Catalogue Điều hòa trung tâm SMMS VRF - Toshiba
Catalogue Điều hòa trung tâm SMMS VRF - Toshiba
Catalogue Điều hòa trung tâm SMMS VRF - Toshiba
INDEX
Introduction 3
SMMS-e features Energy saving 8
Diversity 10
Prevent small animals 11
Capacity range 12
SMMS wave tool 14
DC twin-rotary compressor 16
Heat exchanger 17
Piping design flexibility 18
Slimmer pipe size 20
Propeller fan 21
Reliability 22
Operating temperature range 23
Outdoor units
Outdoor units line-up 24
Outdoor units specifications 26
Outdoor units external view drawings 34
Indoor units
Indoor units line-up for SMMS-e 38
4-way Air Discharge Cassette type 62 40
Compact 4-way Cassette (600 x 600) Type 42
2-way Air Discharge Cassette Type 44
1-way Air Discharge Cassette Type 46
Slim Duct Type 48
Concealed Duct High Static Pressure Type 50
Concealed Duct Type 52
Ceiling Type 76 54
High-wall Type (3 series) 56
Console Type 57
Floor Standing Cabinet Type 58
Floor Standing Concealed Type 59
Floor Standing Type 60
Large capacity Floor Standing Type 61
Fresh Air Intake Indoor Unit Type 62
Air-to-Air Heat Exchanger with DX-coil 64
Air-to-Air Heat Exchanger 66
Indoor unit accessories for SMMS-e 68
Remote controllers 70
Building management systems 74
Open network systems 76
Application controls 78
Safety precautions 80
Toshiba solutions
At Toshiba, we believe that “Evolution is leading
the path to a better future”. Through the decades,
we have been constantly creating innovative and
high-quality electrical appliances to increase our
consumers’ satisfaction. Now, with Toshiba
"SMMS-e", the latest commercial air conditioning
for various buildings,
XPERIENCE
XCELLENCE
RELIABILITY
PRODUCT LINE UP
Product line up
8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40HP 42HP 44HP 46HP 48HP 50HP 52HP 54HP 56HP 58HP 60HP
High efficiency
/High diversity model
ENERGY SAVING
50% load
EER
7.0
6.39 50% load
6.5 6.22
6.0 5.86
5.70 5.64
5.5 5.50
5.0
4.5
4.0
3.5
3.0
2.5
2.0
*Conditions: Cooling: Indoor air temperature 27°C DB/19°C WB, outdoor air temperature 35°C DB
*High efficiency/High diversity model by single outdoor unit
10
RELIABILITY
DIVERSITY
Greater diversity
Thanks to the newly developed refrigerant circuit, the diversity of outdoor units has drastically
increased. This makes it much easier to design for installations with many rooms or offices.
High efficiency model/High diversity model
SMMS-e Current
8HP 8HP 170%
SMMS-e (8HP)
10HP 150%
diversity up to 12HP 135%
170% 14HP
16HP
145%
135%
18HP 150%
20HP 150%
22HP 140%
24HP 135%
26HP 140%
28HP 145%
30HP 140%
32HP 135%
34HP 140% 135%
36HP 135%
38HP 140%
40HP 140%
42HP 145%
44HP 140%
46HP 140%
48HP 135%
50HP 140%
52HP 135%
54HP 145%
56HP 140%
58HP 135%
60HP 135%
11
RELIABILITY
CAPACITY RANGE
New
8 10 12 14 HP
16 18 HP
20 22 HP
22HP 26HP
Previous
model
10HP 12HP 10HP 8HP 8HP
1,980 mm 2,970 mm
SMMS-e
12 HP
Previous SMMS-e
model
60 HP
48 HP
Installation flexibility
While expanding the maximum combination from 48 to 60HP in one system. This helps save more time
and expense on additional unit system required in the previous model. The new compact unit design also
increases more flexibility on installation with less foot print.
60 HP
RELIABILITY
SMMS WAVE TOOL
Previous SMMS-e
model
15
Available data
Whether the product data, system data, fault history or testing and commissioning, all can be
obtained easily even in case of under service maintenance or power failure. The data can be
easily sent to the distant office via email. Possible to receive system data by e-mail without
moving from your office and the operation conditions can be checked in the office.
System
data
data
Test operation
result
Smart phone
@lert
16
RELIABILITY
DC TWIN-ROTARY COMPRESSOR
and performance.
