Transient Voltage ST-CLP##AxDIN-B

Surge Suppressors By:


Data Line Models
Current Loop/Signal Line protection device with Discrete All-Mode Protection

P.O.
P.O. BoxBox 1212
330607
Destin, FL 32540-1212
Ft. Worth, TX 76163
888-987-8877
Phone: 817.483.8497
888-900-8879
Fax: 817.572.2242
www.surgesuppression.com
www.sinetamer.com

The Series CLP##A2DIN-B devices are designed to protect current loop process instrument, data transmission,
control, and signal line circuits. These devices are intended for installation as close to the electrical power source
of the equipment as possible so as to allow for a common point for grounding.
This device is for circuits with up to 3 pair of signal lines connected via the detachable terminal strips provided,
making installation a breeze. A ground lug is provided on the side of the unit to insure a low impedance ground
discharge path.
The unique design of these devices makes them among the most versatile TVSS devices on the market with
superior performance specs and a warranty that is second to none.

GENERAL
Description: Series wired transient voltage surge suppressor with encapsulated Optimal Response
Network circuitry for protection of current loop and data/signal type circuits.
Application: Designed for use on data, signal, current loop and control circuits to protect equipment
from damaging transients generated between terminals and equipment in the data
collection/transmission system.
Warranty: 25 Years Unlimited Free Replacement
Unit Listing: Listed to UL497B

MECHANICAL
Enclosure: Plastic, UL 94-5VA
Mounting: DIN rail mounting foot
Connection Method: Wire clamping detachable box terminals located at the input and output sides of the
device. Wire size: Lines # 12-22 AWG, Ground # 6-12 AWG.
Shipping Weight: < 1 lbs

CIRCUITRY
Circuit Design: Series wired design incorporating discrete all mode protection and utilizing our
encapsulated Optimal Response Network design to provide lowest possible let-through
voltages. All suppression circuits are encapsulated in our high dielectric compound to
assure long component life and complete protection from the environment and/or vibration.
Protection Modes: Dedicated protection components and circuitry for each mode. Discrete each L-L (Normal
Mode) and each L-G (Common Mode)

PERFORMANCE
Maximum Continuous
Operating Voltage: 7.5, 15, 36, 54, and 140 V
Maximum Continuous
Operating Current: 500 mA
Series resistance: 5 Ohms per wire (10 Ohms loop)
Maximum Data Rate: Up to 2 Mbps
Peak Surge Current per Pair: L-L 10 kA, L-G 10 kA

Because we are constantly seeking to improve our products, specifications are subject to change at any time.
 2015ECS International Inc. Specification Last Changed 05/2015
Table of Maximum Suggested Operating Limits, Data Rate & Additional Device Resistance
Maximum Digital/ Analog Data
Maximum Continuous Rates
Nominal System * CLP##AxDIN-B Operating Voltage Maximum Continuous Vs.
Operating Voltage Operating Current
(MCOV) Additional Series Resistance
Operating Voltage
(Vnom) Model Number (MCOC)
Voltage Voltage 2 Mbps / 20 MHz:
(L-L) (L-G)
5 Ohms per line
0 > Vnom ≤ 6 ST-CLP5AxDIN-B ± 7.5 Vpk ± 7.5 Vpk 500 mA
(10 Ohms per pair/loop)
5 Ohms per line
6 > Vnom < 15 ST-CLP12AxDIN-B ± 15 Vpk ± 15 Vpk 500 mA
(10 Ohms per pair/loop)
5 Ohms per line
15 ≤ Vnom < 32 ST-CLP24AxDIN-B ± 36 Vpk ± 36 Vpk 500 mA
(10 Ohms per pair/loop)
5 Ohms per line
32 ≥ Vnom < 60 ST-CLP48AxDIN-B ± 62 Vpk ± 62 Vpk 500 mA
(10 Ohms per pair/loop)
5 Ohms per line
60 ≥ Vnom ≤ 190 ST-CLP140AxDIN-B ± 140 Vpk ± 140 Vpk 500 mA
(10 Ohms per pair/loop)
*Notes: The lower case “x” is set to: 2, 4 or 6 to specify the number of terminals to be protected. Odd numbers of conductors require the use
of the next higher even numbered model or an additional like model. All CLP##AxDIN-B models use 6-position connectors with the appropriate
number of labeled working terminals specified by “x”.

Let-Through Voltages Using ANSI/IEEE C62.45 & C62.41 Test Environment: Static,
positive polarity. All voltages are peak (10%).

Cat. B Impulse Wave


Model Test Mode
6 kV, 3 kA

L-G < 20
ST-CLP5AxDIN-B
L-L < 20
L-G < 30
ST-CLP12AxDIN-B
L-L < 30
L-G < 40
ST-CLP24AxDIN-B
L-L < 40
L-G < 80
ST-CLP48AxDIN-B
L-L < 80
L-G < 160
ST-CLP140AxDIN-B
L-L < 160

Model Dimensions:
4.5” Wide x 4.5” High x 1.4” Deep
Actual unit may vary from picture

Because we are constantly seeking to improve our products, specifications are subject to change at any time.
 2015ECS International Inc. Specification Last Changed 05/2015