Distance Protection Basic PDF PDF
Distance Protection Basic PDF PDF
distance PROTECTION
Prepared by
Engr. Asaduzzaman
Executive Engineer
Power Grid Company of Bangladesh Ltd.
2
BASIC CONCEPT OF POWER SYSTEM PROTECTION
3
BASIC CONCEPT OF POWER SYSTEM PROTECTION
4
BASIC CONCEPT OF POWER SYSTEM PROTECTION
Working Principle of Distance or Impedance Relay
5
BASIC CONCEPT OF POWER SYSTEM PROTECTION
Electromechanical distance relay
6
BASIC CONCEPT OF POWER SYSTEM PROTECTION
7
BASIC CONCEPT OF POWER SYSTEM PROTECTION
8
BASIC CONCEPT OF POWER SYSTEM PROTECTION
R-X Plane of Distance Function
XL Line Angle
20Ω tan-1(X/R)
10Ω
XC
9
BASIC CONCEPT OF POWER SYSTEM PROTECTION
XL
20Ω
XC
10
BASIC CONCEPT OF POWER SYSTEM PROTECTION
1000A
20000A
XL
XC
11
BASIC CONCEPT OF POWER SYSTEM PROTECTION
XL
Lenticular Zone 18Ω
XC
12
BASIC CONCEPT OF POWER SYSTEM PROTECTION
XL
Start Zone
Z1=80% of Protected Line
Z2=120% of PL or 100+50% of SL
Z3=100%PL+50%LL or
Z-3
Load
Angle
Z-2
Reverse Zone
As an offset of Zone-3
XC
13
BASIC CONCEPT OF POWER SYSTEM PROTECTION
Zone Settings Criterion
14
BASIC CONCEPT OF POWER SYSTEM PROTECTION
Reaches
XL
Quadrilateral
Zone
XC
15
BASIC CONCEPT OF POWER SYSTEM PROTECTION
Combination of Directional Characteristic and Load Area
Directional Characteristic Load Area (in Phase Selector)
“AND”
16
BASIC CONCEPT OF POWER SYSTEM PROTECTION
Basic Distance Schemes
A B
BUSBAR
BUSBAR
CB CT CT CB
Transmission Line
PT PT
Distance Distance
Relay Relay
17
BASIC CONCEPT OF POWER SYSTEM PROTECTION
Basic Distance Schemes
200%
Z3A
120%
Z2A
80%
Z1A
D A B C
Z1B
Z2B
Z3B
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
Z1B
Z2B
Z3B
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
Z1B
Z2B
Z3B
Z1 Z1
400ms
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
Disadvantages:
21
BASIC CONCEPT OF POWER SYSTEM PROTECTION
Line Protection Philosophy
Distribution Feeder ( 11kV & 33kV) :
Over current & Earth Fault Protection (Directional / Non directional)
22
Zone 1 Extension Schemes
Z3A
Z2A
Z1A
Z1extA
D A B C
Z1extB
Z1B
Z2B
Z3B
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
23
DISTANCE PROTECTION FUNDAMENTALS (21)
Zone 1 Extension Schemes
Z3A
Z2A
Z1A
Z1extA
D A B C
Z1extB
Z1B
Z2B
Z3B
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
24
DISTANCE PROTECTION FUNDAMENTALS (21)
Zone 1 Extension Schemes
25
Zone 1 Extension Schemes
Advantages:
1. No signaling channel required (may be used as
temporary replacement for carrier aided scheme
when communications Channel out of service)
2. Provides fast fault clearance at both ends for a
transient fault anywhere along the line length
3. Allow the use of high-speed A/R cycle
26
DISTANCE PROTECTION FUNDAMENTALS (21)
Zone 1 Extension Schemes
Disadvantages:
1. Tripping can occur for external faults (but will be
followed by an auto reclose)
2. Basic distance scheme logic applies following reclose (i.e.;
potential for time delayed clearance for permanent fault)
3. Only suitable to systems where auto reclose is used (for
example, can not be used on cable circuits)
27
DISTANCE PROTECTION FUNDAMENTALS (21)
Basic Distance Schemes with aided Schemes
BUSBAR
BUSBAR
CB CT CT CB
Transmission Line
PT PT
Distance Distance
Relay Relay
28
DISTANCE PROTECTION FUNDAMENTALS (21)
Transfer Tripping Schemes
29
DISTANCE PROTECTION FUNDAMENTALS (21)
Direct Under-reach Transfer Tripping Scheme
Z3A
Z2A
Z1A
D A B C
Z1B
Z2B
Z3B
Send Logic : Z1
Trip Logic : Rx
Tx Tx
Rx Rx
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
30
DISTANCE PROTECTION FUNDAMENTALS (21)
Direct Under-reach Transfer Tripping Scheme
Advantages:
1. All faults anywhere along the protected line can be cleared
instantaneously at both line ends
2. Scheme can be advantageous for protecting 3 terminal lines
due to ease of application
Disadvantages:
1. The disadvantage of this scheme is the possibility of undesired
tripping by accidental operation or maloperation of signaling
equipment, or interference on communications channel. As a
result, it is not commonly used.
