Micro-Controller X Model: PXR4, PXR7: Instruction Manual
Micro-Controller X Model: PXR4, PXR7: Instruction Manual
Micro-Controller X Model: PXR4, PXR7: Instruction Manual
Thank you for your purchasing “Fuji Digital Temperature Controller.” Please check that the product is exactly the one
you ordered and use it according to the following instructions. (Please refer to a separate operation manual for
details.) Dealers are cordially requested to ensure the delivery of this Instruction Manual to hands of the end-users.
NOTICE
The contents of this document may be changed in the future without prior notice.
We paid the utmost care for the accuracy of the contents. However, we are not liable for direct and indirect
damages resulting from incorrect descriptions, omission of information, and use of information in this document.
CONTENTS
CONTENTS ...................................................... 1 6-3 Self-tuning ............................................. 21
Check of specifications and accessories .......... 2 6-4 Alarm function [option] .......................... 23
The related documents ..................................... 2 6-5 Ramp/soak function [option] ................. 25
Safety Precautions ............................................ 3 6-6 Communication function [option] .......... 26
Index ............................................................. 9 6-7 Digital input (DI function) [option] .......... 27
1. Installation/mounting ................................... 10 6-8 Other function ....................................... 28
2. Wiring .......................................................... 12 6-9 Re-transmission output function ........... 29
3. Usage (Read before using) ......................... 13 6-10 Remote SV function .............................. 29
4. Display and operation ................................. 14 7. Setting of input type and control algorithm ..... 30
5. Setting methods of temperature and 8. Error indications ............................................. 32
parameters ........................................... 16 [Table 1] Input type code ................................ 33
1st block parameter ..................................... 16 [Table 2] Control output action code ............... 33
2nd block parameter ................................... 17 [Table 3] Input range (Standard range) .......... 34
3rd block parameter .................................... 18 [Table 4] Alarm action type code .................... 35
6. Functions .................................................... 19 [Table 5] Control operation type code ............ 36
6-1 ON/OFF control ................................. 19 PXR Model Code Cofiguration ....................... 37
6-2 Auto-tuning (AT) ................................. 20 Specification ................................................... 38
–1–
Check of specifications and accessories
Before using the controller, check if the type and specifications are as ordered.
(A table of Model code configuration is given in Page 37).
Check that all of the following accessories are included in the package box.
–2–
Safety Precautions
Before using this product, the user is requested to read the following precautions carefully to ensure the
safety. Safety precautions must be taken by every user to prevent accidents.
The safety requirements are classified into “Warning” and “Caution” according to the following interpreta-
tions :
–3–
1. Warning
1.1 Installation and wiring
• This controller designed to be installed at the following conditions.
• The controller must be installed such that with the exception of the connection to the mains, creepage
and clearance distances shown in the table below are maintained between the temperature probe
and any other assemblies which use or generate a voltage shown in the table below.
Failure to maintain these minimum distances would invalidate the EN 61010 safety approval.
• If the voltage shown above exceeds 50Vdc (i.e. hazardous voltage), the basic insulation is required
between all terminals of this controller and the ground, and supplementary insulation is required for
the alarm output.
Isolation class of this controller is as shown below. Be sure to check that the isolation class of the
controller satisfies your requirements before installation.
–4–
• If there is a danger of a serious accident resulting from a failure or a defect in this unit, provide the unit
with an appropriate external protective circuit to prevent an accident.
• The unit is normally supplied without a power switch and fuses.
Make wiring so that the fuse is placed between the main power supply switch and this controller. (Main
power supply: 2 pole breaker, fuse rating: 250V, 1A)
• When wiring the power supply terminal, use vinyl insulated 600 volt cable or equivalent.
• To avoid the damage and failure of controller, supply the power voltage fitting to the rating.
• To avoid an electric shock and controller failure, do not turn ON the power before all wiring is com-
pleted.
• Be sure to check that the distance is kept to avoid electric shock or firing before turning the power ON.
• Keep away from terminals while the circuit is energized in order to avoid an electric shock and a
malfunction.
• Never attempt to disassemble, fabricate, modify, or repair this unit because tampering with the unit
may result in a malfunction, electric shock, or a fire.
–5–
2. Caution
2.1 Cautions on installation
Avoid the following places for installation.
• a place where the ambient temperature may reach beyond the range of from 0 to 50°C while in
operation.
