Experiment 2: Tripping Characteristics of Fuse & MCB
Experiment 2: Tripping Characteristics of Fuse & MCB
Experiment 2:
Group I4 , EE ‘A’
ID e20160160
Year
2019-2020
Institute of Technology of Cambodia Department Electrical and Energy
Contents
I. Objective............................................................................................................................. 2
3. Create fault on bus 2 (B2) and perform short circuit analysis mode to see the capacity
4. Obtain and explain the graph and sequence of protective device when: ........................ 8
V. Conclusion ........................................................................................................................ 16
1
Institute of Technology of Cambodia Department Electrical and Energy
Experiment 2
I. Objective.
To study the time current characteristics of Fuse and MCB for given network.
Practice to use ETAB software for analyses power system.
II. Definition.
Circuit breaker (CB) is an automatically switch off the electrical circuit during
abnormal condition of the network in overload condition as well as faulty condition.
CB is much more sensitive to overcurrent that fuse. The switch operating knob of CB
comes at its off position during tripping, the faulty zone of the electrical circuit can
easily be identified. But in case of fuse, fuse wire should be checked by opening fuse
grip or cutout from fuse base for confirming the blow of fuse wire. The quick restoration
of supply cannot be possible in case of fuse as because fuses have to be rewire able or
replaced for restoring the supply. But in the case of CB, quick restoration is possible by
just switching on operation mode.
2
Institute of Technology of Cambodia Department Electrical and Energy
III. Parameters
3
Institute of Technology of Cambodia Department Electrical and Energy
IV. Procedure.
1. Construct the circuit as shown in circuit diagram in “Edit mode”.
According to the value on the table above, we get this Topology:
For protection system such as: circuit breaker, over current relay and fuse must
compared with component’s rating.
4
Institute of Technology of Cambodia Department Electrical and Energy
5
Institute of Technology of Cambodia Department Electrical and Energy
3. Create fault on bus 2 (B2) and perform short circuit analysis mode to see the capacity
of the fault current in B2.
6
Institute of Technology of Cambodia Department Electrical and Energy
7
Institute of Technology of Cambodia Department Electrical and Energy
4. Obtain and explain the graph and sequence of protective device when:
a. Three-phase faults occur on the motor.
8
Institute of Technology of Cambodia Department Electrical and Energy
When the fault occurs on the motor we see CB3 off. For CB2, Relay1 and Fuse1 are
used for back up as we can on the table above.
9
Institute of Technology of Cambodia Department Electrical and Energy
10
Institute of Technology of Cambodia Department Electrical and Energy
When the fault occurs on the bus3 we see CB2 off. For Fuse1 and Relay1 are used for
back up as we can on the table above.
11
Institute of Technology of Cambodia Department Electrical and Energy
12
Institute of Technology of Cambodia Department Electrical and Energy
When the fault occurs on the Transformer we see Fuse1 off. For Relay1 is used for
back up as we can on the table above.
13
Institute of Technology of Cambodia Department Electrical and Energy
14
Institute of Technology of Cambodia Department Electrical and Energy
15
Institute of Technology of Cambodia Department Electrical and Energy
V. Conclusion
This experiment provides us a lot of benefit about how to protect in power system, works
and Characteristics such as Over Current Relay (OCT), Main Circuit Breaker (MCB), Circuit
Breaker (CB) and Fuse. They have different usages yet they protect the system when fault
occur. Moreover, we can understand same technique of using ETAP software about setting
component for design power system to reach an appreciation value. This experiment is very
significant for students to understand next experiment.
16