Installation and Operating Manual: IOMMASGPXX01-GB - 00

Download as pdf or txt
Download as pdf or txt
You are on page 1of 61

INSTALLATION AND OPERATING MANUAL

10-40 kVA

IOMMASGPXX01-GB_00
ITALIANO
INDEX
10-40 kVA

1. CERTIFICATE AND CONDITIONS OF WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

2. SAFETY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.1 Important. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.2 Description of the symbols used on the labels applied to the . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

3. UNPACKING AND INSTALLATION OF THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8


3.1 Shipping and moving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
3.2 Unpacking procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
3.3 Environmental requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

ENGLISH
3.4 Electrical requisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
3.4.1 Backfeed protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
3.5 Installation procedure and instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.6 Connection of the generator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
3.7 External E.S.D. connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
3.8 Isolation transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
3.9 UPS Parallel configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
3.9.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
3.9.2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
3.9.3 Power connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
3.9.4 Control connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
3.10 External battery cabinet connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23

4. MODES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24


4.1 ON LINE operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
4.2 Operation in high efficiency mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
4.3 Operation with manual maintenance bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
4.4 Operation with external manual bypass. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
4.5 Operation in GE configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
4.6 “Energy Saver” Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26

5. ACCESS TO CONTROLS AND COMMUNICATION INTERFACES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27


5.1 Identifying the switches and interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
5.2 Functions of the switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28

6. MIMIC PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29


6.1 Advanced Mimic Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
6.1.1 Meaning of ideograms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
6.1.2 Meaning of the luminous bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
6.1.3 Mimic panel menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
6.2 Mimic panel concentrator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
6.2.1 Keyboard bloking procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41

IOMMASGPXX01-GB_00 3
INDEX
10-40 kVA

7. OPERATING PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42


7.1 Start-up in normal mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
7.2 Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
7.3 Extended out of service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
7.4 Switching onto manual bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
7.5 Return to normal mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
7.6 Emergency shutdown (ESD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43

8. COMMUNICATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
ITALIANO
ENGLISH

8.1 Multi-Level Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44


8.2 Standard Lan web page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
8.2.1 Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
8.2.2 Description of the functions available . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
8.3 Accessories and SW options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50

9. PROBLEM SOLVING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52


9.1 System alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
9.2 UPS Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
9.3 Preventive maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
9.3.1 Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
9.3.2 Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
9.3.3 Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54

10. OPTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55


10.1 ADC card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
10.2 Kit GSS (Global Supply System) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
10.3 Isolation Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
10.4 Remote mimic panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
10.5 External maintenance bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
10.6 External maintenance bypass with backfeed protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
10.7 ACS PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
10.8 External back-feed protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
10.8.1 Protection on Mains Supply and on Auxiliary Mains Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
10.8.2 Protection on an UPS without auxilary mains supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
10.9 ADC card with temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
10.10 Profibus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
10.11 GSM modem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
10.12 Serial connection PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
10.13 Management of external maual by-pass contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59

11. TECHNICAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60

4 IOMMASGPXX01-GB_00
CERTIFICATE AND CONDITIONS
1 OF WARRANTY 10-40 kVA

This SOCOMEC UPS continuous power system is guaranteed against any manufacturing and material defects.
The period of validity of the warranty is 12 (twelve) months from the date of commissioning, if said activation is
carried out by SOCOMEC UPS personnel or personnel from a support centre authorised by SOCOMEC UPS, and not
however more than 15 (fifteen) months from the date of shipment by SOCOMEC UPS.
The warranty is recognized within national territory. If the UPS is exported out of national territory, the warranty shall
be limited to the cover of the parts used to repair the fault.
The warranty is valid ex-works and covers labour and parts used to repair the fault.

ENGLISH
The warranty shall not apply in the following cases:
r 'BJMVSFTEVFUPGPSUVJUPVTDJSDVNTUBODFTPSGPSDFNBKFVSF MJHIUOJOH óPPET FUD

r 'BJMVSFTEVFUPOFHMJHFODFPSJNQSPQFSVTF VTFPVUPGUPMFSBODFUFNQFSBUVSF IVNJEJUZ WFOUJMBUJPO FMFDUSJDQPX-
FSTVQQMZ BQQMJFEMPBE CBUUFSJFT

r *OTVîDJFOUPSJOBEFRVBUFNBJOUFOBODF
r "UUFNQUFENBJOUFOBODF SFQBJSTPSNPEJñDBUJPOTOPUDBSSJFEPVUCZ40$0.&$614QFSTPOOFMPSQFSTPOOFMGSPN
a support centre authorised by SOCOMEC UPS.
r *GUIFCBUUFSZIBTOPUCFFOSFDIBSHFEJOBDDPSEBODFXJUIUIFUFSNTJOEJDBUFEPOUIFQBDLBHJOHBOEJOUIFNBOVBM 
in cases of extended storage or UPS inactivity.
SOCOMEC UPS may, at its own discretion, opt for the repair of the product or for the replacement of the faulty or
defective parts with new parts or with used parts that are equivalent to new parts with regard to functions and
performance.
Defective or faulty parts replaced free of charge are to be put at the disposal of SOCOMEC UPS who becomes the
sole owner.
Replacements or repairs of parts and any modifications to the product during the warranty period cannot extend
the duration of the warranty.
In no case will SOCOMEC UPS be responsible for damages (including, without limitations, damage for loss of earn-
ings, interruption of activity, loss of information or other economic losses) deriving from the use of the product.
5IFQSFTFOUDPOEJUJPOTBSFTVCKFDUUP*UBMJBOMBX"OZEJTQVUFGBMMTVOEFSUIFQSPWJODFPGUIF$PVSUPG7JDFO[B

IOMMASGPXX01-GB_00 5
2 SAFETY
10-40 kVA

2.1 IMPORTANT.
r 5IJTEPDVNFOUQSPWJEFTJNQPSUBOUJOTUSVDUJPOTGPSUIFTBGFVTF NPWFNFOUBOEDPOOFDUJPOPGUIF."45&3:4–VO-
interruptible power system (UPS).
r 40$0.&$614SFUBJOTUIFGVMMBOEFYDMVTJWFPXOFSTIJQSJHIUTPWFSUIJTEPDVNFOU0OMZBQFSTPOBMSJHIUUPVUJMJ[F
the document for the application indicated by SOCOMEC UPS is granted to the recipient of such document. All
reproduction, modification, dissemination of this document whether in part or whole and by any manner are
expressly prohibited except upon Socomec’s express prior written consent.
r 5IJTEPDVNFOUJTOPUBTQFDJñDBUJPO40$0.&$614SFTFSWFTUIFSJHIUUPNBLFBOZDIBOHFTUPEBUBXJUIPVUQSJPS
notice.
ITALIANO
ENGLISH

r 5IFVOJUNVTUCFJOTUBMMFEBOEBDUJWBUFEPOMZCZRVBMJñFEUFDIOJDBMQFSTPOOFMBOEBVUIPSJTFECZ40$0.&$614

The UPS MUST only be moved by two people at least.


The people MUST take position at the sides of the UPS with respect to the direction of movement.

r 5IFVOJUNVTUSFNBJOJOBWFSUJDBMQPTJUJPOJOBMMDJSDVNTUBODFT
r $POOFDUUIF1&HSPVOEDPOEVDUPSñSTUCFGPSFZPVNBLFBOZPUIFSDPOOFDUJPO
r %POPUFYQPTFUIF614UPSBJOPSMJRVJETJOHFOFSBM%POPUJOUSPEVDFFYUFSOBMCPEJFT
r *GUIF614JTOPUFRVJQQFEXJUIBVUPNBUJDTFDUJPOJOHBHBJOTUCBDLGFFEPSJGUIFTXJUDIJTFYUFSOBMUPUIF614 BîY
a label bearing the following words on all the external switches of the UPS power supply:

ISOLATE THE UPS BEFORE


OPERATING ON THIS CIRCUIT

r ,FFQUIJTNBOVBMIBOEZGPSGVUVSFDPOTVMUBUJPO
r *GUIFVOJUGBJMT JUNVTUCFSFQBJSFEPOMZCZBVUIPSJTFEUFDIOJDJBOTUIBUIBWFCFFOTQFDJBMMZUSBJOFEGPSUIJTQVS-
pose.
r 5IJTFRVJQNFOUDPOGPSNTUPUIF&VSPQFBO$PNNVOJUZEJSFDUJWFTGPSQSPGFTTJPOBMFRVJQNFOUBOECFBSTUIFBQ-
proval mark
r 5IF614SFRVJSFTUISFFQIBTFQMVTOFVUSBMJOQVUDPOOFDUJPOT 1 /

r %POPUDPOOFDUUIFPVUQVUOFVUSBMUPHSPVOE5IF614EPFTOPUNPEJGZUIFOFVUSBMBSSBOHFNFOUTPGUIFTZTUFN
the use of an isolation transformer is required should it be necessary to modify the neutral arrangements down-
stream of the UPS.
r #FGPSFDPOOFDUJOHBOZFYUFSOBMCBUUFSZDBCJOFU FOTVSFUIBUJUJTGVMMZDPNQBUJCMFXJUIUIFNPEFMPG614JUJTUPCF
used with.
r 5IFVTFPGFYUFSOBMCBUUFSZDBCJOFUTOPUTVQQMJFECZUIFNBOVGBDUVSFSTJTOPUSFDPNNFOEFE
r 4XJUDIPíBOEJTPMBUFUIF614BOEUIFOXBJUGPSNJOVUFTCFGPSFSFNPWJOHUIFQSPUFDUJPOQBOFMTJOPSEFSUPDBSSZ
out work on parts under dangerous voltage.
r %BOHFSPGFYQMPTJPOJGUIFCBUUFSJFTBSFSFQMBDFEXJUIPUIFSTPGUIFXSPOHUZQF
r 3FQMBDFECBUUFSJFTNVTUCFEJTQPTFEPGBUBVUIPSJTFEXBTUFEJTQPTBMDFOUSFT

6 IOMMASGPXX01-GB_00
2 SAFETY
10-40 kVA

It is very dangerous to touch any part of the batteries as there is no isolation between the batter-
ies and the mains power source.

The product you have chosen is designed for commercial and industrial use only.
In order to be used for particular “critical applications” such as life support systems, medical applications, commercial
transportation, nuclear facilities or any other application or systems where product failure is likely to cause substan-
tial harms to person or property, the products may have to be adapted.
For such uses we would advise you to contact SOCOMEC UPS beforehand to confirm the ability of these products
to meet the requested level of safety, performance, reliability and compliance with applicable laws, regulations and

ENGLISH
specifications.

2.2 DESCRIPTION OF THE SYMBOLS USED ON THE LABELS APPLIED TO THE UNIT.
All the precautions and the warnings on the labels and plates on the inside and outside of the equipment should
be respected.

DANGER! HIGH VOLTAGE (BLACK/YELLOW)

GROUND TERMINAL

READ THE USER MANUAL BEFORE USING THE UNIT

IOMMASGPXX01-GB_00 7
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA

The packaging guarantees the stability of the UPS during shipping and physical transfer. Carry the packaged unit as
close as possible to the installation site.

When moving the unit on even slightly sloping surfaces, use the blocking equipment and break-
ing devices to ensure that the unit does not fall over.

3.1 SHIPPING AND MOVING.


r 5IF614NVTUSFNBJOJOBWFSUJDBMQPTJUJPOEVSJOHBMMTIJQQJOHBOENPWJOHPQFSBUJPOT
ITALIANO
ENGLISH

r 5IFVOJUIBTXIFFMTUIBUDBOCFVTFEUPNPWFJUGPSTIPSUEJTUBODFT
r &OTVSFUIBUUIFóPPSJTTUSPOHFOPVHIUPTVQQPSUUIFXFJHIUPGUIF614BOEPGUIFCBUUFSZDBCJOFU JGVTFE

Avoid pressing on the front panels when moving the unit.

The UPS MUST only be moved by two people at least. The people MUST take position at the
sides of the UPS with respect to the direction of movement.

CAUTION IF DAMAGED.
BATTERIES, NON SPILLABLE.
Packages, crushed, punctured, or torn such that contents are revealed
must be set aside in an isolated area and inspected by a qualified per-
son. If the package is deemed to be not shippable, the contents must Battery is NOT connected!
be promptly collected, segregated, and either the consignor or consignee
contacted.

All packaging material must be recycled in compliance with the laws in force in the country where
the system is installed.

8 IOMMASGPXX01-GB_00
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA

3.2 UNPACKING PROCEDURE.


3.2.1 Models “S” (h 800 mm) and models “M” (h 1.000 mm).
3.2.1-1 3.2.1-2 3.2.1-3 Remove screws A and screws B.
A

ENGLISH
B

3.2.1-4

The UPS can be moved.


Place the UPS in the installation
2
area.

3.2.1-5 Secure the UPS with feet C.

C Secure the UPS with feet D only when it is in position with cables
C
connected.

IOMMASGPXX01-GB_00 9
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA

3.2.2 Models “T” (h 1.400 mm).


3.2.2-1 3.2.2-2 3.2.2-3 Remove screws A and screws B.
A
ITALIANO
ENGLISH

3.2.2-4 3.2.2-5 Remove screws A.

1 A

2 2

Loosen screws B.
3.2.2-6 Remove screws C. 3.2.2-7 Tighten screws B.

1 B 2 B

1
The UPS can be moved.
1 Place the UPS in the installation
2 C area.

3.2.2-8 Secure the UPS with feet D. 3.2.2-9 Loosen screws B.

