Data Sheet de Un Guardamotor SIEMENS Linea Nueva Tamaño S00
Data Sheet de Un Guardamotor SIEMENS Linea Nueva Tamaño S00
Data Sheet de Un Guardamotor SIEMENS Linea Nueva Tamaño S00
Ambient conditions
Installation altitude at height above sea level
● maximum 2 000 m
Ambient temperature
● during operation -20 ... +60 °C
● during storage -50 ... +80 °C
● during transport -50 ... +80 °C
Temperature compensation -20 ... +60 °C
Relative humidity during operation 10 ... 95 %
Main circuit
Number of poles for main current circuit 3
adjustable pick-up value current of the current- 10 ... 16 A
dependent overload release
Operating voltage
● rated value 690 V
● at AC-3 rated value maximum 690 V
Operating frequency rated value 50 ... 60 Hz
Operating current rated value 16 A
Operating current
● at AC-3
— at 400 V rated value 16 A
Operating power
● at AC-3
— at 230 V rated value 4 000 W
— at 400 V rated value 7 500 W
Auxiliary circuit
Design of the auxiliary switch transverse
Number of NC contacts for auxiliary contacts 1
Number of NO contacts for auxiliary contacts 1
Number of CO contacts
● for auxiliary contacts 0
Operating current of auxiliary contacts at AC-15
● at 24 V 2 A
● at 120 V 0.5 A
● at 125 V 0.5 A
● at 230 V 0.5 A
Operating current of auxiliary contacts at DC-13
● at 24 V 1 A
● at 60 V 0.15 A
UL/CSA ratings
Full-load current (FLA) for three-phase AC motor
● at 480 V rated value 16 A
● at 600 V rated value 16 A
Short-circuit protection
Product function Short circuit protection Yes
Design of the short-circuit trip magnetic
Design of the fuse link
● for short-circuit protection of the auxiliary switch Fuse gL/gG: 10 A, miniature circuit breaker C 6 A (short-circuit
required current Ik < 400 A)
Design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 240 V gL/gG 80 A
● at 400 V gL/gG 63 A
● at 500 V gL/gG 50 A
● at 690 V gL/gG 40 A
Connections/ Terminals
Product function
● removable terminal for auxiliary and control No
circuit
Type of electrical connection
● for main current circuit screw-type terminals
● for auxiliary and control current circuit screw-type terminals
Arrangement of electrical connectors for main current Top and bottom
circuit
Type of connectable conductor cross-sections
● for main contacts
— single or multi-stranded 2x (0,75 ... 2,5 mm²), 2x 4 mm²
— finely stranded with core end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG conductors for main contacts 2x (18 ... 14), 2x 12
Type of connectable conductor cross-sections
● for auxiliary contacts
— single or multi-stranded 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²)
— finely stranded with core end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG conductors for auxiliary contacts 2x (20 ... 16), 2x (18 ... 14)
Certificates/ approvals
Marine / Shipping
other Railway
Confirmation Vibration and Shock Confirmation
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RV2011-4AA15
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RV2011-4AA15
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RV2011-4AA15
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RV2011-4AA15&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RV2011-4AA15/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RV2011-4AA15&objecttype=14&gridview=view1
45 5
49
97
3/L2
5/L3
13
21
-F
14
22
2/T1
4/T2
6/T3