Cylinder
Shaft
2 stage
Shaft
17
HEAT EXCHANGER
16HP 16HP
Previous model SMMS-e
12HP+10HP 22HP
Increased
13%
the surface area
of the total pipe
Use Use
heat exchanger
4-way heat exchanger can realize balanced airflow
Heat exchangers are located on all four sides of the outdoor unit,
ensuring air flow is equal in all directions. Machine room
SMMS-e
18
RELIABILITY
PIPING DESIGN FLEXIBILITY
Total 1,000m
piping length SMMS-e Max. total length
Farthest pipe
from 1st branch 90m
Farthest equivalent length Height between indoor units
The maximum equivalent distance between outdoor unit Another industry’s top class is a maximum vertical distance
and farthest indoor unit tops at 235 meters, which tops between indoor units which reaches up to 40 meters, equal
the industry class. to an entire 11-storied building. SMMS-e’s enhanced piping
capabilities result in more benefits for the system design,
installation flexibility, as well as the less installation cost.
Farthest
equivalent length 235m
19
11F 11F
10F 10F
9F 9F
8F 8F
7F 7F
6F
5F
1 2 6F
5F
4 3
4F 4F
3F 3F
2F 2F
1F 1F
RELIABILITY
SLIMMER PIPE SIZE
22 HP
PROPELLER FAN
1.5 dB
Reduce
Air volume
22
RELIABILITY
RELIABILITY
Backup operation
In case of a compressor failure, SMMS-e can keep working with the backup operation under
All Inverter Control to compensate a failed compressor or header unit. This backup operation
is available in both a single system or as a module.
80%
30%
Noon
Out Comp1/Comp2
rise doo
mp
do or te r te
mp
Out dow
n
Morning Evening
Comp1/Comp2 Comp1/Comp2
23
Cooling
-5 - 46 ( °C )
-25 0 25 50 ( C)
Note : Based on equivalent piping length of 7.5 m and piping height difference of 0 m.
44.2
5F
42.6
40.9
4F
39.3
60 pa 3F 36.8
35.1
2F 33.5
Outdoor units
Space saving model
MAP1206T7P MAP1206T7P MAP1406T7P MAP1206T7P MAP14B6T7P MAP14B6T7P MAP1606T7P MAP14B6T7P MAP1606T7P MAP1606T7P MAP18B6T7P MAP1606T7P MAP18B6T7P MAP18B6T7P MAP2206T7P MAP1606T7P
MAP18B6T7P MAP1606T7P MAP1606T7P MAP18B6T7P MAP18B6T7P MAP1606T7P MAP18B6T7P MAP18B6T7P MAP18B6T7P MAP2006T7P MAP18B6T7P MAP18B6T7P MAP2206T7P MAP18B6T7P MAP18B6T7P MAP2206T7P MAP2206T7P MAP1606T7P
MAP1206T8P MAP1206T8P MAP1406T8P MAP1206T8P MAP1406T8P MAP1406T8P MAP1606T8P MAP1406T8P MAP1606T8P MAP1606T8P MAP1806T8P MAP1606T8P MAP1206T8P MAP1206T8P MAP1206T8P MAP1406T8P MAP1206T8P MAP1206T8P
MAP1206T7P MAP1206T7P MAP1406T7P MAP1206T7P MAP1406T8P MAP1406T8P MAP1606T7P MAP1406T7P MAP1606T7P MAP1606T7P MAP1806T7P MAP1606T7P MAP1206T7P MAP1206T7P MAP1206T7P MAP1406T7P MAP1206T7P MAP1206T7P
MAP1806T8P MAP1606T8P MAP1606T8P MAP2006T8P MAP1606T8P MAP1606T8P MAP2006T8P MAP2006T8P MAP1406T8P MAP2006T8P MAP2006T8P MAP1606T8P MAP2206T8P MAP2006T8P MAP1606T8P MAP2206T8P MAP2206T8P MAP1606T8P
MAP1806T7P MAP1606T7P MAP1606T7P MAP2006T7P MAP1606T7P MAP1606T7P MAP2006T7P MAP2006T7P MAP1406T7P MAP2006T7P MAP2006T7P MAP1606T7P MAP2206T7P MAP2006T7P MAP1606T7P MAP2206T7P MAP2206T7P MAP1606T7P
26
Technical specifications
Equivalent HP 18HP 20HP 22HP
50Hz MMY- MAP18B6T8P MAP2006T8P MAP2206T8P
Model name
60Hz MMY- MAP18B6T7P MAP2006T7P MAP2206T7P
Outdoor unit type Inverter
Power supply (*1) 3phase 4wires 50Hz 400V (380-415V) / 3phase 4wires 60Hz 380V
Capacity 100% (kW) 50.4 56.0 61.5
Power consumption (kW) 16.8 17.90 21.0
Cooling (*2) Capacity 100% 3.00 3.13 2.93
EER
(Energy Efficiency Ratio) Capacity 80% 3.48 3.87 3.61
Capacity 50% 4.62 5.61 5.34
External dimensions (Height / Width / Depth) (mm) 1,800/1,210/780 1,800/1,600/780 1,800/1,600/780
Total weight (kg) 298 369 369
Compressor Motor output (kW) 6.9 x 2 7.6 x 2 9.0 x 2
Motor output (kW) 1.0 2.0 2.0
Fan unit
Air volume (m3/h) 12,600 17,900 18,500
Gas side (mm) ø 28.6 ø 28.6 ø 28.6
Refrigerant
Main pipe diameter Liquid side (mm) ø 15.9 ø 15.9 ø 19.1
piping
Balance pipe (mm) ø 9.5 ø 9.5 ø 9.5
Sound pressure level (dB(A)) 62 61 61
Diversity 130% 140% 135%
27
The standard piping means that main pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
30
The standard piping means that main pipe length is 5m, branching pipe length is 2.5m of branch piping connected with a 0 meter height.