1 B

2
Secure the UPS with feet D
only when it is in position 2
D D with the cable connected.

10 IOMMASGPXX01-GB_00
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA

Tighten screws B.
3.2.2-10 Tighten screws C. 3.2.2-11 Tighten screws A.

2 B 2 A

ENGLISH
1 C

For UPS 15-40kVA height 1.400mm without internal battery:


t XJUICBUUFSZDBCJOFUöUUFEBMPOHTJEF remove leveller E from the cabinet. Fasten the UPS to the
cabinet using the bracket E supplied (figure 3.2.2-12).
t XJUIPVUCBUUFSZDBCJOFUöUUFEBMPOHTJEF TFDVSFUIF614UPUIFóPPS(figure 3.2.2-13).

3.2.2-12 3.2.2-13
E

IOMMASGPXX01-GB_00 11
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA

3.3 ENVIRONMENTAL REQUISITES.


r 5IFSFDPNNFOEFEPQFSBUJOHUFNQFSBUVSF IVNJEJUZBOEBMUJUVEFWBMVFTBSFMJTUFEJOUIFUFDIOJDBMTQFDJñDBUJPOT
table (see chapter 11). Cooling systems may be required to maintain these values.
r "WPJEEVTUZFOWJSPONFOUTPSBSFBTXIFSFUIFSFJTEVTUGSPNDPOEVDUJWFPSDPSSPTJWFNBUFSJBMT FHNFUBMEVTUPS
chemical solutions).
r 5IF614JTOPUEFTJHOFEGPSPVUEPPSVTF
r %POPUFYQPTFUIF614UPEJSFDUTVOMJHIUPSUPTPVSDFTPGFYDFTTJWFIFBU
r "TQBDFPGBUMFBTUDNNVTUCFMFGUBUUIFCBDLGPSBEFRVBUFWFOUJMBUJPO TFFñHVSF

r 5IF614TXJUDIFTBSFBDDFTTFEGSPNUIFGSPOUIPXFWFS BTQBDFPGBUMFBTUNFUSFTTIPVMECFMFGUBUUIFGSPOUPG
ITALIANO
ENGLISH

the UPS for maintenance purposes. It is also recommended to ensure that the cable connections are sufficiently
MPOHBOEóFYJCMFTPUIBUUIFVOJUDBOCFFYUSBDUFEEVSJOHNBJOUFOBODF TFFñHVSF

r *GJUJTOPUQPTTJCMFUPMFBWFTVîDJFOUTQBDFBUUIFGSPOU BEFRVBUFBDDFTTNVTUCFFOTVSFEGSPNCPUITJEFT

3.3-1 3.3-2
40 cm

40 cm
20 cm 20 cm
MASTERYS MASTERYS MASTERYS
UPS OR UPS OR UPS OR MASTERYS MASTERYS
OTHER OTHER OTHER UPS UPS
CABINET CABINET CABINET
1,5 m

1,5 m

12 IOMMASGPXX01-GB_00
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA

3.4 ELECTRICAL REQUISITES.


The installation and the system must comply with national plant regulations.
The electrical distribution panel must have a protection and sectioning system installed for the input mains and the
BVYJMJBSZNBJOT*GBEJíFSFOUJBMTXJUDIJTJOTUBMMFEPOUIFNBJOTQPXFSTXJUDI PQUJPOBM
JUNVTUCFJOTFSUFEVQTUSFBN
from the distribution panel.
The table below show the size of the input protection devices recommended for correct installation.

Size of the input protection devices


UPS Magneto-thermal Magneto-thermal Differential Input/Output Battery Battery
input1 Aux Mains1 input5 cable core size cable core size protection4

ENGLISH
(kVA) (A) (A) (A) (mm2) (mm2) (A)
single parallel2 single parallel2 selective type5 Min Max3 Min Max3
10 3/1 32 40 100 125 0,5 6 35 6 35 50 Gr
100 125 16
if common if common aux mains
input input and output
mains mains
15 3/1 32 40 100 125 0,5 6 35 6 35 50 Gr
100 125 25
if common if common aux mains
input input and output
mains mains e uscita
20 3/1 40 63 125 160 0,5 10 35 10 35 50 Gr
125 160 35
if common if common aux mains
input input and output
mains mains e uscita
10 3/3 32 40 32 40 0,5 6 35 6 35 50 Gr
15 3/3 32 40 32 40 0,5 6 35 6 35 50 Gr
20 3/3 40 63 40 63 0,5 10 35 10 35 50 Gr
30 3/3 63 80 63 80 0,5 16 35 16 35 100 Gr
40 3/3 80 100 80 100 0,5 25 35 25 35 100 Gr
1
Recommended magneto thermal switch: four poles with intervention threshold ≥ 10 In
2
In systems with two or more UPSs operating in a redundant or power parallel configuration.
3
Determined by the size of the terminals.
4
protection on the external battery cabinet.
5
Caution! Use type B four-pole selective (S) circuit breakers. Load leakage currents are added to those generated by the UPS and during transitory
QIBTFT QPXFSGBJMVSFBOEQPXFSSFUVSO
TIPSUDVSSFOUQFBLTNBZPDDVS*GMPBETXJUIIJHIMFBLBHFDVSSFOUBSFQSFTFOU BEKVTUUIFEJíFSFOUJBM
protection. It is advisable in all cases to carry out a preliminary check on the earth current leakage with the UPS installed and operational with the
definitive load, so as to prevent the sudden activation of the above switches.

The UPS is designed for transitory overvoltages in category II installations. If the UPS is part of
the building’s electric circuit or if it is likely to be subject to transitory overvoltages in category III
installations, further external protection must be provided, either on the UPS or in the AC power
supply network to the UPS. In addition, the “Surge arrestor” option, specially designed to protect
against residual overvoltages in category III installations, can be installed in the external manual
bypass cabinet. If used, the distance between the UPS and the centralised 4 kV SPD protections
type 1 must be Up ≤ 4kV is ≥ 15m.

In the event of three-phase distorting loads connected in output, the current on the neutral
conductor may have a value that is 1.5 - 2 times the phase value (also for the input bypass). In this
case, size the neutral cables and the input/output protection adequately.

IOMMASGPXX01-GB_00 13
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA

3.4.1 Back-feed protection.


If the UPS does not have an automatic protection device against current back-feed, the operator/installer must add
a warning label to all the mains power disconnecting switches installed at a distance from the UPS area. This serves
to remind technicians of the fact that the circuit is connected to a UPS (see the CAUTION section in paragraph 2 of
this manual and paragraph 4.5.3. of the EN62040-1-1 2003-11 standard.
The label is supplied with the system.
The back-feed protection device may be built into the system (only on specific request), or an electromechanical
switch may be installed externally in the input of the UPS.
r *GUIF614JODPSQPSBUFTUIJTQSPUFDUJPO QSPDFFEXJUIUIFDPOOFDUJPOTBTEFTDSJCFEJOQBSBHSBQIPGUIJTNBOVBM
ITALIANO
ENGLISH

r 5PJOTUBMMUIFFYUFSOBMCBDLGFFEQSPUFDUJPOJUJTOFDFTTBSZUPVTFUIF#,'DBSEBOEBOFYUFSOBMFMFDUSPNFDIBOJDBM
switch that should be installed . For further information on the connection and the type of remote switch, please
read paragraph 10.9 of this manual.
ATTENTION.
The neutral is not disconnected as, even in the event of a single fault on the UPS, it never has high po-
tential when the mains and/or auxiliary power supplies are disconnected upstream. This is to prevent
transformation of the power source to the UPS every time there is a power failure.
If, in certain anomaly states, or because of the installation upstream (e.g. undetected and protec-
ted earth fault, or high leakage in a phase, or with IT systems) there is a hazardous potential on
neutral, a suitable isolating switch must be provided on the neutral as well, or else there must be
a detection, signalling and protection system.
NOTE.
For equipment with separate Emergency Mains, the neutral of the Emergency Mains line must be electri-
cally common with the neutral of the main input feed line.

14 IOMMASGPXX01-GB_00
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA

3.5 INSTALLATION PROCEDURES AND INSTRUCTIONS.


WARNING!
Before carrying out work on the terminal board or on UPS internal parts, ensure that the UPS is
switched off, remove the power supply, open the external battery cabinet disconnectors, isolate
the system and wait 5 minutes.

3.5-1 Set Q1, Q2 and Q6 to the 0 position. 3.5-2 $BCMFTQFDJöDBUJPOT

ENGLISH
r TUSJQQJOHMFOHUINN
r UJHIUFOJOHUPSRVF œ /N
Q2
Q1
Q6

3/3 Connections if
THE MAINS AND AUX MAINS ARE CONNECTED IN COMMON

L12 L22 L32 N2 L11 L1 L21 L2 L31 L3 N11 N1 +B2 -B2 -B1 +B1

OUTPUT MAINS SUPPLY EXT. BATTERY

L12 N1
OUTPUT L22 L3 MAINS
L32 L2
N2 L1

IOMMASGPXX01-GB_00 15
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA

3/3 Connections if
THE MAINS AND AUX MAINS ARE CONNECTED SEPARATELY

2 L32 N2 L11 L1 L21 L2 L31 L3 N11 N1 +B2 -B2

TPUT MAINS SUPPLY EXT. BA


ITALIANO
ENGLISH

L12 L22 L32 N2 L11 L1 L21 L2 L31 L3 N11 N1 +B2 -B2 -B1 +B1

OUTPUT MAINS SUPPLY EXT. BATTERY

L12 N1
OUTPUT L22
L32
L3 MAINS
L2
N2 L1

L11
AUX L21
MAINS L31
N11

16 IOMMASGPXX01-GB_00
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA

3/1 Connections if
THE MAINS AND AUX MAINS ARE CONNECTED SEPARATELY

L12 L22 L32 N2 L11 L1 L21 L2 L31 L3 N11 N1 +B2 -B2 -B1 +B1

ENGLISH
OUTPUT MAINS SUPPLY EXT. BATTERY

OUTPUT L12 N1
N2 L3 MAINS
L2
L1

AUX L11
MAINS N11

IOMMASGPXX01-GB_00 17
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA

3.5-3 Divert any control cables from the front (RS232, signalling relay contacts, etc.) into the appropriate side
cable run A.

3.5-4 Remove the pre-cut detail C and bend details B to pass the cables, secure the terminal board cover with the
four screws.

3.5-5 Secure the cables to the couplings D located on the rack ensuring that the air vents are not obstructed in
any way.

3.5-6 0ODFUIFDBCMJOHIBTCFFODBSSJFEPVU TFDVSFUIF614XJUIUIFöYJOHGFFUE


ITALIANO
ENGLISH

3.5-7 NOTE.
*GUIFTZTUFNJTJOTUBMMFEPOBSBJTFEóPPS TVDIBTJOBEBUBQSPDFTTJOHSPPN

r MFBWFBTQBDFPGBUMFBTUDNCFUXFFOUIFQPXFSBOEUIFDPOUSPMDBCMFT
r BWPJEQBSBMMFMDIBOOFMMJOHPWFSMPOHEJTUBODFTDIPPTFDBCMFTDSPTTJOHBUžJOTUFBE

3.5-3 3.5-4 3.5-5

A D
B C

N1 +B2 -B2 -B1 +B1

Y EXT. BATTERY

3.5-6 3.5-7
20 cm
B

B 90°

A A

E A. Power cables
E B. Control cables

18 IOMMASGPXX01-GB_00
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA

3.6 CONNECTION OF THE GENERATOR.


If your system uses a generator, connect the “generator set ready” no-potential contact to connector IN 2 on the
optional ADC PCB configured in standard or power safe mode (see paragraph 10.1). This automatically extends the
voltage and frequency value range when power is supplied by the generator set.

3.7 EXTERNAL E.S.D. CONNECTION.


"SFNPUFFNFSHFODZTIVUEPXOTZTUFN &4%
DBOCFJOTUBMMFECZNFBOTPGUIFPQUJPOBM"%$1$#TFFQBSBHSBQI
10.1. Connect a normally closed zero-potential contact to terminals IN1+ and IN1- of the ADC PCB.

ENGLISH
3.8 ISOLATION TRANSFORMER.
The MASTERYSTM IP model of the MASTERYSTM range is fitted with an internal isolation transformer.
If an external isolation transformer cabinet is required, the following instructions should be followed:
r 3FGFSUPDIBQUFSTBOEPGUIJTNBOVBMGPSJOEJDBUJPOTPONPWJOHBOEJOTUBMMJOHUIFDBCJOFU
r 4FFQBSBHSBQIGPSEFUBJMTBCPVUQSPUFDUJPOT
r 5IFQSPUFDUJPODBCMFNBSLFEXJUIUIFHSPVOETZNCPMJTDPOOFDUFEEJSFDUMZUPUIFEJTUSJCVUJPOQBOFM
r 5IFUSBOTGPSNFSDBOFJUIFSCFDPOOFDUFEUPUIF614JOQVUPSPVUQVU

The UPS must not operate without the neutral connection to the input.
The transformer cannot be connected to the output on single UPS unit connected in parallel con-
öHVSBUJPO

For details of the connections, refer to the transformer terminal board diagram.

