can be used as either NPN (pull-down) or PNP (pull-up) lines.

Specification DataMan 300, 360, 370, and 470 Series Readers, and DataMan 503
Reader Description
Voltage 26.4 V maximum through external load
Current 50 mA maximum sink current
OFF state leakage current 100 µA
External load resistance 240 Ohms to 10K Ohms
Each line rated at a maximum 50 mA, protected against over-current, short
circuits and transients from switching inductive loads. High current inductive
loads require external protection diode.

For NPN lines, the external load should be connected between the output and the positive supply voltage (<26.4 VDC).
The outputs pull down to less than 3 VDC when ON, which causes current to flow through the load. When the outputs are
OFF, no current flows through the load.

For PNP lines, the external load should be connected between the output and the negative supply voltage (0 VDC).
When connected to a 24 VDC power supply, the outputs pull up greater than 21 VDC when ON, and current flows
through the load. When the outputs are OFF, no current flows through the load.

96
Electrical Information

97
Electrical Information

DataMan 300, 360, 370, and 470 Series Readers High-Speed


Output Wiring
To connect to an NPN-compatible PLC input, connect Output 0, Output 1, Output 2, or Output 3 directly to the PLC input.
When enabled, the output pulls the PLC input down to less than 3 VDC.

To connect to a PNP-compatible PLC input, connect Output 0, Output 1, Output 2 or Output 3 directly to the PLC input.
When enabled, the output pulls the PLC input up to greater than 21 VDC.

To connect the high-speed outputs to a relay, LED or similar load, connect the negative side of the load to the output and
the positive side to +24 VDC. When the output switches on, the negative side of the load is pulled down to less than 3
VDC, and 24 appears across the load. Use a protection diode for a large inductive load, with the anode connected to the
output and the cathode connected to +24 VDC.

98
Electrical Information

DataMan 300 and 503 Ethernet M12 to RJ45 Cable (CCB-84901-


y00x-xx)
The Ethernet cable provides Ethernet connection for network communications. The Ethernet cable can be connected to a
single device or provide connections to multiple devices via a network switch or router.

P1 Pin# Signal Name Wire Color P2 Pin#


6 TPO+ White/Orange 1
4 TPO- Orange 2
5 TPI+ White/Green 3
7 TRMA Blue 4
1 TRMB White/Blue 5
8 TPI- Green 6
2 TRMC White/Brown 7
3 TRMD Brown 8

99
Electrical Information

DataMan 503 Discrete I/O Connector

5 m Breakout Cable (CCBL-05-01)


The Breakout cable provides access to trigger and high-speed outputs.You can clip unused wires short or use a tie
made of non-conductive material to tie them back.
The figure on the left shows the plug on the device.

DataMan 503 RS-232 Serial Connector


The RS-232 cable (CCB-M8X4.xx) provides an optional connection between the reader and your PC.

100
Electrical Information

DataMan 503 External Light Control


A 4-pin cable (CCB-M12x4MS) is provided for the external light control.
The drawing on the left shows the socket on the device. This socket does not work if the external light is connected to
one of the outputs on the I/O cable.

Current load: average: 500 mA, peak: 1 A (max. 100 µs).

Note: This socket does not work if the external light is connected to one of the outputs on the I/O cable.

DataMan 503 High-Speed Output Wiring


To connect to an NPN-compatible PLC input, connect Output 0, Output 1, Output 2, or Output 3 directly to the PLC input.
When enabled, the output pulls the PLC input down to less than 3 VDC.

To connect to a PNP-compatible PLC input, connect Output 0 or Output 1 directly to the PLC input. When enabled, the
output pulls the PLC input up to greater than 21 VDC.

101
Electrical Information

To connect the high-speed outputs to a relay, LED or similar load, connect the negative side of the load to the output and
the positive side to +24 VDC. When the output switches on, the negative side of the load is pulled down to less than 3
VDC, and 24 appears across the load. Use a protection diode for a large inductive load, with the anode connected to the
output and the cathode connected to +24 VDC.

DataMan 503 Power Requirements


For the DataMan 503 readers, 24 VDC power is provided through the I/O+RS232+24 V cable. Maximum power
consumption is 13 W (High Power Lighting Module).

102
Electrical Information

Connecting the Encoder to a DataMan


Encoder is supported on the following DataMan devices and with the following conditions:

DM50, DM60, DM70, DM150 unidirectional One input counts encoder ticks
DM260, DM300, DM503 bidirectional • One input counts encoder ticks
• Second input for direction information
DM360 bidirectional 2 inputs for quadrature modulated signals

The DataMan 370 and DataMan 470 series readers are configurable to support all encoder modes listed above.
The encoder has four wires. The color coding of the wires is the following:

Wire Color Signal Name


Red +24 VDC
Black common- can be connected to either +24 VDC (NPN) or ground (PNP)
White the output connected to the input line of the DataMan reader
Bare ground

According to the speed of the line, set the number of pulses per revolution on the wheel by using the switches on the
encoder (for more information, see the encoder documentation). The number of pulses, however, must not exceed 150
Hz, except for the DataMan 370 and DataMan 470 series readers, which support pulse frequency up to 50 kHz.
In the DataMan Setup Tool, configure the use of your DataMan reader with the encoder in the Pulse Encoder tab of the
Inputs/Outputs pane.

103
Optics and Lighting

Optics and Lighting


This section contains information about the image formation components of the DataMan 50, 60, 70, 150, 260, 503 and
DataMan 300, 360, 370, and 470 series readers.

DataMan 50 and 60 Reading Distances and Field of View


The following chart shows the horizontal field of view for the DataMan 50 and 60 at a range of working distances,
together with the supported range of reading distances at 45 mm focus position.

This chart shows the supported range of reading distances at 70 mm focus position.

104
Optics and Lighting

This chart shows the supported range of reading distances at 110 mm focus position.

The following table shows the Field of View widths at various distances.