34
Model Name �A
MAP0806 type �19.1
MAP1006 type �22.2
MAP1206 type �28.6
MAP14B6 type �28.6
Square hole (for freight handling) 2-60X200 Gas pipe connection port Ø28.6
Balance pipe connection port Ø9.5
(Note) Liquid pipe connection port Ø15.9 (Unit:mm)
1. IF there is an obstacle at the upper side of
the outdoor unit, set the top end of the outdoor
unit 2000mm apart from the obstacle
2. Limit the height of the obstacle surrounding
the outdoor unit to 800mm or less from the
bottom end of the outdoor unit.
3. Draw out the pipe procured locally to the
front of the outdoor unit horizontally and
keep 500mm or more between the outdoor unit
and traversing pipe if placing pipe
transversely.
4. Dimensional drawing of corrosion heavey
protection model is the same as that
of standard model.
36
Model Name �A
MAP1806 type �15.9
MAP2006 type �15.9
MAP2206 type �19.1
Indoor units
4-way air discharge Compact 4-way cassette 2-way air discharge 1-way air discharge
Cooling capacity (HP equivalent) Concealed duct type
cassette type (600 × 600) type cassette type cassette type
MMD-AP0***4H-E
MMD-AP0***6HP-E
1080 m³/h MMD -AP0481HFE *: Does not connect to refrigerant piping from outdoor unit.
Control wires can be connected.
1680 m³/h MMD-AP0721HFE
RBC-U31PGP(W)-E
Technical specifications
Model name MMU- AP0094HP-E AP0124HP-E AP0154HP-E AP0184HP-E AP0244HP-E AP0274HP-E AP0304HP-E AP0364HP-E AP0484HP-E AP0564HP-E
Cooling/Heating capacity*1 (kW) 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0 8.0/9.0 9.0/10.0 11.2/12.5 14.0/16.0 16.0/18.0
Power requirements 1-phase 50Hz 230V (220–240V) / 1-phase 60Hz 220V (Separate power supply for indoor units required.)
Electrical
characteristics Power consumption 0.023/ 0.026/ 0.043/ 0.088/ 0.112/ 0.112/
0.021/0.021 0.036/0.036
50 Hz/60 Hz (kW) 0.023 0.026 0.043 0.088 0.112 0.112
Total weight: Main unit (Ceiling panel)* (kg) 18 (4)* 20 (4)* 25 (4)*
MMU-AP0074HP-E to AP0564HP-E
32
57
64
200
5
15
Celling
269
323
bottom Check port
surface ( 450)
Knockout for
fresh air intake φ100
° 416.5
Z 860 to 910 Ceiling open dimension
Z view 690±20 Hanging bolt pitch
For branch duct knockout square
950 Panel external dimension Refrigerant pipe
hole φ150 (Also located on the back)
connecting port
Hanging bolt M10 or (Gas side) B
196.5 480 163.5
Drai pipe
W3/8 procured locally connecting port 241.5 72 106.5
*( ): AP0364 to AP0564 Refrigerant pipe
223.5 256.5 263 157
connecting port
384 105 351 337.5 105 397.5 (Liquid side) C
30 101 120 35
n
300 or less
(183)
*
77 105
A 189
172
129
132
112
Stand-up 850 or less
Stand-up
661 or less
30
44
16.5
129
more
more
15 or
15 or
Model MMD- A B C
Bottom face of ceiling AP0094HP-E, AP0124HP-E 256 Ø9.5 Ø6.4
Options
TCB-BC1602UE
TCB-GFC1602UE
Fresh air inlet box
TCB-GB1602UE
Perfect for grid system ceiling Designed for simple & easy installation and
maintenance
This compact unit (575 × 575 mm) fits perfectly The slim design is only 268 mm in height even when
into ceilings and matches standard architectural an electrical box is located inside the unit.
