11.0 Compressors, Blowers, and Fans Preface: Bechtel Confidential
11.0 Compressors, Blowers, and Fans Preface: Bechtel Confidential
11.0 Compressors, Blowers, and Fans Preface: Bechtel Confidential
PREFACE
This section deals with the piping systems containing fans, blowers, and compressors. It
covers some important compression parameters and system design with pressure profile
program.
In general, fans, blowers, and compressors can be differentiated by their discharge pressure.
The type of equipment may be similar in configuration.
· Fan
Fan discharge pressures are normally less than 2 psig. Fans are classified as:
- Centrifugal
- Straight blade
- Axial flow
· Blowers
- Rotary vane
- Centrifugal
- Screw
- Lobe
- Reciprocating
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
Bechtel Confidential
© Bechtel Corporation 2002. Contains confidential and/or proprietary information to Bechtel and its affiliated companies which shall not be
used, disclosed or reproduced in any format by any non-Bechtel party without Bechtel’s prior written permission. All rights reserved.
3DG-M11-K0001-003 PAGE 1 OF 32
· Compressors
When the discharge pressure developed by a blower exceeds 7 psig, it is not a blower
anymore. It is called a compressor. This, of course, depends on application,
equipment, and specifications involved in the service.
- Dynamic displacement
- Positive displacement
Dynamic compressors develop a rise in pressure by increasing the kinetic energy of the
gas flow on a continuous basis. The types within this category include:
- Blowers
- Centrifugal (radial)
- Axial
- Reciprocating
- Rotary
o Screw
o Sliding vane
o Liquid ring
Approximate application ranges in terms of inlet cubic feet per minute (ICFM) and
discharge pressure for four categories of compressors are shown in Figure 11-1.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
11.1.1 Introduction
· Thermodynamic properties of the gas (or mixture of gases) affect the energy required to
do the compression. The energy requirements affect both the size of the driver and the
mechanical design of the compressor. Both are critical design factors.
· In gases with water vapor, the water content needs to be considered for three reasons:
Equation 11-1 defines the behavior of a perfect gas in terms of variables listed: pressure,
temperature, volume, etc. This is a helpful starting point, although few gases actually are
perfect.
where:
10.73wT
PQ = Eq. 11-2
M
where:
10.73wTZ
PQ = Eq. 11-3
M
At standard conditions (14.7 psia, 60oF), the factor (Z) of most gases is generally assumed to
be 1.0. However, at standard conditions, for example, normal butane has a Zo value of 0.975
(Zo denotes the factor at standard conditions).
Values for Z are available in charts for the gas being compressed. If a chart is not available,
or if the gas is a mixture, generalized compressibility charts may be used. To use these
charts, it is necessary to compute the so-called reduced pressure and temperature as follows:
P
Pr = Eq. 11-4
Pc
and:
T
Tr = Eq. 11-5
Tc
Pr = Reduced pressure
P = Actual absolute pressure, psia
Pc = Critical pressure of the gas, psia
Tr = Reduced temperature
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
The compressibility of some pure gases, notably steam and ammonia, cannot be accurately
predicted using the generalized charts. However, steam tables and charts for pure ammonia
are available. When the water vapor or ammonia content of a mixture is small (5 percent or
less), the generalized charts may be used for the mixture with relatively good accuracy.
For gas mixtures containing hydrogen or helium, effective values of critical pressure and
temperature for helium and hydrogen must be used to derive acceptable accuracy from the
generalized charts.
Knowing the mole fractions in a mixture leads to calculation of several important properties of
the mixture:
Ni
Xi = Eq. 11-6
Nm
where:
i
MC p ( m ) = å X i * MC p ( i ) Eq. 11-7
n =1
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
i
Tc ( m ) = å X i * Tc ( i ) Eq. 11-9
n =1
i
M ( m ) = å X i * M (i ) Eq. 11-10
n =1
A “mole” is actually a number of molecules (about 6 x 1023). A “mole fraction” is the ratio of
molecules of one component in a mixture. For example, if the mole fraction of methane in
natural gas is 0.90, this means that 90 percent of the molecules are methane. Since volume
fractions are equivalent to mole fractions, the mixture is also 90 percent (by volume) methane.
The mixture fractions could also be calculated on a mass or weight basis. The mole (volume)
basis is used in compressor calculations because it is simpler and less confusing.