• a place where the ambient humidity may reach beyond the range of from 45 to 85% RH while in
operation.
• a place where a change in the ambient temperature is so rapid as to cause condensation.
• a place where corrosive gases (sulfide gas and ammonia gas, in particular) or combustible gases are
emitted.
• a place where the unit is subject directly to vibration or shock.
(Vibration or shock may cause output relay malfunction.)
• a place exposed to water, oil, chemicals, steam and vapor.
(if immersed with water, take the inspection by sales office to avoid an electr-ical leakage and firing)
• a place where the unit is exposed to dust, salt air, or air containing iron particles.
• a place where the unit is subject to intereference with static electricity, mag netism, and noise.
• a place where the unit is exposed to direct sunlight.
• a place where the heat may be accumulated due to the radiation of heat.
Packing Packing
Unit Unit
Packing
Packing
PXR4TAA1-1YM00-D
PXR4TAA1-1YM00-D
MFD 2000-04
MFD 2000-04
No. 000001T
No. 000001T
Case
Case
Front Case Panel Panel Mounting Screw
bracket (Bad) (Good)
–6–
PXR7
• Please attach the PXR7 with the included Fixtures (2 pieces) to the top and bottom, and tighten with
a screwdriver. The clamp torque is approximately 0.15 · Em.
• It is designed such that overtightening will cause left/right cracking to the central area of the Fixtures
and hence reduce the torque. Cracking to the central area will not cause any problems in terms of
usability of the equipment. (However, do exercise caution in not applying too much torque because
the casing is made of plastic.)
• The front side of this controller conforms to NEMA4X (equivalent with IP66). To ensure the water-
proofness between the instrument and the panel, use packings that are provided as accessories in
the following manner: (The improper fitting of packings will ruin the waterproofness.)
q As shown in Figure 4, fit a packing to the case of the unit and then insert it in the panel.
w Tighten screws on the fixing frame or fixtures so that no gaps are given between the front of
controller and packing and between panels. Check that there are no deviation and deformation of
packing as shown in Fig.3.
• If panel strength is weak, it may causes a gap between the packing and the panel, thus impairing
water resistance.
• In case of using the packing in installation, please note the procedure below.
(The overtightening condition may occur and it makes the enclosure strained.)
♦ Tighten screws until the center of fixture cause left/right cracking and clanking about 5 times.
(The clamping torque will be fitted automatically in this condition.)
Mounting
bracket Screw
Unit
Front
Panel Panel
Mounting Screw
bracket
Figure 4 Figure 5
(Caution)
0°
• Don’t block the openings around the controller, or radiation effect will be re-
o3
0t
duced.
=
α
• Don’t block the ventilation openings at the top of the terminal block.
–7–
2.3 Precautions in wiring connection
• For the thermocouple sensor type, use thermocouple compensation wires for wiring.
For the RTD type, use a wiring material with a small lead wire resistance and no resistance differen-
tials among three wires.
• Keep input lines away from power line and load line to avoid the influence from noise induced.
• For the input and output signal lines, be sure to use shielded wires and keep them away from each
other.
• If a noise level is excessive in the power supply, the additional installation of an insulating transformer
and the use of a noise filter are recommended.
(example: ZMB22R5-11 Noise Filter manufactured by TDK)
Make sure that the noise filter is installed to a place such as a panel that is properly grounded. The
wiring between the noise filter output terminal and the instrument power supply terminal should be
made as short as possible. None of fuses or switches should be installed to the wiring on the noise
filter output side because the filter effect will be degraded by such a installation.
• A better anti-noise effect can be expected by using stranded power supply cable for the instrument.
(The shorter the stranding pitch is, the better the anti-noise effect can be expected.)
• For the unit with an alarm against a failure (burn-out) in the heater, use the same power line for
connection of the power supplies for the heater and the controller.
• A setup time is required for the contact output when the power is turned on. If the contact output is
used as a signal for an external interlock circuit, use a delay relay at the same time.
• Use the auxiliary relay since the life is shortened if full capacity load is connected to the output relay.
SSR/SSC drive output type is preferred if the output operations occur frequently.
[Proportional interval] relay output : 30 seconds or more,
SSR/SSC : one second or more
• If inductive load such as magnetic switches connected as a relay output load, it is recommended to
use Z-Trap manufactured by Fuji Electric Systems to protect a contact from switching serge and keep
a longer life.
