Siemens SIVACON S8, IEC 61439 Switchgear and Control Panel
Siemens SIVACON S8, IEC 61439 Switchgear and Control Panel
Siemens SIVACON S8, IEC 61439 Switchgear and Control Panel
Who is IEC?
-The IEC or International Electrotechnical Commission (IEC) is to promote international cooperation on
electrical and electronic fields.
1941 VDE 0100 "Regulations on the installation of power circuits with nominal voltages below 1000V"
1958 VDE 0100 §29 N Requirements for insulation, short-circuit withstand and protection against contact with live parts.
1973
VDE 0100 §30 b: Construction requirements for not factory
assembled switching and distribution boards
1984 VDE 0660 part 500 (TTA) type-tested switchgear and VDE 0660 part 500 (PTTA) Partially type-tested switch-
(1985) (EN (IEC) 60439-1) controlgear assemblies (EN (IEC) 60439-1) gear and controlgear assemblies
joint construction requirements
EN (IEC) 61439-1/2 New standard for power switchgear and controlgear assemblies
2009 VDE 0660-600-1/2
Unrestricted © Siemens AG 2017
Page 3 April 2017 EM MS
IEC 61439 the standard of Low Voltage Switchgear and Controlgear.
What’s New on IEC 61439 family?
SIVACON
System (Busways) IEC61439 IEC61439-2 Power
Switchgear and
Controlgear Assemblies
ALPHA
IEC61439-4 Particular Requirements for
assemblies for Construction Sites (ACS)
Some manufacturer and specific market segments are ignoring the EN (IEC) 60439.
Enclosure
1 Roof plate 6 Base
2 Rear wall 7 Base compartment cover, ventilated
3 Design side wall 8 Cubicle door, ventilated 1
Technical data
4 Frame 9 Compartment door
11 2 Structure
5 Base cover 10 Head room door
21 Door opening angle 125°,180° with
Busbars 10 stand-alone
installation
11 Main busbar (L1 ... L3, N) – top
12
12 Main busbar (L1 ... L3, N) – rear top 9 Frame height (without 2,000, 2,200 mm
13 Main busbar (L1 ... L3, N) – rear bottom base)
14 Main busbar (PE) – bottom
Base height (optional) 100, 200 mm
15 Distribution busbar (L1 ... L3, N) – device compartment 20 17
16 Distribution busbar (PE) – cable compartment 3 Degree of protection In accordance
19 16 13 with IEC 60529:
17 Distribution busbar (N) – cable compartment
18 IP30, IP31, IP40,
8 15 IP41, IP43, IP54
Internal separation
18 Device compartment/busbar compartment
Main busbars
14
19 Cubicle to cubicle 4 Rated currents up to 7,000 A
20 Compartment to compartment 7
6 Rated peak withstand up to 330 kA
21 Cross-wiring compartment
current (Ipk)
Unrestricted © Siemens AG 2017 5 Rated short-time up to 150 kA
Page 6 April 2017 withstand current (Icw) EM MS
Why IEC 61439 have to replace over IEC 60439?
IEC 61439-0 Technical Reports.
- The IEC 61439-0 Technical Reports are identify scope of test area, definition of the
testing, Type of Installation, Storage and Handling, Maintenancee and Upgrade,
Current capability, ASSEMBLY design and routine verification processes .
- The IEC 61439-1 General Rules is a back bone of IEC 61439 standard, because it
have identify term and definitions of Low Voltage Switchgear and Controlgear,
Symbols and abbreviations, Test Limitation, Definition of Tests Verification,
Derivation and Assessment.
Unrestricted © Siemens AG 2017
Page 8 April 2017 EM MS
Why IEC 61439 have to replace over IEC 60439?
IEC 61439-1 General Rules.
Forms of internal separation
Design verification
“Verification made on a sample of an assembly or on parts of assemblies to show that the design meets the requirements of the relevant assembly standard”
[EN (IEC) 61439-1; 3.9.1].
Routine verification
Verification about the compliance to the relevant assembly standard which has to be performed for every completed assembly.
Dielectric properties
10.9.2 Power-frequency withstand voltage Yes No No
10.9.3 Impulse withstand voltage Yes No Yes
10.10 Temperature-rise limits Yes Yes Yes /No
10.11 Short-circuit withstand strength Yes Yes/No No
10.12 Electromagnetic compatibility (EMC) Yes No Yes
10.13 Mechanical operation Yes No No
For InA > 1600A temperature-rise verifications according to EN (IEC) 61439 have to be provided by testing and derivations; assessments via
calculation are only allowed for assemblies up to 1600A.
Testing Derivation
Only if the worst variant of an assembly was tested, the results of these tests can
be used for verification of favorably variants by derivation.