Distances in mm DM50/DM60
45 36
70 56
110 80

105
Optics and Lighting

DataMan 70, 150 and 260 Reading Distances and Field of View
DataMan 70, 150 and 260 Readers with a 6.2 mm Lens
Short Range (Focused to 105 mm)
The following tables show the field of view (FoV) widths of the 6.2 mm lens focused to 105 mm at various distances.
DM70, DM150 or DM260

Distances in mm 2D min. code 1D min. code


40 4 MIL 4 MIL
65 5 MIL 4 MIL
105 10 MIL 6 MIL

DM72, DM152 or DM262

Distances in mm 2D min. code 1D min. code


40 3 MIL 2 MIL
65 4 MIL 2 MIL
105 7 MIL 5 MIL

The following maps show the field of view (FoV) of the DataMan 70, DataMan 150 or DataMan 260 readers with a 6.2
mm lens. The horizontal and vertical field of view is shown for working distances of 40 mm, 65 mm and 105 mm.
DM70, DM150 or DM260 + 6.2 mm Lens

106
Optics and Lighting

DM72, DM152 or DM262 + 6.2 mm Lens

Long Range (Focused to 190 mm)


The following tables show the FoV widths of the 6.2 mm lens focused to 190 mm at various distances.
DM150 or DM260

Distances in mm 2D min. code 1D min. code


150 12 MIL 6 MIL
190 15 MIL 10 MIL
225 18 MIL 10 MIL
375 30 MIL 15 MIL
500 35 MIL 20 MIL
1m - 35 MIL

DM152 or DM262

Distances in mm 2D min. code 1D min. code


150 10 MIL 5 MIL
190 12 MIL 6 MIL
225 15 MIL 6 MIL
375 20 MIL 10 MIL
500 25 MIL 15 MIL
1m - 30 MIL

107
Optics and Lighting

The following maps show the field of view (FoV) of the DataMan 150 or DataMan 260 readers with a 6.2 mm lens.
The horizontal and vertical field of view is shown for working distances of 150 mm, 190 mm, 225 mm, 375 mm and 500
mm.
DM150 or DM260 + 6.2 mm Lens

DM152 or DM262 + 6.2 mm Lens

108
Optics and Lighting

DataMan 150 or DataMan 260 Readers with a 16 mm Lens


The following tables show the field of view (FoV) widths of the 16 mm lens at various distances.
DM150 or DM260

Distances in mm 2D min. code 1D min. code


80 3 MIL 2 MIL
150 5 MIL 3 MIL
190 6 MIL 4 MIL
225 7 MIL 4 MIL
375 12 MIL 5 MIL
500 15 MIL 10 MIL
1m 25 MIL 15 MIL

DM152 or DM262

Distances in mm 2D min. code 1D min. code


80 2 MIL 2 MIL
150 3 MIL 2 MIL
190 4 MIL 2 MIL
225 4 MIL 3 MIL
375 7 MIL 4 MIL
500 10 MIL 6 MIL
1m 20 MIL 15 MIL

The following maps show the FoV of the DataMan 150/260 and DataMan 152/262 readers with a 16 mm lens. The
horizontal and vertical field of view is shown for working distances of 80 mm, 150 mm, 225 mm, 375 mm, 500 mm and
1000 mm.
DM150 or DM260 + 16 mm Lens

109
Optics and Lighting

DM152 or DM262 + 16 mm Lens

110
Optics and Lighting

DataMan 300 and 360 Series Readers Reading Distances and


Field of View
The DataMan 300 and 360 series readers: DataMan 300/360, DataMan 302/362, and DataMan 303/363 have different
fields of view because of the different regions of the sensor used by each reader.

Scan Map for DataMan 300 and 360 Series Readers Using a 10.3 mm Lens
The map below shows the field of view of the DataMan 300/360, DataMan 302/362 and DataMan 303/363 readers with a
10.3 mm lens (with or without a liquid lens).
The FoV values are shown as follows:

l outer: DM302/362, DM303/363


l inner: DM300/360

The reading distances for the DM300/360 and DM302/362 readers are the same. The DM303/363 features a higher
resolution and more pixels in about the same sensor size.

The following table shows the Field of View widths in mm at various distances.

Distances in mm DM300, DM360 DM302/303, DM362/363


50 26 42
100 46 74
150 66 106
250 106 171
500 207 332

111
Optics and Lighting

Scan Map for DataMan 300 and 360 Series Readers Using a 16 mm Lens
This map shows the field of view of the DataMan 300/360, DataMan 302/362 and DataMan 303/363 readers with a 16
mm lens.
The FoV values are shown as follows:

l outer: DM302/362, DM303/363


l inner: DM300/360

The reading distances for the DM300/360 and DM302/362 readers are the same. The DM303/363 features a higher
resolution and more pixels in about the same sensor size.
To make sure that your DM303/363 reader is able to decode at the minimum reading distances, use the reader in
combination with the extension kit or without the front cover.

The following table shows the Field of View widths in mm at various distances.

Distances in mm DM300, DM360 DM302/303, DM362/363


50 13 20
100 25 40
150 38 60
250 63 101
500 125 202

112
Optics and Lighting

Scan Map for DataMan 300 and 360 Series Readers Using a 19 mm Lens
This map shows the field of view of the DataMan 300/360, DataMan 302/362 and DataMan 303/363 readers with a 19
mm lens (with or without a liquid lens).
The FoV values are shown as follows:

l outer: DM302/362, DM303/363


l inner: DM300/360

The reading distances for the DM300/360 and DM302/362 readers are the same. The DM303/363 features a higher
resolution and more pixels in about the same sensor size.
To make sure that your DM303/363 reader is able to decode at the minimum reading distances, use the reader in
combination with the extension kit or without the front cover.

The following table shows the Field of View widths in mm at various distances.