Model : ENE241D-05A (power supply voltage: 100 V)
ENE471D-05A (power supply voltage: 200 V)
Where to install : Connect it between contacts of the relay control output.
Example)
1 7 13
2 8 14
3 9 15
4 10 16 Z-Trap connection
5 11 17
6 12 18
2.5 Others
• Do not use organic solvents such as alcohol and benzine to wipe this controller. Use a neutral deter-
gent for wiping the controller.
–8–
Index
<Reference items> <Description>
• Confirming that the delivered
Confirming type specification controller is equal to the ordered
one.
• Outline dimensions
1 Installation/mounting • Panel cutout dimensions
• Mounting method on the panel
Power on
*Note • Set value change method
• Basic operation method
3 Usages
• List of parameters
4 Display and operation • List of input/output/alarm codes
5 Setting method of temperature and parameters
6 Functions
7 Setting of input type and control method. • Setting of input type and ranges
• Selecting of control method
Operation
8 Error indications
(Note) *To start the operation, wait for about 30 minutes after the power-on for warm up.
–9–
1 Installation/mounting
Outline and Panel Cutout Dimensions
73 or more
C1 C2 AL1 AL2 AL3
PXR4TAA1-1YM00-D
PV
MFD 2000-04
No. 000001T
44.8
+0.5
48
0
SV
45
SEL
PXR-4
+0.5
45 0
+0.5
0
44.8 48
45
1 7 13
Number 2 3 4 5 6
2 8 14 of units
44.8
3 9 15
a 93 141 189 237 285
57
4 10 16
5 11 17
6.2
6 12 18
PXR7
8.2 79.7 +0.7
72 2 68 0
+0.7
068
92MIN.
Panel
80.8
72
67
44.8
82MIN.
67 t 1 t 8
Packing
67
6.2
– 10 –
Remarks
Note) Panel coating procedure must be taken into account, for the panel cutout dimension should still
conform with the dimensions listed in the left hand column.
Caution on side-by-side installation:
• Maximum ambient temperature is at 45 ˚C when the power supply is at 200VAC or more. When
the PXR4 controller is tightly fixed in vertical and upright direction, the use of 100V AC power
supply is recommended .
(Installation of fan is recommended as a heat release measure)
• Make sure the controller is installed more than 30mm away, when there is an instrument of
more than 70mm depth or a wall on the right side of the controller.
• Side-by-side installation may sacrifice the controller’s waterproof property.
70 or more
30 min.
Caution on wiring:
• Terminals at the left hand side (from No.1 to 6) should be used first.
• Crimp terminals with matching screw size should be used. Tightening torque value should be
approx. 0.8N · m.
• Do not connect anything to the terminals that are not used. (Do not use as relay terminal)
– 11 –
2 Wiring
Terminal Connection Diagram (100 to 240 AC, 24V AC/24V DC)
Alarm output Control output1
· Common q q u !3
Relay output Current output SSR/SSC drive output
!3
· Alarm output1 (AL1) w w i !4 !3 !3
+ +
!4
· Alarm output2 (AL2) e e o !5 !4 !4
!5 - -
· Heater break r
Alarm output3 (AL3) r !0 !6 Measured value input
Thermocouple Resistance bulb Current/voltage
Power supply t !1 !7
24V AC/DC 100-240V AC + !6 A +
y !2 !8 !7 !7
+ t t B
!7
- -
- !8 !8
y y (Note1) B
!8 (Note2)
50/60Hz
Note 1 : Check the power supply voltage before installation.
Note 2 : Connect the I/V unit (250Ω resistor) (accessory)
between the terminal !7 and !8 in case of
current input.
Digtal input Digtal input RS485 com. Digtal input RS485 com. RS485 com. Digtal input
u
+ u u
+ u
+ u u
u
DI1 u
i i
- i i
- i
- i i
In the case of 1 digital input
DI2 Remote SV input Remote SV input CT input Digtal input CT input i
point (the 11th, 12th, or 13th o
digit of the code symbol is “S00”), + o + o o o o o
connect the digital input terminal
- !0 - !0 !0 !0 !0
between terminals u and i. N.C. !0 !0
!1
Re-transmission output Control output2
CT input Remote SV input Re-transmission output Current output SSR/SSC drive output Relay output !2
+ + +
!1 + !1 !1 !1 !1 !1
!2 - - !2
- !2
- !2 !2
!2
In the case of 2 digital input points + heater break alarm,
or 2 digital input points + remote SV specifications, connect the CT
input and remote input terminals between terminals !1 and !2.