The short-circuit withstand strength according to EN (IEC) 61439 can be certificated by derivation for parts of an assembly if the worst variant
was tested before.
Unrestricted © Siemens AG 2017
Page 16 April 2017 EM MS
Why IEC 61439 have to replace over IEC 60439?
IEC 61439 Black Box Concept.
o External design
(open / closed design, panel design, cubicle design, ...)
Grid connection
o Rated voltage of the assembly Un
Installation and ambient
o Rated frequency fn
conditions
o Rated operating voltage Ue
o Measures for protection against electric shock
(Protection class)
o Device operation
(e.g. behind the door, from outside, …)
Partition of the previous chapter “constructional requirements” in the chapters “constructional requirements“
and “performance requirements“ with single changes.
“7 Constructional requirements“
Requirements for strength of materials and parts adopted from the standard for empty enclosures
EN (IEC) 62208.
Constructional Requirements
Changes
8.1 Strength of materials and parts
Adopted requirements from the standard for empty enclosures EN (IEC) 62208
o Corrosion resistance o UV Resistance of enclosure parts made of insulating material for outdoor
o Thermal resistance of enclosure parts installation
made of insulating material o Protection against mechanical impacts (IK code)
o Ability for transportation (lifting)
8.2.2 Protection against contact with live parts, ingress of solid foreign bodies and water
IPX2 is not applicable for fixed mounted assemblies which are not tilted in normal operation conditions.
Routine Verifications
Dielectric test
New test voltage versus EN (IEC) 60439-1.
⇓ Please check the setting possibilities of your test equipment according to the new test parameters for routine verifications.
Routine verification
SIVACON
S8 / 8PT
S8 / 8PT
The object of this standard is to state the definitions and to specify the
service conditions, construction requirements, technical characteristics
and tests for PENDAs. Network parameters may require tests at higher
performance levels.
Unrestricted © Siemens AG 2017
Page 29 April 2017 EM MS
IEC 61439-5 Part 5: Assemblies for power distribution in public
networks.
Respectively in marinas and similar locations (AMHS), camping sites and similar Typical of application:
locations (ACCS), market squares and other similar external public sites (AMPS), o ASSEMBLY for Marinas and harbors sites (AMHS).
charging stations (ACSEV). The term ASSEMBLIES is used for indicating all the
boards. o ASSEMBLY for Camping and Caravan Sites (ACCS).
o Stationary or movable with enclosure which operated by ordinary persons. o ASSEMBLY for Markets and other external public sites
o Combination test requirements as IEC 61439-5 PENA-O. (AMPS)
Protection against electric shock o ASSEMBLY for Electric Vehicles Charging Station
(ACSEV), EV conductive charging system in IEC 61851-
o Electrical separation 1 are included.
o Protection against overcurrent
o Protection against electric shocks. Installation Condition:
o Socket-outlets general. o AMHS, IEC 60364-7-709.
Supports and securing devices of ASSEMBLY o ACCS, IEC 60364-7-708.
o Protection against electric shocks. o AMPS , IEC 60364-7-740.
o Socket-outlets. o ACSEV , IEC 60364-7-722.
o Water and other fluid systems
Your benefit
• Safety for people and plant by means of tests according
to IEC 61439-2/ -7
• Safe power supply with earthquake-tested version for
seismic requirements
• Certifications for application on ships and offshore
platforms
Communication-capable components
SIMARIS control –
• Future-proof integration into building Control system central switchboard operating
and industrial automation systems and monitoring system
The arc barrier restricts the effects to Insulated main busbars prevent the Tests under conditions of arcing in
one cubicle in case of arcing occurrence of arcing accordance with IEC/TR 61641
Erweiterter
Extended Störlichtbogenschutz
protection against internal arcing Höhere Leistungen
Real Time Temperature Monitoring to ensure
for increased personnelund
für erhöhte Personen- and switchboard durch energieeffiziente Kühlung
high plant availability with intelligent
Anlagensicherheit
safety technology
Efficient planning support with the SIMARIS software tools and the new BIM models
SIMARIS design
SIMARIS project
SIMARIS configuration
TIP Consultant Support for planning and conception of electrical power distribution
systems www.siemens.com/siemens.de/tip-cs
Customer Support Center, e-mail: [email protected]
Thank you.
Mr. Passapong Vidhyarkorn
Siemens EM LP, Thailand.
Email : [email protected]
Call : +66-91-576-0958.
+66-81-544-5536.
Subject to changes and errors. The information given in this document only contains general descriptions and/or performance features which may
not always specifically reflect those described, or which may undergo modification in the course of further development of the products. The requested
performance features are binding only when they are expressly agreed upon in the concluded contract.
All product designations, product names, etc. may contain trademarks or other rights of Siemens AG, its affiliated companies or third parties.
Their unauthorized use may infringe the rights of the respective owner.