modules, without the need to cut ceiling tiles. Easy installation is also possible using the panel
The flaps fold tightly against the ceiling when adjust pocket. Use the “adjust pocket” function for
operation stops so that the ceiling is affected fine adjustments after installation.
only slightly even if air conditioning is installed. Available for ceilings up to 3.5 m in height.
The drain-checking hole makes it possible to check
the drain pan through the side case.
3.5m
Technical specifications
Model name MMU- AP0074MH-E AP0094MH-E AP0124MH-E AP0154MH-E AP0184MH-E
Power requirements 1-phase 50Hz 230V (220–240V) / 1-phase 60Hz 220V (Separate power supply for indoor units required.)
Electrical
characteristics Power consumption
0.034/0.034 0.036/0.036 0.038/0.038 0.041/0.041 0.052/0.052
50 Hz/60 Hz (kW)
MMU-AP0074MH-E to AP0184MH-E
145.5
70 105 93
K noc kout s quare hole AP0074MH-E, AP0094MH-E, AP0124MH-E Ø 9.5
150 AP0154MH-E, AP0184MH-E Ø12.7
162
200
575 207
175
C elling bottom s urfac e K noc kout for C hec k port
149
air intake 100 ( 450)
E lec tric parts box 29 64
64 142
Hanging bolt pitc h 525
629.5 or less
Stand-up
unit
575
368.5
320.5
15 or more
1000 or more 1000 or more
15 or more
1000 or more
93 105 70
220.5
268
190.5
145.5
139.5
134
63
55
For branc h duc t knoc kout 158 142 C eiling panel(s old s eparately)
s quare hole 150
(Unit: mm)
Options
Ceiling panel
RBC-UM11PG(W)E
44
Technical specifications
Model name MMU- AP0072WH AP0092WH AP0122WH AP0152WH AP0182WH AP0242WH AP0272WH AP0302WH AP0362WH AP0482WH AP0562WH
Cooling/Heating capacity* 1
(kW) 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0 8.0/9.0 9.0/10.0 11.2/12.5 14.0/16.0 16.0/18.0
Power requirements 1-phase 50Hz 230V (220–240V) / 1-phase 60Hz 220V (Separate power supply for indoor units required.)
Electrical
characteristics
Power consumption
0.029/0.029 0.030/0.030 0.044/0.044 0.054/0.054 0.064/0.064 0.076/0.076 0.088/0.088 0.117/0.117
50 Hz/60 Hz (kW)
Total weight: Main unit (Ceiling panel)* (kg) 19 (10) 26 (14) 36 (14)
MMU-AP0072WH to AP0152WH
Hanging bolt
Ceiling open
dimension
dimension
pitch
680
620
380
295
151
77
20
Bottom face Ceiling panel (sold separetely)
880 of ceiling
Hanging bolt pitch
1000~1010 570
Ceiling open dimension 300 or less 137.5 147.5
1050
Space required for Refrigerant pipe
95 190
connecting port Drain pipe
Panel external dimension installation and servicing (Liquid side) 185 80 20 connecting port
609 or less
850 or less
or more 5 or more
Refrigerant pipe
connecting port
241
(Gas side)
189
103
ceiling Power supply
Knockout hole for auxiliary
1000
connecting port
Drain standing-up size fresh air intake flange
(Only at reverse side)
(Unit: mm)
MMU-AP0182WH to AP0302WH
Adjust cover
Hanging bolt 4-M10 Wireless sensor mounting section
Electric parts box procured locally
1180
Panel external
Hanging bolt
Ceiling open
dimension
dimension
pitch
680
620
380
345
151
77
Refrigerant pipe
connecting port
291
(Gas side)
242
103
more
1000or
(Unit: mm)
MMU-AP0362WH to AP0562WH
Adjust cover
Wireless sensor mounting section
Electric parts box
1600 Hanging bolt 4-M10
procured locally
Panel external
Hanging bolt
Ceiling open
dimension
dimension
pitch
680
620
380
120
345
255
151
77
Refrigerant pipe
5 or
more more
connecting port
291
(Gas side)
242
103
1000or
(Unit: mm)
Options
Filter chamber
TCB-FC283UW-E
Ceiling panel TCB-FC803UW-E
RBC-UW283PG(W)-E TCB-FC1403UW-E
RBC-UW803PG(W)-E
RBC-UW1403PG(W)-E Auxiliary fresh air flange
Super long life filter
TCB-FF151US-E
TCB-LF283UW-E
TCB-LF803UW-E
TCB-LF1403UW-E
46
The perfect choice for hotels and reception Fresh air intake is possible (MMU-AP***4SH-E)
areas
Silent sound design ensures the quiet required for Preparations/connection possible with a circle duct
the office. flange.