2. Circuit breakers at both line ends must be closed and contribute
fault current to obtain high speed fault clearance
3. If the channel fails only the basic scheme logic will be provided
31
DISTANCE PROTECTION FUNDAMENTALS (21)
Permissive Under-reach Transfer Tripping Scheme (PUTT)
Z3A
Z2A
Z1A
D A B C
Z1B
Z2B
Z3B
Send Logic : Z1
Trip Logic : Rx + Z2
Tx Tx
0 0
100 Rx Rx 100
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
32
DISTANCE PROTECTION FUNDAMENTALS (21)
Permissive Under-reach Transfer Tripping Scheme (PUTT)
Z3A
Z2A
Z1A
D A B C
Z1B
Z2B
Z3B
Send Logic : Z1
Trip Logic : Rx + Z2
Tx Tx
0 0
100 Rx Rx 100
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
33
DISTANCE PROTECTION FUNDAMENTALS (21)
Permissive Under-reach Transfer Tripping Scheme (PUTT)
Z3A
Z2A
Z1A
D A B C
Z1B
Z2B
Z3B
Send Logic : Z1
Trip Logic : Rx + Z2
Tx Tx
0 0
100 Rx Rx 100
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
34
DISTANCE PROTECTION FUNDAMENTALS (21)
Permissive Under-reach Transfer Tripping Scheme (PUTT)
Z3A
Z2A
Z1A
D A B C
Z1B
Z2B
Z3B
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
35
DISTANCE PROTECTION FUNDAMENTALS (21)
Permissive Under-reach Transfer Tripping Scheme (PUTT)
Z3A
Z2A
Z1A
D A B C
Z1B
Z2B
Z3B
Send Logic : Z1
Trip Logic : Rx + Z2
Tx Tx
0 0
100 Rx Rx 100
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
36
DISTANCE PROTECTION FUNDAMENTALS (21)
Permissive Under-reach Transfer Tripping Scheme (PUTT)
Advantages:
1. Only a simplex signaling channel required
2. Scheme is very secured as signaling channel only keyed
for internal fault (Zone 1 initiation)
Disadvantages:
37
DISTANCE PROTECTION FUNDAMENTALS (21)
Resistive Fault X
Zone-3
Zone-1
38
DISTANCE PROTECTION FUNDAMENTALS (21)
➢ Permissive Under-reach Acceleration Scheme
39
DISTANCE PROTECTION FUNDAMENTALS (21)
➢Permissive Over-reach Transfer Tripping Scheme (POTT)
Z3A
Z2A
Z1A
D A B C
Z1B
Z2B
Z3B
Send Logic : Z2
Trip Logic : Rx + Z2
Rx Rx
Tx Tx
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
40
DISTANCE PROTECTION FUNDAMENTALS (21)
➢Permissive Over-reach Transfer Tripping Scheme (POTT)
Z3A
Z2A
Z1A
D A B C
Z1B
Z2B
Z3B
Send Logic : Z2
Trip Logic : Rx + Z2
Rx Rx
Tx Tx
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
41
DISTANCE PROTECTION FUNDAMENTALS (21)
➢Permissive Over-reach Transfer Tripping Scheme (POTT)
Z3A
Z2A
Z1A
D A B C
Z1B
Z2B
Z3B
Send Logic : Z2
Trip Logic : Rx + Z2
Rx Rx
Tx Tx
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
42
DISTANCE PROTECTION FUNDAMENTALS (21)
➢Permissive Over-reach Transfer Tripping Scheme (POTT) (Internal fault)
Z3A
Z2A
Z1A
D A B C
Z1B
Z2B
Z3B
Send Logic : Z2
Trip Logic : Rx + Z2
Rx Rx
Tx Tx
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
43
DISTANCE PROTECTION FUNDAMENTALS (21)
➢Permissive Over-reach Transfer Tripping Scheme (POTT) (External fault)
Z3A
Z2A
Z1A
D A B C
Z1B
Z2B
Z3B
Send Logic : Z2
Trip Logic : Rx + Z2
Rx Rx
Tx Tx
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
44
DISTANCE PROTECTION FUNDAMENTALS (21)
➢Permissive Over-reach Transfer Tripping Scheme (POTT) Internal Resistive Fault
Z3A
Z2A
Z1A
D A B C
Z1B
Z2B