– 12 –
3 Usage (Read before using)
Name of Functional Parts and Functions
5 6 7
2
SV
3 SEL
4
PXR-4
S1 S2 S3
Model : PXR4
: RXR7
Setting keys
Name Function
S1 Select key The key shifting to the 1st, the 2nd or the 3rd block parameter, switching the display
between parameter and the data at the 1st, the 2nd and the 3rd block.
S2 Up key · The numerical value is increased by pressing the key once. The numerical value
keeps on increasing by pressing the key continuously.
· For searching parameters within the 1st, the 2nd and the 3rd block.
S3 Down key · The numerical value is decreased by pressing the key once. The numerical value
keeps on decreasing by pressing the key continuously.
· For searching parameters within the 1st, the 2nd and the 3rd block.
Display/Indication
Name Function
q Process value (PV)/parameter 1) Displays a process value (PV).
name display 2) Displays the parameter symbols at parameter setting mode.
3) Displays various error indications (refer to “8. Error indications”).
w Set value (SV) indication lamp The lamp is lit while a set value (SV) is displayed.
e Set value (SV)/parameter setting 1) Displays a set value (SV).
display 2) Display the parameter settings at parameter setting mode.
3) Flickers at Standby mode.
4) Displays the set value (SV ) and “SV-1” alternately when the SV
switching function is used.
5) Displays the set value (SV) and “rSV” alternately while in remote
operation.
r Auto-tuning/self-tuning indicator The lamp flickers while the PID auto-tuning or the self-tuning is being
performed.
t Control output indication lamp C1 : The lamp is lit while the control output 1 is ON.
C2 : The lamp is lit while the control output 2 is ON. (Note 1)
y Alarm output 1 (AL1) The lamp is lit when the alarm output 1 is activated.
indication lamp (Note 1) It flickers during ON-delay operation. (Note 2)
u Alarm output 2 (AL2) The lamp is lit when the alarm output 2 is activated.
indication lamp (Note 1) It flickers during ON-delay operation. (Note 2)
i Alarm output 3 (AL3) The lamp is lit while the alarm output 3 or the heater break alarm
indication lamp (Note 1) output is ON. The lamp flickers while in ON delay operation. (Note 2)
Note 1) Control output 2 and alarm function are optional.
Note 2) The lamp does not flicker while the timer is activated.
– 13 –
4 Display and operation
Standby mode
· To perform standby operation, set “STby” as ON in the
1st block parameter.
· Standby mode:
(Output) Control outputs (1 and 2) and alarm outputs (all) are not
C1 C2 AL1 AL2 AL3 provided. However, depending on setting of “P-n1”, control action, control
outputs are provided at the abnormal input.
PV No alarm output is provided at standby mode, even in
(Fault-condition).
SV
Caution Be careful since the equipment does not provide output of the
alarm of the main unit abnormality during the standby operation.
SEL
(Control) Control is not performed.
PXR-4
(Display) SV display flickers.
Caution The SV display does not flicker while the 1st, 2nd and 3rd block
parameters are displayed.
(Setting) SV and parameter settings are able to perform.
Switching by
1st block
Operation mode
ST by settings
1 Change of set value (SV)
When the SV lamp is lit, the set value
(SV) is displayed at the lower line.
PV
SV
SEL
PXR-4
The set value (SV) can be changed.
Switching by
the SEL key
– 14 –
Switching by
the SEL key
Parameter setting mode
Operation mode PV PV
Press the
SV SEL once. SV
Parameter setting procedure
1 Select a parameter you want to SEL SEL
set by pressing the or
PXR-4 PXR-4
key.
Parameter search. Parameter change.
2-1 Press the SEL key to allow the Increases parameter
parameter to change. set value
Press the . Press the .
(Under the changing condition, Decreases parameter
the parameter set value flickers). set value
SEL
2-2 Pressing the or key, to
Registers parameter set value,
change the parameter set value. C1 C2 AL1 AL2 AL3 returning to the parameter
shift mode 1 .
PV
2-3 After the parameter has been
changed, press the SEL key
for registration. SV
3 To shift to Operation/Standby
mode, press the SEL key for 2 sec. SEL
PXR-4
By repeating the same procedure, the
parameters can be displayed according to the
parameter list shown in 5, Setting methods of
temperature and parameters.
