ABB Standard Macro: Actual Signals and Parameters 128 I/O Terminals 34

This document provides a default macro for an ABB drive with three constant speeds. It includes the default I/O connections and parameter values. The macro gives a general purpose I/O configuration with three constant speeds. The default connections are presented for the signal cable shield, analog and digital inputs and outputs, and relay outputs.

Uploaded by

Nicolas Gonzalez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
253 views1 page

ABB Standard Macro: Actual Signals and Parameters 128 I/O Terminals 34

This document provides a default macro for an ABB drive with three constant speeds. It includes the default I/O connections and parameter values. The macro gives a general purpose I/O configuration with three constant speeds. The default connections are presented for the signal cable shield, analog and digital inputs and outputs, and relay outputs.

Uploaded by

Nicolas Gonzalez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

77

ABB Standard macro


This is the default macro. It provides a general purpose I/O configuration with three
constant speeds. Parameter values are the default values given in chapter Actual
signals and parameters, starting from page 128.
If you use other than the default connections presented below, see section I/O
terminals on page 34.

Default I/O connections


X1A
1 SCR Signal cable shield (screen)
2 AI1 Output frequency reference: 0…10 V 1)
1…10 kohm 3 GND Analog input circuit common
4 +10V Reference voltage: 10 VDC, max. 10 mA
5 AI2 Not in use by default. 0…10 V
6 GND Analog input circuit common
max. 500 ohm 7 AO Output frequency value: 0…20 mA
8 GND Analog output circuit common
4)
9 +24V Auxiliary voltage output: +24 VDC, max. 200 mA
10 GND Auxiliary voltage output common
11 DCOM Digital input common
12 DI1 Stop (0) / Start (1)
13 DI2 Forward (0) / Reverse (1)
14 DI3 Constant speed selection 2)
15 DI4 Constant speed selection 2)
16 DI5 Acceleration and deceleration selection 3)
X1B
17 ROCOM Relay output
18 RONC No fault [Fault (-1)]
19 RONO
20 DOSRC Digital output, max. 100 mA
21 DOOUT No fault [Fault (-1)]
22 DOGND

1) 3)
AI1 is used as a speed reference if vector mode 0 = ramp times according to parameters 2202
is selected. and 2203.
2)
See parameter group 12 CONSTANT SPEEDS: 1 = ramp times according to parameters 2205
and 2206.
DI3 DI4 Operation (parameter)
4)
360 degree grounding under a clamp.
0 0 Set speed through AI1
1 0 Speed 1 (1202)
0 1 Speed 2 (1203)
1 1 Speed 3 (1204)

Application macros