Installation and Operating Manual: IOMMASGPXX01-GB - 00
Installation and Operating Manual: IOMMASGPXX01-GB - 00
Installation and Operating Manual: IOMMASGPXX01-GB - 00
10-40 kVA
IOMMASGPXX01-GB_00
ITALIANO
INDEX
10-40 kVA
2. SAFETY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.1 Important. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.2 Description of the symbols used on the labels applied to the . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
ENGLISH
3.4 Electrical requisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
3.4.1 Backfeed protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
3.5 Installation procedure and instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.6 Connection of the generator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
3.7 External E.S.D. connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
3.8 Isolation transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
3.9 UPS Parallel configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
3.9.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
3.9.2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
3.9.3 Power connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
3.9.4 Control connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
3.10 External battery cabinet connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
IOMMASGPXX01-GB_00 3
INDEX
10-40 kVA
8. COMMUNICATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
ITALIANO
ENGLISH
4 IOMMASGPXX01-GB_00
CERTIFICATE AND CONDITIONS
1 OF WARRANTY 10-40 kVA
This SOCOMEC UPS continuous power system is guaranteed against any manufacturing and material defects.
The period of validity of the warranty is 12 (twelve) months from the date of commissioning, if said activation is
carried out by SOCOMEC UPS personnel or personnel from a support centre authorised by SOCOMEC UPS, and not
however more than 15 (fifteen) months from the date of shipment by SOCOMEC UPS.
The warranty is recognized within national territory. If the UPS is exported out of national territory, the warranty shall
be limited to the cover of the parts used to repair the fault.
The warranty is valid ex-works and covers labour and parts used to repair the fault.
ENGLISH
The warranty shall not apply in the following cases:
r 'BJMVSFTEVFUPGPSUVJUPVTDJSDVNTUBODFTPSGPSDFNBKFVSF MJHIUOJOH
óPPET
FUD
r 'BJMVSFTEVFUPOFHMJHFODFPSJNQSPQFSVTF VTFPVUPGUPMFSBODFUFNQFSBUVSF
IVNJEJUZ
WFOUJMBUJPO
FMFDUSJDQPX-
FSTVQQMZ
BQQMJFEMPBE
CBUUFSJFT
r *OTVîDJFOUPSJOBEFRVBUFNBJOUFOBODF
r "UUFNQUFENBJOUFOBODF
SFQBJSTPSNPEJñDBUJPOTOPUDBSSJFEPVUCZ40$0.&$614QFSTPOOFMPSQFSTPOOFMGSPN
a support centre authorised by SOCOMEC UPS.
r *GUIFCBUUFSZIBTOPUCFFOSFDIBSHFEJOBDDPSEBODFXJUIUIFUFSNTJOEJDBUFEPOUIFQBDLBHJOHBOEJOUIFNBOVBM
in cases of extended storage or UPS inactivity.
SOCOMEC UPS may, at its own discretion, opt for the repair of the product or for the replacement of the faulty or
defective parts with new parts or with used parts that are equivalent to new parts with regard to functions and
performance.
Defective or faulty parts replaced free of charge are to be put at the disposal of SOCOMEC UPS who becomes the
sole owner.
Replacements or repairs of parts and any modifications to the product during the warranty period cannot extend
the duration of the warranty.
In no case will SOCOMEC UPS be responsible for damages (including, without limitations, damage for loss of earn-
ings, interruption of activity, loss of information or other economic losses) deriving from the use of the product.
5IFQSFTFOUDPOEJUJPOTBSFTVCKFDUUP*UBMJBOMBX"OZEJTQVUFGBMMTVOEFSUIFQSPWJODFPGUIF$PVSUPG7JDFO[B
IOMMASGPXX01-GB_00 5
2 SAFETY
10-40 kVA
2.1 IMPORTANT.
r 5IJTEPDVNFOUQSPWJEFTJNQPSUBOUJOTUSVDUJPOTGPSUIFTBGFVTF
NPWFNFOUBOEDPOOFDUJPOPGUIF."45&3:4VO-
interruptible power system (UPS).
r 40$0.&$614SFUBJOTUIFGVMMBOEFYDMVTJWFPXOFSTIJQSJHIUTPWFSUIJTEPDVNFOU0OMZBQFSTPOBMSJHIUUPVUJMJ[F
the document for the application indicated by SOCOMEC UPS is granted to the recipient of such document. All
reproduction, modification, dissemination of this document whether in part or whole and by any manner are
expressly prohibited except upon Socomec’s express prior written consent.
r 5IJTEPDVNFOUJTOPUBTQFDJñDBUJPO40$0.&$614SFTFSWFTUIFSJHIUUPNBLFBOZDIBOHFTUPEBUBXJUIPVUQSJPS
notice.
ITALIANO
ENGLISH
r 5IFVOJUNVTUCFJOTUBMMFEBOEBDUJWBUFEPOMZCZRVBMJñFEUFDIOJDBMQFSTPOOFMBOEBVUIPSJTFECZ40$0.&$614
r 5IFVOJUNVTUSFNBJOJOBWFSUJDBMQPTJUJPOJOBMMDJSDVNTUBODFT
r $POOFDUUIF1&HSPVOEDPOEVDUPSñSTUCFGPSFZPVNBLFBOZPUIFSDPOOFDUJPO
r %POPUFYQPTFUIF614UPSBJOPSMJRVJETJOHFOFSBM%POPUJOUSPEVDFFYUFSOBMCPEJFT
r *GUIF614JTOPUFRVJQQFEXJUIBVUPNBUJDTFDUJPOJOHBHBJOTUCBDLGFFEPSJGUIFTXJUDIJTFYUFSOBMUPUIF614
BîY
a label bearing the following words on all the external switches of the UPS power supply:
r ,FFQUIJTNBOVBMIBOEZGPSGVUVSFDPOTVMUBUJPO
r *GUIFVOJUGBJMT
JUNVTUCFSFQBJSFEPOMZCZBVUIPSJTFEUFDIOJDJBOTUIBUIBWFCFFOTQFDJBMMZUSBJOFEGPSUIJTQVS-
pose.
r 5IJTFRVJQNFOUDPOGPSNTUPUIF&VSPQFBO$PNNVOJUZEJSFDUJWFTGPSQSPGFTTJPOBMFRVJQNFOUBOECFBSTUIFBQ-
proval mark
r 5IF614SFRVJSFTUISFFQIBTFQMVTOFVUSBMJOQVUDPOOFDUJPOT 1/
r %POPUDPOOFDUUIFPVUQVUOFVUSBMUPHSPVOE5IF614EPFTOPUNPEJGZUIFOFVUSBMBSSBOHFNFOUTPGUIFTZTUFN
the use of an isolation transformer is required should it be necessary to modify the neutral arrangements down-
stream of the UPS.
r #FGPSFDPOOFDUJOHBOZFYUFSOBMCBUUFSZDBCJOFU
FOTVSFUIBUJUJTGVMMZDPNQBUJCMFXJUIUIFNPEFMPG614JUJTUPCF
used with.
r 5IFVTFPGFYUFSOBMCBUUFSZDBCJOFUTOPUTVQQMJFECZUIFNBOVGBDUVSFSTJTOPUSFDPNNFOEFE
r 4XJUDIPíBOEJTPMBUFUIF614BOEUIFOXBJUGPSNJOVUFTCFGPSFSFNPWJOHUIFQSPUFDUJPOQBOFMTJOPSEFSUPDBSSZ
out work on parts under dangerous voltage.
r %BOHFSPGFYQMPTJPOJGUIFCBUUFSJFTBSFSFQMBDFEXJUIPUIFSTPGUIFXSPOHUZQF
r 3FQMBDFECBUUFSJFTNVTUCFEJTQPTFEPGBUBVUIPSJTFEXBTUFEJTQPTBMDFOUSFT
6 IOMMASGPXX01-GB_00
2 SAFETY
10-40 kVA
It is very dangerous to touch any part of the batteries as there is no isolation between the batter-
ies and the mains power source.
The product you have chosen is designed for commercial and industrial use only.
In order to be used for particular “critical applications” such as life support systems, medical applications, commercial
transportation, nuclear facilities or any other application or systems where product failure is likely to cause substan-
tial harms to person or property, the products may have to be adapted.
