Data Sheet 6ES7517-3HP00-0AB0: General Information

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Data sheet 6ES7517-3HP00-0AB0

SIMATIC S7-1500H, CPU 1517H-3 PN, central processing unit with


work memory 2 MB for program and 8 MB for data, 1st interface:
PROFINET RT With 2-port switch, 2nd interface: PROFINET, 3rd/4th
interface: H-SYNC, SIMATIC memory card required
******************************* Special release required. Please contact
your Siemens representative

General information
Product type designation CPU 1517H-3 PN
HW functional status FS02
Firmware version V2.8
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No

Display
Screen diagonal [cm] 6.1 cm

Control elements
Number of keys 6
Mode selector switch 1

Supply voltage
Type of supply voltage 24 V DC
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Mains buffering

6ES7517-3HP00-0AB0 Subject to change without notice


Page 1/8 04/28/2020 © Copyright Siemens
● Mains/voltage failure stored energy time 5 ms

Input current
Current consumption (rated value) 1.5 A
Inrush current, max. 2.4 A; Rated value
I²t 0.02 A²·s

Power loss
Power loss, typ. 24 W

Memory
Number of slots for SIMATIC memory card 1
SIMATIC memory card required Yes
Work memory
● integrated (for program) 2 Mbyte
● integrated (for data) 8 Mbyte
Load memory
● Plug-in (SIMATIC Memory Card), max. 32 Gbyte
Backup
● maintenance-free Yes

CPU processing times


for bit operations, typ. 4 ns
for word operations, typ. 6 ns
for fixed point arithmetic, typ. 6 ns
for floating point arithmetic, typ. 24 ns

CPU-blocks
Number of elements (total) 12 000; Blocks (OB, FB, FC, DB) and UDTs
DB
● Number range Number range: 1 to 59 999
● Size, max. 8 Mbyte; For non-optimized block accesses, the max. size of the
DB is 64 KB
FB
● Number range 0 ... 65 535
● Size, max. 1 Mbyte
FC
● Number range 0 ... 65 535
● Size, max. 1 Mbyte
OB
● Size, max. 1 Mbyte
● Number of free cycle OBs 100
● Number of time alarm OBs 20
● Number of delay alarm OBs 20
● Number of cyclic interrupt OBs 20

6ES7517-3HP00-0AB0 Subject to change without notice


Page 2/8 04/28/2020 © Copyright Siemens
● Number of process alarm OBs 50
● Number of startup OBs 100
● Number of asynchronous error OBs 4
● Number of synchronous error OBs 2
● Number of diagnostic alarm OBs 1
Nesting depth
● per priority class 24

Counters, timers and their retentivity


S7 counter
● Number 2 048
Retentivity
— adjustable Yes
IEC counter
● Number Any (only limited by the main memory)
Retentivity
— adjustable Yes
S7 times
● Number 2 048
Retentivity
— adjustable Yes
IEC timer
● Number Any (only limited by the main memory)
Retentivity
— adjustable Yes

Data areas and their retentivity


Retentive data area (incl. timers, counters, flags), 768 kbyte
max.
Flag
● Number, max. 16 kbyte
● Number of clock memories 8; 8 clock memory bit, grouped into one clock memory byte
Data blocks
● Retentivity adjustable Yes
● Retentivity preset No
Local data
● per priority class, max. 64 kbyte; max. 16 KB per block

Address area
Number of IO modules 8 192; max. number of modules / submodules
I/O address area
● Inputs 32 kbyte; All inputs are in the process image
● Outputs 32 kbyte; All outputs are in the process image
per integrated IO subsystem

6ES7517-3HP00-0AB0 Subject to change without notice


Page 3/8 04/28/2020 © Copyright Siemens
— Inputs (volume) 16 kbyte
— Outputs (volume) 16 kbyte
Subprocess images
● Number of subprocess images, max. 32

Hardware configuration
Number of distributed IO systems 1
Number of IO Controllers
● integrated 1

Time of day
Clock
● Type Hardware clock
● Backup time 6 wk; At 40 °C ambient temperature, typically
● Deviation per day, max. 10 s; Typ.: 2 s
Operating hours counter
● Number 16
Clock synchronization
● supported Yes
● on Ethernet via NTP Yes

Interfaces
Number of PROFINET interfaces 2

1. Interface
Interface types
● Number of ports 2
● integrated switch Yes
● RJ 45 (Ethernet) Yes; X1
Protocols
● IP protocol Yes; IPv4
● PROFINET IO Controller Yes
● PROFINET IO Device No
● SIMATIC communication Yes; Only Server
● Open IE communication Yes
● Web server No
● Media redundancy Yes; MRP Automanager according to IEC 62439-2 Edition 2.0
PROFINET IO Controller
Services
— PG/OP communication Yes
— S7 routing Yes
— Isochronous mode No
— IRT No
— MRP Yes; Only Manager Auto, max. 50 nodes

6ES7517-3HP00-0AB0 Subject to change without notice


Page 4/8 04/28/2020 © Copyright Siemens
— MRPD No
— PROFIenergy Yes
— Number of connectable IO Devices, max. 256
Update time for RT
— for send cycle of 1 ms 1 ms to 512 ms