The molal specific heat is used to determine the k value (ratio of specific heats) as follows:
The k value is often called the adiabatic exponent, and is a value used in the calculation of
horsepower, adiabatic head, and adiabatic discharge temperature. The k value is:
Cp MC p ( m ) MC p ( m )
k= = = Eq. 11-11
Cv MC p ( m ) - Ro MC p ( m ) - 1.986
778
where:
MCp(m) should be taken at the desired temperature (usually the average of suction and
discharge temperature). This aspect will be covered in Isentropic (Adiabatic) Compression.
Note that the k value of the mixture must be determined by first determining the molal heat
capacity of the mixture. It is a common mistake to multiply the k values of the individual gas
components by their respective mole fractions to determine the k value of the mixture.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
The specific gravity of the gas mixture is determined by dividing the molecular weight of the
mixture by that of air.
Mm
S .G. = Eq. 11-12
28.96
11.1.3.3 Humidity
For air compressors, it is usually necessary to account for water vapor content. It is important
to know the moisture content accurately when a process requires a definite quantity of dry air.
Furthermore, the moisture in the inlet air affects the power requirement and water drop-out in
intercoolers and aftercoolers.
Note that water-vapor content must also be accounted for as a component in process streams,
if present. In those cases, the content is usually available from the process group.
The following information discusses how to account for water content in air.
Pv
% R. H = * 100 Eq. 11-13
Psat
where:
Specific Humidity is the ratio of the weight of the water vapor content to the weight of dry air at
the existing conditions of pressure and temperature, and is determined as follows:
Wv 18 Pv Pv
S .H . = = * = 0.622 * Eq. 11-14
Wda 28.96 P - Pv P - Pv
where:
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
For example, if a standard (14.7 psia) psychrometric chart were used for conditions of
5,000 feet elevation (12.23 psia), 80°F dry bulb, the indicated specific humidity would be low
by about 25 percent and the relative humidity by 10 percent.
If the altitude is more than 200 or 300 feet above sea level, the following equation should be
used instead of a psychrometric chart:
P - Pv ( wb )
Pv = Pv ( wb ) - * (t - t wb ) Eq. 11-15
2830 - 1.44t wb
where:
Pv(wb) = Vapor pressure in psia corresponding to wet bulb temperature (from steam
tables)
t = Dry bulb temperature, °F
twb = Wet bulb temperature, °F
Knowing Pv, the relative and specific humidities can be calculated with Equations 11-13 and
11-14. The volumetric or mole percent of the water vapor can be calculated as follows:
Pv
mol % H 2O = * 100 Eq. 11-16
P
The mole percent of dry air is then 100 minus the mole percent of the water vapor. The other
properties of the mixture of air and water vapor (molecular weight, MCp, etc.) may then be
calculated.
· MMscfd
· Moles/hour (MPH)
· scfm
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
· Weight flow
11.1.4.1 MMscfd
MMscfd denotes millions of standard cubic feet per day, where standard means 14.7 psia and
60°F. This notation is often used in gas plant, gas transmission, and refinery applications.
Process engineers often use MPH in material balance computations. (A mole is a fixed
quantity of molecules. This concept greatly simplifies process calculations.) A mole of any
gas occupies approximately 379.4 cubic feet at standard conditions (14.7 psia, 60°F) and it
has a weight in pounds equal to the molecular weight of the gas. For example, a mole of
methane (CH4) would have a volume of 379.4 cubic feet at standard conditions and that
volume would weigh 16.04 pounds. Knowing the moles per hour, the MMscfd may be
determined from:
MPH * 379.4 * 24
MMscfd = Eq. 11-17
10 6
11.1.4.3 scfm
Scfm denotes standard cubic feet per minute and is frequently used in compression work.
11.1.4.4 ACFM
Actual cubic feet per minute (ACFM) at the inlet, often called Q, is related to the physical size
of the compressor. Several design parameters are based on Q. ACFM at inlet is also
abbreviated ICFM. ACFM at the compressor discharge is sometimes of interest, and in this
manual it will be abbreviated DCFM (discharge cubic feet per minute).
However, note that ICFM is the more appropriate term to use when referring to inlet
conditions. In many cases, ACFM is often used interchangeably with ICFM. If there is any
doubt, be sure to get clarification.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
14.7 T1 Z1
Q1 = ACFM = ( scfm) * * * Eq. 11-18
P1 520 Z 0
where:
P1, T1, Z1 = Absolute pressure (psia), absolute temperature (°R), and compressibility at
the condition of interest.
