ISOVER Massivbausystem für Passivhäuser (WDVS) Page 80

ISOVER Solid Construction Systems for Passive Houses (CIS)

10.8 Ridged roof (insulation on rafters) – Eaves


Abbreviation: ISOV_6a_MB-CIS

Ridged roof (insulation on rafters)


Eaves

Constructional drawing – Vertical section

Build-up A in cm
1.5 Interior plaster
24.0 Vertically perforated brick HLzW
14.0 ISOVER Sillatherm WVP 1-035
14.0 ISOVER Sillatherm WVP 1-035
1.5 Thick plaster

Build-up B in cm
Roof covering
3.0 Roof lathing 3/5
Airtight level 5.0 Counter battens 5/5 with Integra AB twin UD fixed onto rafters
20.0 ISOVER Integra AB SolidBlack 035
1.9 Timber panelling
14.0 ISOVER Integra ZKF-1 032 (rafters 8/14 e=70cm, 10% wp)
Vapour retarder
Compriband
1.9 Tongue and groove panelling

Airtight level
ISOVER Massivbausystem für Passivhäuser (WDVS) Page 81
ISOVER Solid Construction Systems for Passive Houses (CIS)

Graphical representation of the results (ISOV_6a_MB-CIS):

Material l Size
Model
mm
W/(mK)

External plaster 1.0 15

Insulation 0.036 140

Insulation 0.036 140 AASD


Masonry 0.250 240

Interior plaster 0.700 15

Concrete 2.300 90x190


Wooden
0.130 19
composite board
Insulation 0.035 200

läq,ASD,TE
*)
0.042 140

Wood 0.130 -
AAW

Temperature °C Isothermal image

see Section ‎3.14


*)
ISOVER Massivbausystem für Passivhäuser (WDVS) Page 82
ISOVER Solid Construction Systems for Passive Houses (CIS)

Result of the calculation in accordance with DIN EN ISO 10211 (ISOV_6a_MB-CIS):

project: ISOVER Massivbausystem für Passivhäuser (WDVS)


detail number: ISOV_6a_MB-WDVS
connection detail: Ridged roof (insulation on rafters) - eaves

description symbol value unit


base values
permissible limiting value for absence of thermal bridge a 0.01 W/(mK)
external temperature e -10.00 °C
room temperature i 20.00 °C
ground temperature g 5.00 °C
exterior heat transfer resistance Rse 0.04 (m²K)/W
exterior heat transfer resistance (exterior wall, ventilated) Rse 0.13 (m²K)/W
exterior heat transfer resistance (roof, ventilated) Rse 0.10 (m²K)/W
interior heat transfer resistance, upwards Rsi 0.10 (m²K)/W
interior heat transfer resistance, horizontal Rsi 0.13 (m²K)/W
interior heat transfer resistance, downwards Rsi 0.17 (m²K)/W
heat transfer resistance to the ground Rsg 0.00 (m²K)/W
heat transfer coefficients

External wall solid construction with CIS (AW): standard UAW,MB 0.11 W/(m²K)

Ridged roof with insulation on rafters (ASD): standard UASD 0.10 W/(m²K)

results

reference temperature difference of the heat transfer coefficient D 30 K

linear thermal bridge loss coefficient a -0.025 W/(mK)

minimal interior surface temperature at -10°C  min 18.6 °C

without thermal bridges? The connection is thermal bridge free.


temperature factor at Rsi = 0.25 (m²K)/W fRsi=0.25 0.95 -

a: Thermal bridge loss coefficient based on external dimensions

The connection is free of thermal bridges.

Component
Suitable
for
Passive Houses
Dr. Wolfgang Feist
ISOVER Massivbausystem für Passivhäuser (WDVS) Page 83
ISOVER Solid Construction Systems for Passive Houses (CIS)

10.9 Ridged roof (insulation on rafters) – Verge


Abbreviation: ISOV_6b_MB-CIS

Ridged roof (insulation on rafters)


Verge

Constructional drawing – Section perpendicular to the roof level

Build-up A in cm
1.5 Interior plaster
24.0 Vertically perforated brick HLzW
14.0 ISOVER Sillatherm WVP 1-035
14.0 ISOVER Sillatherm WVP 1-035
1.5 Thick plaster

Build-up B in cm
Roof covering
3.0 Roof lathing 3/5
5.0 Counter battens 5/5 with Integra AB twin UD fixed onto rafters
20.0 ISOVER Integra AB SolidBlack 035
1.9 Timber panelling
Airtight level 14.0 ISOVER Integra ZKF-1 032 (rafters 8/14 e=70cm, 10% wp)
Vapour retarder
1.9 Tongue and groove panelling
ISOVER Massivbausystem für Passivhäuser (WDVS) Page 84
ISOVER Solid Construction Systems for Passive Houses (CIS)

Graphical representation of the results (ISOV_6b_MB-CIS):

Material l Size
Model
mm
W/(mK)

External plaster 1.0 15


AASD
Insulation 0.036 140

Insulation 0.036 140

Masonry 0.250 240

Interior plaster 0.700 15

Concrete 2.300 240x300


Wooden
0.130 19
composite board
Gypsum AAW
0.250 25
plasterboard
Insulation 0.035 200

läq,ASD,TE
*)
0.042 140

Wood 0.130 -

Temperature °C Isothermal image

see Section ‎3.14


*)
ISOVER Massivbausystem für Passivhäuser (WDVS) Page 85
ISOVER Solid Construction Systems for Passive Houses (CIS)

