Fixed Gas Detector Operation Manual
Fixed Gas Detector Operation Manual
Fixed Gas Detector Operation Manual
Precautions:
To avoid personal safety injury, Instrument damage and potential
dangerous accident; do not install the gas detector before reading this
manual
1. Brief Introduction
TC100N fixed gas detector adopts
advanced catalytic gas sensor or
electrochemical sensor, which can
translate the gas concentration in the
air to the digital signal output.
TC100N adopts three wire 4~20mA
electric current signal to connect to
9. Normal fault and solution
Fault description Reason Solution the gas monitor panel.
time-lapse doesn’t The detector working with gas
Wait till it ends
No response for end controller can be used to detect gas
detection gas Sensor broken Change sensor in refinery, chemical plant, LPG
Circuit fault Factory maintain
Wire connection Check the wire station, boiler room, painting plant
Abnormal Fault connection and other places with gas exists.
connection Open circuit of Inspect the open
with Controller signal output circuit
Circuit Fault Factory maintain
2. Specifications Disconnect the sensor module from the detector. At the same time, hold
Gas Range Resolution Low alarm High alarm both S2 and S3 buttons continuously for 1-2 seconds, the green power
LEL (0~100)%LEL 1%LEL 20%LEL 50%LEL LED starts to flicker, which indicates the device enters into calibration
HC vapour (0~100)%LEL 1%LEL 20%LEL 50%LEL status. Adjust the first digit of DIP switch to "ON". Red LED starts to
O2 (0~30)%vol 0.1%vol 19.5%vol 23.5%vol flicker and green LED is continuously on. After several minutes, resume
CO (0~1000)ppm 1ppm 35ppm 200ppm the first digit of DIP switch to the original position, and the detector
H2S (0~100)ppm 1ppm 10ppm 15ppm remembers this value as zero. Red LED flickers several times and then
CL2 (0~20)ppm 0.1ppm 5ppm 10ppm is off. Zero calibration is completed.
7.4.2 Single Point Calibration (20.9%VOL)
SO2 (0~500)ppm 1ppm 10ppm 50ppm
After zero calibration, connect the sensor module to the detector correctly
NH3 (0~100)ppm 1ppm 25ppm 50ppm
and electrify the detector. After working for 10 minutes, follow the above
instruction to enter into calibration status. Adjust the second digit of DIP
Sensor type: Catalytic or electrochemical gas sensor switch to "ON" (which is 20.9%VOL. Red LED starts to flicker. After
Sampling: Natural diffusion several seconds, resume the DIP switch to the original position and the
Working type: Continuously working detector will remember this value. Red LED flickers several times and
Error: ≤±5%F.S. then is off. The calibration is completed.
Response time (T90): ≤30s (LEL) / ≤60s (toxic gas) 8. Sensor replacement
Working condition: In normal working environment, the catalytic sensor life is 3 years and
Temperature: -40~70℃ (LEL) / -20~50℃ (toxic gas) electrochemical sensor is 2 years. When the sensor life is overdue or the
Humidity: ≤95%RH (no condensation) sensor is damaged, please follow the following instruction to replace the
sensor.
Explosion-proof grade: ExdⅡCT6
Before replacing sensor, please first cut off power supply. The user
Protection grade: IP55
doesn’t need to open the detector cover, but only need to open the cover
Working voltage: DC24V±25%
the sensor module.
Working pressure: 86kPa~106kPa
8.1 Take off the calibration cover in counter-clockwise.
Signal output: 4-20mA 3-line 8.2 Pull out the decoration part downwards.
Consumption: 2W/channel 8.3 Screw off the jbckscrew from the sensor protection cover.
Life: Catalytic sensor 3 years; electrochemical sensor: 2 years 8.4 Take off the protection cover in counter-clockwise.
Connection screw size: G1/2” 8.5 Take out the old sensor.
Cable required: 3-line cable, ≥3 mm2 8.6 Put the new sensor into the sensor cover.
Transforming distance: ≤1000m Note: Please put the new sensor into the correct fixing holes. It's
Dimension and weight: l×b×h mm 196×186×68.5 App. 1200g forbidden to rotate the sensor.
8.7 Then install in turns protection cover, jbckscrew, decoration part and
DIP DIP 3. Structural Drawing
Calibration Calibration
switch switch The device consists of the housing, sensor part and PCB. The housing
10%F.S calibration consists of upper cover, lower cover, O-type circle and cable input hole
Zero calibration
point part. The housing function is to protect the inside part. The sensor part
40%F.S calibration 20%F.S calibration consists of gas sensor, sensor protection cover, decoration part and
point point calibration cap. The sensor and housing is connected by potting epoxy
50%F.S calibration 60%F.S calibration resin. The following is the structural drawing:
point point
Note: Black part is position of the DIP switch.
7.3.2.2 Connect gas bottle and gas flow meter correctly. Open the gas
bottle and adjust the flow meter according to the above table. Connect the
tube to the calibration cap of the detector. After 2 minutes of inputing gas,
when the controller displaying value will be the same with the standard
gas concentration, resume the DIP switch to the original position and the
detector will remember this value. Red LED flickers several times and
then is off. Then close the gas bottle and take off the tube. The calibration
is completed.
5.4 After the correct wire connection, take out the useless wire from the
enclosure. Then screw on the connector, tighten the compaction circle,
rubber air-proof circle and wire. Explosion-proof soft tube can also be
connected with the device directly.
Note: The size of the wire between the controller and detector should be
1 Wall
not less than 6mm, and the distance should be note more than 1000m.
2 Fixing holes
5.5 After checking all the connection well, install the display PCB and the
3 Bolts
front cover. Make sure O-type circle is put on and connected with the
cover tightly.
6. Debugging
Before adjusting, please be noted of the following information: Fig. 3 Wall Mounted