Zo = Compressibility at standard conditions.
Weight flow (w) may be calculated from any conditions of interest using the following equation
(derived from Equation 11-3):
P1Q1 M
w= Eq. 11-19
10.73T1Z 1
Zo is often taken as 1.0 regardless of its actual value. It is important to use the same value for
Zo in all calculations. Although the discrepancy would generally be no more than one or two
percent in a single calculation, it could be compounded after conversions are made back and
forth by several parties involved with the compressor project. Be consistent.
When specifying compressors for purchase, it is best to provide the manufacturer the weight
flow, gas analysis, inlet pressure and temperature, and the desired discharge pressure.
If standard volume flow (MMscfd or scfm) is used, the standard conditions should be stated
explicitly.
Standard conditions of 14.7 psia and 60°F have been referred to in foregoing paragraphs.
This standard is prevalent in the USA in the petroleum and natural gas industries. API
Standards use these standard conditions. However, in working with air compression systems,
"Standard Air" as adopted by ASME is defined as air at a pressure of 14.7 psia, a temperature
of 68°F, and a relative humidity of 36%. These conditions correspond to an air density of
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
In the metric system, the normal cubic meter per hour is a widely used term for flow. Normal
refers to conditions of 760 mmHg Absolute (14.7 psia) and 0°C (32°F). Weight flow is
generally stated in kilograms per hour. The SI system uses kilopascals for pressure (1 kPa =
0.145 psi). Other metric units such as kilograms per square centimeter or Newtons per square
meter are used.
Another common use of “standard” conditions is in the determination of the ISO power rating
of combustion of gas turbines. “Standard” conditions in this case are atmospheric pressure of
760 mm Hg Absolute, 15°C, and 60 percent relative humidity.
ISO power ratings of turbines are only useful in comparing the relative output of different
turbine models. ISO power shall never be used in calculations where shaft power is required.
When shaft power is required, the ISO power shall be replaced with the gas turbine site rated
power.
The site rated power includes the power losses due to inlet and exhaust system components,
ambient temperatures, atmospheric pressure, and relative humidity. The site rated power of a
turbine may only be 80 percent of its ISO power.
The two actual methods used to calculate thermodynamic relationships are isentropic
(adiabatic) and polytropic. These calculations are the basis for determining capacity, driver
size, and mechanical design. The following explains the differences and when they are used.
Figure 11-2 shows the compression paths of three theoretical processes: isothermal,
isentropic, and polytropic. The theoretical work needed for isothermal compression is
described by the area ABEF. It can be seen that the isothermal work is appreciably less than
that of the isentropic area ABDF. Similarly, the isentropic area is smaller than the polytropic
area ABCF.
These differences can be attributed to differences in heat transfer (cooling). The isothermal
process would require continuous cooling during compression to negate all of the temperature
rise. In an actual compressor the theoretical isentropic discharge temperature can sometimes
be achieved by a moderate amount of cooling during compression. Even so, the resultant
process will not be purely isentropic due to other losses in an actual machine. The polytropic
path BC best represents an actual process where there is no cooling during compression.
In practice, the isentropic and polytropic methods of analysis are both usable for designing
and predicting the performance of compressors.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
The polytropic process is typically applied to dynamic compressors in which there is no cooling
during the compression that takes place in any individual stage. (There may be cooling
between each stage or series of stages, but not within a given stage.)
“Head” is a term often used for the work input to the compression process. The units of head
are foot-pounds (force) divided by pounds (mass). In general practice, the unit of head is
usually taken as feet. The theoretical head for an isothermal process is:
where:
P2
r= = pressure ratio
P1
Equation 11-22 may be used to evaluate other compression processes with various amounts
of cooling.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
Isentropic means constant entropy. Adiabatic describes a process wherein no heat is added
or subtracted. For the sake of this discussion, it can be assumed that isentropic and adiabatic
are the same (although different thermodynamically).
where:
C = Constant
k = Ratio of specific heats
k -1
RT1 Z1 + Z 2
H ad = * (r k
- 1) * Eq. 11-24
k -1 2
k
where:
ft - lbs
Had = adiabatic head, abbreviated as “ft.”
lbm
k -1
X =r k
-1 Eq. 11-25
where:
where:
wH ad
Ghp = Eq. 11-28
33000h ad
where:
Notice that Equation 11-24 has been corrected by an average compressibility, (Z1 + Z2)/2.