Distances in mm DM300, DM360 DM302/303, DM362/363


50 11 17
100 22 34
150 33 52
250 56 86
500 111 172

113
Optics and Lighting

Scan Map for DataMan 300 and 360 Series Readers Using a 24 mm Lens
with Liquid Lens
The maps in this section show the field of view of the DataMan 300/360, DataMan 302/362, and DataMan 303/363
readers with a 24 mm lens with a liquid lens and DM360-HPIL-RE-01 or DM360-HPIL-RE-P-01 cover.
The FoV values are shown as follows:

l outer: DM303/DM363
l middle: DM302/DM362
l inner: DM300/DM360

The reading distances for the DM300 and DM302 readers are the same. The DM303 and DM363 feature a higher
resolution and more pixels in about the same sensor size.
The following table shows the FoV widths in mm at various distances.

Distances in mm DM300 DM302/DM362 DM303/DM363


80 11 19 20
250 43 68 73
500 87 139 148
1000 175 281 298

114
Optics and Lighting

Scan Map for the DataMan 300 Series Readers with a 24 mm Lens with Liquid Lens

115
Optics and Lighting

Scan Map for the DataMan 360 Series Readers with a 24 mm Lens with Liquid Lens

Scan Map for DataMan 300 and 360 Series Readers Using a 25 mm Lens
This map shows the field of view of the DataMan 300/360, DataMan 302/362, and DataMan 303/363 readers with a 25
mm lens.
The FoV values are shown as follows:

l outer: DM302/362, DM303/363


l inner: DM300/360

The reading distances for the DM300/360 and DM302/362 readers are the same. The DM303/363 features a higher
resolution and more pixels in about the same sensor size.

116
Optics and Lighting

The following table shows the Field of View widths in mm at various distances.

Distances in mm DM300, DM360 DM302/303, DM362/363


50 8 12
100 16 25
150 23 37
250 39 62
500 78 125

DataMan 370 Series Readers Reading Distances and Field of


View
The following maps show the reading distance and field of view charts for the various lenses that can be used with the
DataMan 370 series readers. Reading distance values are also provided for 1-D and 2-D example code distances.

Reading Distance and Field of View for DataMan 370 Series Readers with a
10 mm High-Speed Liquid Lens
Note: Due to tolerances, ranges can vary by +/- 5 % from unit to unit.

The following map shows the FoV of the DataMan 370 series readers with a 10 mm high-speed liquid lens.

117
Optics and Lighting

Device Distances in mm / 1D min code Distances in mm / 2D min code


10 mm HSLL 10 mm HSLL
445 6 MIL 307 6 MIL
591 8 MIL 408 8 MIL
738 10 MIL 509 10 MIL
DM37x
958 13 MIL 660 13 MIL
1104 15 MIL 761 15 MIL
1471 20 MIL 1013 20 MIL

Reading Distance and Field of View for DataMan 370 Series Readers with a
16 mm High-Speed Liquid Lens
Note: Due to tolerances, ranges can vary by +/- 5 % from unit to unit.

The following map shows the FoV of the DataMan 370 series readers with a 16 mm high-speed liquid lens.

118
Optics and Lighting

Device Distances in mm / 1D min code Distances in mm / 2D min code


16 mm HSLL 16 mm HSLL
676 6 MIL 465 6 MIL
901 8 MIL 620 8 MIL
1125 10 MIL 774 10 MIL
DM37x
1462 13 MIL 1006 13 MIL
1687 15 MIL 1160 15 MIL
2249 20 MIL 1547 20 MIL

Reading Distance and Field of View for DataMan 370 Series Readers with a
24 mm High-Speed Liquid Lens
Note: Due to tolerances, ranges can vary by +/- 5 % from unit to unit.

The following map shows the FoV of the DataMan 370 series readers with a 24 mm high-speed liquid lens.

119
Optics and Lighting

Device Distances in mm / 1D min code Distances in mm / 2D min code


24 mm HSLL 24 mm HSLL
1029 6 MIL 709 6 MIL
1370 8 MIL 944 8 MIL
1711 10 MIL 1178 10 MIL
DM37x
2223 13 MIL 1530 13 MIL
2564 15 MIL 1764 15 MIL
3417 20 MIL 2351 20 MIL

DataMan 470 Series Readers Reading Distances and Field of


View
The following maps show the reading distance and field of view charts for the various lenses that can be used with the
DataMan 470 series readers. Reading distance values are also provided for 1-D and 2-D example code distances.

Reading Distance and Field of View for DataMan 470 Series Readers with a
10 mm High-Speed Liquid Lens
Note: Due to tolerances, ranges can vary by +/- 5 % from unit to unit.

The map below shows the field of view (FoV) of the DataMan 470 series readers with a 10 mm high-speed liquid lens.

120
Optics and Lighting

Device Distances in mm / 1D min code Distances in mm / 2D min code


10 mm HSLL 10 mm HSLL
445 6 MIL 307 6 MIL
591 8 MIL 408 8 MIL
738 10 MIL 509 10 MIL
DM47x
958 13 MIL 660 13 MIL
1104 15 MIL 761 15 MIL
1471 20 MIL 1013 20 MIL

Reading Distance and Field of View for DataMan 470 Series Readers with a
16 mm High-Speed Liquid Lens
Note: Due to tolerances, ranges can vary by +/- 5 % from unit to unit.

The following map shows the FoV of the DataMan 470 series readers with a 16 mm high-speed liquid lens.

121
Optics and Lighting

Device Distances in mm / 1D min code Distances in mm / 2D min code


16 mm HSLL 16 mm HSLL
676 6 MIL 465 6 MIL
901 8 MIL 620 8 MIL
1125 10 MIL 774 10 MIL
DM47x
1462 13 MIL 1006 13 MIL
1687 15 MIL 1160 15 MIL
2249 20 MIL 1547 20 MIL

Reading Distance and Field of View for DataMan 470 Series Readers with a
24 mm High-Speed Liquid Lens
Note: Due to tolerances, ranges can vary by +/- 5 % from unit to unit.

The following map shows the FoV of the DataMan 470 series readers with a 24 mm high-speed liquid lens.