For such uses we would advise you to contact SOCOMEC UPS beforehand to confirm the ability of these products
to meet the requested level of safety, performance, reliability and compliance with applicable laws, regulations and
ENGLISH
specifications.
2.2 DESCRIPTION OF THE SYMBOLS USED ON THE LABELS APPLIED TO THE UNIT.
All the precautions and the warnings on the labels and plates on the inside and outside of the equipment should
be respected.
GROUND TERMINAL
IOMMASGPXX01-GB_00 7
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA
The packaging guarantees the stability of the UPS during shipping and physical transfer. Carry the packaged unit as
close as possible to the installation site.
When moving the unit on even slightly sloping surfaces, use the blocking equipment and break-
ing devices to ensure that the unit does not fall over.
r 5IFVOJUIBTXIFFMTUIBUDBOCFVTFEUPNPWFJUGPSTIPSUEJTUBODFT
r &OTVSFUIBUUIFóPPSJTTUSPOHFOPVHIUPTVQQPSUUIFXFJHIUPGUIF614BOEPGUIFCBUUFSZDBCJOFU
JGVTFE
The UPS MUST only be moved by two people at least. The people MUST take position at the
sides of the UPS with respect to the direction of movement.
CAUTION IF DAMAGED.
BATTERIES, NON SPILLABLE.
Packages, crushed, punctured, or torn such that contents are revealed
must be set aside in an isolated area and inspected by a qualified per-
son. If the package is deemed to be not shippable, the contents must Battery is NOT connected!
be promptly collected, segregated, and either the consignor or consignee
contacted.
All packaging material must be recycled in compliance with the laws in force in the country where
the system is installed.
8 IOMMASGPXX01-GB_00
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA
ENGLISH
B
3.2.1-4
C Secure the UPS with feet D only when it is in position with cables
C
connected.
IOMMASGPXX01-GB_00 9
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA
1 A
2 2
Loosen screws B.
3.2.2-6 Remove screws C. 3.2.2-7 Tighten screws B.
1 B 2 B
1
The UPS can be moved.
1 Place the UPS in the installation
2 C area.
1 B
2
Secure the UPS with feet D
only when it is in position 2
D D with the cable connected.
10 IOMMASGPXX01-GB_00
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA
Tighten screws B.
3.2.2-10 Tighten screws C. 3.2.2-11 Tighten screws A.
2 B 2 A
ENGLISH
1 C
3.2.2-12 3.2.2-13
E
IOMMASGPXX01-GB_00 11
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA
the UPS for maintenance purposes. It is also recommended to ensure that the cable connections are sufficiently
MPOHBOEóFYJCMFTPUIBUUIFVOJUDBOCFFYUSBDUFEEVSJOHNBJOUFOBODF TFFñHVSF
r *GJUJTOPUQPTTJCMFUPMFBWFTVîDJFOUTQBDFBUUIFGSPOU
BEFRVBUFBDDFTTNVTUCFFOTVSFEGSPNCPUITJEFT
3.3-1 3.3-2
40 cm
40 cm
20 cm 20 cm
MASTERYS MASTERYS MASTERYS
UPS OR UPS OR UPS OR MASTERYS MASTERYS
OTHER OTHER OTHER UPS UPS
CABINET CABINET CABINET
1,5 m
1,5 m
12 IOMMASGPXX01-GB_00
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA
ENGLISH
(kVA) (A) (A) (A) (mm2) (mm2) (A)
single parallel2 single parallel2 selective type5 Min Max3 Min Max3
10 3/1 32 40 100 125 0,5 6 35 6 35 50 Gr
100 125 16
if common if common aux mains
input input and output
mains mains
15 3/1 32 40 100 125 0,5 6 35 6 35 50 Gr
100 125 25
if common if common aux mains
input input and output
mains mains e uscita
20 3/1 40 63 125 160 0,5 10 35 10 35 50 Gr
125 160 35
if common if common aux mains
input input and output
mains mains e uscita
10 3/3 32 40 32 40 0,5 6 35 6 35 50 Gr
15 3/3 32 40 32 40 0,5 6 35 6 35 50 Gr
20 3/3 40 63 40 63 0,5 10 35 10 35 50 Gr
30 3/3 63 80 63 80 0,5 16 35 16 35 100 Gr
40 3/3 80 100 80 100 0,5 25 35 25 35 100 Gr
1
Recommended magneto thermal switch: four poles with intervention threshold ≥ 10 In
2
In systems with two or more UPSs operating in a redundant or power parallel configuration.
3
Determined by the size of the terminals.
4
protection on the external battery cabinet.
5
Caution! Use type B four-pole selective (S) circuit breakers. Load leakage currents are added to those generated by the UPS and during transitory
QIBTFT QPXFSGBJMVSFBOEQPXFSSFUVSO
TIPSUDVSSFOUQFBLTNBZPDDVS*GMPBETXJUIIJHIMFBLBHFDVSSFOUBSFQSFTFOU
BEKVTUUIFEJíFSFOUJBM
protection. It is advisable in all cases to carry out a preliminary check on the earth current leakage with the UPS installed and operational with the
definitive load, so as to prevent the sudden activation of the above switches.
The UPS is designed for transitory overvoltages in category II installations. If the UPS is part of
the building’s electric circuit or if it is likely to be subject to transitory overvoltages in category III
installations, further external protection must be provided, either on the UPS or in the AC power
supply network to the UPS. In addition, the “Surge arrestor” option, specially designed to protect
against residual overvoltages in category III installations, can be installed in the external manual
bypass cabinet. If used, the distance between the UPS and the centralised 4 kV SPD protections
type 1 must be Up ≤ 4kV is ≥ 15m.
In the event of three-phase distorting loads connected in output, the current on the neutral
conductor may have a value that is 1.5 - 2 times the phase value (also for the input bypass). In this
case, size the neutral cables and the input/output protection adequately.
IOMMASGPXX01-GB_00 13
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA
r 5PJOTUBMMUIFFYUFSOBMCBDLGFFEQSPUFDUJPOJUJTOFDFTTBSZUPVTFUIF#,'DBSEBOEBOFYUFSOBMFMFDUSPNFDIBOJDBM
switch that should be installed . For further information on the connection and the type of remote switch, please
read paragraph 10.9 of this manual.
ATTENTION.
The neutral is not disconnected as, even in the event of a single fault on the UPS, it never has high po-
tential when the mains and/or auxiliary power supplies are disconnected upstream. This is to prevent
transformation of the power source to the UPS every time there is a power failure.
If, in certain anomaly states, or because of the installation upstream (e.g. undetected and protec-
ted earth fault, or high leakage in a phase, or with IT systems) there is a hazardous potential on
neutral, a suitable isolating switch must be provided on the neutral as well, or else there must be
a detection, signalling and protection system.
NOTE.
For equipment with separate Emergency Mains, the neutral of the Emergency Mains line must be electri-
cally common with the neutral of the main input feed line.
14 IOMMASGPXX01-GB_00
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA
ENGLISH
r TUSJQQJOHMFOHUINN
r UJHIUFOJOHUPSRVF
/N
Q2
Q1
Q6
3/3 Connections if
THE MAINS AND AUX MAINS ARE CONNECTED IN COMMON
L12 L22 L32 N2 L11 L1 L21 L2 L31 L3 N11 N1 +B2 -B2 -B1 +B1
L12 N1
OUTPUT L22 L3 MAINS
L32 L2
N2 L1
IOMMASGPXX01-GB_00 15
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA
3/3 Connections if
THE MAINS AND AUX MAINS ARE CONNECTED SEPARATELY
L12 L22 L32 N2 L11 L1 L21 L2 L31 L3 N11 N1 +B2 -B2 -B1 +B1
L12 N1
OUTPUT L22
L32
L3 MAINS
L2
N2 L1
L11
AUX L21
MAINS L31
N11
16 IOMMASGPXX01-GB_00
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA
3/1 Connections if
THE MAINS AND AUX MAINS ARE CONNECTED SEPARATELY
L12 L22 L32 N2 L11 L1 L21 L2 L31 L3 N11 N1 +B2 -B2 -B1 +B1
ENGLISH
OUTPUT MAINS SUPPLY EXT. BATTERY
OUTPUT L12 N1
N2 L3 MAINS
L2
L1
AUX L11
MAINS N11
IOMMASGPXX01-GB_00 17
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA
3.5-3 Divert any control cables from the front (RS232, signalling relay contacts, etc.) into the appropriate side
cable run A.