Averaging is a fairly accurate approximation of the correction required.
Because of the non-ideal (non-perfect) behavior of many gases, the k exponent does not
remain constant during compression. For air, diatomic gases, and inert gases, the change in k
is small when the pressures are moderate. However, for most hydrocarbon gases, the
variance of k during compression is substantial. The usual correction is to calculate k using
MCp at the average of the compressor (or stage) suction and discharge temperature.
Using the MCp at atmospheric pressure and average compression temperature for compressor
head and power calculations is sufficiently accurate for most applications. However, for very
high pressures or other unusual conditions, further corrections are necessary. Such
corrections will be covered under Polytropic Compression.
Since the change in entropy is not zero in an actual adiabatic compression process, an
adiabatic efficiency (had) is used in Equations 11-27 and 11-28. In order to calculate MCp at
average compression temperature, it is necessary to estimate the adiabatic efficiency to arrive
at a discharge temperature per Equation 11-27. If the estimate is inaccurate, a second
iteration may be required.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
Thermodynamic-property diagrams account directly for deviations of a real gas from ideal
relationships. These diagrams are a plot of gas properties, commonly including: enthalpy,
entropy, pressure, and temperature. Occasionally, a special diagram is developed for a widely
used gas mixture such as a refrigerant. However, note that few charts are available for
mixtures, and this method is therefore not commonly used for hydrocarbon mixtures.
When a diagram is used to predict changes of state during compression, compressibility and
variance of k are not needed because these variables are already factored into the diagrams.
In general, then, this method is more accurate than Equation 11-24 and when charts are
available, it is certainly more convenient. Diagrams are often used in compressor calculations
for heavier hydrocarbon gases such as propane and propylene that tend to deviate
considerably. Diagrams for many pure gases are well established.
The following equations pertain to the use of diagrams for compressor calculations. Note that
for an isentropic process, there is no change in entropy, S.
where:
where:
Dh( theo )
h2 = + h1 Eq. 11-31
h ad
where:
Note that the actual discharge temperature T2 may now be found on the thermodynamic
diagram at the point corresponding to h2 and P2.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
The previous discussion of the adiabatic process showed that its relationships need
mathematical corrections to make credible predictions. The corrections are compromises
between theory and actual gas deviations, and they do not always yield sufficiently accurate
predictions for some types of applications. Unfortunately, even polytropic compression
requires adjustments to account for the non-ideal behavior of many gases.
where:
n = Polytropic exponent
k -1
hp = k Eq. 11-34
n -1
n
where:
hp = Polytropic efficiency
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
where:
n -1
T 2=T 1r n
Eq. 11-36
wH poly
Ghp = Eq. 11-37
33000h poly
A thermodynamic diagram can be used for a polytropic calculation by first determining the
adiabatic head Had using Equations 11-30 and 11-32. Polytropic head Hpoly can then be
determined by:
hp
H poly = H ad Eq. 11-38
h ad
k -1
r k
-1
h ad = k -1
Eq. 11-39
kh p
r -1
From the foregoing discussion, it should be obvious that k is not equal to n. In some of the
early compressor publications, the k and n exponents were erroneously treated as the same
value. This error may have been one of nomenclature. At any rate, it is important to
recognize that k is associated with the adiabatic process, and n with the polytropic process.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
Some gases have extraordinarily large deviations from ideal behavior near their critical
conditions or at high pressures. For example, carbon dioxide at 1500 psia and 100°F has a
compressibility factor, Z, of about 0.27. Furthermore, if the temperature is increased by only
20°F, there is a 40 percent increase in the compressibility factor. If a small amount of
methane is mixed with carbon dioxide, the compressibilities change significantly, and
predictions of these compressibilities by generalized charts is not reliable.
There are a few compressor applications that must deal with widely deviating gases. The values
for Z and k vary so much that conventional methods of calculations for the compressor gas
properties do not have sufficient accuracy. For these somewhat rare occasions, various
equations of state are used. There are a number of these empirical relationships in existence,
and each set of relationships tends to have some advantages over the other sets for certain gas
compositions.
All compressor manufacturers calculate gas properties with their own programs. When they
quote performance of their equipment, their predictions will often be different from calculations
by Bechtel’s process group. Vendor’s predictions will form the basis for any performance tests
or guarantees.