IOMMASGPXX01-GB_00 19
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA

3.9 UPS PARALLEL CONFIGURATION.


3.9.1 General.
Parallel connection enhances UPS system reliability, performance and power.
All MASTERYSTM models can be installed in parallel configuration provided they have the special parallel kit that can
be installed in factory or later by specialist personnel.
UPS modules for parallel operation are identical to standard UPS modules, as a result safety, shipping and installation
recommendations in chapters 2 and 3 also apply.
ITALIANO
ENGLISH

3.9.2 Installation.
UPS units operating in parallel are interconnected using control cables B ñH
BOEBSFDPOñHVSFEEJíFSFOUMZ
depending on the position they are assigned.
For this reason the units have a position label C (Fig. 3.9.4-1):
r 5IFi-&'5uMBCFMNFBOTUIBUUIFVOJUNVTUCFQPTJUJPOFEUPUIFMFGU
r 5IFi3*()5uMBCFMNFBOTUIBUUIFVOJUNVTUCFQPTJUJPOFEUPUIFSJHIU
r 5IFi*/5&3/"-uMBCFM VTFEPOMZPOTZTUFNTXJUIUISFF614
NFBOTUIBUUIJTVOJUNVTUCFQPTJUJPOFECFUXFFOUIF
two other cabinets.
The control cables supplied allow a maximum distance of about 3 metres between the UPS units. This gives enough
room for an external battery cabinet to be inserted beside each UPS.

3.9.3 Power connections.


r 5IFQPXFSTVQQMZUPFBDIVOJUNVTUCFQSPUFDUFEBTJOEJDBUFEJOUIFUBCMFJOQBSBHSBQI
r 5IFDSPTTTFDUJPOBOEMFOHUIPGUIFJOQVUBOEPVUQVUDBCMFTNVTUCFJEFOUJDBMGPSBMMUIFVOJUT
r 5IFQIBTFSPUBUJPONVTUCFUIFTBNFGPSFBDIVOJUDPOOFDUFEJOQBSBMMFMBOEBMTPPOBOZFYUFSOBMNBOVBMCZQBTT
line.
r $BCMFTPGUIFTBNFMFOHUIBOEDSPTTTFDUJPONVTUCFVTFEGPSUIFDPOOFDUJPOCFUXFFOUIFHFOFSBMQPXFSTXJUDI
A, the switches C and the respective UPS units. The length of the cables from A to each UPS module must not
exceed 25 meters (Fig. 3.9.3-1).
r 5IFDBCMFTGSPNUIF614NPEVMFUPDJSDVJUCSFBLFSF must be of the same length (max. 15 metres) with multi-core
cables.
r *GBEJíFSFOUJBMTXJUDIJTJOTUBMMFEPOUIFNBJOTQPXFSTXJUDI PQUJPOBM
JUNVTUCFJOTFSUFEVQTUSFBNGSPNUIF
distribution panel (see fig. 3.9.3-1, detail H), it must be a selective type and the trigger value must be 0.5 A by
the number of UPS connected in parallel.

Only activate circuit breaker D after carrying out the procedure for switching onto the mainte-
nance bypass.

Only activate circuit breaker E after turn off the UPS.

20 IOMMASGPXX01-GB_00
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA

3.9.3-1 RECOMMENDED PARALLEL CONFIGURATION.

A
25 m max D

ENGLISH
C C C C C C

B
B
B
B
L B
I
I
I
I
R

E
E
E
E
E
E

 x
  A: 7.5 m max
F

A System input switch D Ext. bypass magneto-thermal switch I Internal UPS “INTERNAL”
B “Parallel bus” cable E Output switch L Left UPS “LEFT”
C Single UPS magneto-thermal switch (if a F System shutdown switch R Right UPS “RIGHT”
separate auxiliary power source is used, G Distribution
add a magneto-thermal switch for each H.BJOEJíFSFOUJBMNBHOFUPUIFSNBMTXJUDI
UPS)

IOMMASGPXX01-GB_00 21
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA

3.9.4 Control connections.


In order for units connected in a parallel configuration to operate correctly, control cables are required to exchange
data between the various UPS units making up the parallel system, for management of correct load sharing and
synchronisation logic.
The cables in question are supplied with the UPS in case of standard parallel setting or are attached to the parallel
kit in case of later upgrading of the system.
1BSBMMFMDPOöHVSBUJPONVTUPOMZCFBDUJWBUFECZ40$0.&$614RVBMJöFEQFSTPOOFMJOFBDIDBTFBSSBOHFUIF
running of the control cables in the relative cable run as shown in figure 3.9.4-1, leaving the connector(s) uncon-
nected (in the central UPS one incoming and one outgoing control cable must be used).
ITALIANO
ENGLISH

3.9.4-1

A
C

A Control cables cable run.


B i1BSBMMFMCVTuDBCMFMFBWFBQQSPYBDNDBCMFMFOHUIBUUIFFYJUPGUIFDBCMFSVO
C Label for unit positioning.

22 IOMMASGPXX01-GB_00
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA

3.10 EXTERNAL BATTERY CABINET CONNECTION.

If the UPS has internal batteries, connecting external battery cabinets is prohibited.

Position the battery cabinet next to the UPS.


Before carrying out any operation, ensure that:
t UIFCBUUFSZGVTFTMPDBUFEJOTJEFUIFCBUUFSZDBCJOFUBSFPQFO
t UIF614JTOPUMJWF
t BMMNBJOTPSCBUUFSZTXJUDIFTBSFPQFO

ENGLISH
t UIFTXJUDIFTVQTUSFBNPGUIF614BSFPQFO
r 3FNPWFUIFUFSNJOBMCPBSETQSPUFDUJPO
r $POOFDUUIFHSPVOEDBCMF ñHVSF

r $POOFDUUIFDBCMFTCFUXFFOUIF614UFSNJOBMTBOEUIFCBUUFSZDBCJOFUUFSNJOBMT TUSJDUMZPCTFSWJOHUIFQPMBSJUZPG
each individual string (figure 3.10-1) and the cross-sections indicated in table 3.4.

Use double insulated cables or the cables supplied with the unit to connect the UPS to the Bat-
tery cabinet. The lenght L of battery cable must not be more than 8 metres long (if L > 8 m, please
contact the support service).

Cabling errors with inversion of the battery polarity may cause permanent damage to the equip-
ment.

r 3FQMBDFUIFUFSNJOBMCPBSETQSPUFDUJPO

If using cabinets not supplied by the manufacturers of the UPS, it is the installer’s responsibility
to check the electrical compatibility and the presence of appropriate protection devices between
the UPS and the battery cabinet (fuses and switches of sufficient capacity to protect the cables
from the UPS to the battery cabinet). As soon as the UPS is switched on (before closing the bat-
UFSZTXJUDIFT
UIFCBUUFSZQBSBNFUFSTNVTUCFWFSJöFEBDDPSEJOHMZ WPMUBHF DBQBDJUZ OVNCFSPG
elements, etc.) on the mimic panel menu. If the values indicated on the battery cabinet data plate
are different from those shown on the mimic panel, use the SERVICE > CONFIGURATIONS menu
to correct the settings.

3.10-1
BATTERY CABINET
+B2

+B1
–B2
–B1

EXTERNAL BATTERY
L12 L22 L32 N2 L11 L1 L21 L2 L31 L3 N11 N1 +B2 -B2 -B1 +B1

OUTPUT MAINS SUPPLY EXT. BATTERY

UPS

IOMMASGPXX01-GB_00 23
4 MODES OF OPERATION
10-40 kVA

4.1 ON LINE OPERATIONS.


"TQFDJBMGFBUVSFPGUIF."45&3:4–TFSJFTJTUIFi0/-*/&uEPVCMFDPOWFSTJPOGFBUVSFJODPOKVODUJPOXJUIMPXEJT-
tortion mains power absorption. With ON LINE mode, the UPS is able to supply a voltage that is fully stabilised in
frequency and amplitude, regardless of any interference in the mains power supply within the most stringent clas-
sification of UPS regulations.
ON LINE operation provides three operating modes according to mains and load conditions:
r “Normale” mode.
This is the most frequent operating condition: the energy is drawn from the primary mains power supply and is
converted and used by the inverter to generate the output voltage to power the loads connected.
ITALIANO
ENGLISH

The inverter is constantly synchronised in frequency with the auxiliary mains to enable load transfer (due to an
overload or inverter shutdown) without any break in the power supply to the load.
The battery charger supplies the energy required to maintain or recharge the battery.
r “Bypass” mode.
In case of inverter failure, the load is automatically transferred onto the auxiliary mains without any interruption in
the power supply. This procedure may occur in the following situations:
- in the event of a temporary overload, the inverter continues to power the load. If the condition persists, the UPS
output is switched onto the auxiliary mains via the automatic bypass. Normal operation, which is from inverter,
returns automatically a few seconds after the overload disappears.
 XIFOUIFWPMUBHFHFOFSBUFECZUIFJOWFSUFSHPFTJTPVUPGUPMFSBODFTEVFUPBNBKPSPWFSMPBEPSBGBVMUPOUIF
inverter.
- wWhen the internal temperature exceeds the maximum value allowed.
r “Battery” mode.
In the event of a mains failure (micro interruptions or extended black-outs), the UPS continues to power the load
using the energy stored in the battery. The Expert Battery System keeps the user constantly informed on the
battery status and on the back-up time available. The disconnection of non mission critical applications during
battery discharge can be programmed (after a certain laps of time) by using the Power Share option, so that the
battery resources can be reserved for the most critical applications.

4.2 OPERATION IN HIGH EFFICIENCY MODE.


The UPS has a selectable and programmable “economy” operating mode that can increase overall efficiency by
up to 98% for energy saving purposes. With this mode of operation, specific daily or weekly time intervals can be
selected and programmed to power the applications directly from the auxiliary mains. If the power supply outage,
the UPS will automatically switch onto the inverter and continue to supply power to the load by drawing energy
from the battery.
This mode does not provide perfect stability in frequency and voltage like the ON LINE mode. Thus the use of this
mode should be carefully evaluated according to the level of protection required by the application.
The Eco Mode operation provides very high efficiency, since the application is powered directly from the auxiliary
mains via the automatic bypass in normal operating conditions.

24 IOMMASGPXX01-GB_00
10-40 kVA

4.3 OPERATION WITH MANUAL MAINTENANCE BYPASS.


If the maintenance bypass is activated using the appropriate procedure, the load is powered directly from the
NBJOUFOBODFCZQBTT XIJMFUIF614JTTFQBSBUFEGSPNUIFQPXFSTVQQMZBOEDBOCFTXJUDIFEPí
This operating mode can be selected for maintenance to be carried out on the system so that the necessary actions
can be performed by service personnel without having to disconnect the power supply to the load.

4.4 OPERATION WITH EXTERNAL MANUAL BYPASS.


The external maintenance bypass may be placed on the general distribution panel when the UPS is installed, or by
installing the bypass panel that is supplied on request. By-pass panel connection diagram.

ENGLISH
If the UPS has an input for the auxiliary power supply, the Q2 switch must be connected to this input and the main
power supply input must be disconnected on the control panel.
If the maintenance bypass is activated with the appropriate procedure, the load is powered directly from the main-
UFOBODFCZQBTT XIJMFUIF614JTTFQBSBUFEGSPNUIFQPXFSTVQQMZBOEDBOCFTXJUDIFEPí
This operating mode can be selected for maintenance to be carried out on the system so that the necessary actions
can be performed by service personnel without having to disconnect the power supply to the load.

Bypass panel connection diagram.


4.4-1 3-phase input/3-phase output for UPS 3/3.

L1 L1
Mains L2 L2
IN
L3 L3
N N
Q2

UPS
Q1
Q3
L1 L1
L2 L2
L3 L3 OUT
Load N N

4.4-2 3-phase input/1-phase output for UPS 3/1.

L1 L1
Mains L2 L2
IN
L3 L3
N N
Q2
UPS
Q1
Q3
Lo Lo
N N OUT Q1 Bypass switch.
Load
Q2 Mains power switch.
Q3 Output switch.

IOMMASGPXX01-GB_00 25
4 MODES OF OPERATION
10-40 kVA

4.5 OPERATION IN GE CONFIGURATION.


."45&3:4–DBOCFPQFSBUFEJODPOKVODUJPOXJUIBHFOFSBUPS (&

With a generator, the frequency and voltage ranges of the auxiliary mains can be increased to accept the instabil-
ity of the GE and at the same time to avoid operation from the battery or risks of out-of-synchronisation switching
onto the bypass.
The use of the GSS interface, described in the options section, also increases the amount of diagnostic information
exchanged between the continuous power system and the generator.
ITALIANO

4.6 “ENERGY SAVER” MODE.


ENGLISH

This mode ensures that the UPS system always operates at the highest load efficiency (40-70% of the nominal
power).

This mode can only be activated on UPS connected in parallel and operating in normal mode.

In cases of low load, the system shuts down any unnecessary UPS units, thus increasing the load on the remaining
units.
This leads to higher system efficiency, as the UPS in stand-by are not using any power, while the active units with a
high load are operating at maximum productivity.
When the load increases, the units in stand-by are immediately reactivated to guarantee continuous power supply.
Monitoring the hours of operation means that the hours are distributed on all the UPS, alternating the units that are
shut down from time to time. This prolongs the life of the units and reduces the risk of failure.

4.6-1 Load sharing. 4.6-2 Load sharing + Energy Saver.

% load % load
% load % load
% load % load

 


   
   

26 IOMMASGPXX01-GB_00
ACCESS TO CONTROLS
5 AND COMMUNICATION INTERFACES 10-40 kVA

This chapter identifies the electromechanical switches, described below, and used for start-up, shutdown and
maintenance bypass procedures.