3.5-4 Remove the pre-cut detail C and bend details B to pass the cables, secure the terminal board cover with the
four screws.
3.5-5 Secure the cables to the couplings D located on the rack ensuring that the air vents are not obstructed in
any way.
3.5-7 NOTE.
*GUIFTZTUFNJTJOTUBMMFEPOBSBJTFEóPPS TVDIBTJOBEBUBQSPDFTTJOHSPPN
r MFBWFBTQBDFPGBUMFBTUDNCFUXFFOUIFQPXFSBOEUIFDPOUSPMDBCMFT
r BWPJEQBSBMMFMDIBOOFMMJOHPWFSMPOHEJTUBODFTDIPPTFDBCMFTDSPTTJOHBUJOTUFBE
A D
B C
Y EXT. BATTERY
3.5-6 3.5-7
20 cm
B
B 90°
A A
E A. Power cables
E B. Control cables
18 IOMMASGPXX01-GB_00
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA
ENGLISH
3.8 ISOLATION TRANSFORMER.
The MASTERYSTM IP model of the MASTERYSTM range is fitted with an internal isolation transformer.
If an external isolation transformer cabinet is required, the following instructions should be followed:
r 3FGFSUPDIBQUFSTBOEPGUIJTNBOVBMGPSJOEJDBUJPOTPONPWJOHBOEJOTUBMMJOHUIFDBCJOFU
r 4FFQBSBHSBQIGPSEFUBJMTBCPVUQSPUFDUJPOT
r 5IFQSPUFDUJPODBCMFNBSLFEXJUIUIFHSPVOETZNCPMJTDPOOFDUFEEJSFDUMZUPUIFEJTUSJCVUJPOQBOFM
r 5IFUSBOTGPSNFSDBOFJUIFSCFDPOOFDUFEUPUIF614JOQVUPSPVUQVU
The UPS must not operate without the neutral connection to the input.
The transformer cannot be connected to the output on single UPS unit connected in parallel con-
öHVSBUJPO
For details of the connections, refer to the transformer terminal board diagram.
IOMMASGPXX01-GB_00 19
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA
3.9.2 Installation.
UPS units operating in parallel are interconnected using control cables B ñH
BOEBSFDPOñHVSFEEJíFSFOUMZ
depending on the position they are assigned.
For this reason the units have a position label C (Fig. 3.9.4-1):
r 5IFi-&'5uMBCFMNFBOTUIBUUIFVOJUNVTUCFQPTJUJPOFEUPUIFMFGU
r 5IFi3*()5uMBCFMNFBOTUIBUUIFVOJUNVTUCFQPTJUJPOFEUPUIFSJHIU
r 5IFi*/5&3/"-uMBCFM VTFEPOMZPOTZTUFNTXJUIUISFF614
NFBOTUIBUUIJTVOJUNVTUCFQPTJUJPOFECFUXFFOUIF
two other cabinets.
The control cables supplied allow a maximum distance of about 3 metres between the UPS units. This gives enough
room for an external battery cabinet to be inserted beside each UPS.
Only activate circuit breaker D after carrying out the procedure for switching onto the mainte-
nance bypass.
20 IOMMASGPXX01-GB_00
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA
A
25 m max D
ENGLISH
C C C C C C
B
B
B
B
L B
I
I
I
I
R
E
E
E
E
E
E
x
A: 7.5 m max
F
A System input switch D Ext. bypass magneto-thermal switch I Internal UPS “INTERNAL”
B “Parallel bus” cable E Output switch L Left UPS “LEFT”
C Single UPS magneto-thermal switch (if a F System shutdown switch R Right UPS “RIGHT”
separate auxiliary power source is used, G Distribution
add a magneto-thermal switch for each H.BJOEJíFSFOUJBMNBHOFUPUIFSNBMTXJUDI
UPS)
IOMMASGPXX01-GB_00 21
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA
3.9.4-1
A
C
22 IOMMASGPXX01-GB_00
UNPACKING AND INSTALLATION
3 OF THE UNIT 10-40 kVA
If the UPS has internal batteries, connecting external battery cabinets is prohibited.
ENGLISH
t UIFTXJUDIFTVQTUSFBNPGUIF614BSFPQFO
r 3FNPWFUIFUFSNJOBMCPBSETQSPUFDUJPO
r $POOFDUUIFHSPVOEDBCMF ñHVSF
r $POOFDUUIFDBCMFTCFUXFFOUIF614UFSNJOBMTBOEUIFCBUUFSZDBCJOFUUFSNJOBMT
TUSJDUMZPCTFSWJOHUIFQPMBSJUZPG
each individual string (figure 3.10-1) and the cross-sections indicated in table 3.4.
Use double insulated cables or the cables supplied with the unit to connect the UPS to the Bat-
tery cabinet. The lenght L of battery cable must not be more than 8 metres long (if L > 8 m, please
contact the support service).
Cabling errors with inversion of the battery polarity may cause permanent damage to the equip-
ment.
r 3FQMBDFUIFUFSNJOBMCPBSETQSPUFDUJPO
If using cabinets not supplied by the manufacturers of the UPS, it is the installer’s responsibility
to check the electrical compatibility and the presence of appropriate protection devices between
the UPS and the battery cabinet (fuses and switches of sufficient capacity to protect the cables
from the UPS to the battery cabinet). As soon as the UPS is switched on (before closing the bat-
UFSZTXJUDIFT
UIFCBUUFSZQBSBNFUFSTNVTUCFWFSJöFEBDDPSEJOHMZ WPMUBHF
DBQBDJUZ
OVNCFSPG
elements, etc.) on the mimic panel menu. If the values indicated on the battery cabinet data plate
are different from those shown on the mimic panel, use the SERVICE > CONFIGURATIONS menu
to correct the settings.
3.10-1
BATTERY CABINET
+B2
+B1
–B2
–B1
EXTERNAL BATTERY
L12 L22 L32 N2 L11 L1 L21 L2 L31 L3 N11 N1 +B2 -B2 -B1 +B1
UPS
IOMMASGPXX01-GB_00 23
4 MODES OF OPERATION
10-40 kVA
The inverter is constantly synchronised in frequency with the auxiliary mains to enable load transfer (due to an
overload or inverter shutdown) without any break in the power supply to the load.
The battery charger supplies the energy required to maintain or recharge the battery.
r “Bypass” mode.
In case of inverter failure, the load is automatically transferred onto the auxiliary mains without any interruption in
the power supply. This procedure may occur in the following situations:
- in the event of a temporary overload, the inverter continues to power the load. If the condition persists, the UPS
output is switched onto the auxiliary mains via the automatic bypass. Normal operation, which is from inverter,
returns automatically a few seconds after the overload disappears.
XIFOUIFWPMUBHFHFOFSBUFECZUIFJOWFSUFSHPFTJTPVUPGUPMFSBODFTEVFUPBNBKPSPWFSMPBEPSBGBVMUPOUIF
inverter.
- wWhen the internal temperature exceeds the maximum value allowed.
r “Battery” mode.
In the event of a mains failure (micro interruptions or extended black-outs), the UPS continues to power the load
using the energy stored in the battery. The Expert Battery System keeps the user constantly informed on the
battery status and on the back-up time available. The disconnection of non mission critical applications during
battery discharge can be programmed (after a certain laps of time) by using the Power Share option, so that the
battery resources can be reserved for the most critical applications.
24 IOMMASGPXX01-GB_00
10-40 kVA
ENGLISH
If the UPS has an input for the auxiliary power supply, the Q2 switch must be connected to this input and the main
power supply input must be disconnected on the control panel.
If the maintenance bypass is activated with the appropriate procedure, the load is powered directly from the main-
UFOBODFCZQBTT
XIJMFUIF614JTTFQBSBUFEGSPNUIFQPXFSTVQQMZBOEDBOCFTXJUDIFEPí
This operating mode can be selected for maintenance to be carried out on the system so that the necessary actions
can be performed by service personnel without having to disconnect the power supply to the load.
L1 L1
Mains L2 L2
IN
L3 L3
N N
Q2
UPS
Q1
Q3
L1 L1
L2 L2
L3 L3 OUT
Load N N
L1 L1
Mains L2 L2
IN
L3 L3
N N
Q2
UPS
Q1
Q3
Lo Lo
N N OUT Q1 Bypass switch.