Note: If the upper display (PV) comes off (or kept distinguished), make the setting once again by adding 64 to the set value of parameter DP13.
– 15 –
5 Setting methods of temperature and parameters
Operation/Standby mode
Standby
Alarm status
Control output status Operation C1 C2 AL1 AL2 AL3
– 16 –
Operation/Standby mode
Standby
Alarm status
Control output status Operation C1 C2 AL1 AL2 AL3
. . 0 : No decimal point
“1”
“2”
PVOF PV offset Shift the display of process value (PV). 0
(Setting range: -10 to 10%FS)
P-dF Time constant of input filter Time constant (Setting range: 0.0 to 900.0 sec.) 5.0
ALM1 Type of alarm 1 0/5
Note 2) When using the heater break alarm, set the parameter “TC” to 20 or more.
Set the CT (current transformer) so that it measures the current of the heater connected to the
control output 1.
Disconnection of the control output 2 cannot be detected.
Never set “TC” / “TC2” = 0.
· Some parameters may not be displayed on the screen, depending upon the types.
– 17 –
Operation/Standby mode
Standby
Alarm status
Control output status Operation C1 C2 AL1 AL2 AL3
SEL
Press for about 5 sec.
SEL Press for about 2 sec.
Note 2) When using the heater break alarm, set the parameter “TC” to 20 or more.
Set the CT (current transformer) so that it measures the current of the heater connected to the control output 1.
Disconnection of the control output 2 cannot be detected.
Never set “TC” / “TC2” = 0.
· Some parameters may not be displayed on the screen, depending upon the types.
Note 3) De-energized: Contact opens when the alarm “ON”.
– 18 –
6 Functions
Relation between
Output
PV and SV
ON
PV > SV OFF PV
PV < SV ON when PV decreases
SV
Example 2 : Direct operation
Parameter Setting value
P 0.0 ON
PV
P-n1 2 (or 3)
when PV increases
HYS Any value HYS
Relation between
Output
PV and SV
PV > SV ON ON
PV
PV < SV OFF when PV decreases
SV
– 19 –
6-2 Auto-tuning (AT)
Autotuning is the automatic calculation and entering of the control parameters (P,I and D) into memory. Prior to
the auto-tuning, complete the setting of input range
(P-SL,P-SU, P-dP), a set value (SV), alarm setting (AL1, AL2), and cycle time (TC).
(a) The P.I.D. parameter calculated by auto-tuning remains even if the power is turned off. If the power is
turned off before the auto-tuning is completed, you must restart the auto-tuning.
(b) The PV may be changed greatly depending on the process, because the control output is ON/OFF
action (two position operation) in the auto-tuning. So, do not use the auto-turning if the process does
not allow a significant variation of PV.
In addition, the auto-tuning should not be used in any process such as pressure control and flow
control, where a quick-response is required.
(c) If the auto-tuning isn’t completed in four hours, the auto-tuning is suspected to fail. In this case, check
the wiring and parameters such as the control action, input type, etc.
(d) Carry out the auto-tuning again, if there is any change in SV, input range (P-SL, P-SV or P-dP) or
process condition. Perform the auto-tuning if fuzzy control is selected as the control algorithm.
(e) While carring out auto-tuning, PV operates as shown in Figs 1 and 2.
(f) Execute the auto-tuning also when fuzzy control is selected in control type setting.
(g) When resetting the AT parameter, set the parameter to “0” once, then reset it.
– 20 –
6-3 Self-tuning
1) At power on, changing a set value or the external disturbance, tuning is made automatically so that the PID
parameters are re-optimized.
It is useful where modification of PID parameters is required repeatably due to frequent change in process
condition.
If high controllability is important, select the PID or fuzzy control algorithm and use auto-tuning.
3) Self-tuning indication
C1 C2 AL1 AL2
PV
SV
SV
L : Dead time
The point indicator at the lower Tuning
T : Delay time
right corner keeps blinking while
self-tuning is underway.
L T
– 21 –
4) Self-tuning is executed by any of the following conditions.
q During temperature rise at power ON.
w During temperature rise at SV changing if necessary.
e When control is out of stable condition and is judged as being out of stable condition continuously.
6) Cautions
· Turn on the power of the whole system. The controller should be turned on at even later. Otherwise, the
self-tuning might not be performed successfully.
· Don’t change the SV while the self-tuning is executing.