Access to the control area is from the front by opening the upper door 5-1
using the red handle as shown in figure 5-1. The control area also contains
the communication interface connectors and the slots for the optional sig-
nalling cards. Please refer to the relevant chapter for more details on the
connection and use of the related communication interfaces/cards.

ENGLISH
5.1 IDENTIFYING THE SWITCHES AND INTERFACES.
5.1-1
Legend.
S S1 Q1 B Internal batteries
Q2
B1 External batteries
Q6 C1 Serial connector RS232/485
C3
C2 serial connector RS232 for Modem
C3 LAN connector RJ45 for Ethernet
C1
S Mimic panel
C2 S1 Options slot 1
S2 Options slot 2
S2
Q1 Battery switch (for internal batteries)
Q2 Input circuit breaker
Q6 Output disconnecting switch (E.S.D.)

$POöHVSBUJPOXJUIDPNNPONBJOT $POöHVSBUJPOXJUITFQBSBUFNBJOT

AUX MAINS

Q2 2 Q6 Q2 2 Q6
1 1
MAINS 0 OUT MAINS 0 OUT
Q1 Q1
B B
B1 B1

IOMMASGPXX01-GB_00 27
ACCESS TO CONTROLS
5 AND COMMUNICATION INTERFACES 10-40 kVA

5.2 FUNCTIONS OF THE SWITCHES.


Input switch Q2.
The input switch provides the primary power supply to the UPS.
In normal operating conditions it should be in position 1 ON.
The position 0 OFF will cause the batteries to discharge.
In a configuration with separate mains, the switch only interrupts the rectifier power supply.
Output disconnecting switch Q6.
The disconnecting switch Q6 has three positions with the following functions:
ITALIANO
ENGLISH

r Position 1 “UPS”UIJTJTUIFQPTJUJPOGPSOPSNBMPQFSBUJPOPGUIF614GPSBDPOUJOVPVTQPXFSTVQQMZUPUIFMPBE
r Position 2 “MANUAL BY-PASS”: This position should only be selected for ordinary or extraordinary maintenance
PQFSBUJPOT NBOVBMCZQBTT
UIFMPBEJTDPOOFDUFEEJSFDUMZUPUIFNBJOTQPXFSTVQQMZ*UNBZCFVTFEJOUIFFWFOU
of a UPS failure to power applications from the auxiliary mains while awaiting the intervention of technical person-
OFM
r Position 0 “OFF”: This completely isolates the UPS output by removing the voltage from the applications in any
operating condition. It is used for the emergency shutdown of the system (internal E.S.D.).
Battery switch Q1 (UPS batteries).
When closed, this switch connects the batteries of the UPS to the DC/DC converter stage to power the inverter in
the event of a mains failure. The normal operating position is 1 (closed).

28 IOMMASGPXX01-GB_00
6 MIMIC PANEL
10-40 kVA

6.1 ADVANCED MIMIC PANEL.


The LCD mimic panel (figure 6.1-1) located on the upper part of the UPS provides all the information on operating
status, electrical measurements, and access to controls and configuration parameters.

The information is grouped into four sections:


A. JEFPHSBNTUIBUJEFOUJGZUIFTVCTFUTBOEUIFFOFSHZóPX

B. NVMUJDPMPVSFEMVNJOPVTCBSUIBUJEFOUJñFTUIFDPOEJUJPOPGUIFQPXFSTVQQMZUPUIFMPBE

C. alphanumeric information that uses a menu layout to provide details on any alarms that may occur and on the

ENGLISH
measurements, controls and parameters.

D. use of the buttons:


· ESCFYJUGSPNUIFDVSSFOUNFOVQBSBNFUFSBDUJPO
· UP : scrolls the available menus/values upwards. It increases the value each time it is pressed when chang-
JOHBQBSBNFUFS
· DOWN : scrolls the available menus/values downwards. It decreases the value each time it is pressed when
DIBOHJOHBQBSBNFUFS
· ENTER: enters the menu displayed on the screen to confirm the choice/changes made .

6.1-1

D
B

IOMMASGPXX01-GB_00 29
6 MIMIC PANEL
10-40 kVA

6.1.1 Meaning of ideograms.

6.1.1-1

M18
M19

M20
ITALIANO
ENGLISH

M3 M21

M4
M22

M5 M28
M23
M24 M27
M6 M25 M26

M7

M1

M2 M8 M9

M30
M10 M11

M29 M31
M12 M13 M14 M15 M16 M17

30 IOMMASGPXX01-GB_00
6 MIMIC PANEL
10-40 kVA

Meaning of ideograms
Code Description Condition
M1 Load on bypass, in Eco-mode or Maintenance bypass closed Steady
Automatic bypass alarm Flashing
M2 Input rectifier active. Steady
Input rectifier general alarm. Flashing
M3 Battery OK. Steady
Battery alarm. Flashing
M4-M7 Remaining battery capacity. Steps of 25%
Battery recharging. Sequence M7 M4

ENGLISH
M8 Inverter on Steady
Inverter general alarm. Flashing
M9 Output voltage present. Steady
M10 Input mains OK. Steady
Input mains alarm. Flashing
M11 Inverter on. Steady
M12 Module 1 present. Steady
Module 1 general alarm. Flashing
M13 Module 2 present. Steady
Module 2 general alarm. Flashing
M14 Module 3 present. Steady
Module 3 general alarm. Flashing
M15 Module 4 present. Steady
Module 4 general alarm. Flashing
M16 Module 5 present. Steady
Module 5 general alarm. Flashing
M17 Module 6 present. Steady
Module 6 general alarm. Flashing
M18 Load present. Steady
Overload. Flashing
M19-M28 Output load indicator. Steps of 10%
M29 Periodic maintenance alarm/warning. Flashing
M30 Activation code alarm. Steady
General alarm. Flashing
M31 LAN connection ready (Cable Connected). Steady

IOMMASGPXX01-GB_00 31
6 MIMIC PANEL
10-40 kVA

6.1.2 Meaning of the luminous bar.


The luminous bar (figure 6.1-1) provides an immediate indication of the condition of the power supply to the load
:
r 3FEQPXFSTVQQMZOPUQSFTFOUPSTIVUEPXOJNNJOFOU óBTIJOH

r :FMMPXQPXFSTVQQMZQSFTFOUCVUVOTUBCMFPSUFNQPSBSZ
r (SFFOQPXFSTVQQMZTBGFBOETUBCMF
Meaning of the luminous bar
Colour Conditions displayed
ITALIANO
ENGLISH

3&%óBTIJOH *NNJOFOUTIVUEPXOBMBSN UIFMPBEXJMMCFEJTDPOOFDUFEJOBGFXNJOVUFT

RED Load not powered or battery circuit open


:&--08óBTIJOH 614JOTUBOECZPS6QTPONBOVBMCZQBTT  
Alarm indicating request for ordinary maintenance according to conditions of use (type of load,
UFNQFSBUVSF
BGUFSPWFSmIPVSTPGPQFSBUJPO .óBTIJOHBOEBMBSN"

YELLOW Warning for preventive maintenance according to conditions of use (type of load, temperature),
BGUFSPWFSIPVSTPGPQFSBUJPO .óBTIJOH

:&--08 -PBEPOCBUUFSZPSCBUUFSZEJTDIBSHJOHJG.JTPOTUFBEZBOE.JTPí
YELLOW On automatic bypass if M1 is on steady
YELLOW First maintenance period expired (10,000 hours of operation) UPS in maintenance mode
(3&&/óBTIJOH #BUUFSZUFTUJOQSPHSFTT
GREEN Load powered from inverter or in high efficiency mod

6.1.3 Mimic panel menu.


The paragraph below describes the menus available on the mimic panel and their functions.
The displays are organised into menus and submenus as shown in the figure 6.1.3-1:
r UPBDDFTTBNFOVQSFTTUIFENTER LFZ
r UPSFUVSOUPUIFIJHIFSMFWFMQSFTTESCLFZ
r 6TFUIFUP and DOWN keys to scroll the information available at each level.
When the UPS is connected in parallel, the mimic panel shows the system information as if it were a single UPS.
Select the UPS number to display information on the individual units.

6.1.3-1
Legend.
A Current menu
B Active sub menu
C Additional values or information
A D Scrolling contextual help line
B E Scroll bar
F F Statistical graphics display
C E
D D

32 IOMMASGPXX01-GB_00
6 MIMIC PANEL
10-40 kVA

Parallel UPS
Single UPS

MAIN SYSTEM 1 ALARMS 1.1 ACTIVE ALARMS

1.2 EVENT LOG

2 MEASUREMENTS 2.1 PRESENT MEASURES

ENGLISH
2.2 STATISTICS

3 COMMANDS 3.1 IMMEDIATE COMMAND

3.2 EXTENDED COMMAND

4 PARAMETERS 4.1 PRESENT CONFIG.

4.2 PRESENT DATA

5 SERVICE 5.1 COMMISSIONING

5.2 SETTING

5.3 SERVICE CODE

6 HYSTORY 6.1 HISTORY LOG

MODULE 1 1 ALARMS 1.1 ACTIVE ALARMS

MODULE 2 2 MEASUREMENTS 2.1 PRESENT MEASURES

MODULE 3 3 COMMANDS 3.1 IMMEDIATE COMMAND

MODULE 4 4 PARAMETERS 4.1 PRESENT CONFIG

MODULE 5

MODULE 6

IOMMASGPXX01-GB_00 33
6 MIMIC PANEL
10-40 kVA

6.1.3.1 “Alarms” menu.


This is used to display all the alarms that are active at the time of access.
The alarms menu is activated automatically when an alarm condition occurs.
ALARMS menu
Code Mimic panel description Meaning
A00 GENERAL ALARM
A01 BATTERY ALARM Battery circuit failure or faulty operation.
A02 OUTPUT OVERLOAD Power required in output over the limits.
A06 AUXILIARY MAINS OUT OF TOLERANCE The voltage or frequency limits accepted by the bypass have been
ITALIANO
ENGLISH

exceeded.
A07 OVER TEMPERATURE Temperature excessive or ventilation problems.
A08 MAINTENANCE BYPASS ACTIVE Q6 in position 2.
A17 IMPROPER CONDITION OF USE Improper conditions of use verified (load, mains, and temperature).
A18 BLOCKING INVERTER FOR OVERLOAD Inverter shutdown due to overload.
" 830/($0/'*(63"5*0/ &SSPSJOUIFDPOñHVSBUJPOQBSBNFUFST FHEJíFSFOUQBSBNFUFST
between several UPSs in parallel).
A22 INPUT MAINS OUT OF TOLERANCE The voltage or frequency limits accepted by the rectifier have been
exceeded.
A23 RECTIFIER GENERAL ALARM Rectifier fault.
A25 INVERTER GENERAL ALARM Inverter fault.
A26 BATTERY CHARGER GENERAL ALARM Battery charger fault.
A29 BYPASS GENERAL ALARM Bypass fault.
A30 STOP FOR OVERLOAD The duration of the overload has inhibited the bypass.
A32 MODULE 1 GENERAL ALARM Module 1 failure.
A33 MODULE 2 GENERAL ALARM Module 2 failure.
A34 MODULE 3 GENERAL ALARM Module 3 failure.
A35 MODULE 4 GENERAL ALARM Module 4 failure.
A36 MODULE 5 GENERAL ALARM Module 5 failure.
A37 MODULE 6 GENERAL ALARM Module 6 failure.
A38 EXTERNAL ALARM 1 Signalling from ADC input.
A39 EXTERNAL ALARM 2 Signalling from ADC input.
A40 EXTERNAL ALARM 3 Signalling from ADC input.
A41 EXTERNAL ALARM 4 Signalling from ADC input.
A42 E-SERVICE GENERAL ALARM Alarm that generates automatic sending of a signal to the support
centre (if the service has been activated).
A43 REDUNDANCY LOST The power required by the load no longer allows the preset
 SFEVOEBODZ/ YUPCFNBJOUBJOFE GPS614TJOQBSBMMFMPOMZ

A44 PERIODIC SERVICE CHECK-UP Warning for periodic check by support service.
A47 MAX BATTERY TEMPERATURE Control of the temperature of battery cabinet.
A49 BATTERY DISCHARGED The energy available in the battery has been used up.
A51 OPTION BOARD GENERAL ALARM Fault related to the optional PCBs in the slots.
A56 GENERATOR SET GENERAL ALARM Minor alarm on generator set.
" (&/&3"5034&5'"6-5 .BKPSBMBSNPOHFOFSBUPSTFU
A58 ESD ACTIVATED The remote emergency shutdown command has been activated.
A59 BATTERY CIRCUIT OPEN The battery switch is open.
A60 FAN FAILURE Fans faulty or blocked.
A61 PHASE ROTATION FAULT Wrong phase cycle direction.

34 IOMMASGPXX01-GB_00
6 MIMIC PANEL
10-40 kVA

6.1.3.2 “Measurements” menu.