Z3B
Send Logic : Z2
Trip Logic : Rx + Z2
Rx Rx
Tx Tx
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
45
DISTANCE PROTECTION FUNDAMENTALS (21)
➢Permissive Over-reach Transfer Tripping Scheme (POTT) Internal Resistive Fault
Z3A
Z2A
Z1A
D A B C
Z1B
Z2B
Z3B
Send Logic : Z2
Trip Logic : Rx + Z2
Rx Rx
Tx Tx
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 T3 Z3
46
DISTANCE PROTECTION FUNDAMENTALS (21)
➢Permissive Over-reach Transfer Tripping Scheme (POTT)
X
Resistive Fault
Zone-3
Zone-1
47
DISTANCE PROTECTION FUNDAMENTALS (21)
➢ Permissive Over-reach Transfer Tripping Scheme (POTT) CB Echo Logic
Z3A
Z2A
Z1A
D A B C
Z1B
Z2B
Z3B
CB & & CB
Open Rx Rx Open
1 Tx Tx 1
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Z3 T3 Send Logic : Z2 T3 Z3
Trip Logic : Rx + Z2
Open Terminal Echo: CB Open + Rx
48
DISTANCE PROTECTION FUNDAMENTALS (21)
➢ Permissive Over-reach Transfer Tripping Scheme (POTT) Echo Logic
Z3A
Z2A
Z1A
D A B C
Z1B
Z2B
Z3B
CB & & CB
Open Rx Rx Open
1 Tx Tx 1
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Send Logic : Z2
Trip Logic : Rx + Z2
Z3 T3 Open Terminal Echo: CB Open + Rx T3 Z3
49
DISTANCE PROTECTION FUNDAMENTALS (21)
➢ Permissive Over-reach Transfer Tripping Scheme (POTT) Echo Logic
Z3A
Z2A
Z1A
D A B C
Z1B
Z2B
Z3B
CB & & CB
Open Rx Rx Open
1 Tx Tx 1
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Send Logic : Z2
Z3 T3 Trip Logic : Rx + Z2 T3 Z3
Open Terminal Echo: CB Open + Rx
50
DISTANCE PROTECTION FUNDAMENTALS (21)
Permissive Overreach Transfer Trip (WI Echo Logic)
Z4
Z2
Z1
Z1
Z2 Z4
CB & & CB
Open Rx Rx Open
Z4 & & Z4
1 Tx Tx 1
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Send Logic : Z2
Z3 T3 Trip Logic : Rx + Z2 T3 Z3
Open Terminal Echo : CB Open + Rx
Weak Infeed echo : Z4 + Rx
Permissive Overreach Transfer Trip (WI Echo Logic)
Z4
Z2
Z1
A B
Strong Z1 Weak
Source Z2 Source
Z4
CB & & CB
Open Rx Rx Open
Z4 & & Z4
1 Tx Tx 1
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Send Logic : Z2
Z3 T3 Trip Logic : Rx + Z2 T3 Z3
Open Terminal Echo : CB Open + Rx
Weak Infeed echo : Z4 + Rx
Permissive Overreach Transfer Trip (WI Echo Logic) Internal Fault
Relay B failed to see any
Z4 fault due to weak infeed
Z2
Z1
A B
Strong Z1 Weak
Source Z2 Source
Z4
CB & & CB
Open Rx Rx Open
Z4 & & Z4
1 Tx Tx 1
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Send Logic : Z2
Z3 T3 Trip Logic : Rx + Z2 T3 Z3
Open Terminal Echo : CB Open + Rx
Weak Infeed echo : Z4 + Rx
Permissive Overreach Transfer Trip (WI Echo Logic) Internal Fault
Relay B failed to see any
Z4 fault due to weak infeed
Z2
Z1
A B
Strong Z1 Weak
Source Z2 Source
Z4
CB & & CB
Open Rx Rx Open
Z4 & & Z4
1 Tx Tx 1
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Send Logic : Z2
Z3 T3 Trip Logic : Rx + Z2 T3 Z3
Open Terminal Echo : CB Open + Rx
Weak Infeed echo : Z4 + Rx
Permissive Overreach Transfer Trip (WI Echo Logic) Internal Fault
Relay B failed to see any
Z4 fault due to weak infeed
Z2
Z1
A B
Strong Z1 Weak
Source Z2 Source
Z4
CB & & CB
Open Rx Rx Open
Z4 & & Z4
1 Tx Tx 1
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Send Logic : Z2
