Provided: XT XB YT YB
Provided: XT XB YT YB
X-DIRECTION Y-DIRECTION
Check for Reinforcement for Bending Moment TOP STEEL BOT.STEEL TOP STEEL BOT.STEEL
M XT M XB M YT M YB
Factored Moment(kN-m)(Modified as per Wood crieteria) 221.0 -449.4 247.8 -344.6
Plate number 244 76 244 244
Factored load combination 580 635 580 519
Grade of concrete,f ck (N/mm2 ) 25 25 25 25
2
Grade of steel,fy (N/mm ) 500 500 500 500
Width of section,b (mm) 1000 1000 1000 1000
Thickness of section,h(mm) 700 700 700 700
Cover to reinforcement(mm) 50 50 50 50
Mu/bd2 0.537 1.098 0.633 0.891
Area of Design steel required(mm2) 814 1708 940 1332
Area of Minimum steel required(mm2 ) 840 1190 840 1190
2
Area of steel provided(mm ) 1005 2094 1005 1608
Dia of Main rebar(mm) 16 20 16 16
Spacing of main bars 200 150 200 125
Effective depth,d(mm) 642 640 626 622
%pt provided 0.157 0.327 0.161 0.259
Check for one way shear stress at d distance from pedestal in X direction at critical Section:
Governing load case from summary force = 635
The values of shear stress across the section are given below for the governing load case
v = 0.474 N/mm2
%pt provided = 0.327
c from Table 19 of IS 456-2000 = 0.410 N/mm2
Enhanced shear strength as per IS:456 clause 40.5 = 0.819 N/mm2
Safe in shear
Check for one way shear stress at d distance from pedestal in Y direction at critical Section:
Governing load case from summary force = 519 1.5*(D
The values of shear stress across the section are given below for the governing load case
v = 0.413 N/mm2
%pt provided = 0.259
c from Table 19 of IS 456-2000 = 0.370 N/mm2
Enhanced shear strength as per IS:456 clause 40.5 = 0.740 N/mm2
Safe in shear
Cheque for Punching Shear due to Columns
28/56
Check for Sliding
Area of combined fooitng CF1 = 38.250 m2
Thickness of combined fooitng CF1 = 0.7 m
Elevation of bottom of footing = -2 m
Thickness of soil considered CF1 = 1.1 m
Load due to soil (1) = 663.156 kN
Load due to selfweight (2) = 669.375 kN
Minimum vertical load from super structure (3) = -557 kN
Load combination = 120 0.9*(DL+EQ)+1*(TL+W2)
Corresponding horizontal load = 132 kN
Total vertical load (1) + (2) + (3) = 642.278 kN
Friction coefficient = 0.4
Factor of safety against sliding = 0.4 x 642.2779/132
1.9463
Safe in sliding