This menu is used to display all the measurements relating to the UPS input, output and to the battery.
'PSNPEFMTXJUITJOHMFQIBTFJOQVUPSPVUQVU UIFWPMUBHFBOEDVSSFOUEJTQMBZTBSFBEKVTUFEBVUPNBUJDBMMZ
MEASUREMENTS menu
Type of measurements Value Value Value Note
OUTPUT STAR VOLTAGE ___ V ___ V ___ V
OUTPUT PH-PH VOLTAGE ___ V ___ V ___ V
OUTPUT LOAD __ % __ % __ %
OUTPUT ACTIVE POWER ___ kW

ENGLISH
OUT APPARENT POWER __._ kVA __._ kVA __._ kVA
OUTPUT CURRENT __._ A __._ A __._ A
OUTPUT FREQUENCY __._ Hz
AUXILIARY VOLTAGE ___ V ___ V ___ V
AUXILIARY FREQUENCY __._ Hz
INPUT STAR VOLTAGE ___ V ___ V ___ V
INPUT PH-PH VOLTAGE ___ V ___ V ___ V
INPUT FREQUENCY __._ Hz
INPUT APPARENT POWER __._ kVA __._ kVA __._ kVA
BATTERY VOLTAGE B1___ V B2___ V
CAPACITY __ % CHARGING
BACKUP T___MIN DISCHARGING
*/5&3/"-5&.1&3"563& @@ž$
BATTERY TEMPERATURE @@ž$   0OMZXJUIBTFOTPSQSFTFOUBOETFU

“Statistical measurements” menu.


Once a (programmable) reference period has been defined, the system reports measurements that are made avail-
able in digital or graphical format. The values that are represented graphically can be used to analyse the situation
over the last 24 hours. This information, together with the programmed interval information, provides an enhanced
evaluation on the operating mode of the equipment in order to verify whether certain critical operating situations
are repetitive or only casual.
STATISTICAL MEASUREMENTS menu
Measurement Value Option Option
INPUT APPARENT POWER MIN. AVERAGE MAX. ENTER displays ENTER displays
weekly graphics 24 hr graphics
BACKUP TIME LESS THAN 2 MINUTES NUMBER OF EVENTS
BACKUP TIME BETWEEN 2 AND 5 MINUTES NUMBER OF EVENTS
BACKUP TIME MORE THAN 5 MINUTES NUMBER OF EVENTS
OUTPUT LOAD MIN. AVERAGE MAX. ENTER displays ENTER displays
weekly graphics 24 hr graphics
OVERLOAD TIME LESS THAN 5 SECONDS NUMBER OF EVENTS
OVERLOAD TIME MORE THAN 5 SECONDS NUMBER OF EVENTS
REDUNDANCY LOST NUMBER OF EVENTS
INTERNAL TEMPERATURE MIN. AVERAGE MAX. ENTER displays ENTER displays
weekly graphics 24 hr graphics
BATTERY TEMPERATURE MIN. AVERAGE MAX. ENTER displays ENTER displays
weekly graphics 24 hr graphics
WORKING TIME ON GEN SET NUMBER OF HOURS

IOMMASGPXX01-GB_00 35
6 MIMIC PANEL
10-40 kVA

6.1.3.3 “Commands” menu.


This is used to send some immediate commands to activate the UPS or various operating modes. It can also be used
to send extended commands to define some UPS settings.
To activate the commands select the command with UP or DOWN , press ENTER, select YES or NO to
execute and press ENTER to confirm.
“Extended commands”.
They can only be displayed if the extended commands item in the configurations menu has been activated.
ITALIANO
ENGLISH

IMMEDIATE COMMANDS menu


Command Description
START PROCEDURE UPS start-up command.
STOP PROCEDURE UPS shutdown command.
MAINTENANCE BY-PASS Control to activate the manual bypass and shutdown of the UPS.
PROCEDURE
HIGH EFFICIENCY MODE Activates Eco mode / always on mode.
NORMAL MODE Activates normal double conversion operation.
ALARM RESET Resets all the alarms.
LEDS TEST Performs the test on the mimic panel LEDs.

EXTENDED COMMAND menu


Command Description
MANUAL BATTERY TEST Activates the battery test.
BATTERY COMMISSION Activates battery commissioning (use only if necessary for the type of battery).
SET LAN DEFAULT VALUE Resets all the values of the LAN.
JBUS TUNNELING ENABLE Enables the connection of advanced software (BMS or Uni vision) via the LAN network.
JBUS TUNNELLING DISABLE
DHCP ENABLE Enables the automatic allocation of the IP address by the network server.
DHCP DISABLE
FORCE MODEM DIAL OUT Forces sending of an immediate test modem call.
ENERGY SAVER ENABLE Enables energy save mode on a parallel system.
ENERGY SAVER DISABLE
DISABLE CHECK-UP Deactivates the periodic maintenance message (visible only if alarm A44 is present).

36 IOMMASGPXX01-GB_00
6 MIMIC PANEL
10-40 kVA

6.1.3.4 “Parameters” menu.


Displays only the configuration parameters set for the UPS.
The messages in this menu are identified by an asterisk in the configurations service menu.
The parameters can only be changed by entering the service / configurations menu.
CURRENT DATA menu
Message Description
SINOTTICO Identifie the size, the phases configuation input and output and the serial number
SN. 0000000000 of the UPS.
FW. X.XX CKS. XXXX

ENGLISH
LAN SINOTTICO MAC ADDRESS Identifie the mac addres of LAN PCB.
XX . XX . XX . XX . XX . XX
FW X.XX
SCHEDA DIGITALE Identifie the micro prosessor software version.
UP RV 000 CKS: 0000 Identifie the mac addres of LAN PCB.
DSP RV 000 CKS: 0000

6.1.3.5 “Service” menu.


This is used to change the configuration parameters, insert the warranty activation code and display the service code.
“Activation code” menu.
During activation of the equipment a warranty activation code, made up of four characters, is requested to com-
plete the start-up procedure.
The activation code is provided directly by the reference Support Centre upon communication of the serial number
MANUFACTURER WARRANTY
VALIDATION
PLEASE INSERT THE CODE

of the equipment which is displayed in the next message by pressing ENTER.


Inserting the code does not limit the availability of the equipment’s functionality.
SEE INSTALLATION MANUAL
FOR PROCEDURE
SN: 0000000000

When contact is made with the Support Centre for the activation code, detailed information can be obtained on the
UPS functions available and on the periodic preventive maintenance programmes.
Once the code is obtained, enter it by pressing ENTER to activate the entry (two asterisks will appear). Select the
first character with the UP and DOWN keys and confirm with ENTER to accept the character. Then move
on to the next character. Pressing the ENTER key after selecting the fourth character activates code.
SEE INSTALLATION MANUAL
FOR PROCEDURE
CODE = - - - - **

An error message is displayed if the code is incorrect. Check that the code displayed corresponds to the one pro-
vided by the Support Centre and repeat the procedure.

IOMMASGPXX01-GB_00 37
6 MIMIC PANEL
10-40 kVA

i$POöHVSBUJPOTwNFOV
This is used to change the configuration parameters.
Press ENTER. Access is via the password MAST which is keyed in by using the UP and DOWN keys and
ENTER to go on to the next letter.
Note.
Column A shows whether the parameter is visible in the PARAMETERS “CONFIGURATIONS” menu.

CONFIGURATIONS menu
A Parameter Description Allowed values
ITALIANO
ENGLISH

LANGUAGE SELECTION Selects the required language ENG, FRA, ITA


 r /6.#&30'.0%6-&4 0OMZBQQFBSTJODBTFPGQBSBMMFMTZTUFNT  
Indicates the number of UPSs in the system.
 r 3&%6/%"/$:-&7&- 0OMZBQQFBSTJODBTFPGQBSBMMFMTZTUFNT '30.505)&/6.#&3
Indicates the number of redundant UPSs. OF MODULES LESS ONE
 r 06516570-5"(& 4FUTUIFSFRVJSFEPVUQVUWPMUBHFWBMVF 
 r 065165'3&26&/$: 4FUTUIFSFRVJSFEPVUQVUGSFRVFODZWBMVF 
 r $0/7&35&3 4FUTXIFUIFSUIF614IBTUPPQFSBUFBTBGSFRVFODZ :&4/0 
converter.
WARNING!
Set only on UPS with mains power (MAINS) and auxiliary mains (AUX MAINS) separated
and with the auxiliary mains (AUaX MAINS) disconnected!
Do not set on UPS with common mains lines as it could damage the load!
 r "6500/ 4FUTXIFUIFSUIF614IBTUPSFTUBSUBVUPNBUJDBMMZBGUFS :&4/0 
shutdown due to minimum battery level.
BATTERY AVAILABLE Indicates whether the batteries are present YES/NO
BATTERY TEMP. SENSOR Indicates if the battery sensor is present ON/OFF
 r BATTERY TYPE Selects the type of batteries used SEALED, OPEN VENT, NI-CD
 r BATTERY RECHARGE Selects the type of recharge required AUTO, MAINTENANCE,
2 LEVELS, INTERMITTENT
 r #"55&3:$"1"$*5: 4FUTUIFCBUUFSZDBQBDJUZJO"I  œ YOVNCFSPG614

 r #"55&3:&-&.&/54 *OEJDBUFTUIFOVNCFSPGFMFNFOUTJOTFSJFT œ œGPS/J$E

in a branch.
 r #"55&3:3&$)"3(& *OEJDBUFTUIFNBJOUFOBODFWPMUBHFWBMVFQFSDFMM  œ   œ GPS/J$E

FLOATING VOLTAGE
 r #"55&3:3&$)"3(& *OEJDBUFTUIFTFDPOEMFWFMSFDIBSHFWPMUBHFWBMVF  œ   œ GPS/J$E

LEVEL TWO VOLTAGE 
 r #"55&3:3&$)"3(& *OEJDBUFTUIFDVSSFOUUISFTIPMEJOPG$UPQBTT œ 
FLOATING RECHARGE  from maintenance voltage to recharge voltage.
 r #"55&3:3&$)"3(& *OEJDBUFTUIFDVSSFOUUISFTIPMEJOPG$UPQBTT œ 
RECHARGE  FLOATING from recharge voltage to maintenance voltage (<!).
 r #"55&3:3&$)"3(& *OEJDBUFTUIFCBUUFSZDPNNJTTJPOJOHWPMUBHF  œ   œ GPS/J$E

FORMING VOLTAGE value (>!).

38 IOMMASGPXX01-GB_00
6 MIMIC PANEL
10-40 kVA

CONFIGURATIONS menu
A Parameter Description Allowed values

 r #"55&3:3&$)"3(& *OEJDBUFTUIFCBUUFSZDPNNJTTJPOJOHDVSSFOUWBMVF œ GPS/J$E



FORMING CURRENT
 r #"55&3:3&$)"3(& 4FUTUIFFRVBMJTBUJPOWPMUBHFWBMVF  œ  
EQUALISATION VOLTAGE
 r #"55&3:3&$)"3(& 4FUTUIFSFDIBSHFWPMUBHFDPNQFOTBUJPOWBMVF :&4/0 
TEMP COMPENSATION according to the battery temperature (not present
with external battery cabinets.

ENGLISH
 r #"$,'&&%5:1& 4FUTUIFUZQFPGCBDLGFFEQSPUFDUJPO %*4"#-& 
1. BYPASS
2. BYPASS-INPUT ALONE
3. BYPASS-INPUT COMMON
 r #"55&3:5&45 4FUTUIFGSFRVFODZSBUFPGUIFCBUUFSZUFTUJOEBZT œ 
TEST EVERY XX DAYS (zero = do not perform the test).
 r 108&34)"3&1-6(5:1& 4FMFDUTUIFDPOñHVSBUPOPGQPXFSTIBSFSFRVJSFE 45"/%"3% 
(see paragraph 10.5). EMERGENCY LIGHTING
REMAINING TIME
RESIDUAL CAPACITY
 r POWER SHARE PLUG1 VALUE Sets the required intervention value
(minutes for remaining time and Ah for capacity) (optional).
 r 108&34)"3&1-6(5:1& "TQMVHUZQF PQUJPOBM

 r POWER SHARE PLUG2 VALUE As plug1 value (optional).
 r 4&3*"--*/,#"6%3"5& *OTFSUTUIFTFSJBMDPNNVOJDBUJPOQBSBNFUFST 
 r 4&3*"--*/,1"3*5: *OTFSUTUIFTFSJBMDPNNVOJDBUJPOQBSBNFUFST PEEFWFOOPOF
 r -"/*145"5*$0 4FUTUIFTUBUJD*1BEESFTTPGUIF-"/ 
XXX . XXX . XXX .XXX
 r 4&3*"--*/,+#64 4FUTUIFNJNJDQBOFMKCVTOPEF  
SLAVE NUMBER
DATE AND TIME Sets the date and time DD/MM/YY HH:MM
 r &95&/%&%$0.."/% &OBCMFT%JTBCMFTUIFNJNJDQBOFMFYUFOEFEDPNNBOET :&4/0
 r 3&.05&$0.."/% &OBCMFTEJTBCMFTUIFSFNPUFDPOUSPMT :&4/0
BUZZER Enables/Disables the buzzer YES/NO
LCD CONTRAST Sets the LCD display contrast 0/100
 r 45"5*45*$41&3*0% *OEJDBUFTUIFUJNFJOXFFLTGPSUIFDBMDVMBUJPOPGTUBUJTUJDT 
 r (445*.&%&-": 4FUTUIFHFOFSBUPSTUBSUVQEFMBZUJNF WJTJCMFPOMZXIFO .*/65&4 
the GSS PCB is installed)
E-SERVICE TYPE Select e-service operating mode NONE, MODEM, SMS
E-SERVICE TELEPHONE NUMBER Insert the phone number to call for e-service messages MAX 20 CHARACTERS
AUX TRANSFORMER VOLTAGE Set the auxiliary voltage measure with transformer SETTABLE ONLY BY
AFTER SALE SERVICES
INPUT TRANSFORMER VOLTAGE Set the input voltage measure with transformer SETTABLE ONLY BY
AFTER SALE SERVICES

IOMMASGPXX01-GB_00 39
6 MIMIC PANEL
10-40 kVA

“Service code” menu. 6.1.3.5-1


This displays the service code to be sent to the support
service to make an accurate and rapid diagnostic of the
problem. In the event of a fault, select the menu SERV-
ICE > SERVICE CODE and inform the support centre of
the code displayed.
ITALIANO
ENGLISH

6.1.3.6 “Event Log” menu.


