ArcFlash Example13-Solution PDF
ArcFlash Example13-Solution PDF
The upgrade for the system will be to place a controllable fuse along with a bypass switch which can be modeled
as an external relay interlocked to operate contactors in ETAP. This example will utilize ETAP base features such
as revisions, out-in service state, scenarios, and presentations to best execute and present the original and
mitigated design.
In this example, we will learn how to model relay controllable fuse in ETAP and its different mode of operations.
Figure 2: (L) Initial Arc Flash and (R) Arc Flash @ 5 cycles (Conventional E-Rated Fuse)
Setup
Load the project file named “AF-Example13”. (The solution to this example is located in a directory
inside of this exercise called “Solution”. Open the solution project only to compare against your exercise
once completed.)
Utilize the library from AF-Example13.lib (inside the current project directory).
Select the following ETAP\Options (Preferences) before executing the exercise steps.
Procedure
Step1
Go to scenario wizard. Set up following scenarios. Fill in the incident energy results in table 1 for a fault on the
line side of the Main CB.
Table 1: Scenarios and Incident Energy Results for a Fault on the Line Side of the Main CB
Incident Energy for Arc
Scenario Name Revision Config Output Report
Fault at Main CB (cal/cm2)
E-RATED-FUSE E-RATED Normal E-RATED-FUSE 43.44
MVCF-NORMAL Normal Mode Normal MVCF-NORMAL 14.46
MAINTENANCE Maintenance Normal MAINT-MVCF 1.72
1.1 What was the fault clearing time for a fault at the line side of “Main CB” for scenario E-RATED-FUSE?
1.286 sec
___________________________________________________________________________________
1.2 What is the fault clearing time for a fault at the line side of “Main CB” after the MVCF is installed and it is
operating under normal operating conditions?
0.437 sec
____________________________________________________________________________________
1.3 How is the MVCF “Maintenance” mode being simulated in ETAP? What setting needs to be changed to
configure the near instantaneous operation of the primary side switch and fuse?
It is being implemented by changing instantaneous and overcurrent setting of the relay .OC1 and OC2 needs to be
modified in order to execute this mode of operation.
_____________________________________________________________________________________
1.4 How is the MVCF total clearing time of the MVCF fuse being modeled in ETAP? What setting needs to be
changed to configure the maintenance mode operation of the primary side switch and fuse total clearing time?
Total clearing time of the MVCF fuse is being modeled inside a multi-function relay1.Relay1 on the secondary of
the transformer controls the primary side fuse with OC1 being modelled as instantaneous bypass SW and OC2
being modelled as controllable fuse.
_____________________________________________________________________________________
Step2
Inspect the TCC “Star1” for each of the following revisions:
E-RATED
Normal Mode
Maintenance
Observe the coordination, the time differences between devices and also identify the magnitude of the arc current.
These are all factors which need to be considered when applying this type of incident energy mitigation
technique.