122
Optics and Lighting

Device Distances in mm / 1D min code Distances in mm / 2D min code


24 mm HSLL 24 mm HSLL
1029 6 MIL 709 6 MIL
1370 8 MIL 944 8 MIL
1711 10 MIL 1178 10 MIL
DM47x
2223 13 MIL 1530 13 MIL
2564 15 MIL 1764 15 MIL
3417 20 MIL 2351 20 MIL

123
Optics and Lighting

DataMan 503 Readers Reading Distances and Field of View


The following scan maps show the reading distance and field of view charts for the various lenses that can be used with
the DataMan 503 reader.

Scan Map for DataMan 503 Series Readers Using a 16 mm Lens Module
The following map shows the reading distance and field of view charts for the DataMan 503 reader with a 16 mm lens for
1-D codes. The minimum 1-D resolution is at 1.2 pixels per module.

The following map shows the reading distance and field of view charts for the DataMan 503 reader with a 16 mm lens for
2-D codes. The minimum 2-D resolution is at 2.5 pixels per module.

124
Optics and Lighting

Scan Map for DataMan 503 Series Readers Using a 25 mm Lens Module
The following map shows the reading distance and field of view charts for the DataMan 503 reader with a 25 mm lens for
1-D codes. The minimum 1-D resolution is at 1.2 pixels per module.

The following map shows the reading distance and field of view charts for the DataMan 503 reader with a 25 mm lens for
2-D codes. The minimum 2-D resolution is at 2.5 pixels per module.

Scan Map for DataMan 503 Series Readers Using a 35 mm Lens Module
The following map shows the reading distance and field of view charts for the DataMan 503 reader with a 35 mm lens for
1-D codes. The minimum 1-D resolution is at 1.2 pixels per module.

125
Optics and Lighting

The following map shows the reading distance and field of view charts for the DataMan 503 reader with a 35 mm lens for
2-D codes. The minimum 2-D resolution is at 2.5 pixels per module.

CS-Mount Lens Characteristics


This section provides information on using CS-mount lenses.

DataMan 503 CS-Mount Lens Characteristics


CS-mount lenses must meet the following requirements to be used with DataMan 503:

l No aspect of the lens may protrude past the end of the lens threads.
l The threads must be no more than 4 mm deep.
l The maximum size lens barrel that fits within the CS-mount lens cover is 30 mm long (measured from lens mount
base) and 28 mm in diameter. You can remove the lens (and front) covers from DataMan to fit a larger lens, but
the reader will not maintain its IP rating.

126
Optics and Lighting

Internal Lighting
This section describes the working mechanism of the built-in lighting of DataMan 50, 60, 70, 150, 260, 503 and DataMan
300, 360, 370, and 470 series readers.

DataMan 50 and 60 Internal Lighting


All DataMan 50 and 60 readers include built-in (internal) lighting. During operation, the DataMan 50 and 60
automatically regulate image exposure time and imager gain to produce usable image quality at the highest possible
frame rate.
As the working distance between the reader and code increases, additional light intensity or longer exposure times are
required to maintain the same image quality. When the maximum illumination intensity is reached, the frame rate may be
reduced to permit a longer exposure time.

DataMan 70, 150 and 260 Internal Lighting


All DataMan 70, 150 and 260 readers include built-in (internal) lighting. During operation, the DataMan 70, 150 and 260
automatically regulate image exposure time and imager gain to produce usable image quality at the highest possible
frame rate.
As the working distance between the reader and code increases, additional light intensity or longer exposure times are
required to maintain the same image quality. When the maximum illumination intensity is reached, the frame rate may be
reduced to permit a longer exposure time.

DataMan 300, 360, 370, and 470 Series Readers Internal Lighting
The internal illumination module offers two rings of LEDs with four quadrants each. Each quadrant is controllable
individually, that is, ON/OFF and intensity.
You can turn the quadrants ON or OFF by clicking on the dots (representing the LEDs) on the front image of the DataMan
300, 360, 370, or 470 in the DataMan Setup Tool’s Optimize Image pane. The quadrants that are ON are displayed in
red, as shown in the example below.

127
Optics and Lighting

Tuning
By tuning, your DataMan 300, DataMan 360, DataMan 370, and DataMan 470 series reader automatically selects the
best settings for the given reading situation, based on parameters of illumination, camera and decoder properties, and
focal distance. Use this feature to create an optimum setting to read your DataMatrix codes.

Note: Tune button can toggle the aimer light ON and OFF.

128
Optics and Lighting

External Lighting
This section details the external lighting options for DataMan 50, 60, 503 and DataMan 300, 360, 370, and 470 series
readers.

DataMan 50 and 60 External Lighting


The DataMan 50 and 60 readers have a dedicated output for external light control. In addition, the DataMan 60 has an
external illumination connector on the front side of the reader.

You can control the intensity output of the external illumination connector if the external illumination you use supports
this control. In the DataMan Setup Tool, go to the Optimize Image pane and check the External checkbox. You can also
choose your light type from the drop-down box below. In the Optimize Image pane's Advanced tab, you can make
further external illumination settings.

DataMan 50 and 60 Illumination Strobe Output


The strobe output is provided by a diode that is added to the push-pull circuit, with series to the pull-up transistor. This
diode blocks the higher voltage when the output is pulled up when used as open-collector type driving, but enables the
driving of high level in TTL mode.

TTL output type characteristics


High level 4.0-5.0 V
Low level 0-0.4 V
Output current 25 mA
Short-circuit current 125 mA
Short-circuit protection multifuse – 50 mA

Open-collector output type characteristics


Output voltage range 0-26 V
Low level 0-0.4 V
Output current 25 mA max
Short-circuit current 125 mA
Short-circuit protection multifuse – 50 mA

The following figure shows the wiring diagram of the illumination strobe output.

129
Optics and Lighting

130
Optics and Lighting

DataMan 50 and 60 External Load Strobe Output


The following image shows the external load strobe output for the DataMan 50. The DataMan 60 has the same
characteristics.

DataMan 300, 360, 370, and 470 Series Readers External Lighting
On the back of the reader, there is a socket dedicated to external light control (1, 2, 3, and 4 in the following image).

There are four mounting holes on the front of the reader to mount external illumination.