Shows a list of UPS events in chronological order.
It allows the user to analyse UPS operation with regard to variations in the power supply, load or the environment.

6.1.3.6-1
Legend.
A B A Shows date and time of event.
B Shows the event code.
C Describes the event.
D ON/OFF status of event.
E Progressive number of event.
C E

40 IOMMASGPXX01-GB_00
6 MIMIC PANEL
10-40 kVA

6.2 MIMIC PANEL CONCENTRATOR.


In systems with 2 or more UPS units connected in parallel, advanced mimic panels can provide an overall view of the
system and a detailed view of the UPSs in a single point.
During the installation phase, one of the UPSs and the relative mimic panel is defined as the concentrator. It is then
possible to manage and install in one step all the options required for external communication.

6.2.1 Keyboard blocking procedure.


Is possible to block/unblock the keyboard using the buttons in following sequence: ENTER, DOWN , UP , ESC
(pressed for over 3 seconds). The sequence must be done in no more than 15 seconds.

ENGLISH

IOMMASGPXX01-GB_00 41
7 OPERATING PROCEDURES
10-40 kVA

The operating modes to activate and manage the UPS are defined 7.1
in this chapter; please also refer to chapters 6 “Mimic panel” and 8 Q1 Q2
“Menus”. Q6

For UPSs connected in parallel:


t QFSGPSNUIFTXJUDIJOHPQFSBUJPOTPOBMM614TCFGPSF
HPJOHPOUPUIFOFYUPQFSBUJPO
t FBDITXJUDIJOHPQFSBUJPONVTUCFDBSSJFEPVUPOCPUI
614TXJUIJOTFDPOET
t QFSGPSNUIFPQFSBUJPOTPOUIFNJNJDQBOFMPG614
ITALIANO
ENGLISH

45"3561*//03."-.0%&
t 4VQQMZUIFNBJOTBOEBVYJMJBSZNBJOTUPUIF614
t 1VUTXJUDIQ2 into position 1 (mains ON);
t 8BJUGPSUIFNJNJDQBOFMUPTXJUDIPO
t "DUJWBUFUIFQSPDFEVSFCOMMANDS > IMMEDIATE COMMANDS > START PROCEDURE;
t $BSSZPVUUIFPQFSBUJPOTJOEJDBUFEPOUIFNJNJDQBOFM

4)65%08/
4IVUEPXOJOUFSSVQUTUIFQPXFSTVQQMZUPUIFMPBEBOEDBVTFTUIF614BOEUIFCBUUFSZDIBSHFSUPTUPQ
t "DUJWBUFUIFQSPDFEVSFCOMMANDS > IMMEDIATE COMMANDS > STOP PROCEDURE;
t 8BJUBQQSPYNJOVUFTGPSUIF614UPTIVUEPXO UIFDPOUSPMMFETIVUEPXOPGBOZTFSWFSTJTNBOBHFEXJUI
TIVUEPXOTPGUXBSF

t $BSSZPVUUIFPQFSBUJPOTJOEJDBUFEPOUIFNJNJDQBOFM

&95&/%&%0650'4&37*$&
*GUIF614JTEFBDUJWBUFEGPSTPNFUJNF UIFCBUUFSJFTNVTUCFSFDIBSHFESFHVMBSMZUIFZTIPVMECFSFDIBSHFE
FWFSZUISFFNPOUIT
t 4VQQMZUIFNBJOTBOEBVYJMJBSZNBJOTUPUIF614
t 1VUTXJUDIQ2 into position 1 (mains ON);
t 8BJUGPSUIFNJNJDQBOFMUPTXJUDIPO
t "DUJWBUFUIFQSPDFEVSFCOMMANDS > IMMEDIATE COMMANDS > START PROCEDURE;
t 1VUUIFFYUFSOBMCBUUFSZEJTDPOOFDUPSTJOUPQPTJUJPO CBUUFSZDJSDVJUDMPTFE

t 1VUPSLFFQTXJUDIFTQ3 and Q5 in position 0 JOWFSUFSJOPVUQVU0''BOECZQBTT0''

t 5IFCBUUFSZNVTUCFDIBSHFEGPSBUMFBTUUFOIPVST
t 0ODFUFOIPVSTIBWFFMBQTFE DBSSZPVUUIFSTOP PROCEDURE to deactivate the UPS.

42 IOMMASGPXX01-GB_00
7 OPERATING PROCEDURES
10-40 kVA

48*5$)*/(0/50."/6"-#:1"44
4XJUDIJOHPOUPUIFNBOVBMCZQBTTDSFBUFTBEJSFDUDPOOFDUJPOCFUXFFOUIF614JOQVUBOEPVUQVU DPNQMFUFMZ
FYDMVEJOHUIFFRVJQNFOUDPOUSPMQBSU5IJTPQFSBUJPOJTQFSGPSNFEJOUIFFWFOUPGPSEJOBSZNBJOUFOBODFPO
UIFFRVJQNFOU TPBTOPUUPSFNPWFUIFQPXFSTVQQMZGSPNUIFMPBE PSJOUIFFWFOUPGBTFSJPVTGBJMVSFXIJMF
XBJUJOHGPSUIFFRVJQNFOUUPCFSFQBJSFE
t "DUJWBUFUIFQSPDFEVSFCOMMANDS > IMMEDIATE COMMANDS > BYPASS PROCEDURE;
t $BSSZPVUUIFPQFSBUJPOTJOEJDBUFEPOUIFNJNJDQBOFM

*GUIFSFJTBOFYUFSOBMNBOVBMCZQBTT DBSSZPVUUIFQSPDFEVSFEFTDSJCFEBCPWFCFGPSFBDUJWBU

ENGLISH
JOHUIJTTXJUDI

3&563/50/03."-.0%&
t 1VUTXJUDIQ2 into position 1 (mains ON);
t 8BJUGPSUIFNJNJDQBOFMUPTXJUDIPO
t "DUJWBUFUIFQSPDFEVSFCOMMANDS > IMMEDIATE COMMANDS > START PROCEDURE;
t $BSSZPVUUIFPQFSBUJPOTJOEJDBUFEPOUIFNJNJDQBOFM

*GUIFSFJTBOFYUFSOBMNBOVBMCZQBTT QVUUIFTXJUDIUPQPTJUJPO0''

&.&3(&/$:4)65%08/ &4%

4IPVMEJUCFOFDFTTBSZUPJOUFSSVQUUIFDPOUJOVPVTQPXFSTVQQMZQSPWJEFECZUIF614RVJDLMZ FNFSHFODZTIVU-
EPXO
UIJTDBOCFEPOFCZQVUUJOHTXJUDIQ3 to position 0PS XIFSFBQQMJDBCMF CZBDUJWBUJOHUIFFNFSHFODZ
CVUUPOTXJUDIDPOOFDUFEUPUIFADC PCB.

5IF614PVUQVUDBOPOMZCFFMFDUSJDBMMZEJTDPOOFDUFECZNFBOTPG2
 *GUIF614JTPQFSBUJOHGSPNUIFNBOVBMCZQBTT 2JOQPTJUJPO
XJUINBJOTQSFTFOU UIFFNFS
HFODZTIVUEPXOEPFTOPUJOUFSSVQUUIFQPXFSTVQQMZUPUIFMPBE*OFNFSHFODZDPOEJUJPOTBMM
UIFQPXFSTVQQMJFTVQTUSFBNPGUIF614NVTUCFEJTDPOOFDUFE

IOMMASGPXX01-GB_00 43
8 COMMUNICATION
10-40 kVA

8.1 MULTILEVEL COMMUNICATION.


."45&3:4–JTBCMFUPNBOBHFBWBSJFUZPGTFSJBM DPOUBDUBOE&UIFSOFUDPNNVOJDBUJPODIBOOFMTTJNVMUBOFPVTMZ
The various PCBs and signalling accessories are inserted in the two standard communication slots.
5IJTHJWFT."45&3:4–JNNFEJBUFJOUFSGBDJOHBOEJOUFHSBUJPOóFYJCJMJUZBTTPPOBTUIFVOJUJTJOTUBMMFEXJUIOPOFFE
for trained personnel.
The table below lists the possible connections between the communication channels and external devices.

5 communication levels 8.1-1


ITALIANO
ENGLISH

5 4 3 2 1
Slot 1 Slot 2 RS 232/485 RS 232 RJ45 10BT
ADC card r r
GSS card r r 9 8 7 6
NetVision card r2
r2

UniVision pro  r  r4
Legend pin RS232/485 C1 Legend pin Modem C2
Remote Panel  r 1 Not connected 1 Reserved
BMS  r
1
r1
r4 2 RX for RS232 2 RX for RS232
Modem   r 3 3 TX for RS232 3 TX for RS232
LAN (ethernet)    r 4 %BUB
5 GND for RS232
4 Reserved
5 GND for RS232
1
Building Management System. 6 Data − 6 Not connected
2
Ethernet adapter with Web/SNMP 10/100Mb functions 7 Reserved 7 RTS
(E-service via Web required). 8 Not connected 8 CTS
3
For T-service via telephone network. 9 7 9 7
4
 #ZKCVTUVOOFMMJOHPO5$1*1

"TFBDIDIBOOFMJTJOEFQFOEFOU TJNVMUBOFPVTDPOOFDUJPOTDBOCFNBEFUPTBUJTGZUIFEJíFSFOUMFWFMTPGTJHOBMMJOH
and remote monitoring.
See the options paragraph to access the detailed functions of the PCBs installed in the slots.

Please note that two Net Vision cards or two GSS cards cannot be connected simultaneously.

44 IOMMASGPXX01-GB_00
8 COMMUNICATION
10-40 kVA

8.2 STANDARD LAN WEB PAGE.


By connecting the UPS to a standard LAN network, the operating status of the UPS can be monitored from any PC
connected to the network through an html page.

8.2.1 Activation.
Comply with the following operations to activate the monitoring system:
r $POOFDUUIF614UPUIF-"/OFUXPSL DPOOFDUPSC3 in Fig. 8.2.1-1).

8.2.1-1

ENGLISH
C3

A. If the BOOT DHCP protocol is enabled in the local network: verify the IP address shown in the PARAMETERS >
PRESENT CONFIG > LOCAL AREA NETWORK IP menu on the UPS mimic panel (go to point C).

B. If the BOOT DHCP protocol is not enabled in the local network:


Foreword: the following is applicable only if the user is in possession of the administrator rights, otherwise the
procedure indicated below is only valid if using a stand-alone PC (i.e. not in a network of computers with admin-
istrator privileges) and a network twisted cable.
Deactivate DHCP mode in the COMMAND> EXT.COMMAND> DHCP DISABLE menu on the UPS mimic
panel.
Read the IP address given in the PARAMETERS > PRESENT CONFIG > LOCAL AREA NETWORK IP menu
on the UPS mimic panel (by default 192.168.7.19).
From a PC connected to the network add the address read by means of the following command: Route add
192.168.7.19 210.67.192.147 (assuming 210.67.192.147 to be the IP address of the PC being used).
C. Open an internet browser and key in the address http://XXX.XXX.XXX.XXX and press send (where xxx.xxx.xxx.xxxx
is the IP address read on the mimic panel).

IOMMASGPXX01-GB_00 45
8 COMMUNICATION
10-40 kVA

D. A login and a password will be requested (fig. 8.2.1-2), 8.2.1-2


the default parameters are:
r MPHJOBENJO
r QBTTXPSEQVCMJD

Insert data and click OK.


The main web supervisor page will be displayed and
the functions are described in the following para-
graph.
ITALIANO
ENGLISH

8.2.2 Description of the functions available.


The main web page shows the general status of the UPS.
This page like all the “sub-pages” are dynamic i.e. the data, images or type of messages shown vary in accordance
with the UPS status and configuration.

8.2.2-1
A

B C

Legend.
A Navigation bar.
B Menu bar.
C system information area.

46 IOMMASGPXX01-GB_00
8 COMMUNICATION
10-40 kVA

8.2.2.1 Navigation bar.


Consult the on-line guide for details about the various icons.
The graphics interface shows a number of icons, each of which is associated to a specific function:
Connection to the www.socomec.com web site. Regularly check the news that the SOCOMEC group
publishes on the site so as to take full advantage of the MASTERYSTM unit.

UPS information: Serial number, type, power, etc.

ENGLISH
Alarm present: shows the alarms table (this icon appears when the UPS detects an anomaly).

Generator operating mode (this icon appears when the UPS is powered by the generator).

Technical support department e-mail address. This connection opens the e-mail program and automati-
DBMMZñMMTJOUIFBEESFTTFFBOETVCKFDUMJOFT

Information on the network interface: a help page in html is loaded.

8.2.2.2 Menu bar.


The menu bar displays links to html pages that provide detailed information on the unit and describe how to con-
figure special options.

8.2.2.3 List of alarms.


Shows the list of alarms present in table form.

8.2.2.4 Statistics.
The counter folder shows the number of events that have occurred over a given period of time.
The average minimum and maximum values of a measurement can be seen by clicking on the measurement folder.
A sampling time from one to 10 weeks can be set by clicking on the period folder.