· Once PID parameters are optimized, the self-tuning is not excuted at the next power on unless SV is
changed.
· After the execution of self-tuning, if the controlability is not your expected level, please select PID or
FUZZY at “CTrL” parameter, and then, start the auto-tuning.
– 22 –
6-4 Alarm function [option]
1) Kinds of alarm
• Absolute value alarm, deviation alarm, combination alarm, and zone alarm are available.
(For details, see Table 4, Alarm action type codes on page 35.)
ON delay function
ON
Alarm
OFF
ON
Without ON delay function
OFF
ON
With ON delay function
OFF
ON delay setting time
Energizing/de-energizing function
ON
Alarm
OFF
Without ON
De-energizing
function
OFF
ON
With
De-energing
function OFF
– 23 –
Combination of alarm functions
Cautions on alarms
No. Cautions Items/Classification
1 Note that the ON delay function is effective for alarm in error status. Alarm in error
status
2 Even during “Err” display, alarms in error status work. Alarm at error
3 Even when “LLLL” or “UUUU” is displayed, an alarm function works normally. indication
4 Alarm action type codes in No.12 to 15 are also included in No.24 to 27. Alarm action type
It is, therefore, recommended to use No.24 to 27. In addition, please note code
when selecting No.12 to 15, setting in ALM2, dLY2, and A2hy are effective.
5 With the HB alarm, ON delay function, de-energizing function and latch HB alarm
function cannot be used.
6 The minimum alarm set value is –199.9. Alarm set value
7 As the alarm action type changed, the alarm set value may also be
changed accordingly.
8 Note that all of alarm outputs are not provided at the standby condition. Alarm at standby
9 Error status alarm is not provided at the standby mode. mode.
10 The HOLD function is effective even if the PV value is in the hysteresis area
when the power is turned ON.
11 Select “0” for alarm action type code to use error status alarm.
– 24 –
6-5 Ramp/soak function [option]
1. Function
Changes the set value (SV) as the time elapses according to a predetermined program pattern, as shown
below.
Either 4 ramp/soak x 2 patterns or 8 ramp/soak x 1 pattern can be programmed. The first ramp starts from
the process value (PV) just before the programming is executed.
SV-8
SV-7
SV-3
SV-4
SV-2
SV-5
SV-1
SV-6
PV
TM1r TM1s TM4rTM4s TM5rTM5s TM8rTM8s Time
8 steps
2. Setting
· Select the program pattern (PTn) and set the rUn at “ProG” PTn Pattern Ramp/Soak
parameter. 1 1 4
· Ramp/soak pattern can not be changed while ramp/soak pro- 2 2 4
gram is running. 3 1+2 8
Note:
· The ramp/soak program is canceled if the controller becomes
to standby mode.
Then, if the controller becames to opration mode, the program
doesn’t run again.
– 25 –
6-6 Communication function [option]
1) Function
· Internal data can be read/written via MODBUS or ASCII communications.
2) To use the function, the following three parameters must be set.
PV PV PV
SV SV SV
Set the station No. at “STno” Set the parity at “COM”. Set the communi-
(station No. setting paramter). CoM cation protocols.
[Sample: station No. = 18] 0 Odd
1 Even PCoL
2 No parity 1 Modbus
2 ASCII
[Sample: Odd parity]
3) Caution
· Station No. can be set in the range of 0 to 255. (No communication is allowed when Modbus is selected,
or Stno=0.)
· After changing the setting of parity at “COM”, please power off and re-start the controller.
· Baud rate is fixed to 9600 bps.
– 26 –
6-7 Digital input (DI function) [option]
1) Function
· With Digital input, the follwing functions are available.
q SV switching
w Control mode; RUN/STANDBY selection
e Ramp/soak RUN/RESET selection
r Auto-tuning start/stop
t Alarm latch cancel
y Timer start/reset
2) To use DI function;
· Select the function with the parameter “di-1” or “di-2” refering to the Table shown below.
PV or
SV
DI function code
(0 to 12)
3) Table of DI function
DI
function Function Description
code
1 Set value (SV) switcing Switching between local SV and “ ”“ ”“ ”
2 Control mode, RUN/STANDBY At standby mode, control is not provided and SV flickers.
3 Auto-tuning (standard)
start Start/Stop can be switched at the time of DI raising up or
4 Auto-tuning (low PV) dropping down.
start
5 All alarm latch cancel
6 Alarm 1 latch cancel
When this function is not used, DI is not effective.