131
Optics and Lighting

You can control the intensity output of the external illumination connector if the external illumination you use supports
this control. In the DataMan Setup Tool, go to the Optimize Image pane and check the External checkbox. You can also
choose your light type from the drop-down box below. In the Optimize Image pane's Advanced tab, you can make
further external illumination settings.
The DataMan 300, 360, 370, and 470 series readers support high power illumination accessories. For more information,
see the Accessories sections in the DataMan 300 Reference Manual, the DataMan 360 Reference Manual, the DataMan
370 Reference Manual, and the DataMan 470 Reference Manual.
For detailed instructions on how to set the DataMan 370 and 470 series readers up with high power illumination
accessories, see the following sections:

DataMan 370 series readers with High Power Integrated Light Installing the Liquid Lens Module with High
Power Integrated Light (HPIL) on page 43
DataMan 370 series readers with High Power Illumination Accessory Installing a Lens with High Power Illumination
Accessory (HPIA) on page 47
DataMan 370 series readers with High Power Integrated Torch (HPIT) Installing High Power Integrated Torch (HPIT)
on page 49
DataMan 470 series readers with High Power Integrated Light Installing the Liquid Lens Module with High
Power Integrated Light (HPIL) on page 43
DataMan 470 series readers with High Power Illumination Accessory Installing a Lens with High Power Illumination
Accessory (HPIA) on page 1
DataMan 470 series readers with High Power Integrated Torch (HPIT) Installing High Power Integrated Torch (HPIT)
on page 49

External Light Mounting Brackets


You can mount your reader using external light mounting brackets. The brackets are intended to mount any of the
different lights to the reader. They can also be used to mount the reader (with lights attached) to your machine. Pivot
mounting, as illustrated, is optional. Perform the following steps:

132
Optics and Lighting

1. Mount your reader on the camera plate and attach the screws.

2. Mount your reader with the camera plate attached to any of the external light bracket adapters.

Choose one of the following external light options:

Accessory
Ring Light CLRR-R7030G1CLR

Back Light CLRB-F100100G1

Coaxial (DOAL) Light CLRO-K5050G1

Spot Light CLRS-P14G1

Dark-field Light CLRD-D120G1

Brick Light IVSL-ODDM-S75-xxx

133
Optics and Lighting

Accessory
Bar Light IVSL-YLW2X-xxx

Bar Light IVSL-LX520-xxx

LX280-series Light IVSL-LX280-xxx

DataMan 50, 60, 300, 360, 370, and 470 External Lighting Duration
In all cases, as soon as the trigger is detected, external illumination is turned on. There is a 600 µSec pre-charge time
before exposure starts; the lighting is on during this period. In the DataMan Setup Tool's Optimize Image pane, you can
click the Tune button's drop-down icon and from the Optimize Brightness section select Automatic Exposure
(autoregulation) or Manual Exposure (non-autoregulation) according to your needs. You can also reach the same
settings by navigating to the Setup Tool's Applicaton Details pane.
If you use a DataMan 302 reader with full Field of View (FoV), consider the following:

l In non-autoregulation cases, exposure occurs for an amount of time you specify. You can configure this time in
the DataMan Setup Tool’s Application Details pane. When exposure ends, illumination is turned off. Altogether,
the exposure duration equals the exposure time you set and the 600 µSec pre-charge time.
l If autoregulation is enabled, the duration can vary depending on the maximum allowed exposure value
configured and the computed exposure time (which will be different for each acquisition). To calculate a ”worst
case” duration, set a maximum exposure value, and the longest the lights will be on is
600 uSec precharge time + max exposure time

Exposure occurs for the amount of time determined by autoregulation. When exposure ends, illumination is turned off. If
you use a reduced FoV for a DataMan 50, 60, 300, 360, 370, or 470 reader, the image transfer time will scale
proportionally to the FoV/Sensor size.

DataMan 503 External Lighting Duration


In all cases, as soon as the trigger is detected, external illumination is turned on. There is a user adjustable µSec pre-
charge time before exposure starts; the lighting is on during this period. In the DataMan Setup Tool’s Application Details
pane, you can select Automatic Exposure (autoregulation) or Manual Exposure (non-autoregulation) according to your
needs.

l In non-autoregulation cases, exposure occurs for an amount of time you specify. You can configure this time in
the DataMan Setup Tool’s Application Details pane. When exposure ends, illumination is turned off. Altogether,
the exposure duration equals the exposure time you set, the adjusteble µSec pre-charge time, plus a maximum
17,15 ms image transfer time.
l If autoregulation is enabled, the duration can vary depending on the maximum allowed exposure value
configured and the computed exposure time (which will be different for each acquisition). To calculate a ”worst
case” duration, set a maximum exposure value, and the longest the lights will be on is
Max. allowed precharge time + max exposure time

Exposure occurs for the amount of time determined by autoregulation. When exposure ends, illumination is turned off.

134
Operations Guide

Operations Guide
This section contains information about configuring and using your DataMan reader.

Trigger Modes
The fixed-mount DataMan readers provide the following trigger modes:

Self-Trigger
DataMan fixed-mount readers support self-triggered operation. In self-trigger mode, the reader automatically detects and
decodes codes in its field of view. The high-speed image acquisition and processing capabilities of the DataMan allow it
to detect and decode codes.
Self-trigger mode has the following characteristics:

l Ease of setup. No external trigger is required.


l Flexible timing. Parts can arrive at irregular intervals.
l Maximum throughput.

Manual
Manual triggering starts acquiring and attempting to decode images when you send an external trigger. The reader
continues to acquire and attempt to decode images until you stop the external triggering. 2-D DPM codes are
automatically learned.
Manual trigger mode is typically used during debugging or system design.

Burst
Burst triggering acquires a pre-defined number of images when an external trigger is signaled, then attempts to decode
the acquired images. You can control the interval between the acquired images. The number of images acquired per
burst depends on the size of the region of interest that you specify.