There are two types of compressors, defined by either an axial (horizontally split) or radial
(vertically split) casing construction.
The top half of the axially-split casing is removed to access the internals. The stationary
diaphragms are installed individually in the top and bottom half of the casing. Main process
connections may be located either in the top or bottom half.
The axially-split down-connected casing has the advantage of allowing removal of the top half
for access to the rotor without requiring removal of major process piping.
Radially-split or barrel compressors have a complete cylindrical outer casing. The stationary
diaphragms are assembled around the rotor to make up an inner casing, and installed inside
the outer casing as a unit, contained by heads or end closures at each end. Some later
designs hold the heads in place by use of shear rings. The internal assembly is frequently
referred to as the bundle.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
API 617 (Centrifugal Compressors) requires the use of the radially-split casings when the
partial pressure of hydrogen at the maximum allowable working pressure exceeds 200 psig.
Other factors which influence the axially/vertical split decision include the absolute operating
pressure of the service and ease of maintenance for a particular plant layout.
Both the axially and radially-split casing designs allow removal of bearings and shaft-end seals
for maintenance without disassembly of major casing components.
11.2.2 Surge
Surge is a condition of unstable flow within the compressor typified by rapid flow and pressure
oscillations, rapidly rising temperature, thrust reversals and often damage. Surge at full
operation can be caused by process upsets, jammed valves, molecular weight changes or
intercooler failure, and at reduced operation by start/stops or load changes. Surge is not
limited to reduced throughput and can occur at full operation. It occurs when the imposed
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
Dedicated surge control systems are available to dynamically monitor surge approach and
prevent surge as well as to provide optimum compressor operation. Controls for compressors
in series must be configured such that one stage doesn't force another into surge. Controls
for compressors in parallel should maintain both machines an equal distance above surge for
optimum load sharing, rather than base loading one machine or simply dividing the flow
equally.
· Speed variation – Most efficient and sometimes combined with adjustable guide vanes
Performance and surge controls can conflict in their manipulation of the compressor operating
point and must be decoupled to operate efficiently. Similarly, performance controls must
respect other limits such as maximum driver power, maximum discharge pressure and
temperature, and minimum suction pressure.
11.2.3 Stonewall
Another major factor affecting the theoretical head-capacity curve is choke or stonewall. The
terms surge and stonewall are sometimes incorrectly used interchangeably, probably due to
the fact that serious performance deterioration is observed in either case.
A compressor stage is considered to be in stonewall, in theory, when the Mach Number equals
one. At this point the impeller passage is choked and no more flow can be passed. Industry
practice normally limits the inlet Mach Number to less than 0.90 for any specified operating
point.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
Positive Displacement Compressor selection involves a great deal of cooperation between the
Process, Project/Systems and Mechanical Groups to select an optimum machine.
· Rod loading
Discharge temperature is the most important factor affecting the number of stages. Class A
and B reciprocating compressors are generally limited to 300°F for most gases. API 618
further limits the discharge temperature of hydrogen-rich gases to 275°F. These limits restrict
the stage pressure ratios. It is often necessary to increase the number of stages so that
intercoolers can be added to keep the discharge temperature within limits, while achieving the
required overall pressure ratio.
· Reciprocating compressors are already highly efficient, and adding an intercooler adds
pressure drop which offsets the power savings
The rod-load limit can affect the number of stages since the combined rod loading is related to
the differential pressure across the cylinder. Increasing the number of stages obviously
reduces the differential pressure of each stage.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
Occasionally a given pressure ratio might be achieved in one stage with satisfactory discharge
temperature and rod loading, but an actual cylinder does not exist to handle both the capacity
(ICFM) and pressure. In these situations, it is necessary to use two stages, or use two smaller
single stage cylinders depending on hardware and economics.
Pressure profiles for vapor systems are prepared similar to pump hydraulic profiles. Low
pressure systems can be particularly critical as pressure drops available are very low. Many
clients require pressure profiles for plant control as well as design.
Determine pressure drops through equipment and piping from vendor data or estimates,
arrangements and the Linesize program are similar. Elevation differences are often ignored
except in low available pressure drop or high-pressure/high-density systems.