Load
Q2 Mains power switch.
Q3 Output switch.
IOMMASGPXX01-GB_00 25
4 MODES OF OPERATION
10-40 kVA
This mode ensures that the UPS system always operates at the highest load efficiency (40-70% of the nominal
power).
This mode can only be activated on UPS connected in parallel and operating in normal mode.
In cases of low load, the system shuts down any unnecessary UPS units, thus increasing the load on the remaining
units.
This leads to higher system efficiency, as the UPS in stand-by are not using any power, while the active units with a
high load are operating at maximum productivity.
When the load increases, the units in stand-by are immediately reactivated to guarantee continuous power supply.
Monitoring the hours of operation means that the hours are distributed on all the UPS, alternating the units that are
shut down from time to time. This prolongs the life of the units and reduces the risk of failure.
% load % load
% load % load
% load % load
26 IOMMASGPXX01-GB_00
ACCESS TO CONTROLS
5 AND COMMUNICATION INTERFACES 10-40 kVA
This chapter identifies the electromechanical switches, described below, and used for start-up, shutdown and
maintenance bypass procedures.
Access to the control area is from the front by opening the upper door 5-1
using the red handle as shown in figure 5-1. The control area also contains
the communication interface connectors and the slots for the optional sig-
nalling cards. Please refer to the relevant chapter for more details on the
connection and use of the related communication interfaces/cards.
ENGLISH
5.1 IDENTIFYING THE SWITCHES AND INTERFACES.
5.1-1
Legend.
S S1 Q1 B Internal batteries
Q2
B1 External batteries
Q6 C1 Serial connector RS232/485
C3
C2 serial connector RS232 for Modem
C3 LAN connector RJ45 for Ethernet
C1
S Mimic panel
C2 S1 Options slot 1
S2 Options slot 2
S2
Q1 Battery switch (for internal batteries)
Q2 Input circuit breaker
Q6 Output disconnecting switch (E.S.D.)
$POöHVSBUJPOXJUIDPNNPONBJOT $POöHVSBUJPOXJUITFQBSBUFNBJOT
AUX MAINS
Q2 2 Q6 Q2 2 Q6
1 1
MAINS 0 OUT MAINS 0 OUT
Q1 Q1
B B
B1 B1
IOMMASGPXX01-GB_00 27
ACCESS TO CONTROLS
5 AND COMMUNICATION INTERFACES 10-40 kVA
r Position 1 “UPS”UIJTJTUIFQPTJUJPOGPSOPSNBMPQFSBUJPOPGUIF614GPSBDPOUJOVPVTQPXFSTVQQMZUPUIFMPBE
r Position 2 “MANUAL BY-PASS”: This position should only be selected for ordinary or extraordinary maintenance
PQFSBUJPOT NBOVBMCZQBTT
UIFMPBEJTDPOOFDUFEEJSFDUMZUPUIFNBJOTQPXFSTVQQMZ*UNBZCFVTFEJOUIFFWFOU
of a UPS failure to power applications from the auxiliary mains while awaiting the intervention of technical person-
OFM
r Position 0 “OFF”: This completely isolates the UPS output by removing the voltage from the applications in any
operating condition. It is used for the emergency shutdown of the system (internal E.S.D.).
Battery switch Q1 (UPS batteries).
When closed, this switch connects the batteries of the UPS to the DC/DC converter stage to power the inverter in
the event of a mains failure. The normal operating position is 1 (closed).
28 IOMMASGPXX01-GB_00
6 MIMIC PANEL
10-40 kVA
B. NVMUJDPMPVSFEMVNJOPVTCBSUIBUJEFOUJñFTUIFDPOEJUJPOPGUIFQPXFSTVQQMZUPUIFMPBE
C. alphanumeric information that uses a menu layout to provide details on any alarms that may occur and on the
ENGLISH
measurements, controls and parameters.
6.1-1
D
B
IOMMASGPXX01-GB_00 29
6 MIMIC PANEL
10-40 kVA
6.1.1-1
M18
M19
M20
ITALIANO
ENGLISH
M3 M21
M4
M22
M5 M28
M23
M24 M27
M6 M25 M26
M7
M1
M2 M8 M9
M30
M10 M11
M29 M31
M12 M13 M14 M15 M16 M17
30 IOMMASGPXX01-GB_00
6 MIMIC PANEL
10-40 kVA
Meaning of ideograms
Code Description Condition
M1 Load on bypass, in Eco-mode or Maintenance bypass closed Steady
Automatic bypass alarm Flashing
M2 Input rectifier active. Steady
Input rectifier general alarm. Flashing
M3 Battery OK. Steady
Battery alarm. Flashing
M4-M7 Remaining battery capacity. Steps of 25%
Battery recharging. Sequence M7 M4
ENGLISH
M8 Inverter on Steady
Inverter general alarm. Flashing
M9 Output voltage present. Steady
M10 Input mains OK. Steady
Input mains alarm. Flashing
M11 Inverter on. Steady
M12 Module 1 present. Steady
Module 1 general alarm. Flashing
M13 Module 2 present. Steady
Module 2 general alarm. Flashing
M14 Module 3 present. Steady
Module 3 general alarm. Flashing
M15 Module 4 present. Steady
Module 4 general alarm. Flashing
M16 Module 5 present. Steady
Module 5 general alarm. Flashing
M17 Module 6 present. Steady
Module 6 general alarm. Flashing
M18 Load present. Steady
Overload. Flashing
M19-M28 Output load indicator. Steps of 10%
M29 Periodic maintenance alarm/warning. Flashing
M30 Activation code alarm. Steady
General alarm. Flashing
M31 LAN connection ready (Cable Connected). Steady
IOMMASGPXX01-GB_00 31
6 MIMIC PANEL
10-40 kVA
YELLOW Warning for preventive maintenance according to conditions of use (type of load, temperature),
BGUFSPWFSIPVSTPGPQFSBUJPO .óBTIJOH
:&--08 -PBEPOCBUUFSZPSCBUUFSZEJTDIBSHJOHJG.JTPOTUFBEZBOE.JTPí
YELLOW On automatic bypass if M1 is on steady
YELLOW First maintenance period expired (10,000 hours of operation) UPS in maintenance mode
(3&&/óBTIJOH #BUUFSZUFTUJOQSPHSFTT
GREEN Load powered from inverter or in high efficiency mod
6.1.3-1
Legend.
A Current menu
B Active sub menu
C Additional values or information
A D Scrolling contextual help line
B E Scroll bar
F F Statistical graphics display
C E
D D
32 IOMMASGPXX01-GB_00
6 MIMIC PANEL
10-40 kVA
Parallel UPS
Single UPS
ENGLISH
2.2 STATISTICS
5.2 SETTING
MODULE 5
MODULE 6
IOMMASGPXX01-GB_00 33
6 MIMIC PANEL
10-40 kVA
exceeded.
A07 OVER TEMPERATURE Temperature excessive or ventilation problems.
A08 MAINTENANCE BYPASS ACTIVE Q6 in position 2.
A17 IMPROPER CONDITION OF USE Improper conditions of use verified (load, mains, and temperature).
A18 BLOCKING INVERTER FOR OVERLOAD Inverter shutdown due to overload.
" 830/($0/'*(63"5*0/ &SSPSJOUIFDPOñHVSBUJPOQBSBNFUFST FHEJíFSFOUQBSBNFUFST
between several UPSs in parallel).
A22 INPUT MAINS OUT OF TOLERANCE The voltage or frequency limits accepted by the rectifier have been
exceeded.
A23 RECTIFIER GENERAL ALARM Rectifier fault.
A25 INVERTER GENERAL ALARM Inverter fault.
A26 BATTERY CHARGER GENERAL ALARM Battery charger fault.
A29 BYPASS GENERAL ALARM Bypass fault.
A30 STOP FOR OVERLOAD The duration of the overload has inhibited the bypass.
A32 MODULE 1 GENERAL ALARM Module 1 failure.
A33 MODULE 2 GENERAL ALARM Module 2 failure.
A34 MODULE 3 GENERAL ALARM Module 3 failure.
A35 MODULE 4 GENERAL ALARM Module 4 failure.