Z3 T3 Trip Logic : Rx + Z2 T3 Z3
Open Terminal Echo : CB Open + Rx
Weak Infeed echo : Z4 + Rx
Permissive Overreach Transfer Trip (WI Echo Logic) Internal Fault
Relay B failed to see any
Z4 fault due to weak infeed
Z2
Z1
A B
Strong Z1 Weak
Source Z2 Source
Z4
CB & & CB
Open Rx Rx Open
Z4 & & Z4
1 Tx Tx 1
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Send Logic : Z2
Z3 T3 Trip Logic : Rx + Z2 T3 Z3
Open Terminal Echo : CB Open + Rx
Weak Infeed echo : Z4 + Rx
➢ The fault current can also be initially too low due to the
fault current distribution. Here, the fault current increases
when the breaker opens in the strong terminal, and a
sequential tripping is achieved. This requires a detection
of the fault by an independent tripping zone 1. To avoid
sequential tripping as described, and when zone 1 is not
available, weak-end infeed tripping logic is used.
57
Permissive Overreach Transfer Trip (WI Echo Logic) External Fault
Z4
Z2
Z1
A B
Strong Z1 Weak
Source Z2 Source
Z4
CB & & CB
Open Rx Rx Open
Z4 & & Z4
1 Tx Tx 1
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Send Logic : Z2
Z3 T3 Trip Logic : Rx + Z2 T3 Z3
Open Terminal Echo : CB Open + Rx
Weak Infeed echo : Z4 + Rx
Permissive Overreach Transfer Trip (WI Echo Logic) External Fault
Z4
Z2
Z1
A B
Strong Z1 Weak
Source Z2 Source
Z4
CB & & CB
Open Rx Rx Open
Z4 & & Z4
1 Tx Tx 1
& &
Z1 Z1
1 Trip Trip 1
Z2 T2 T2 Z2
Send Logic : Z2
Z3 T3 Trip Logic : Rx + Z2 T3 Z3
Open Terminal Echo : CB Open + Rx
Weak Infeed echo : Z4 + Rx
Permissive Overreach Transfer Trip (Current reversal logic)
60
Permissive Overreach Transfer Trip (Current reversal logic)
Current reversal
Trip????
61
➢Permissive Over-reach Transfer Tripping Scheme (POTT)
Advantages:
62
DISTANCE PROTECTION FUNDAMENTALS (21)
➢Permissive Over-reach Transfer Tripping Scheme (POTT)
Disadvantages:
63
DISTANCE PROTECTION FUNDAMENTALS (21)
➢ SOTF
➢ AR
➢ PSB
➢Fuse fail
64
DISTANCE PROTECTION FUNDAMENTALS (21)
SOTF
• The main purpose of the SOTF switch-on-to-fault function is to provide high-
speed tripping when energizing a power line on to a short-circuit fault on the
line.
65
DISTANCE PROTECTION FUNDAMENTALS (21)
• Various changes in power system may cause oscillations of rotating
units. The most typical reasons for these oscillations are big
changes in load or changes in power system configuration caused
by different faults and their clearance. As the rotating masses strive
to find a stable operate condition, they oscillate with damped
oscillations until they reach the final stability.
• The extent of the oscillations depends on the extent of the
disturbances and on the natural stability of the system.
• The oscillation rate depends also on the inertia of the system and on
the total system impedance between different generating units.
66
• Power Swing:A variation in three phase power flow which occurs when the
generator rotor angles are advancing or retarding relative to each other in
response to changes in load magnitude and direction, line switching, loss of
generation, faults, and other system disturbances.
67
68
69
BASIC CONCEPT OF POWER SYSTEM PROTECTION