11.5 FANS
Fans are used for low pressures, in general, for pressure heads of less than 0.5 psi. They are
usually classified as of the centrifugal type or the axial-flow type. Both types are used for
ventilating work, supplying draft to boilers and furnaces, moving large volumes of air or gas
through ducts, supplying air for drying, conveying material suspended in the gas stream,
removing fumes, etc.
These are made in three general types, the straight-blade, or steel-plate, the forward-curved-
blade fan, and the backward-curved-blade fan.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
These fans have rotors of comparatively large diameter with a few (5 to 12) radial blades
resembling paddle wheels. These operate at comparatively low speed. They are often used
in exhaust work, particularly where wastes are carried in the air stream.
These fans are usually of the multi-blade (20 to 64) "Sirocco" type. The rotors are of smaller
diameters and they operate at higher speeds than straight-blade units. They have less
stability than backward curved blades.
These fans are of the multi-blade (10 to 50) type. Such fans have a wide range of usefulness.
These fans are made in two general types, disk type and propeller type.
Disk-type fans have plain or curved blades similar to an ordinary household fan. They are
usually for general circulation or exhaust work without ducts.
Propeller-type fans have blades similar to aeronautical designs. Such fans may be two
staged.
The theory of operation of a centrifugal fan is much like that of a centrifugal pump, the
pressure developed arising from two sources. These are centrifugal force due to the rotation
of an enclosed volume of air or gas, and velocity imparted to the air or gas by the blades and
partly converted to pressure by the volute or scroll shaped fan casing.
The centrifugal force developed by the rotor produces a compression of the air or gas which,
in fan engineering, is called the static pressure. The amount of this static pressure developed
depends on the ratio of the velocity of the air leaving the tips of the blades to the velocity of the
air entering the fan at the heel of the blades. Therefore, the longer the blades, the greater the
static pressure developed by the fan.
Operating efficiencies of fans are in the range of 40 to 70 percent. Operating pressure is the
sum of the static pressure and the velocity head of the air leaving the fan. It is generally
expressed in inches of water gauge, or in ounces per square inch.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
144Q( P2 - P1 )
Air hp = = 0.000157Q * developed head (in inches of water)
33000
Eq. 11-40
Air hp
Shaft hp = Eq. 11-41
Efficiency
where:
The performance of a centrifugal fans varies with changes in conditions such as temperature,
speed, and density of the gas being handled. It is important to keep this in mind in using the
catalog data of various fan manufacturers, since such data are usually based on assumed
standard conditions, such as 70°F and 29.92 in. barometric pressure, or 68°F and 50 percent
relative humidity. Corrections must be made for variations from these assumed standards.
· Horsepower and pressure vary inversely as the absolute temperature (speed and
capacity being constant)
· Horsepower and pressure vary directly as the density (speed and capacity being
constant)
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
It is common practice among fan manufacturers to publish complete data in tabular form
showing capacities, pressures, speeds, and horsepowers of their fans under standard
conditions of temperature and air density. These tables are of great use to the heating and
ventilating engineer and to others who specialize in fan engineering. Those who do not
specialize along these lines, should not attempt to select fans from these tables. The proper
course to follow is to put full data concerning the job to be done in the hands of fan
manufacturers and allow them to specify the fan they are willing to guarantee to do the
required work at the best obtainable economy. A comparison of several such proposals from
manufacturers will indicate the best choice.
In order to provide preliminary data for vendor quotations, compressor service conditions must
be developed before equipment layouts are available. While making the compressor
calculations, equipment design pressures can be determined by development of the system
pressure profile.
For convenience and ease in maintaining records, the compressor calculation has been
prepared to indicate the original calculation I, the purchase calculation II, and the final
calculation III. Calculations II, III are generally made by the Project Engineer. Calculation I
may be prepared by Process Engineering.
Note: Calculation III will be done only for blowers and compressors in critical service. For non-
critical applications, Calculations I and II alone will be performed. After Calculation II has been
done and changes occur in plot plan or system design by addition or deletion of equipment
affecting a non critical compressor circuit, the necessity of Calculation III shall be explored. A
decision can be taken in a short time by re-running the PPS program and by substituting new
values in Calculation II. If results indicate a doubt in the adequacy of contingency, Calculation
III should be performed.