8.2.2.5 UPS management.


The commands folder shows the commands that can be sent to the UPS.
The setting folder shows the parameter settings on the UPS.

8.2.2.6 Change language.


$MJDLPOUIFSFMBUJWFóBHUPDIPPTFBEJíFSFOUMBOHVBHF*GUIFEFTJSFEMBOHVBHFJTOPUMJTUFE TFFJGJUJTEPXOMPBEBCMF
from the www.socomec.com web site.
Refer to the chapter on software updating for instructions on how to install a new language.

IOMMASGPXX01-GB_00 47
8 COMMUNICATION
10-40 kVA

8.2.2.7 Local network.


Enable the user to modify the network communication parameters.
r Dynamic IP address: if enabled, the IP address is automatically assigned by the network server
r Static IP address: the IP address is used if the dynamic IP address is disabled.
r Network mask: this is used if the dynamic IP address is disabled.
r Gateway: the gateway address used to send TCP/IP data out of the local network.
r Password: allows the user to change the password to access the html. To authorise access only to users that have
a password. Insert the new password and write it down in case of need.
r JBUS TCP/IP Port: used to accept a JBUS frame through LAN tunnelling .
ITALIANO
ENGLISH

r Client JBUS IP address to be authorised: if a specific IP address is inserted in this box, then only that address/
user will be able to access the html pages. If the address 0.0.0.0 is used, all the PCs on the network will be able to
access the supervisor (one client at a time). If the address 255.255.255.255 is inserted, access will be denied to all
users.
r Software updating: if on, allows the supervisor to be updated.
r Page refresh (sec): the page refresh rate can be set.
r Installation: text string used to describe the UPS installation site, which is useful if there are more than one unit
connected (this value is inserted in SMS messages or e-mails).
r NTP Server: indicates the IP address of the time server to automatically update the date and time on the system.
r GMT Correction (minutes):JOEJDBUFTMPDBMUJNFBOEUIFPíTFUJONJOVUFTXJUISFTQFDUUPUIF[FSPNFSJEJBOPG
Greenwich
r Apply the parameter settings: restarts the monitoring system with the new settings.

$POöHVSJOHFNBJM
This menu lets the user configure parameters for sending e-mails.
r Event that will send an e-mail: as required, the e-mail may be deactivated or activated to send a message in the
event of serious alarms or for all alarm conditions.
r E-mail server address: insert the IP address (xxx.xxx.xxx.xxx) of the SMTP e-mail server from which you wish to
send messages.
r e-mail account: Insert the UPS’s dedicated “user account”, which is often the same as the user’s e-mail address.
r Addressee: insert the e-mail address to which the alarm messages will be sent.
r Periodic connection: set the frequency at which an e-mail is to be sent to verify the connection.
r Force an e-mail to be sent now: by selecting “execute” a test e-mail will be sent.

48 IOMMASGPXX01-GB_00
8 COMMUNICATION
10-40 kVA

8.2.2.9 .PEFNDPOöHVSBUJPO.
This menu lets the user configure the parameters of a modem
r Rings before reply: Set the number of rings after which the modem should respond.
r Outgoing call1: sets the type of outgoing call: SMS or E- service (to activate e-service a contract to the support
centre is required).
r Reason for callout: set the reasons for the call (all alarms or for serious faults).
r Installation: text string used to describe the UPS installation site, which is useful if there are more than one unit
connected (this value is inserted in SMS messages or e-mails).
r Telephone number: insert the number to be called.

ENGLISH
r Modem initialisation: initial string to be sent to the modem (for special configurations or certain types of mo-
dem).
r Connection period: set the number of days between two calls even if no faults occur.
r Force an outgoing call: by selecting EXECUTE a test connection is immediately carried out.
 "DUJWBUJOHPOFDPOñHVSBUJPOFYDMVEFTUIFPUIFSUIFSFGPSFJGBO&TFSWJDF5TFSWJDFDPOUSBDUJTTVCTDSJCFE DBMMTJOPVUQVUDBOOPUCFDPOñHVSFE
2 In the event that the E-service/T-service contains the control code provided by after-sales personnel.

8.2.2.10 Software updating.


This html page is used to update automatically the monitoring software, which could be useful to add new languages
or the SNMP function.
Once the file has been acquired (by requesting it from the support service) select it with the browse button.
$MJDLPOUIFiTUBSUVQEBUFuCVUUPOPODFUIFVQEBUFIBTCFFODPNQMFUFE SFMPBEUIFIUNMQBHF

8.2.2.11 System Information Area.


This area of the screen page shows
the measurements and the UPS op-
erating mode.
r $MJDLPOJDPOA to display the input D
measurements.
C
r $MJDLPOJDPOB to display the bat-
A B
tery measurements.
r $MJDLPOJDPOC or D to display the
output measurements.

IOMMASGPXX01-GB_00 49
8 COMMUNICATION
10-40 kVA

8.3 ACCESSORIES AND SW OPTIONS.


A large number of SW solutions can be adopted on MASTERYSTM thanks to its advanced communication facilities.
These solutions have been specially designed for the efficient management of power protection devices.
UNI VISION PRO is the solution for managing a UPS connected to the local server
via RS232 interface or via LAN network. It is normally used at departmental level
to automatically shutdown the systems and ensure secure control of the UPS that
in turn protect servers and workstations.
The main functions are:
ITALIANO
ENGLISH

r (SBQIJDNPOJUPSJOHPGUIF614WJBXFCCSPXTFS
r -PDBMTIVUEPXOPGBTFSWFSDPOOFDUFEWJBTFSJBMJOUFSGBDF
r 3FNPUFTIVUEPXOWJBQSPYZBHFOUBOEPQUJPOBM+BWBTIVUEPXODMJFOUT
r /PUJñDBUJPOPGBOPNBMJFTWJBFNBJMUPBNBYJNVNPGBEESFTTF

NET VISION is a solution for managing UPS units connected directly to the local
network. It is normally used on medium/large, complex networks and in multi-
server environments where the IT manager centrally controls all the network re-
sources. The physical position of the UPS is not significant.
The main functions are:
r .C&UIFSOFUDPOOFDUJPO 3+

r (SBQIJDNPOJUPSJOHPGUIF614WJBXFCCSPXTFS
r 3FNPUFTIVUEPXOPGVQUPDPNQVUFST
r /PUJñDBUJPOPGBOPNBMJFTWJBFNBJMUPBNBYJNVNPGBEESFTTFT
r 614NBOBHFNFOUVTJOH4/.1QSPUPDPM
r %JBHOPTUJDTWJB*OUFSOFUPíFSFECZF4FSWJDF

Java & .NET shutdown Client (JNC) is an optional Java application to be installed
on a server for the automatic shutdown of the computers on the network before
the UPS stops due critical operating conditions (imminent battery failure, overload,
etc.). It is supplied as an option and can be associated to the UNI VISION PRO or NET
VISION communication solutions.
The main features/functions are:
r 6TFPGUIF5$1*1TUBOEBSEOFUXPSLQSPUPDPM
r (SBQIJDTJOUFSGBDFGPSFBTZDPOñHVSBUJPO
r .JOJNVNVTFPG$16SFTPVSDFT
r 1FSTPOBMJTBUJPOPGTIVUEPXOQBSBNFUFSTBOETDSJQU
r $POUJOVPVTNPOJUPSJOHPGUIFFîDJFODZPGUIFDPOOFDUJPOUPUIF614

50 IOMMASGPXX01-GB_00
8 COMMUNICATION
10-40 kVA

This is a cutting edge supervision service ensuring 24/7/365 service.


*UFOTVSFTFíFDUJWFQSFWFOUJPOBOEDPOTUBOUNPOJUPSJOHPGUIFTZTUFN
Communication between the UPS and the local Socomec Service Centre is via
modem (free-air GSM or ANALOG fixed line).
The auto-diagnostic system analyses UPS operating conditions, identifies faults
and monitors environmental conditions such as temperature, overload, avoid-
ing the risk of equipment stoppages. In the event of a failure, the system imme-
diately sends a “diagnostic report” via modem to the Service Centre.
Any emergency situation is managed and resolved extremely quickly and re-

ENGLISH
motely by the Service Centre, with immediate intervention on site if needed.

IOMMASGPXX01-GB_00 51
9 PROBLEM SOLVING
10-40 kVA

The alarm messages displayed enable an immediate diagnosis.


Alarms are divided into two categories:
r Alarms related to the UPS external circuits: input mains, output mains, temperature and environment.
r "larms related to the UPS internal circuits: in this case, the corrective actions will be carried out by the After Sales
Department.

9.1 SYSTEM ALARMS.


t "PVUQVUPWFSMPBE.
The power required by the loads is higher than the power available.
Check that the load is well balanced on the three phases by checking the measurements on the display. If needed,
ITALIANO
ENGLISH

disconnect any loads that do not need uninterruptible power.


Important!
The accepted overload time limit is defined in the technical specifications. When this time limit is exceeded, the
loads will no longer be powered by the inverter.
t "BVYJMJBSZNBJOTPVUPGUPMFSBODF.
The auxiliary mains exceeds the acceptable tolerance values. Possible causes are:
r /PWPMUBHFPSGSFRVFODZQSFTFOUPSWPMUBHFBOEGSFRVFODZPVUPGBDDFQUBCMFWBMVFT TFFUIFUFDIOJDBMTQFDJñDB-
tions).
r 5IFGSFRVFODZJTTVCKFDUUPDPOUJOVPVTWBSJBUJPOT UZQJDBMXJUIQPXFSTVQQMJFEGSPNBOJODPSSFDUMZTJ[FE(&

t "UFNQFSBUVSFPWFSUIFMJNJUT
5IF614JOUFSOBMUFNQFSBUVSFJTIJHIFSUIBOž$ QMFBTFSFGFSUP.FBTVSFNFOUTNFOVPOUIFNJNJDQBOFM

Check the ventilation or air conditioning system in the UPS room.
t "NBJOUFOBODFCZQBTTBDUJWBUFE
The output disconnecting switch Q6 is in position 2 (maintenance bypass).
The load is therefore powered directly by mains power supply.
t "JNQSPQFSDPOEJUJPOTPGVTF
This alarm does not indicate a malfunction or failure of the UPS, but an incorrect use/sizing of the system. It is
activated in the event of:
r 0QFSBUJPOGPSMPOHQFSJPETBUIJHIUFNQFSBUVSFT CBUUFSZEFUFSJPSBUJPO

r )JHIOVNCFSPGPWFSMPBET XSPOHTJ[JOH

r $POUJOVPVTCBUUFSZEJTDIBSHJOH NBJOTOPUTUBCMF

r )JHIOVNCFSPGTXJUDIFTPOUPUIFCZQBTT IJHIJNQVMTJWFMPBET

t "JOQVUNBJOTPVUPGUPMFSBODF
The input mains is not present or not sufficient (voltage and/or frequency values incorrect with reference to the
UFDIOJDBMEBUB
JGUIFSFJTOPJOQVUNBJOTPVUBHF DIFDLJGOPQSPUFDUJPOTVQTUSFBNPGUIF614IBWFUSJQQFE
Check that the voltage applied and frequency values are in compliance with the values set on the mimic panel.
t " " " "FYUFSOBMBMBSN   
0OFPGUIF"%$1$#JOQVUTIBTCFFOBDUJWBUFEDIFDLUIFTJUVBUJPOPGUIFEFWJDFTDPOOFDUFEUPUIJT1$#
t " "HFOFSBUPSHFOFSBMBMBSN
5IFHFOFSBUPSIBTTFOUBOBMBSNDIFDLEJSFDUMZPOUIF(&

52 IOMMASGPXX01-GB_00
9 PROBLEM SOLVING
10-40 kVA

t "XSPOHQIBTFDZDMFEJSFDUJPO
The phase cycle sequence is incorrect. In this case, invert two phases of the input mains. For a UPS with separate
auxiliary mains, exchange the two phases of the auxiliary mains only.

9.2 UPS ALARMS.


t "CBUUFSZBMBSN
Failure or problem on the battery circuit. Check that the battery switch is closed.
t "JOWFSUFSCMPDLFEEVFUPPWFSMPBE
Reduce the load rate applied to the UPS and reset the alarms.

ENGLISH
t "XSPOHDPOöHVSBUJPO
&SSPSJOUIFDPOñHVSBUJPOQBSBNFUFSTQMFBTFDPOUBDUUIFTVQQPSUTFSWJDF
t "CMPDLEVFUPPWFSMPBE
Reduce the load rate applied to the UPS and reset the alarms.
t "54FSWJDFHFOFSBMBMBSN
5IF."45&3:4–QSPEVDUTDBOCFSFNPUFMZTFSWJDFE5IJTBMBSNJOEJDBUFTUIBUBQSPDFEVSFGPSBOBMZTJOHUIF614
failure has been activated by the support centre (if an e-service contract has been concluded).
t "QSPHSBNNFEDPOUSPM
The equipment has to undergo periodic checks by the support service in order to ensure optimum perform-
ance and efficiency. If the “Programmed Control” signal appears on the mimic panel, the equipment should be
inspected by an adequately trained technician.
t "CBUUFSZDJSDVJUPQFO
Battery switch open.
t "GBOGBJMVSF
'BVMUJOUIFWFOUJMBUJPOTZTUFNDIFDLUIBUUIFBJSJOMFUBUUIFGSPOUBOEUIFBJSPVUMFUBUUIFCBDLPGUIF614BSFOPU
obstructed.