A36 MODULE 5 GENERAL ALARM Module 5 failure.
A37 MODULE 6 GENERAL ALARM Module 6 failure.
A38 EXTERNAL ALARM 1 Signalling from ADC input.
A39 EXTERNAL ALARM 2 Signalling from ADC input.
A40 EXTERNAL ALARM 3 Signalling from ADC input.
A41 EXTERNAL ALARM 4 Signalling from ADC input.
A42 E-SERVICE GENERAL ALARM Alarm that generates automatic sending of a signal to the support
centre (if the service has been activated).
A43 REDUNDANCY LOST The power required by the load no longer allows the preset
SFEVOEBODZ/YUPCFNBJOUBJOFE GPS614TJOQBSBMMFMPOMZ
A44 PERIODIC SERVICE CHECK-UP Warning for periodic check by support service.
A47 MAX BATTERY TEMPERATURE Control of the temperature of battery cabinet.
A49 BATTERY DISCHARGED The energy available in the battery has been used up.
A51 OPTION BOARD GENERAL ALARM Fault related to the optional PCBs in the slots.
A56 GENERATOR SET GENERAL ALARM Minor alarm on generator set.
" (&/&3"5034&5'"6-5 .BKPSBMBSNPOHFOFSBUPSTFU
A58 ESD ACTIVATED The remote emergency shutdown command has been activated.
A59 BATTERY CIRCUIT OPEN The battery switch is open.
A60 FAN FAILURE Fans faulty or blocked.
A61 PHASE ROTATION FAULT Wrong phase cycle direction.
34 IOMMASGPXX01-GB_00
6 MIMIC PANEL
10-40 kVA
ENGLISH
OUT APPARENT POWER __._ kVA __._ kVA __._ kVA
OUTPUT CURRENT __._ A __._ A __._ A
OUTPUT FREQUENCY __._ Hz
AUXILIARY VOLTAGE ___ V ___ V ___ V
AUXILIARY FREQUENCY __._ Hz
INPUT STAR VOLTAGE ___ V ___ V ___ V
INPUT PH-PH VOLTAGE ___ V ___ V ___ V
INPUT FREQUENCY __._ Hz
INPUT APPARENT POWER __._ kVA __._ kVA __._ kVA
BATTERY VOLTAGE B1___ V B2___ V
CAPACITY __ % CHARGING
BACKUP T___MIN DISCHARGING
*/5&3/"-5&.1&3"563& @@$
BATTERY TEMPERATURE @@$ 0OMZXJUIBTFOTPSQSFTFOUBOETFU
IOMMASGPXX01-GB_00 35
6 MIMIC PANEL
10-40 kVA
36 IOMMASGPXX01-GB_00
6 MIMIC PANEL
10-40 kVA
ENGLISH
LAN SINOTTICO MAC ADDRESS Identifie the mac addres of LAN PCB.
XX . XX . XX . XX . XX . XX
FW X.XX
SCHEDA DIGITALE Identifie the micro prosessor software version.
UP RV 000 CKS: 0000 Identifie the mac addres of LAN PCB.
DSP RV 000 CKS: 0000
When contact is made with the Support Centre for the activation code, detailed information can be obtained on the
UPS functions available and on the periodic preventive maintenance programmes.
Once the code is obtained, enter it by pressing ENTER to activate the entry (two asterisks will appear). Select the
first character with the UP and DOWN keys and confirm with ENTER to accept the character. Then move
on to the next character. Pressing the ENTER key after selecting the fourth character activates code.
SEE INSTALLATION MANUAL
FOR PROCEDURE
CODE = - - - - **
An error message is displayed if the code is incorrect. Check that the code displayed corresponds to the one pro-
vided by the Support Centre and repeat the procedure.
IOMMASGPXX01-GB_00 37
6 MIMIC PANEL
10-40 kVA
i$POöHVSBUJPOTwNFOV
This is used to change the configuration parameters.
Press ENTER. Access is via the password MAST which is keyed in by using the UP and DOWN keys and
ENTER to go on to the next letter.
Note.
Column A shows whether the parameter is visible in the PARAMETERS “CONFIGURATIONS” menu.
CONFIGURATIONS menu
A Parameter Description Allowed values
ITALIANO
ENGLISH
in a branch.
r #"55&3:3&$)"3(& *OEJDBUFTUIFNBJOUFOBODFWPMUBHFWBMVFQFSDFMM
GPS/J$E
FLOATING VOLTAGE
r #"55&3:3&$)"3(& *OEJDBUFTUIFTFDPOEMFWFMSFDIBSHFWPMUBHFWBMVF
GPS/J$E
LEVEL TWO VOLTAGE
r #"55&3:3&$)"3(& *OEJDBUFTUIFDVSSFOUUISFTIPMEJOPG$UPQBTT
FLOATING RECHARGE from maintenance voltage to recharge voltage.
r #"55&3:3&$)"3(& *OEJDBUFTUIFDVSSFOUUISFTIPMEJOPG$UPQBTT
RECHARGE FLOATING from recharge voltage to maintenance voltage (<!).
r #"55&3:3&$)"3(& *OEJDBUFTUIFCBUUFSZDPNNJTTJPOJOHWPMUBHF
GPS/J$E
FORMING VOLTAGE value (>!).
38 IOMMASGPXX01-GB_00
6 MIMIC PANEL
10-40 kVA
CONFIGURATIONS menu
A Parameter Description Allowed values
ENGLISH
r #"$,'&&%5:1& 4FUTUIFUZQFPGCBDLGFFEQSPUFDUJPO %*4"#-&
1. BYPASS
2. BYPASS-INPUT ALONE
3. BYPASS-INPUT COMMON
r #"55&3:5&45 4FUTUIFGSFRVFODZSBUFPGUIFCBUUFSZUFTUJOEBZT
TEST EVERY XX DAYS (zero = do not perform the test).
r 108&34)"3&1-6(5:1& 4FMFDUTUIFDPOñHVSBUPOPGQPXFSTIBSFSFRVJSFE 45"/%"3%
(see paragraph 10.5). EMERGENCY LIGHTING
REMAINING TIME
RESIDUAL CAPACITY
r POWER SHARE PLUG1 VALUE Sets the required intervention value
(minutes for remaining time and Ah for capacity) (optional).
r 108&34)"3&1-6(5:1& "TQMVHUZQF PQUJPOBM
r POWER SHARE PLUG2 VALUE As plug1 value (optional).
r 4&3*"--*/,#"6%3"5& *OTFSUTUIFTFSJBMDPNNVOJDBUJPOQBSBNFUFST
r 4&3*"--*/,1"3*5: *OTFSUTUIFTFSJBMDPNNVOJDBUJPOQBSBNFUFST PEEFWFOOPOF
r -"/*145"5*$0 4FUTUIFTUBUJD*1BEESFTTPGUIF-"/
XXX . XXX . XXX .XXX
r 4&3*"--*/,+#64 4FUTUIFNJNJDQBOFMKCVTOPEF
SLAVE NUMBER
DATE AND TIME Sets the date and time DD/MM/YY HH:MM
r &95&/%&%$0.."/% &OBCMFT%JTBCMFTUIFNJNJDQBOFMFYUFOEFEDPNNBOET :&4/0
r 3&.05&$0.."/% &OBCMFTEJTBCMFTUIFSFNPUFDPOUSPMT :&4/0
BUZZER Enables/Disables the buzzer YES/NO
LCD CONTRAST Sets the LCD display contrast 0/100
r 45"5*45*$41&3*0% *OEJDBUFTUIFUJNFJOXFFLTGPSUIFDBMDVMBUJPOPGTUBUJTUJDT
r (445*.&%&-": 4FUTUIFHFOFSBUPSTUBSUVQEFMBZUJNF WJTJCMFPOMZXIFO .*/65&4
the GSS PCB is installed)
E-SERVICE TYPE Select e-service operating mode NONE, MODEM, SMS
E-SERVICE TELEPHONE NUMBER Insert the phone number to call for e-service messages MAX 20 CHARACTERS
AUX TRANSFORMER VOLTAGE Set the auxiliary voltage measure with transformer SETTABLE ONLY BY
AFTER SALE SERVICES
INPUT TRANSFORMER VOLTAGE Set the input voltage measure with transformer SETTABLE ONLY BY
AFTER SALE SERVICES
IOMMASGPXX01-GB_00 39
6 MIMIC PANEL
10-40 kVA
6.1.3.6-1
Legend.