Continuous
Continuous triggering begins acquiring images based on a single external trigger and continues to acquire and decode
images at a user-specified interval until a symbol is found, or until multiple images containing as many codes as
specified in multicode mode are located. The external trigger can be configured as a latch (acquisition continues while
the line is held high) or acquisition can be started on the first pulse, stopped on the second pulse. If you scan items on a
conveyor, make sure that each item reaches trigger OFF before the next item generates trigger ON.

Single
Single triggering acquires a single image and attempts to decode any symbol it contains, or more than one symbol in
cases where multicode is enabled. The reader relies on an external trigger source.

Presentation
Presentation triggering repeatedly scans for a symbol and decodes it whenever one is detected. The reader relies on an
internal timing mechanism to acquire images.

135
Operations Guide

Presentation mode is similar to manual trigger mode, without using the trigger as a signal to start acquisition.

Package Detection Support


You can connect your package detection sensor to one of the digital inputs of your DataMan reader. When the reader
receives a signal that a package is detected, images that the reader collected are not discarded at the end of the trigger.
This way you can make sure that there was a package there, only the code was not readable. Looking at the No Read
images will help you find out why there was no decode results.
Package detection is only supported with Continuous trigger mode. Continuous (external) trigger mode means that the
trigger stops if the event generating the trigger stopped, or if there is a good read. Until the trigger stops, the reader
collects images. These are No Read images (otherwise the trigger would stop).
You can use this feature in a stand-alone configuration, or in a multi-reader sync configuration. In the latter case, connect
the sensor to the Primary reader. The Primary reader will initiate a request to save images and collect the images from
the secondary readers.
To make sure that the No Read images are collected, perform the following:

1. Connect your package detection device to one of the Inputs of your reader.
2. In the DataMan Setup Tool’s Inputs/Outputs pane's Inputs tab, check Allow Buffered No-Read Images on the
input you connected your reader to.
3. In the Inputs/Outputs pane, click the Buffering and Transfer link next to or above the tabs. This directs you to the
Buffering and Transfer pane. On the Image Buffering tab, change What Results to Buffer to All, or No Read.
l In the case of All, good reads are also saved together with No Reads.
l In the case of No Read, the image is buffered if the reader fails to read.

The following diagram shows the working mechanism:

The signal from the sensor tells the reader not to discard the collected images at the end of the trigger event.

Test Mode
Test mode lets you configure and test a reader that is connected to a production line without needing to slow down or
stop your line. To enter Test mode,

l Press the button (to which you previously assigned this function) on the device for 3 seconds
l Send a DataMan Control Command (DMCC)
l Click the Test Mode button in the DataMan Setup Tool

While in test mode, the reader, by default, ignores all external trigger sources and disables all input and output lines.
Test mode provides two ways for you to test your reader configuration:

136
Operations Guide

l Check Automatic Triggering, and the reader will simulate external triggers at the interval that you specify. This
allows you to examine the result of each trigger and images with the configuration used in production but at a
slower rate. Because inputs and outputs are disabled, the reader will not interfere with the normal operation of
your line.
l If you click Accept Trigger Batch, the reader will accept and process a limited number of external triggers (you
can specify the number) at production speed. You can then examine these results and corresponding images to
verify how the reader is processing triggers in production.

If needed, you can enable both inputs and outputs during test mode, but you may encounter I/O process latencies.

Code Training
You can train the DataMan fixed-mount readers for single or multiple codes. Training can improve performance, since
the reader does not have to determine code parameters as it reads the codes.
Code training is only supported for the following trigger modes:

l Burst
l Continuous
l Self (internal trigger)
l Single (external trigger)

You can train codes in the following ways:

l In the DataMan Setup Tool's Optimize Image pane, check the Train Code After Tuning checkbox and tune your
reader. In the Image Panel on the right, you will see a message such as in the following image:

For further code training settings in the Setup Tool, go to the Code Details pane's Advanced tab.

l Use the TRIG Button tab in the Inputs/Outputs pane to configure the button to train codes, then present the
codes to the reader and press and hold the button for 3 seconds.
l Use the Inputs tab in the Inputs/Outputs pane to configure a discrete input to perform code training.

Automatic Code Training for DPM Symbols


Manual and Presentation modes automatically train 2-D symbols. This improves robustness on DPM symbologies when
reading consecutive parts of the same type. Sequential dissimilar parts will still decode.

Image Buffering and Image Recording


You can configure the DataMan fixed-mount readers to store selected images in the memory of the reader.
You can select the following options on which images to store:

137
Operations Guide

l No images.
l No-read images. (Images where the reader was triggered but either no code was present or the code could not
be decoded.)
l Images where a code was successfully decoded.
l All images.

If you select all images or no-read images, you can specify a sampling rate to control the number of images that are
buffered.

Retrieving Buffered Images


You can use the DataMan Setup Tool to view and download images from your DataMan device, or you can configure the
DataMan reader to automatically transfer the buffered images to an FTP server that you specify.
For more information, see the DataMan Setup Tool Reference Manual.

DataMan Multi-Reader Sync Configuration


Overview
If you have multiple DataMan fixed-mount readers connected to the same network, you can configure multiple readers to
use group triggering. Readers configured to use group triggering all acquire an image simultaneously, and then
combine their individual read results to form a composite result.
There are two important aspects to group triggering:

l Readers configured for group triggering consolidate reader results from among all readers in the group and
transmit them from the primary reader only. This simplifies the task of collecting and processing read results from
multiple readers.
l Readers configured for group triggering can be triggered simultaneously based on a single input trigger signal
received by the primary reader.

Multi-Reader Sync configurations are typically used to expand the field of view for broad conveyor applications and to
read codes from multiple surfaces of packages or objects:

138
Operations Guide

Primary Reader
Within a group, one reader is defined as the primary reader. When the primary reader is triggered (regardless of what
type of trigger it uses), all the readers in the group are also triggered. For self-trigger mode, you must designate the
primary reader explicitly. For externally triggered modes (single, burst, and continuous), whichever reader receives the
trigger is designated the primary reader for that acquisition. (In most cases, only a single reader in the group will be
connected to the external trigger.)
To account for network latency, you specify a trigger delay for the primary reader in the group. When the primary reader
is triggered, it immediately sends triggers to the other group members, but delays its own acquisition for the specified
delay, allowing the trigger signal to reach the other readers. You can also configure a separate trigger timeout, which will
cause the primary reader to wait for a specified period of time for secondary readers to send data before collecting the
results and transmitting them.

