ECE 476 Power System Analysis: Lecture 16: Economic Dispatch, Optimal Power Flow
ECE 476 Power System Analysis: Lecture 16: Economic Dispatch, Optimal Power Flow
1
Economic Dispatch Lagrangian
2
Economic Dispatch Example
What is economic dispatch for a two generator
system PD = PG1 + PG 2 = 500 MW and
C1 ( PG1 ) = 1000 +20 PG1 + 0.01PG21 $ / hr
C2 ( PG 2 ) = 400 +15 PG 2 + 0.03PG22 $ / hr
Using the Largrange multiplier method we know
dC1 ( PG1 )
−λ =20 + 0.02 PG1 − λ =
0
dPG1
dC2 ( PG 2 )
−λ =15 + 0.06 PG 2 − λ =0
dPG 2
500 − PG1 − PG 2 =0
3
Economic Dispatch Example, cont’d
5
Lambda-Iteration Algorithm
i=1 i=1
While λ H − λ L > ε Do
λ=
M
(λ H + λ L ) / 2
m
If ∑ Gi
P ( λ M
) − PD > 0 Then λ H
λ
= M
i=1
Else λ L = λ M
End While
6
Lambda-Iteration: Graphical View
7
Lambda-Iteration Example
i=1
m
∑ Gi ) − 1000 > 0
P ( λ H
i=1
m
Try λ L 20 then ∑ PGi (20)
= − 1000
i =1
λ − 15 λ − 20 λ − 18
+ + − 1000 =
−670 MW
0.02 0.01 0.025
m
Try λ H 30 then ∑ PGi (30)
= − 1000 1230 MW
i =1
9
Lambda-Iteration Example, cont’d
λM =(λ H + λ L ) / 2 =25
m
Then since ∑ Gi
P =
(25) − 1000 280 =
we set λ H
25
i =1
Since 25 − 20 > 0.05
λM =
(25 + 20) / 2 =
22.5
m
∑ Gi
P (22.5) − 1000 =
−195 we set λ L
=
22.5
i =1
10
Lambda-Iteration Example, cont’d
12
Lambda-Iteration with Gen Limits
13
Lambda-Iteration Gen Limit Example
15
Back of Envelope Values
16
Inclusion of Transmission Losses
17
Impact of Transmission Losses
18
Impact of Transmission Losses
23
Thirty Bus ED Example, cont
24
Area Supply Curve
7.50
Supply
curve for 5.00
thirty bus
2.50
system
0.00
0 100 200 300 400
Total Area Generation (MW)
25
Economic Dispatch - Summary
27
Electricity Markets
28
Electricity Futures Example
31
Two Bus Economic Dispatch
Example
Bus A Bus B
300.0 MW 300.0 MW
199.6 MW 400.4 MW
AGC ON AGC ON
32
Market Marginal (Incremental) Cost
15.00 15.00
14.00 14.00
13.00 13.00
12.00 12.00
0 175 350 525 700 0 350 700 1050 1400
Generator Power (MW) Total Area Generation (MW)
34
Optimal Power Flow (OPF)
35
OPF, cont’d
• Inequality constraints
– transmission line/transformer/interface flow limits
– generator MW limits
– generator reactive power capability curves
– bus voltage magnitudes (not yet implemented in
Simulator OPF)
• Available Controls
– generator MW outputs
– transformer taps and phase angles
36