A B A Shows date and time of event.
B Shows the event code.
C Describes the event.
D ON/OFF status of event.
E Progressive number of event.
C E
40 IOMMASGPXX01-GB_00
6 MIMIC PANEL
10-40 kVA
ENGLISH
IOMMASGPXX01-GB_00 41
7 OPERATING PROCEDURES
10-40 kVA
The operating modes to activate and manage the UPS are defined 7.1
in this chapter; please also refer to chapters 6 “Mimic panel” and 8 Q1 Q2
“Menus”. Q6
45"3561*//03."-.0%&
t 4VQQMZUIFNBJOTBOEBVYJMJBSZNBJOTUPUIF614
t 1VUTXJUDIQ2 into position 1 (mains ON);
t 8BJUGPSUIFNJNJDQBOFMUPTXJUDIPO
t "DUJWBUFUIFQSPDFEVSFCOMMANDS > IMMEDIATE COMMANDS > START PROCEDURE;
t $BSSZPVUUIFPQFSBUJPOTJOEJDBUFEPOUIFNJNJDQBOFM
4)65%08/
4IVUEPXOJOUFSSVQUTUIFQPXFSTVQQMZUPUIFMPBEBOEDBVTFTUIF614BOEUIFCBUUFSZDIBSHFSUPTUPQ
t "DUJWBUFUIFQSPDFEVSFCOMMANDS > IMMEDIATE COMMANDS > STOP PROCEDURE;
t 8BJUBQQSPYNJOVUFTGPSUIF614UPTIVUEPXO UIFDPOUSPMMFETIVUEPXOPGBOZTFSWFSTJTNBOBHFEXJUI
TIVUEPXOTPGUXBSF
t $BSSZPVUUIFPQFSBUJPOTJOEJDBUFEPOUIFNJNJDQBOFM
&95&/%&%0650'4&37*$&
*GUIF614JTEFBDUJWBUFEGPSTPNFUJNF
UIFCBUUFSJFTNVTUCFSFDIBSHFESFHVMBSMZUIFZTIPVMECFSFDIBSHFE
FWFSZUISFFNPOUIT
t 4VQQMZUIFNBJOTBOEBVYJMJBSZNBJOTUPUIF614
t 1VUTXJUDIQ2 into position 1 (mains ON);
t 8BJUGPSUIFNJNJDQBOFMUPTXJUDIPO
t "DUJWBUFUIFQSPDFEVSFCOMMANDS > IMMEDIATE COMMANDS > START PROCEDURE;
t 1VUUIFFYUFSOBMCBUUFSZEJTDPOOFDUPSTJOUPQPTJUJPO CBUUFSZDJSDVJUDMPTFE
t 1VUPSLFFQTXJUDIFTQ3 and Q5 in position 0 JOWFSUFSJOPVUQVU0''BOECZQBTT0''
t 5IFCBUUFSZNVTUCFDIBSHFEGPSBUMFBTUUFOIPVST
t 0ODFUFOIPVSTIBWFFMBQTFE
DBSSZPVUUIFSTOP PROCEDURE to deactivate the UPS.
42 IOMMASGPXX01-GB_00
7 OPERATING PROCEDURES
10-40 kVA
48*5$)*/(0/50."/6"-#:1"44
4XJUDIJOHPOUPUIFNBOVBMCZQBTTDSFBUFTBEJSFDUDPOOFDUJPOCFUXFFOUIF614JOQVUBOEPVUQVU
DPNQMFUFMZ
FYDMVEJOHUIFFRVJQNFOUDPOUSPMQBSU5IJTPQFSBUJPOJTQFSGPSNFEJOUIFFWFOUPGPSEJOBSZNBJOUFOBODFPO
UIFFRVJQNFOU
TPBTOPUUPSFNPWFUIFQPXFSTVQQMZGSPNUIFMPBE
PSJOUIFFWFOUPGBTFSJPVTGBJMVSFXIJMF
XBJUJOHGPSUIFFRVJQNFOUUPCFSFQBJSFE
t "DUJWBUFUIFQSPDFEVSFCOMMANDS > IMMEDIATE COMMANDS > BYPASS PROCEDURE;
t $BSSZPVUUIFPQFSBUJPOTJOEJDBUFEPOUIFNJNJDQBOFM
*GUIFSFJTBOFYUFSOBMNBOVBMCZQBTT DBSSZPVUUIFQSPDFEVSFEFTDSJCFEBCPWFCFGPSFBDUJWBU
ENGLISH
JOHUIJTTXJUDI
3&563/50/03."-.0%&
t 1VUTXJUDIQ2 into position 1 (mains ON);
t 8BJUGPSUIFNJNJDQBOFMUPTXJUDIPO
t "DUJWBUFUIFQSPDFEVSFCOMMANDS > IMMEDIATE COMMANDS > START PROCEDURE;
t $BSSZPVUUIFPQFSBUJPOTJOEJDBUFEPOUIFNJNJDQBOFM
*GUIFSFJTBOFYUFSOBMNBOVBMCZQBTT QVUUIFTXJUDIUPQPTJUJPO0''
&.&3(&/$:4)65%08/ &4%
4IPVMEJUCFOFDFTTBSZUPJOUFSSVQUUIFDPOUJOVPVTQPXFSTVQQMZQSPWJEFECZUIF614RVJDLMZ FNFSHFODZTIVU-
EPXO
UIJTDBOCFEPOFCZQVUUJOHTXJUDIQ3 to position 0PS
XIFSFBQQMJDBCMF
CZBDUJWBUJOHUIFFNFSHFODZ
CVUUPOTXJUDIDPOOFDUFEUPUIFADC PCB.
5IF614PVUQVUDBOPOMZCFFMFDUSJDBMMZEJTDPOOFDUFECZNFBOTPG2
*GUIF614JTPQFSBUJOHGSPNUIFNBOVBMCZQBTT 2JOQPTJUJPO
XJUINBJOTQSFTFOU
UIFFNFS
HFODZTIVUEPXOEPFTOPUJOUFSSVQUUIFQPXFSTVQQMZUPUIFMPBE*OFNFSHFODZDPOEJUJPOTBMM
UIFQPXFSTVQQMJFTVQTUSFBNPGUIF614NVTUCFEJTDPOOFDUFE
IOMMASGPXX01-GB_00 43
8 COMMUNICATION
10-40 kVA
5 4 3 2 1
Slot 1 Slot 2 RS 232/485 RS 232 RJ45 10BT
ADC card r r
GSS card r r 9 8 7 6
NetVision card r2
r2
UniVision pro r r4
Legend pin RS232/485 C1 Legend pin Modem C2
Remote Panel r 1 Not connected 1 Reserved
BMS r
1
r1
r4 2 RX for RS232 2 RX for RS232
Modem r 3 3 TX for RS232 3 TX for RS232
LAN (ethernet) r 4 %BUB
5 GND for RS232
4 Reserved
5 GND for RS232
1
Building Management System. 6 Data − 6 Not connected
2
Ethernet adapter with Web/SNMP 10/100Mb functions 7 Reserved 7 RTS
(E-service via Web required). 8 Not connected 8 CTS
3
For T-service via telephone network. 9 7 9 7
4
#ZKCVTUVOOFMMJOHPO5$1*1
"TFBDIDIBOOFMJTJOEFQFOEFOU
TJNVMUBOFPVTDPOOFDUJPOTDBOCFNBEFUPTBUJTGZUIFEJíFSFOUMFWFMTPGTJHOBMMJOH
and remote monitoring.
See the options paragraph to access the detailed functions of the PCBs installed in the slots.
Please note that two Net Vision cards or two GSS cards cannot be connected simultaneously.
44 IOMMASGPXX01-GB_00
8 COMMUNICATION
10-40 kVA
8.2.1 Activation.
Comply with the following operations to activate the monitoring system:
r $POOFDUUIF614UPUIF-"/OFUXPSL DPOOFDUPSC3 in Fig. 8.2.1-1).
8.2.1-1
ENGLISH
C3
A. If the BOOT DHCP protocol is enabled in the local network: verify the IP address shown in the PARAMETERS >
PRESENT CONFIG > LOCAL AREA NETWORK IP menu on the UPS mimic panel (go to point C).