7 Alarm 2 latch cancel
8 Alarm 3 latch cancel
9 ALM1 timer ON/OFF delay timer operation is available. The remaining
10 ALM2 timer time of the timer can be checked with timer-1 and -2
11 ALM3 timer display parameters (first block).
12 Ramp/soak RUN/RESET RUN/RESET of ramp/soak can be performed at the time
of DI raising up or dropping down.
– 27 –
6-8 Other functions
The parameters “bAL” and “Ar” are masked at defauit setting.
If necessary to appear these parameters, please refer to the following procedure.
1) Function
• “bAL” and “Ar” are functions to suppress overshoot.
(Usually it is not necessary to change the setting.)
2) If they aren’t optimum value, sometime you don’t get the good control. Usually it is not necessary to set them.
3) “Ar” (Anti-reset wind-up) is automatically set by “Auto tuning”.
1 bAL
MV is calculated by adding the offset (bAL) to MV’ ,the result of PID calculation, from PV and SV.
100%
Integral action
2 Ar
Ar
SV Work
Ar
Don't work
Time
2 To mask
q Display the “dSP3” in the third block parameter and then add 128 to current value.
w Display the “dSP4” in the third block parameter and then add 1 to current value.
– 28 –
6-9 Re-transmission output function
1) Function
Outputs PV, SV, MV, and DV as a unified 4 to 20mA signal.
PV
SV
1 to 5V
voltage
signal
* is the setting for remote SV input filter. Use the equipment with the value set to 0.0 (set at the time
of delivery) unless the change is required.
– 29 –
7 Setting of input type and control algorithm
Note:
Please set “P-n2”: Input sensor type and “P-SL/P-SU/P-dP”: input range setting prior to any other parameter
settings. When “P-n2” and/or “P-SL/P-SU/P-dP” is changed, some other parameters may also be influenced.
Please check all parameters before starting control.
– 30 –
q Select the type of control output action.
2 Setting of Control Setting procedure
Description
the algorithm output action
Set parameter
Heating Reverse As PV increases, “P-n1” = 0 or 1.
* Read if the control MV decreases. (Refer to Table 2)
doesn't work as you As PV decreases,
expect. MV increases. Set parameter
Cooling Direct As PV increases, “P-n1” = 2 or 3.
MV also increases. (Refer to Table 2)
As PV decreases,
MV also decreases.
– 31 –
8 Error indications
Error indications
This controller has a display function to indicate several types of error code shown below.
If any of the error codes is displayed, please eliminate the cause of error immediately.
After the cause is eliminated, turn off the power once, and then re-start the controller.
AL3 lamp lit Break of the heater (when provided with Normal control
heater break alarm) II
– 32 –
[Table 1] Input type code
Parameter :
Group Input type Code Group Input type Code
RTD II 1 to 5V DC, 16
· Pt100 (IEC) 1 4 to 20mA DC
– 33 –
[Table 3] Input range (Standard range)
Parameter : , ,
Note 1) Except for the following, the input accuracy is ±0.5% FS ±1 digit ±1 °C (Input accuracy
does not be guaranteed for the ranges of measurement other than in the table above.)
R thermocouple 0 to 500 °C
: in these ranges, this controller may display an incorrect
B thermocouple 0 to 400 °C process value due to the characteristic of the sensor.
Note 2) In case a measuring range of -150 to 600 °C or -150 to 850 °C is used for resistance bulb
input, temperatures below -150°C does not be indicated correctly. Therefore, “LLLL” does
not appear despite a continuous fall below -150°C.
Note 3) If the resistance bulb or thermocouple is used at a temperature below the lowest value in
the measurement range, the input accuracy cannot be guaranteed.
Note 4) Addition of decimal point is impossible if the input range or span is larger than 999.9 at the
RTD/thermocouple input.
– 34 –
[Table 4] Alarm action type code
Parameter : , ,
· Standard alarm code · Alarm code with dual set value
ALM ALM ALM ALM ALM ALM
Alarm type Action diagram Alarm type Action diagram
1 2 3 1 2 3
High High/Low
0 0 0 No alarm PV /Low 16 16 16 PV
absolute alarm
limit An-L An-H
Absolute alarm An-L An-H
1 1 1 High alarm High/Low
value PV 17 17 17 PV
ALn deviation alarm
alarm SV
Note) · When alarm action type code is changed, alarm set value may also become different from previous
settings.