After a read attempt, only the primary reader transmits a result. It combines all of the available results from the other
readers in the group in the same way that multicode results are combined.

Secondary Readers
In many applications, the multi-reader sync configuration is set to trigger the secondary readers whenever the primary
reader is triggered. If the secondary readers are configured for Self triggering, then they will also trigger whenever they
detect a code. In this case, the primary reader will generate and transmit a read result whenever any reader detects a
code. This result aggregation greatly simplifies multiple reader operation.

Data Formatting
When the reader is triggered, the result string will be formatted as you specified, before it is transmitted to the primary
reader for aggregation. Note, however, that you have to check Standard Formatting Enabled for the primary reader and
supply the formatting tokens you want to use for the secondary readers. Any data formatting that you specify for the
primary reader will be applied to the formatted result strings produced by the secondary readers. The Format Data pane
includes a token that allows you to insert the name of the reader generating the result string; you can use this to identify
which reader produced which result.

Limitations
l No image buffering and recording is supported for any reader that is part of a group.

l Presentation mode triggering is not supported.


l Multi-Reader Sync triggering only works correctly if the Primary and the Secondary readers use specific, allowed
combinations of trigger modes. They are the following:
l Self/Self
l Single/Burst, Single/Single, Burst/Burst, Burst/Single
l Manual/Continuous, Manual/Manual, Continuous/Continuous, Continuous/Manual

Synchronized Acquisition
Synchronized Acquisition is only available for the DataMan 300, 360, 370 and 470 readers with an -M option, and the
DataMan 503. In Single, Burst, Continuous, and Self trigger modes, it is possible to sync0hronize image acquisition on
multiple devices using the synchronization interface.
Synchronization allows using one shared strobe illumination to expose all sensors simultaneously. You can synchronize
multiple readers, with optionally triggering them in a defined sequence to avoid that opposing readers blind each other.

139
Operations Guide

Note: This and other imager settings will not get synchronized by this mechanism - for example, you must configure
exposure and gain on each reader individually.

This feature only synchronizes the actual image acquisition, triggering happens through the existing multi-reader sync
mechanism.

Synchronized Acquisition for the DataMan 300, 360, 370, and 470
To set up synchronized acquisition on your reader, enable PTP (Precision Time Protocol) on the Multi-Reader Sync
pane of the DataMan Setup Tool under Synchronized Readers (IE1588).
Perform the following steps:

1. Check Enable PTP.


2. Keep Secondary Camera Only checked if there is already a PTP Primary Reader clock in the network (uncheck
the checkbox otherwise on at least one reader).
3. Enable MRS Synchronized by PTP to synchronize Multi-Reader Sync triggering.
4. Set the Time between Trigger Start and the Synchronized Acquisition Timestamp. This is the time the Primary
Reader adds to the trigger to make sure all devices already received the trigger message before this time stamp
(Primary Reader Only).
5. Set the Local Offset Added to the Synchronized Acquisition Timestamp. This is the time the Secondary
Reader adds to the timestamp to realize offset image acquisitions (Secondary Reader Only).

Synchronized Acquisition for the DataMan 503


Enable Synchronized Exposure on the DataMan Setup Tool’s Multi-Reader Sync pane. Set the Acquisition Delay (μs)
(relative to the received signal through the synchronization interface) on each reader individually to optionally define an
exposure sequence in case the illumination of some readers might affect other readers.
You must also set which two readers on the ends of the synchronization interface bus are bus terminators by checking
the End of Sync Cable checkbox for the currently connected devices at the end of a sync cable.

140
Operations Guide

Connecting the DataMan 503 Through the Synchronized Acquisition Cable


Plug the synchronized acquisition cable into the dedicated connector on the DataMan 503.

If you are connecting more than two DataMan 503 devices, you need a Y connector with female ends to be able to use
the synchronized acquisition cables.

141
Operations Guide

Using C/CS-Mount Lenses

Aperture Setting
Because of the extreme sensitivity of the DataMan image sensor, for most applications, a small aperture (F8 or less)
provides sufficient light for full-rate image processing while also maximizing depth of field.

Selecting Optimum Focus


You can enter live video, but for best focus optimization, place the reader in automatic trigger mode and adjust the focus
until the peak read rate is obtained.

Optimizing Performance

Read Interval and Timeout Configuration


Careful configuration of the read interval (Self and Continuous triggering) or timeout value (Burst mode) can improve
read rates and throughput.

l If your application uses clearly printed symbols, you can improve performance by reducing the interval or timeout
value. This is because DataMan acquires images at such a high rate that a shorter timeout or interval allows the
reader multiple chances to decode the symbol.
l If your application experiences poorly printed or degraded symbols, increasing the interval or timeout value can
improve performance by allowing the DataMan to spend more time decoding difficult images.

In all cases, make sure that you specify an interval that allows the reader to capture at least one image of the symbol.

Optimizing Burst Trigger Parameters


Since a Burst trigger is ideal for moving applications, it is necessary to determine the correct burst size and interval in
order to capture the desired length of the part as it moves under the camera. Once the interval time is determined, you
can adjust the size of the burst depending on the length of the part. The variables necessary for this calculation are:

1. Line speed in mm per second

2. Code size w/quiet zone in mm


3. FOV = Field of View (x or y) in mm

You can then use the following equation to determine the interval time:
Interval Time = 1000 * ((FOV – 2(Code Size)) / Line Speed)

Once the interval time is determined, the size of the burst can be adjusted depending on the length of the code to
capture. The max object length in mm is:

Burst Size * (FOV – (2*Code Size))

The (2 * Code Size) variable allows for overlap of the frames taken. This takes into consideration the condition where the
code is slightly out of the field of view in one frame (acquisition). The (2 * Code Size) will overlap the field of view
between successive frames and allow the code to be viewed in the field of view of the next frame.