IOMMASGPXX01-GB_00 45
8 COMMUNICATION
10-40 kVA
8.2.2-1
A
B C
Legend.
A Navigation bar.
B Menu bar.
C system information area.
46 IOMMASGPXX01-GB_00
8 COMMUNICATION
10-40 kVA
ENGLISH
Alarm present: shows the alarms table (this icon appears when the UPS detects an anomaly).
Generator operating mode (this icon appears when the UPS is powered by the generator).
Technical support department e-mail address. This connection opens the e-mail program and automati-
DBMMZñMMTJOUIFBEESFTTFFBOETVCKFDUMJOFT
8.2.2.4 Statistics.
The counter folder shows the number of events that have occurred over a given period of time.
The average minimum and maximum values of a measurement can be seen by clicking on the measurement folder.
A sampling time from one to 10 weeks can be set by clicking on the period folder.
IOMMASGPXX01-GB_00 47
8 COMMUNICATION
10-40 kVA
r Client JBUS IP address to be authorised: if a specific IP address is inserted in this box, then only that address/
user will be able to access the html pages. If the address 0.0.0.0 is used, all the PCs on the network will be able to
access the supervisor (one client at a time). If the address 255.255.255.255 is inserted, access will be denied to all
users.
r Software updating: if on, allows the supervisor to be updated.
r Page refresh (sec): the page refresh rate can be set.
r Installation: text string used to describe the UPS installation site, which is useful if there are more than one unit
connected (this value is inserted in SMS messages or e-mails).
r NTP Server: indicates the IP address of the time server to automatically update the date and time on the system.
r GMT Correction (minutes):JOEJDBUFTMPDBMUJNFBOEUIFPíTFUJONJOVUFTXJUISFTQFDUUPUIF[FSPNFSJEJBOPG
Greenwich
r Apply the parameter settings: restarts the monitoring system with the new settings.
$POöHVSJOHFNBJM
This menu lets the user configure parameters for sending e-mails.
r Event that will send an e-mail: as required, the e-mail may be deactivated or activated to send a message in the
event of serious alarms or for all alarm conditions.
r E-mail server address: insert the IP address (xxx.xxx.xxx.xxx) of the SMTP e-mail server from which you wish to
send messages.
r e-mail account: Insert the UPS’s dedicated “user account”, which is often the same as the user’s e-mail address.
r Addressee: insert the e-mail address to which the alarm messages will be sent.
r Periodic connection: set the frequency at which an e-mail is to be sent to verify the connection.
r Force an e-mail to be sent now: by selecting “execute” a test e-mail will be sent.
48 IOMMASGPXX01-GB_00
8 COMMUNICATION
10-40 kVA
8.2.2.9 .PEFNDPOöHVSBUJPO.
This menu lets the user configure the parameters of a modem
r Rings before reply: Set the number of rings after which the modem should respond.
r Outgoing call1: sets the type of outgoing call: SMS or E- service (to activate e-service a contract to the support
centre is required).
r Reason for callout: set the reasons for the call (all alarms or for serious faults).
r Installation: text string used to describe the UPS installation site, which is useful if there are more than one unit
connected (this value is inserted in SMS messages or e-mails).
r Telephone number: insert the number to be called.
ENGLISH
r Modem initialisation: initial string to be sent to the modem (for special configurations or certain types of mo-
dem).
r Connection period: set the number of days between two calls even if no faults occur.
r Force an outgoing call: by selecting EXECUTE a test connection is immediately carried out.
"DUJWBUJOHPOFDPOñHVSBUJPOFYDMVEFTUIFPUIFSUIFSFGPSFJGBO&TFSWJDF5TFSWJDFDPOUSBDUJTTVCTDSJCFE
DBMMTJOPVUQVUDBOOPUCFDPOñHVSFE
2 In the event that the E-service/T-service contains the control code provided by after-sales personnel.
IOMMASGPXX01-GB_00 49
8 COMMUNICATION
10-40 kVA
r (SBQIJDNPOJUPSJOHPGUIF614WJBXFCCSPXTFS
r -PDBMTIVUEPXOPGBTFSWFSDPOOFDUFEWJBTFSJBMJOUFSGBDF
r 3FNPUFTIVUEPXOWJBQSPYZBHFOUBOEPQUJPOBM+BWBTIVUEPXODMJFOUT
r /PUJñDBUJPOPGBOPNBMJFTWJBFNBJMUPBNBYJNVNPGBEESFTTF
NET VISION is a solution for managing UPS units connected directly to the local
network. It is normally used on medium/large, complex networks and in multi-
server environments where the IT manager centrally controls all the network re-
sources. The physical position of the UPS is not significant.
The main functions are:
r .C&UIFSOFUDPOOFDUJPO 3+
r (SBQIJDNPOJUPSJOHPGUIF614WJBXFCCSPXTFS
r 3FNPUFTIVUEPXOPGVQUPDPNQVUFST
r /PUJñDBUJPOPGBOPNBMJFTWJBFNBJMUPBNBYJNVNPGBEESFTTFT
r 614NBOBHFNFOUVTJOH4/.1QSPUPDPM
r %JBHOPTUJDTWJB*OUFSOFUPíFSFECZF4FSWJDF
Java & .NET shutdown Client (JNC) is an optional Java application to be installed
on a server for the automatic shutdown of the computers on the network before
the UPS stops due critical operating conditions (imminent battery failure, overload,
etc.). It is supplied as an option and can be associated to the UNI VISION PRO or NET
VISION communication solutions.
The main features/functions are:
r 6TFPGUIF5$1*1TUBOEBSEOFUXPSLQSPUPDPM
r (SBQIJDTJOUFSGBDFGPSFBTZDPOñHVSBUJPO
r .JOJNVNVTFPG$16SFTPVSDFT
r 1FSTPOBMJTBUJPOPGTIVUEPXOQBSBNFUFSTBOETDSJQU
r $POUJOVPVTNPOJUPSJOHPGUIFFîDJFODZPGUIFDPOOFDUJPOUPUIF614
50 IOMMASGPXX01-GB_00
8 COMMUNICATION
10-40 kVA
ENGLISH
motely by the Service Centre, with immediate intervention on site if needed.
IOMMASGPXX01-GB_00 51
9 PROBLEM SOLVING
10-40 kVA
r )JHIOVNCFSPGPWFSMPBET XSPOHTJ[JOH
r $POUJOVPVTCBUUFSZEJTDIBSHJOH NBJOTOPUTUBCMF
r )JHIOVNCFSPGTXJUDIFTPOUPUIFCZQBTT IJHIJNQVMTJWFMPBET
t "JOQVUNBJOTPVUPGUPMFSBODF
The input mains is not present or not sufficient (voltage and/or frequency values incorrect with reference to the
UFDIOJDBMEBUB
JGUIFSFJTOPJOQVUNBJOTPVUBHF
DIFDLJGOPQSPUFDUJPOTVQTUSFBNPGUIF614IBWFUSJQQFE
Check that the voltage applied and frequency values are in compliance with the values set on the mimic panel.
t "
"
"
"FYUFSOBMBMBSN
0OFPGUIF"%$1$#JOQVUTIBTCFFOBDUJWBUFEDIFDLUIFTJUVBUJPOPGUIFEFWJDFTDPOOFDUFEUPUIJT1$#
t "
"HFOFSBUPSHFOFSBMBMBSN
5IFHFOFSBUPSIBTTFOUBOBMBSNDIFDLEJSFDUMZPOUIF(&
52 IOMMASGPXX01-GB_00
9 PROBLEM SOLVING
10-40 kVA
t "XSPOHQIBTFDZDMFEJSFDUJPO
The phase cycle sequence is incorrect. In this case, invert two phases of the input mains. For a UPS with separate
auxiliary mains, exchange the two phases of the auxiliary mains only.