Result of the calculation in accordance with DIN EN ISO 10211 (ISOV_6b_MB-CIS):

project: ISOVER Massivbausystem für Passivhäuser (WDVS)


detail number: ISOV_6b_MB-WDVS
connection detail: Ridged roof (insulation on rafters) - verge

description symbol value unit


base values
permissible limiting value for absence of thermal bridge a 0.01 W/(mK)
external temperature e -10.00 °C
room temperature i 20.00 °C
ground temperature g 5.00 °C
exterior heat transfer resistance Rse 0.04 (m²K)/W
exterior heat transfer resistance (exterior wall, ventilated) Rse 0.13 (m²K)/W
exterior heat transfer resistance (roof, ventilated) Rse 0.10 (m²K)/W
interior heat transfer resistance, upwards Rsi 0.10 (m²K)/W
interior heat transfer resistance, horizontal Rsi 0.13 (m²K)/W
interior heat transfer resistance, downwards Rsi 0.17 (m²K)/W
heat transfer resistance to the ground Rsg 0.00 (m²K)/W
heat transfer coefficients

External wall solid construction with CIS (AW): standard UAW,MB 0.11 W/(m²K)

Ridged roof with insulation on rafters (ASD): standard UASD 0.10 W/(m²K)

results

reference temperature difference of the heat transfer coefficient D 30 K

linear thermal bridge loss coefficient a -0.043 W/(mK)

minimal interior surface temperature at -10°C  min 18.0 °C

without thermal bridges? The connection is thermal bridge free.


temperature factor at Rsi = 0.25 (m²K)/W fRsi=0.25 0.93 -

a: Thermal bridge loss coefficient based on external dimensions

The connection is free of thermal bridges.

Component
Suitable
for
Passive Houses
Dr. Wolfgang Feist
ISOVER Massivbausystem für Passivhäuser (WDVS) Page 86
ISOVER Solid Construction Systems for Passive Houses (CIS)

10.10 Ridged roof (insulation on rafters) – Roof ridge


Abbreviation: ISOV_6c_MB-CIS

Ridged roof (insulation on rafters)


Roof ridge

Constructional drawing – Vertical section

Build-up A in cm
1.5 Interior plaster
24.0 Vertically perforated brick HLzW
14.0 ISOVER Sillatherm WVP 1-035
14.0 ISOVER Sillatherm WVP 1-035
1.5 Thick plaster

Build-up B in cm
Roof covering
3.0 Roof lathing 3/5
Airtight level 5.0 Counter battens 5/5 with Integra AB twin UD fixed onto rafters
20.0 ISOVER Integra AB SolidBlack 035
1.9 Timber panelling
14.0 ISOVER Integra ZKF-1 032 (rafters 8/14 e=70cm, 10% wp)
Vapour retarder
1.9 Tongue and groove panelling
Compriband

Airtight level
ISOVER Massivbausystem für Passivhäuser (WDVS) Page 87
ISOVER Solid Construction Systems for Passive Houses (CIS)

Graphical representation of the results (ISOV_6c_MB-CIS):

Material l Size
Model
mm
W/(mK)
Wooden
0.130 19
composite board
Wooden
0.130 19
composite board
Insulation 0.035 200
AASD
läq,ASD,TE
*)
0.042 140

Temperature °C Isothermal image

see Section ‎3.14


*)
ISOVER Massivbausystem für Passivhäuser (WDVS) Page 88
ISOVER Solid Construction Systems for Passive Houses (CIS)

Result of the calculation in accordance with DIN EN ISO 10211 (ISOV_6c_MB-CIS):

project: ISOVER Massivbausystem für Passivhäuser (WDVS)


detail number: ISOV_6c_MB-WDVS
connection detail: Ridged roof (insulation on rafters) - roof ridge

description symbol value unit


base values
permissible limiting value for absence of thermal bridge a 0.01 W/(mK)
external temperature e -10.00 °C
room temperature i 20.00 °C
ground temperature g 5.00 °C
exterior heat transfer resistance Rse 0.04 (m²K)/W
exterior heat transfer resistance (exterior wall, ventilated) Rse 0.13 (m²K)/W
exterior heat transfer resistance (roof, ventilated) Rse 0.10 (m²K)/W
interior heat transfer resistance, upwards Rsi 0.10 (m²K)/W
interior heat transfer resistance, horizontal Rsi 0.13 (m²K)/W
interior heat transfer resistance, downwards Rsi 0.17 (m²K)/W
heat transfer resistance to the ground Rsg 0.00 (m²K)/W
heat transfer coefficients

Ridged roof with insulation on rafters (ASD): standard UASD 0.10 W/(m²K)

results

reference temperature difference of the heat transfer coefficient D 30 K

linear thermal bridge loss coefficient a -0.035 W/(mK)

minimal interior surface temperature at -10°C  min 18.1 °C

without thermal bridges? The connection is thermal bridge free.


temperature factor at Rsi = 0.25 (m²K)/W fRsi=0.25 0.94 -

a: Thermal bridge loss coefficient based on external dimensions

The connection is free of thermal bridges.

Component
Suitable
for
Passive Houses
Dr. Wolfgang Feist