142
Operations Guide

Reducing DataMan Processing Requirements


The more information that you can provide to DataMan about your application, the less work – and processing time – will
be required to decode symbols.

l Only enable the symbologies that your application uses. Disabling unused symbologies reduces processing
time.
l Train codes.
l Only enable extended mode decoding if your application requires it.

Avoiding Reflections and Glare


If the DataMan is mounted perpendicular to the surface containing the code to be read, reflections from the built-in
illumination system can cause reflections and glare that may reduce decoding performance.
You can avoid this problem by mounting the reader at a 15° angle from vertical.

143
Application Guide

Application Guide
This section provides specific recommendations tailored to specific types of applications. Except for the sections about
Multi-Reader Configurations and Variable Size Box Conveyer, all sections apply to all the DataMan fixed-mount readers.

Understanding Your Application Envelope


A wide variety of factors affects the performance and capabilities of the DataMan in a given application. You can think of
this collection of factors as your application’s envelope:

The following table describes the different parameters that define a DataMan application envelope.

Parameter Description
Linespeed The linear speed of the part surface containing the code to decode.
Nominal working distance How far the code is from the front of the DataMan.
Working distance range The range of distances, with respect to the nominal working distance, at which
codes may be present.
Working width The width of the area in which codes may appear.

144
Application Guide

Parameter Description
Tilt, pitch, rotation, and package The degree to which a code may be rotated, tilted, or pitched with respect to a
spacing plane perpendicular to the DataMan optical axis.
Package spacing means a distance in time. If you use a conveyor that moves
very fast, you need more space between the boxes. If it moves very slow, you
need less space. In general, the minimum time distance between boxes must
be greater than the distance between trigger on and trigger off.
Tilt and pitch should be limited to 15-20 degrees in most cases, while rotation
may be absent or may occur up to 360 degrees (omnidirectional reading).
As described in the section Reducing DataMan Processing Requirements, the
more information that you can provide to DataMan about your application, the
less work – and processing time – will be required to decode symbols.

l Only enable the symbologies that your application uses. Disabling


unused symbologies reduces processing time.

l Train codes.
l Only enable extended mode decoding if your application requires it.
Avoiding Reflections and Glare, you should mount the reader so that the
surface containing the code to be read is not perpendicular to the reader. If
your application includes tilt or pitch, make sure that the reader is mounted so
that even at maximum tilt or pitch, the reader still is angled with respect to the
surface being read.
Code module size The size of a code element (typically the smallest bar) in Mils.
Codes per minute The maximum number of codes that pass in front of the reader location per
minute.
Codes per image The number of codes visible at the same time.
Trigger and output signal requirements Whether an external trigger signal is available or a discrete output signal is
required.

The following sections describe typical application envelopes for typical DataMan code reading applications, along with
suggested configuration values.

Tote Scanning
Tote scanning applications typically involve reading a single barcode that is relatively well-fixtured.

145
Application Guide

The following table lists typical values for this application:

Parameter Typical Values


Line speed 50 FPM
Nominal working distance 6-12"
Working distance range +/- 5"
Working width 6"
Tilt, pitch, and rotation +/- 2°
Code module size 20 Mil
Codes per minute 20-30
Trigger and output signals Optional

Side Scanning
Side scanning applications typically involve reading a single barcode at a consistent distance but a variable offset.

The following table lists typical values for this application:

Parameter Typical Values


Line speed 200-300 FPM
Nominal working distance 6-12"
Working distance range +/- 1"
Working width 12-24"
Tilt, pitch, and rotation +/- 2°
Code module size 20 Mil
Codes per minute 100-200
Trigger and output signals Optional

Side Scanning (Large Field)


Side scanning applications typically involve reading a single barcode at a consistent distance but a variable offset.
The following table lists typical values for this application:

Parameter Typical Values


Line speed 200-300 FPM

146
Application Guide

Parameter Typical Values


Nominal working distance 6-12"
Working distance range +/- 1"
Working width 12-24"
Tilt, pitch, and rotation +/- 2°
Code module size 20 Mil
Codes per minute 100-200
Trigger and output signals Optional

Print Verification (Carton Coding and Print & Apply)


This configuration reads and verifies codes from packages immediately after they are applied. The codes may be printed
directly on the object (carton coding) or on a label (print & apply).

The following table lists the typical values for this application:

Parameter Typical Values


Line speed 200-300 FPM
Nominal working distance 5-10"
Working distance range +/- 0.5"
Working width 2-4"
Tilt, pitch, and rotation +/- 2° (pitch, tilt, and rotation)
Code module size 20 Mil
Codes per minute up to 200
Trigger and output signals Likely

147
Application Guide

Manual Presentation Scanning


This configuration reads codes from objects presented manually.

The following table lists the typical values for this application:

Parameter Typical Values


Line speed N/A
Nominal working distance 10-20"
Working distance range +/- 10-
Working width 10-20
Tilt, pitch, and rotation +/- 20° (pitch and tilt)
360° (rotation)
Code module size 20 Mil
Codes per minute 10-20
Trigger and output signals Possible

148
Precautions

Precautions
To reduce the risk of injury or equipment damage, observe the following precautions when you install the Cognex
product:

l Route cables and wires away from high-current wiring or high-voltage power sources to reduce the risk of
damage or malfunction from the following causes: over-voltage, line noise, electrostatic discharge (ESD), power
surges, or other irregularities in the power supply.
l Changes or modifications not expressly approved by the party responsible for regulatory compliance could void
the user’s authority to operate the equipment.
l Ensure that the cable bend radius begins at least six inches from the connector. Cable shielding can be
degraded or cables can be damaged or wear out faster if a service loop or bend radius is tighter than 10X the
cable diameter.
l This device is certified for office use only and if used at home, there can be frequency interference problems.
l This device should be used in accordance with the instructions in this manual.
l All specifications are for reference purposes only and can change without notice.

149
Copyright © 2019
Cognex Corporation. All Rights Reserved.

You might also like