Eccentric Load On Column Footing PDF
Eccentric Load On Column Footing PDF
Figure 7.8
Various pressure distributions for rectangular footings are shown in Fig. 7.9.
Figure a
If the load acts through the kern point (Fig.C), 𝑞 = 0 at one side and 𝑞 = 2𝑞 at
the other.
If the load falls outside the kern point, the resultant upward load is equal and
opposite to the resultant downward load, as shown in Fig. 7-9 d. Generally, such a
pressure distribution would not be acceptable, because it makes inefficient use of
the footing concrete, tends to overload the soil, and may cause the structure to
tilt.
Figure 7.9
Example: the rectangular footing has width of 2.5 m and it will be support (400*400
mm) column that is carry the following loads
𝑃 = 800𝑘𝑁 𝑃 = 530𝑘𝑁
𝑀 = 100𝑘𝑁. 𝑚 𝑀 = 80𝑘𝑁. 𝑚
Solution:
- Assume the soil pressure distribution at the base of the footing is horizontal.
3- Check the footing thickness for two way shear (punching shear)
𝑑 = 600 − 75 − 20 = 505𝑚𝑚
Use average soil pressure to find the shear force inside critical parameter.
149.1 + 231.5
𝑞 = = 190.3 𝑘𝑁 ⁄𝑚
2
𝑣 = 1808 − 190.3(0.4 + 0.505) = 1652.13𝑘𝑁
2 2
𝑣 = 0.17 1 + 𝜆 𝑓′𝑐 𝑏° 𝑑 = 0.17 1 + √21 × 3620 × 505 × 10−3 = 4272.5𝑘𝑁
𝛽 1
𝛼𝑠 𝑑 40×505
𝑣 = 0.083 2 + 𝜆 𝑓′𝑐 𝑏° 𝑑 = 0.083 2 + √21 × 3620 × 505 × 10−3 =
𝑏° 3620
5270.6𝑘𝑁
4- Check the footing thickness for one way shear (beam shear)
It is conservative to assume that the maximum factored soil pressure of (231.5 kN/m2)
acts on the entire shaded region. Thus, the factored shear force to be resisted at the
critical section is:
1.7 1 2
𝑀 = 185.96 × 2.5 × 1.7 × + × 2.5 × (231.5 − 185.96) × 1.7 × × 1.7
2 2 3
= 781.46𝑘𝑁. 𝑚
∅𝑀 ≥ 𝑀
𝑓𝑦
∅𝑀 = ∅𝜌𝑏𝑑 𝑓𝑦 1 − 0.59 × × 𝜌 → 𝜌 = 0.00355 → 𝐴 = 4482𝑚𝑚
𝑓′𝑐
𝐴 . = 0.0018 × 𝐵 × 𝑡 = 2700 𝑚𝑚
ACI 13.3.3.3 In rectangular footings, reinforcement shall be distributed in accordance with (a) and (b):
(a) Reinforcement in the long direction shall be distributed uniformly across entire width of footing.
4482
𝑛= = 14.27 , 𝑢𝑠𝑒 15∅20 𝑚𝑚,
314.16
2500 − 150
𝑠= = 156.6𝑚𝑚 𝑢𝑠𝑒 150𝑚𝑚
15
The minimum spacing should be smallest of
- 450 mm
- 3t=1800mm
S= 150mm< Smin. ok
b- Short direction
(b) For reinforcement in the short direction, a portion of the total reinforcement, 𝛾 As, shall be
distributed uniformly over a band width equal to the length of short side of footing, centered on
centerline of column or pedestal.
Remainder of reinforcement required in the short direction,(1– 𝛾 )As, shall be distributed uniformly
outside the center band width of footing
𝛾= = . = 0.79
.