ENGLISH
t "XSPOHDPOöHVSBUJPO
&SSPSJOUIFDPOñHVSBUJPOQBSBNFUFSTQMFBTFDPOUBDUUIFTVQQPSUTFSWJDF
t "CMPDLEVFUPPWFSMPBE
Reduce the load rate applied to the UPS and reset the alarms.
t "54FSWJDFHFOFSBMBMBSN
5IF."45&3:4QSPEVDUTDBOCFSFNPUFMZTFSWJDFE5IJTBMBSNJOEJDBUFTUIBUBQSPDFEVSFGPSBOBMZTJOHUIF614
failure has been activated by the support centre (if an e-service contract has been concluded).
t "QSPHSBNNFEDPOUSPM
The equipment has to undergo periodic checks by the support service in order to ensure optimum perform-
ance and efficiency. If the “Programmed Control” signal appears on the mimic panel, the equipment should be
inspected by an adequately trained technician.
t "CBUUFSZDJSDVJUPQFO
Battery switch open.
t "GBOGBJMVSF
'BVMUJOUIFWFOUJMBUJPOTZTUFNDIFDLUIBUUIFBJSJOMFUBUUIFGSPOUBOEUIFBJSPVUMFUBUUIFCBDLPGUIF614BSFOPU
obstructed.
IOMMASGPXX01-GB_00 53
9 PROBLEM SOLVING
10-40 kVA
."45&3:4
JOPSEFSUPPíFSPQUJNVNPQFSBUJOHFîDJFODZBOEBWPJEEPXOUJNFPGUIFFRVJQNFOU
It is strongly recommended to give due consideration to any requests for preventive maintenance automatically
displayed with alarm message M29 (refer to paragraph 6.2.3.1).
All operations on the equipment must be only carried out by SOCOMEC UPS personnel or by authorised support
personnel.
Maintenance consists of accurate functional checks on electronic and mechanical parts with replacement of parts
TVCKFDUUPXFBSJGOFDFTTBSZ UZQJDBMMZCBUUFSJFT
GBOTBOEDBQBDJUPST
9.3.1 Batteries.
ITALIANO
ENGLISH
9.3.2 Fans.
The life of the fans used to cool the power parts is dependent on the using and environmental conditions (tem-
perature, dust).
Preventive replacement by an authorised technician is recommended within four years (in normal operating condi-
tions).
8IFOOFFEFE GBOTTIPVMECFSFQMBDFEBTQFSTQFDJöDBUJPOTCZ40$0.&$614
9.3.3 Capacitors.
The equipment houses electrolytic capacitors (used in the rectifier and inverter section) and filtering capacitors
(used in the output section), whose life is dependent on using and environmental conditions.
The average expected life of these components is shown below:
r &MFDUSPMZUJDDBQBDJUPSTZFBST
r 'JMUFSJOHDBQBDJUPSTZFBST
*OBOZDBTFUIFFíFDUJWFTUBUFPGUIFDPNQPOFOUTJTWFSJñFEEVSJOHQSFWFOUJWFNBJOUFOBODF
54 IOMMASGPXX01-GB_00
10 OPTIONS
10-40 kVA
10-1
Legend.
S1 C1 Serial connector RS232/485
C2 serial connector RS232 for Modem
C3 LAN connector RJ45 for Ethernet
C3
S1 Options slot 1
S2 Options slot 2
C1
C2
ENGLISH
S2
IOMMASGPXX01-GB_00 55
10 OPTIONS
10-40 kVA
56 IOMMASGPXX01-GB_00
10 OPTIONS
10-40 kVA
10.8.1-1 UPS 3/3 with separate auxiliary supply. 10.8.1-2 UPS 3/1 with separate auxiliary supply.
A UPS A UPS
ENGLISH
Q1 T1 M1 Q1 T1 M1
L1 L1 L1 L1
L2 L2 L2 L2
L3 L3 L3 L3
N N N N
B B
Q2 T2 M2 Q2 T2 M2
L11 L11
L21 L21
L31 L31 L11 L11
N1 N1 N1 N1
B B
XB1 XB1
BKF card BKF card
XB2 XB2
Legend. 1
Remote switches - rated current
A Distribution panel
B Coil remote switch Model T1 T2
L1-L2-L3-N Input power source 10 3/1 32 A AC1 45 A AC1
L11-L21-L31-N1 Backup power source 15 3/1 32 A AC1 45 A AC1
M1 Input power terminal board 20 3/1 45 A AC1 60 A AC1
M2 Backup power terminal board
10 3/3 32 A AC1 32 A AC1
T1 Remote switch1
T2 Remote switch1
15 3/3 32 A AC1 32 A AC1
Q1 Input power switch 20 3/3 45 A AC1 45 A AC1
Q2 Backup power switch 30 3/3 60 A AC1 60 A AC1
XB1 Connector on BKF PCB 40 3/3 90 A AC1 90 A AC1
XB2 Connector on BKF PCB
IOMMASGPXX01-GB_00 57
10 OPTIONS
10-40 kVA
Diagram of principle.
1
10.8.2-1 UPS 3/3 without separate auxiliary supply. Remote switches - rated current
Model T1
A UPS 10 3/1 32 A AC1
Q1 T1 M1
15 3/1 32 A AC1
ITALIANO
ENGLISH
L1 L1
L2 L2 20 3/1 45 A AC1
L3 L3 10 3/3 32 A AC1
N N 15 3/3 32 A AC1
B
20 3/3 45 A AC1
30 3/3 60 A AC1
XB1
BKF card
40 3/3 90 A AC1
Legend.
A Distribution panel Q1 Input power switch
B Coil remote switch T1 Remote switch1
L1-L2-L3-N Input power source XB1 Connector on BKF PCB
M1 Input power terminal board
Attention.
The neutral on the input or the output of the UPS are identical. Consequently there is no risk of high potential when
the input power supply is absent.
However, depending on the type of system connected in the output or in some failure conditions (earth leakage,
significant phase dispersion or in case of non-isolated neutral system), high potential can be detected. It will there-
fore be necessary to install either adequate neutral switching or protection system.
58 IOMMASGPXX01-GB_00
10 OPTIONS
10-40 kVA
10.10 PROFIBUS.
On request, the UPS can be provided with a Profibus protocol converter, installation software, configuration softwa-
re and user manuals. If the RS232/485 serial connector is installed on the mimic panel, it should be disabled.
ENGLISH
10.11 GSM MODEM.
Enables sending of SMS messages regarding the equipment’s operating status.
IOMMASGPXX01-GB_00 59
11 TECHNICAL SPECIFICATIONS
10-40 kVA
Models
10 15 20 30 40
Input/Output phases 3/1 and 3/3 3/1 and 3/3 3/1 and 3/3 3/3 3/3
&MFDUSJDBMTQFDJöDBUJPOT*OQVU
10 15 20 30 40
.BJOTWPMUBHF 1/7 VQUP!PGOPNJOBMMPBE
Input frequency 50-60 Hz ±10%
ITALIANO
ENGLISH
&MFDUSJDBMTQFDJöDBUJPOT0VUQVU
10 15 20 30 40
Output voltage UISFFQIBTFOFVUSBM
230 V single phase (selectable: 208*/220/230/240 V) ±1%
400 V three phase (selectable 360*/380/400/415 V) ±1%
Frequency 50-60 Hz ±2% (from 1% to 8% if generator is used)
Automatic bypass nominal output voltage ±15%
(from 10% to 20% selectable if generator is used)
Nominal power (kW) 9 13,5 18 27 36
Overload on mains power supply 125% 10 minutes
150% 1 minute
Crest factor 3:1
Voltage distortion 1% with linear load
!1PVU1OPN
Environment
10 15 20 30 40
0QFSBUJOHUFNQFSBUVSF $ $SFDPNNFOEFEGPSMPOHFSCBUUFSZMJGF
4UPSBHFUFNQFSBUVSF $
3FMBUJWFIVNJEJUZ DPOEFOTBUJPOGSFF
.BYBMUJUVEF N GU
XJUIPVUEFSBUJOHN GU
NBY
Acoustic noise (dB) < 52 < 52 < 52 < 55 < 55
Required cooling capacity (m3/h) 280 280 280 465 465
Dissipated power max (W) 680 900 1150 1750 2300
Dissipated power (BTU/h) 2300 3050 4070 6050 7900
Standards
10 15 20 30 40
Safety (TÜV certified) EN 62040-1-1, EN 60950-1
Type and performance EN 62040-3 (VFI-SS-111)
EMC EN 62040-2
Product certification
Protection level IP20 (compliant with 60529), IP21 on request
60 IOMMASGPXX01-GB_00
11 TECHNICAL SPECIFICATIONS
10-40 kVA
1.400
1.000
ENGLISH
800
795 795 795
444 444 444
WEIGHT