9.3 PREVENTIVE MAINTENANCE.


We would like to inform you that specialised periodic maintenance (with yearly frequency) is recommended for the

IOMMASGPXX01-GB_00 53
9 PROBLEM SOLVING
10-40 kVA

."45&3:4– JOPSEFSUPPíFSPQUJNVNPQFSBUJOHFîDJFODZBOEBWPJEEPXOUJNFPGUIFFRVJQNFOU
It is strongly recommended to give due consideration to any requests for preventive maintenance automatically
displayed with alarm message M29 (refer to paragraph 6.2.3.1).
All operations on the equipment must be only carried out by SOCOMEC UPS personnel or by authorised support
personnel.
Maintenance consists of accurate functional checks on electronic and mechanical parts with replacement of parts
TVCKFDUUPXFBSJGOFDFTTBSZ UZQJDBMMZCBUUFSJFT GBOTBOEDBQBDJUPST


9.3.1 Batteries.
ITALIANO
ENGLISH

The state of the battery is fundamental to UPS operation.


Thanks to the Expert Battery System, the information relating to the state and the conditions of use of the battery
are processed in real time and the recharging and discharging procedures are selected automatically in order to
PQUJNJTFCBUUFSZMJGFFYQFDUBODZBOEPíFSNBYJNVNQFSGPSNBODF
'VSUIFSNPSF EVSJOHUIFPQFSBUJOHMJGFPGUIFCBUUFSZ ."45&3:4–TUPSFTTUBUJTUJDTPOUIFDPOEJUJPOTPGVTFPGUIF
battery for analysis.
Since the expected life of the batteries is very much dependent on operating conditions (number of charging and
discharging cycles, load rate, temperature), a periodic check by authorised personnel is recommended.
8IFOSFQMBDJOHUIFCBUUFSJFT VTFUIFTBNFUZQFBOEDPOöHVSBUJPOCZQMBDJOHUIFNJOUIFBQQSP-
priate containers so as to avoid the risk of acid leakage.
The replaced batteries must be disposed of at authorised recycling and disposal centres.
Do not open the plastic cover of the batteries as they contain harmful substances.

9.3.2 Fans.
The life of the fans used to cool the power parts is dependent on the using and environmental conditions (tem-
perature, dust).
Preventive replacement by an authorised technician is recommended within four years (in normal operating condi-
tions).

8IFOOFFEFE GBOTTIPVMECFSFQMBDFEBTQFSTQFDJöDBUJPOTCZ40$0.&$614

9.3.3 Capacitors.
The equipment houses electrolytic capacitors (used in the rectifier and inverter section) and filtering capacitors
(used in the output section), whose life is dependent on using and environmental conditions.
The average expected life of these components is shown below:
r &MFDUSPMZUJDDBQBDJUPSTZFBST
r 'JMUFSJOHDBQBDJUPSTZFBST
*OBOZDBTFUIFFíFDUJWFTUBUFPGUIFDPNQPOFOUTJTWFSJñFEEVSJOHQSFWFOUJWFNBJOUFOBODF

54 IOMMASGPXX01-GB_00
10 OPTIONS
10-40 kVA

10-1
Legend.
S1 C1 Serial connector RS232/485
C2 serial connector RS232 for Modem
C3 LAN connector RJ45 for Ethernet
C3
S1 Options slot 1
S2 Options slot 2
C1

C2

ENGLISH
S2

10.1 ADC CARD.


Up to two cards can be installed per UPS in a vacant slot, S1 or S2.
The card enables configurable management of up to four normally closed or normally open outputs, and up to
three digital inputs. Two dip-switches allow the selection of up to four operating modes (Standard, Power Safe,
Security and Environmental), which can be used to manage the following events:
rCBUUFSZMPXPSJNNJOFOUTUPQ
rCBUUFSZEJTDIBSHJOH
r&4%BOE&4%BDUJWBUJPO
rFYUFSOBMBMBSN"
rFYUFSOBMBMBSN"
rFYUFSOBMBMBSN*O
rHFOFSBM"MBSN
rJTPMBUJPODPOUSPMMFS
rNBOBHFNFOUPGFOFSHZDPOTVQUJPO
rPWFSIFBUJOH
rPWFSMPBEMPTTPGSFEVOEBODZ
rQPXFSTBGFQMVH QPXFSTBGFQMVH QPXFSTBGFQMVH
rTVQQMZGSPN(FO4FU
r614POCZQBTT

IOMMASGPXX01-GB_00 55
10 OPTIONS
10-40 kVA

10.2 KIT GSS (GLOBAL SUPPLY SYSTEM).


This kit optimises generator sizing and control when connected to the UPS input.
The generator set can be instructed to start up automatically the moment the mains power is lost, or alternatively,
following a user-set time period without the mains power, and/or when the batteries have discharged to their
residual capacit.

10.3 ISOLATION CONTROLLER.


This device continually checks the transformer isolation, displaying an alarm message on the mimic panel.
ITALIANO
ENGLISH

10.4 REMOTE MIMIC PANEL.


This device monitors and interacts with the UPS through a serial link RS 485 (maximum distance of 175 m) 25 m
DBCMFTVQQMJFETUBOEBSENDBCMFBWBJMBCMFBTBOPQUJPO


10.5 EXTERNAL MAINTENANCE BYPASS.


This device will electrically exclude and isolate the UPS (e.g. for maintenance operations) without interrupting the
power supplied to the load.

10.6 EXTERNAL MAINTENANCE BYPASS WITH BACKFEED PROTECTION.


This device will electrically exclude and isolate the UPS (e.g. for maintenance operations) without interrupting the
power supplied to the load. 3-pole contactors are used for the back-feed protection (refer to paragraph 10.8).
Note.
An additional option is available to bring the manual bypass signal back to the UPS.

10.7 ACS PCB.


4ZODISPOJTFT614PVUQVUXJUIBOFYUFSOBMQPXFSTPVSDF BOPUIFS614 FWFOPGBEJíFSFOUCSBOE HFOFSBUPSPSUSBO-
sformer).

10.8 EXTERNAL BACK-FEED PROTECTION.


External devices can be installed to protect against the
10.8-1
backfeed of dangerous currents, both on the MAINS
SUPPLY and on the AUX MAINS SUPPLY. These devices
are controlled by the BKF PCB installed in the position
shown in figure 10.8.1.
L31 L3 N11 N1 +B2 -B2 -B1 +B1
Refer to the following paragraphs for details on the
S SUPPLY EXT. BATTERY
electrical connections and on activating the chosen
protection.

56 IOMMASGPXX01-GB_00
10 OPTIONS
10-40 kVA

10.8.1 Protection on Mains Supply and on Auxiliary Mains Supply.


Activating UPS protection on the mimic panel: access the Configuration menu on the mimic panel (see the Con-
figuration Menu section in the manual) and set the BACKFEED TYPE parameter to 2.BYPASS-INPUT Alone.
Diagram of principle.

10.8.1-1 UPS 3/3 with separate auxiliary supply. 10.8.1-2 UPS 3/1 with separate auxiliary supply.

A UPS A UPS

ENGLISH
Q1 T1 M1 Q1 T1 M1
L1 L1 L1 L1
L2 L2 L2 L2
L3 L3 L3 L3
N N N N

B B

Q2 T2 M2 Q2 T2 M2
L11 L11
L21 L21
L31 L31 L11 L11
N1 N1 N1 N1

B B

XB1 XB1
BKF card BKF card
XB2 XB2

Legend. 1
Remote switches - rated current
A Distribution panel
B Coil remote switch Model T1 T2
L1-L2-L3-N Input power source 10 3/1 32 A AC1 45 A AC1
L11-L21-L31-N1 Backup power source 15 3/1 32 A AC1 45 A AC1
M1 Input power terminal board 20 3/1 45 A AC1 60 A AC1
M2 Backup power terminal board
10 3/3 32 A AC1 32 A AC1
T1 Remote switch1
T2 Remote switch1
15 3/3 32 A AC1 32 A AC1
Q1 Input power switch 20 3/3 45 A AC1 45 A AC1
Q2 Backup power switch 30 3/3 60 A AC1 60 A AC1
XB1 Connector on BKF PCB 40 3/3 90 A AC1 90 A AC1
XB2 Connector on BKF PCB

IOMMASGPXX01-GB_00 57
10 OPTIONS
10-40 kVA

10.8.2 Protection on an UPS without auxilary mains supply.


Activating UPS protection on the mimic panel: access the Configuration menu on the mimic panel (see the Configu-
ration Menu section in the manual) and set the BACKFEED TYPE parameter to 3.BYPASS-INPUT Common.

Diagram of principle.
1
10.8.2-1 UPS 3/3 without separate auxiliary supply. Remote switches - rated current
Model T1
A UPS 10 3/1 32 A AC1
Q1 T1 M1
15 3/1 32 A AC1
ITALIANO
ENGLISH

L1 L1
L2 L2 20 3/1 45 A AC1
L3 L3 10 3/3 32 A AC1
N N 15 3/3 32 A AC1
B
20 3/3 45 A AC1
30 3/3 60 A AC1
XB1
BKF card
40 3/3 90 A AC1

Legend.
A Distribution panel Q1 Input power switch
B Coil remote switch T1 Remote switch1
L1-L2-L3-N Input power source XB1 Connector on BKF PCB
M1 Input power terminal board

Attention.
The neutral on the input or the output of the UPS are identical. Consequently there is no risk of high potential when
the input power supply is absent.
However, depending on the type of system connected in the output or in some failure conditions (earth leakage,
significant phase dispersion or in case of non-isolated neutral system), high potential can be detected. It will there-
fore be necessary to install either adequate neutral switching or protection system.

58 IOMMASGPXX01-GB_00
10 OPTIONS
10-40 kVA

10.9 ADC CARD WITH TEMPERATURE SENSOR.


This card can be used to manage up to four normally closed or normally open outputs and up to three digital inputs
in configurable mode.
*GNPSFUIBOPOF"%$DBSEJTVTFETJNVMUBOFPVTMZ UIFEJQTXJUDIDPOñHVSBUJPOTNVTUCFEJíFSFOU

10.10 PROFIBUS.
On request, the UPS can be provided with a Profibus protocol converter, installation software, configuration softwa-
re and user manuals. If the RS232/485 serial connector is installed on the mimic panel, it should be disabled.

ENGLISH
10.11 GSM MODEM.
Enables sending of SMS messages regarding the equipment’s operating status.

10.12 SERIAL CONNECTION PCB.


"TFSJBM34DPOOFDUPS%#BOEBOJTPMBUFE34DPOOFDUPSBSFBWBJMBCMFPOUIFDBSE 359 BOE359¢


10.13 MANAGEMENT OF EXTERNAL MANUAL BY-PASS CONTACT.


"MMPXTNBOBHFNFOUPGPOPíJOEJDBUJPOGPSUIFFYUFSOBMNBOVBMCZQBTTJTPMBUJOHTXJUDI

IOMMASGPXX01-GB_00 59
11 TECHNICAL SPECIFICATIONS
10-40 kVA

Models
10 15 20 30 40
Input/Output phases 3/1 and 3/3 3/1 and 3/3 3/1 and 3/3 3/3 3/3

&MFDUSJDBMTQFDJöDBUJPOT*OQVU
10 15 20 30 40
.BJOTWPMUBHF 1 /7  VQUP!PGOPNJOBMMPBE

Input frequency 50-60 Hz ±10%
ITALIANO
ENGLISH

Input power factor 0,99


THDI < 2.5%

&MFDUSJDBMTQFDJöDBUJPOT0VUQVU
10 15 20 30 40
Output voltage UISFFQIBTF OFVUSBM
230 V single phase (selectable: 208*/220/230/240 V) ±1%
400 V three phase (selectable 360*/380/400/415 V) ±1%
Frequency 50-60 Hz ±2% (from 1% to 8% if generator is used)
Automatic bypass nominal output voltage ±15%
(from 10% to 20% selectable if generator is used)
Nominal power (kW) 9 13,5 18 27 36
Overload on mains power supply 125% 10 minutes
150% 1 minute
Crest factor 3:1
Voltage distortion 1% with linear load
!1PVU1OPN

Environment
10 15 20 30 40
0QFSBUJOHUFNQFSBUVSF œž$ œž$SFDPNNFOEFEGPSMPOHFSCBUUFSZMJGF

4UPSBHFUFNQFSBUVSF œž$
3FMBUJWFIVNJEJUZ œDPOEFOTBUJPOGSFF
.BYBMUJUVEF N GU
XJUIPVUEFSBUJOHN GU
NBY
Acoustic noise (dB) < 52 < 52 < 52 < 55 < 55
Required cooling capacity (m3/h) 280 280 280 465 465
Dissipated power max (W) 680 900 1150 1750 2300
Dissipated power (BTU/h) 2300 3050 4070 6050 7900

Standards
10 15 20 30 40
Safety (TÜV certified) EN 62040-1-1, EN 60950-1
Type and performance EN 62040-3 (VFI-SS-111)
EMC EN 62040-2
Product certification
Protection level IP20 (compliant with 60529), IP21 on request

60 IOMMASGPXX01-GB_00
11 TECHNICAL SPECIFICATIONS
10-40 kVA

Mechanical characteristics with standard batteries

1.400

1.000

ENGLISH
800
795 795 795
444 444 444

Model: T Model: M Model: S


8FJHIUŸLH 8FJHIUŸLH 8FJHIUŸLH

WEIGHT

ООО "Энергетические и Телекоммуникационные Системы"


Тел./факс: (495) 981-13-66
http://www.entel.ru, E-Mail: [email protected]
61

You might also like