UL Code Numbering System
UL Code Numbering System
Numbering System
The Importance of Listed Systems Designs
Think of a listed systems design as a universal standard, which allows
for the sale of firestopping products for exact applications as outlined
in the systems designs. If a product does not have a third party listed
systems design to cover a specific application, the product cannot be
used for that application, no matter how many listings it has for other
uses.
The listing also provides a trail of liability to the listing agency and the
manufacturer. If you have installed or passed an application without a
listing you have just accepted all liability associated with an improper
installation.
The numeric grouping will use the following sequences of numbers for
the penetrating items shown:
0000-0999 None
1000-1999 Metal pipe, conduit, or tubing
2000-2999 Non-metallic pipe, conduit, or tubing
3000-3999 Cables
4000-4999 Cables in a cable tray
5000-5999 Insulated pipes
6000-6999 Miscellaneous electrical penetrants
6000-7000 Miscellaneous mechanical penetrants
8000-8999 Mixed penetrants containing any of the above
9000-9999 Reserved for future use
Penetrating Items
Conduit, as a penetrating item, is intended for use with electrical
conductors, in accordance with the National Electrical Code. Electrical
conductors may not be used without conduit unless permitted by the
National Electrical Code and when the conductors are specifically
described in the firestop system.