Please check these parameters, turn off the power once, and then re-start the controller, before start-
ing control.
· When selecting No.12 to 15, setting in ALM2, dLY2, and A2hy are effective, and output to the AL2
relay.
· ALn means alarm set value (AL1, AL2 or AL3).
· An-H means alarm set value (A1-H, A2-H or A3-H).
· An-L means alarm set value (A1-L, A2-L or A3-L).
· dLYn means alarm set value (dLY1, dLY2 or dLY3).
– 35 –
[Table 5] Control operation type code
Parameter :
[MOD code list]
MOD Power ON start Output at END Output at OFF Repeat operation
0 Without Control continued Control continued Without
1 Without Control continued Control continued With
2 Without Control continued Standby mode Without
3 Without Control continued Standby mode With
4 Without Standby mode Control continued Without
5 Without Standby mode Control continued With
6 Without Standby mode Standby mode Without
7 Without Standby mode Standby mode With
8 With Control continued Control continued Without
9 With Control continued Control continued With
10 With Control continued Standby mode Without
11 With Control continued Standby mode With
12 With Standby mode Control continued Without
13 With Standby mode Control continued With
14 With Standby mode Standby mode Without
15 With Standby mode Standby mode With
[Description of functions]
1. Power ON start: Starts ramp/soak with the current PV value.
2. Output at END: Displays the output status at the time when ramp/soak is at END.
3. Output at OFF: Displays the output status at the time when ramp/soak is at OFF.
4. Repeat operation: After the ramp/soak step is terminated once, runs ramp/soak repeatedly.
The PV value set in the previous step is maintained in normal state (without repeat operation).
* Standby mode: Output -3%
Alarm OFF
Standby mode where no control operation is performed.
– 36 –
PXR Model Code Configuration
4 5 6 7 8 9 10 11 12 13
PXR 1 -
– 37 –
Specification
Power voltage: 100 (–15%) to 240V AC (+10%) 50/60Hz, 24V (±10%) AC/DC
Power consumption: 10VA or less (at 100V AC), 12VA or less (at 220V AC),
12VA or less (at 24V AC/DC)
Relay contact output: Control output 1: SPDT contact, 220V AC /30V DC 3A (resistive load)
Control output 2: SPST contact, 220V AC /30V DC 3A (resistive load)
SSR/SSC driving output *1: ON: 24V DC (17 to 25V DC)
(voltage pulse output) OFF: 0.5V DC or less
Maximum current ; 20mA or less
Resistive load 850Ω or more
4-20mA DC output: Allowable load resistor 600Ω or less
Alarm output (up to 2 outputs): Relay contact (SPST contact) 220V AC / 30V DC 1A (resistive load)
Heater disconnection alarm output: Relay contact (SPST contact) 220V AC / 30V DC 1A (resistive load)
Communication function *2: RS-485 interface
Transmission system ; Half-dueplex bit serial start-stop
synchronization
Transmission rate ; 9600bps
Transmission protocol ; In conformity to Modbus RTU or Z-ASCII
(PXR protocol)
Transmission distance ; Up to 500m (total length)
Connectable units ; Up to 31units
Digital input : Number of inputs; 2 inputs
Judged as ON : 3VDC or higher
Judged as OFF : 2VDC or lower
Input contact capacity ; 5V, 2mA DC
Input pulse width ; Min 0.5 sec
Re-transmission output: Output accuracy ±0.3% or lower
Permissible load resistance 600Ω or less
Remote SV input: Input accuracy ±0.5% FS or lower
(Without input break detection function)
Set resolution 3000 or higher
Input filtering function provided
Ambient temperature: -10 to 50°C
-10 to 45°C (when side by side mounting)
Operating ambient humidity: 90%RH or less (no condensation)
Preservation temperature: -20 to 60°C
Time accuracy: Within ±0.5%
*1 : The following table shows the difference of outputs among other micro-controller X series models.
SSR/SSC driving output Allowable load
resistance for 4 to
Voltage Maximum current 20mA DC output
PXR3 15V DC 20mA 100 to 500Ω
PXR4/5/7/9 24V DC 20mA 600Ω or less
PXV3 5.5V DC 20mA 600Ω or less
PXV/W/Z 24V DC 60mA 600Ω or less
– 38 –