2. Interface
Interface types
● Number of ports 1
● integrated switch No
● RJ 45 (Ethernet) Yes; X2
Protocols
● IP protocol Yes; IPv4
● PROFINET IO Controller No
● PROFINET IO Device No
● SIMATIC communication Yes; Only Server
● Open IE communication Yes
● Web server No
● Media redundancy No

3. Interface
Interface type Pluggable interface module (IF)
Plug-in interface modules Synchronization module 6ES7960-1CB00-0AA5 or 6ES7960-
1FB00-0AA5

4. Interface
Interface type Pluggable synchronization submodule (FO)
Plug-in interface modules Synchronization module 6ES7960-1CB00-0AA5 or 6ES7960-
1FB00-0AA5

Interface types
RJ 45 (Ethernet)
● 100 Mbps Yes
● Autonegotiation Yes
● Autocrossing Yes
● Industrial Ethernet status LED Yes

Protocols
Number of connections
● Number of connections, max. 288
● Number of connections reserved for 10
ES/HMI/web
● Number of S7 routing paths 64
Redundancy mode
Media redundancy

6ES7517-3HP00-0AB0 Subject to change without notice


Page 5/8 04/28/2020 © Copyright Siemens
— MRP Yes; Manager Auto is permanently set in TIA. Max. 50 nodes are
possible
— MRPD No
— Switchover time on line break, typ. 200 ms; PROFINET MRP
— Number of stations in the ring, max. 50
SIMATIC communication
● S7 communication, as server Yes
● S7 communication, as client No
Open IE communication
● TCP/IP Yes
— Data length, max. 64 kbyte
— several passive connections per port, Yes
supported
● ISO-on-TCP (RFC1006) Yes
— Data length, max. 64 kbyte
● UDP Yes
— Data length, max. 2 kbyte; 1 472 bytes for UDP broadcast
— UDP multicast Yes; Max. 5 multicast circuits
● DHCP No
● SNMP Yes
● DCP Yes
● LLDP Yes
Web server
● HTTP No
● HTTPS No
OPC UA
● OPC UA client No
● OPC UA server No
Further protocols
● MODBUS Yes; MODBUS TCP

Isochronous mode
Equidistance No

S7 message functions
Number of login stations for message functions, max. 64
Program alarms Yes
Number of configurable program messages, max. 10 000; Program messages are generated by the
"Program_Alarm" block, ProDiag or GRAPH
Number of loadable program messages in RUN, 5 000
max.
Number of simultaneously active program alarms
● Number of program alarms 1 000
● Number of alarms for system diagnostics 1 000

6ES7517-3HP00-0AB0 Subject to change without notice


Page 6/8 04/28/2020 © Copyright Siemens
Test commissioning functions
Joint commission (Team Engineering) No
Status block Yes; Up to 16 simultaneously
Single step No
Number of breakpoints 20; Breakpoints are only supported in RUN-Solo status
Status/control
● Status/control variable Yes
● Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers,
counters
● Number of variables, max.
— of which status variables, max. 200; per job
— of which control variables, max. 200; per job
Forcing
● Forcing Yes
● Forcing, variables Peripheral inputs/outputs
● Number of variables, max. 200
Diagnostic buffer
● present Yes
● Number of entries, max. 3 200
— of which powerfail-proof 1 000
Traces
● Number of configurable Traces 8
● Memory size per trace, max. 512 kbyte

Interrupts/diagnostics/status information
Diagnostics indication LED
● RUN/STOP LED Yes
● ERROR LED Yes
● MAINT LED Yes
● Connection display LINK TX/RX Yes

Supported technology objects


Motion Control No
Controller
● PID_Compact Yes; Universal PID controller with integrated optimization
● PID_3Step Yes; PID controller with integrated optimization for valves
● PID-Temp Yes; PID controller with integrated optimization for temperature
Counting and measuring Yes
● High-speed counter No

Ambient conditions
Ambient temperature during operation
● horizontal installation, min. 0 °C

6ES7517-3HP00-0AB0 Subject to change without notice


Page 7/8 04/28/2020 © Copyright Siemens
● horizontal installation, max. 60 °C; Display: 50 °C, at an operating temperature of typically 50
°C, the display is switched off
● vertical installation, min. 0 °C
● vertical installation, max. 40 °C; Display: 40 °C, at an operating temperature of typically 40
°C, the display is switched off
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see
manual

Configuration
Programming
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC No
— GRAPH Yes
Know-how protection
● User program protection/password protection Yes
● Copy protection No
● Block protection Yes
Access protection
● Password for display Yes
● Protection level: Write protection Yes
● Protection level: Read/write protection Yes
● Protection level: Complete protection Yes
Cycle time monitoring
● lower limit adjustable minimum cycle time
● upper limit adjustable maximum cycle time

Dimensions
Width 210 mm
Height 147 mm
Depth 129 mm

Weights
Weight, approx. 2 119 g; Interface modules: 2x 18 g

last modified: 04/28/2020

6ES7517-3HP00-0AB0 Subject to change without notice


Page 8/8 04/28/2020 © Copyright Siemens