Tebevert Iii Modular 5-25 Kva Inverter System: Key Features

The document describes a modular inverter system called the TEBEVERT III that can provide critical AC power for telecom and IT applications in 5 kVA increments up to 25 kVA. It has redundant and hot-swappable modules to ensure continuous power availability and can be scaled as needed.

Uploaded by

Michael Besa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
305 views2 pages

Tebevert Iii Modular 5-25 Kva Inverter System: Key Features

The document describes a modular inverter system called the TEBEVERT III that can provide critical AC power for telecom and IT applications in 5 kVA increments up to 25 kVA. It has redundant and hot-swappable modules to ensure continuous power availability and can be scaled as needed.

Uploaded by

Michael Besa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

TEBEVERT III MODULAR

5-25 kVA INVERTER SYSTEM


The BENNING TEBEVERT III Modular System is
designed to address the critical AC power
requirements of telecommunications and
information technology applications. The TEBEVERT
III Modular Inverter System can be scaled in 5 kVA
increments up to 25 kVA. Unlike conventional stand
alone inverters, these modules operating in parallel
can also be operated in N+1 redundant
configuration. This insures power availability for
your critical applications. A failure of one inverter
module will not effect the operation of the
remaining modules. Since all units are designed for
“hot plug” replacement, a faulty module can easily
be unplugged and replaced without disturbing
critical loads.

Key Features

 NEBS Level 3 Certified


 No Single Point Of Failure
 Cabinet Requires No Rear Access
 Automatic Master-Slave Operation
 Integrated Maintenance Bypass Switch
 User Friendly Display Of Operating Mode
 Complies with EN 55022 Class B Requirements
 Bulk DC Input or Individual DC Input per Module
 High Efficiency Operation, Lowers Operating Costs
 Hot Plug 5 kVA Inverter and Static Switch Modules
 Less than 3% Harmonic Distortion on Output Voltage
 Up to Five Inverter Modules Can Be Paralleled To Meet Load Requirements
 Can Be Used With 120, 208, 220, 240, or 480VAC Commercial AC By-pass
 500% Overload Capability Supports High Inrush Current Loads
 Can Supply Fully Protected 120 or 120/240VAC Output
 Optional—Remote Monitoring via SNMP, or HTML
 Optional—Internal AC Load Distribution Circuit Breakers
 Optional—Molded Case Output Circuit Breaker

Tebevert lll (R9) © Benning Power Electronics 2018 Specifications are subject to change without notice.
Technical Specifications
Maximum System Capacity 5-25 kVA (4-20 kW)

Inverter Module Rating 5 kVA (4 kW)

Maximum Modules Per System 5

Overload Capability 200% for Approx. 1.25 Seconds (Module)

Static Bypass Switch (SBS) Standard

SBS Priority Inverter or Commercial AC By-pass


SYSTEM

SBS Transfer Time <2ms

SBS Overload Capability 500% for 100ms

Overload, Modules Over Temperature, Short Circuit On Output, Low DC


SBS Transfer Criteria
Voltage, Manual Initiation, and Output AC Voltage Out Of Range

(1) Form “C” Summary Alarm; Optional Relay Card (8 Alarms), HTML and
Remote Alarming
SNMP Alarms Available

Metering Graphic Display, Power Flow diagram, and LED’s, Optional Digital Metering

On, Output Present, DC Input OK, Inverter Fault, Parallel Operation,


Indicators Overload, and Bar Graph for Output Power

AC Output Voltage 120 VAC Standard, Optional—120/240


SYSTEM OUTPUT

AC Output Current (Max) @ 120 VAC 208 A (0.8 leading), 168 A (Unity pf)
AC BYPASS &

AC Output Frequency 60Hz

Commercial AC By-pass Input Voltages Available 120 VAC Standard, Optional—208, 220, 240 or 480VAC

Load Power Factor Range 0.7 Lagging to 0.8 Leading

Output Voltage Regulation +/- 5% For All Combinations of Line, Load, and Temperature

Distortion < 3% @ 100% Rated Linear Load

DC Input Voltage 40.8 to 60VDC (48VDC nominal)

93A @54VDC (115 A max), 150A DC Input Protection Recommended/Module


INPUT

DC Input Current/Module
or 700A DC Input Protection for Bulk DC Systems Recommended
DC

DC Inrush Current Soft Start, Current Limited

Efficiency >86.5% (on-line mode) / >97% (off-line mode)

Operating Temperature Range 32˚ to +131˚F (0˚ to +55˚C)


CONDITIONS
OPERATING

Operating Humidity Range 0-95% Non-Condensing

Heat Output Per Module < 2,040 BTUs Per Hour @ 100% Load

Cooling Temperature Controlled Fans

Elevation 6000’ (1800 m)

Cabinet Dimensions 84” x 23.6” x 23.6” (2134 mm x 600 mm x 600 mm)


PHYSICAL

Cabinet Weight 765 lbs. (347 Kg) without Modules

Inverter Module Weight 77.2 lbs. (35 Kg)

Module Mounting Hot Pluggable

Safety UL60950
WORLDWIDE
STANDARDS

Design Seismic Zone 0 (Standard), NEBS Level 3— Zone 4 Optional

EMI Emissions GR-1089, EN62040-2, FCC Class A

EMI Immunity GR-1089, EN61000-4-4, EN610004-5

Electrostatic Discharge Immunity EN61000-4-2

Benning Power Electronics, Inc. Toll Free North America: 800.910.3601


1220 Presidential Dr.Richardson, TX 75081 Local: 214.553.1444
E-Mail: [email protected] Canada: 905.997.6076
Web: www.benning.us Fax: 214.553.1355

Tebevert lll (R9) © Benning Power Electronics 2018 Specifications are subject to change without notice.