Compressors that are in critical service will be defined at the beginning of each project. These
critical services normally involve more than one destination, multiple heat exchangers in
series/parallel, and a multitude of control valves. Any inadequacy in flow or head of such
applications will not allow sustained plant operation.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
· Process
· Project
· Machinery
The Project Engineer usually prepares the Calculation I using Linesize Program of Pressure
Profile Suite (PPS). It's important that any alternate service conditions be specified as different
cases. These alternate service conditions should be shown as a range of flowrates (min.,
max.) or different process condition. The Project Engineer then assigns a drawing number to
the Compressor Calculation Sheet, and completes the calculation, system sketch, and
pressure profile. The Project Engineer will prepare the pressure profile in psia on the lower
graph section of the Compressor and Control Valve Design Sheet.
It is important to remember that vendor information for vessels, exchangers, heaters, etc., is
normally not available at this stage. Therefore, engineering judgment is required to set design
pressures for this equipment during the early stages.
However, the compressor datasheet prepared by Process Engineering Group can be treated
as Compressor Calculation I to save cost, if specified in the Project Work Instruction.
11.6.2 Calculation II
The second phase of calculations is made by the Project Engineer using the PPS program
just prior to the purchase of the compressors. Compressor quotations have been received with
estimated performance curves. In addition, the quoted pressure drops for exchangers, etc.,
may be available. Changes in equipment design pressures and rated compressor head
should be made as early as possible and preferably prior to start of vendor's engineering and
fabrication to minimize extra costs and/or delivery delays. The Project Engineer then assigns a
drawing number to the Compressor and Control Valve Design Sheet, and completes the
calculation, system sketch, and pressure profile. The pressure profile must be presented in
psia on the lower graph section of the Compressor and Control Valve Design Sheet, showing
the estimated system pressure profile at normal flow or min and max flow conditions.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
Equipment pressure drops are based on equipment selected for purchase and piping studies.
After the Project Engineer has completed the calculation and adjusted the system pressure
profile for the actual compressor curves, the calculation sheet is issued as "Design Basis for
Purchase."
The compressor calculation III will also be performed by the Project Engineer using the PPS
program once equipment layouts and isometric drawings are available. The Project Engineer
is responsible for verifying the specified compressor service conditions by using the
manufacturer's equipment pressure drops, and line losses calculated by the Linesize program
in PPS using the length and fittings taken from isometric drawings. The line loss calculations
from simplified piping sketch can also be used if isometric drawings are not available. The
pressure profile is firmed up to indicate final design and final data is developed in the
Calculation III Compressor and Control Valve Design Sheet.
It is most important to check compressor maximum head versus mechanical design pressure
of all affected systems, specially when revisions are made to the system.
All compressors should be rated for 110% of normal flow. This is Bechtel's standard practice
and must be implemented, unless specified otherwise by the Client.
· Exchangers
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
A 10 psi pressure drop may be assumed for high pressure, 2-5 psi for low pressure and
0.5-2 psi for atmospheric coolers.
· Orifice meters
A nominal pressure drop of 2 psi (corresponds to 100-inch meter orifice) will be used for
all orifice meters.
· Other equipment
For equipment in which pressure losses vary considerably (heaters, filters, etc.) consult
Process Engineering and Vendor specifications.
The selection of the pressure drop through control valves is a function of the dynamic losses in
the system. The dynamic losses are the pressure drops which vary with flow, such as
through piping, heat exchangers, and filters. (These do not include the pressure drop through
the control valves.)
In practice, the losses in most compressor discharge systems are in a range that result in using
the basis of 50% of the system dynamic loss at normal flow. Pressure drop through equipment
is determined based on normal flow. A check should be made at rated flow to insure a minimum
of 10 psi control valve pressure drop is available. If the check reveals a deficiency, the
pressure drop at rated flow should be set at 10 psi and the pressure drop at normal flow
increased accordingly.
Decreasing the percentage of the system dynamic loss used for the control valve also
decreases the ability of the valve to control.
Line losses must be calculated by the Linesize program. For estimating line losses, discharge
lines, assume 1.0-1.5 psi/100 ft for pressures above 100 psig and 10% of discharge pressure
for pressures below 100 psig. Suction lines 1.0-1.5 psi/100 ft for above 100 psig (including
recycle lines) and 0.1-0.3 psi/100 ft for 1 atm - 50 psig. (These losses are inclusive of all
fittings.)
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
A simple approximation of the horsepower for estimating purposes may be obtained from the
formula.
P2
hp = 0.0044 p1Q ln( ) Eq. 11-43
P1
where:
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in BecRef for current revisions.