Technical specifications
Model name MMU- AP0074YH-E AP0094YH-E AP0124YH-E AP0154SH-E AP0184SH-E AP0244SH-E
Power requirements 1-phase 50Hz 230V (220–240V) / 1-phase 60Hz 220V (Separate power supply for indoor units required.)
Electrical
characteristics Power consumption
0.053/0.056 0.042/0.041 0.046/0.045 0.075/0.073
50 Hz/60 Hz (kW)
Total weight: Main unit (Ceiling panel)* (kg) 22 (3.5)* 21 (5.5)* 22 (5.5)*
MMU-AP0074YH-E to AP0124YH-E
20
dimension 430
dimension 470
Panel external
Hanging bolt
Ceiling open
pitch 330
Power supply connecting por t
400
Drain pipe connecting por t
100 or mor e 100 or mor e
or more
150
20
245
Center of panel Hanging bolt 4-M10
225 100 400
procured locally
850
200 or mor e
Support metal
200
235
120
140
85
18
Ceiling panel (Sold separately ) 100 or less
150 or less
(Gas side) 1050
Stand-up
Refrigerant pipe
connecting port
(Liquid side)
470
MMU-AP0154SH-E to AP0244SH-E
112
43
1000 or more
Panel externaldimension 800
bolt pitch 475 100
Ceilin g
122 233
1000 or more
220 Hanging
60
Obstacl e
710
800
80
216
135
200 or more
20
1000
Stand-up
73.4
Options
Ceiling panel
Auxiliary fresh air flange
RBC-UY136PG
TCB-FF101URE2
Ceiling panel
AP0154SH-E/AP0184SH-E/AP0244SH-E RBC-US21PGE
48
4-step static pressure setup. Can be used with any style of air diffuser.
Technical specifications
Model name MMD- AP0074SPH-E AP0094SPH-E AP0124SPH-E AP0154SPH-E AP0184SPH-E AP0244SPH-E AP0274SPH-E
Cooling/Heating capacity*1 (kW) 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0 8.0/9.0
Power supply 1-phase 50Hz 230V (220–240V) / 1-phase 60Hz 220V (Separate power supply for indoor units required.)
Electrical
characteristics Power consumption
0.039/0.037 0.043/0.041 0.045/0.043 0.054/0.052 0.105//0.105
50 Hz/60 Hz (kW)
4-14-29-44
External static pressure (Pa) 6-16-31-46 (4 steps) 5-15-30-45 (4 steps) 2-12-22-42 (4 steps)
(4 steps)
Sound pressure Under air inlet (dB(A)) 36/33/30 38/35/32 39/36/33 40/38/36 49/47/44
level*2
(High/Med./Low) Back air inlet (dB(A)) 28/26/24 29/27/25 32/30/28 33/31/29 38/36/33
Note 1 : The capacities are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 m height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
49
MMD-AP0074SPH-E to AP0274SPH-E
845
21
57
168 (inside)
Refrigerant pipe
connecting port
210
(Liquid side) Model MMD-
AP0074SPH-E to AP0274SPH-E
Refrigerant pipe
21 803 (inside) 21
20 21
connecting port
103
Air filter (Gas side)
67
4- 4
19
511
645
PUSH FOR OPE N PUSH FOR OPE N PUSH FOR OPEN
>ABS <
31
押すと取りはずせます 押すと取りはずせます 押すと取りはずせます
168
359
372
422
502
92
80
120
67
40
805
80 59 910 33
163
Drain pipe
Fresh air intake connecting port
(knock-out hole)
Hanger plate
(Unit: mm)
Options
MMD-AP***4H-E
MMD-AP***6HP-E
Technical specifications
Model name MMD- AP0186HP-E AP0246HP-E AP0276HP-E AP0366HP-E AP0486HP-E AP0566HP-E AP0724H-E AP0964H-E
Cooling/Heating capacity* 1
(kW) 5.6/6.3 7.1/8.0 8.0/9.0 11.2/12.5 14.0/16.0 16.0/18.0 22.4/25.0 28.0/31.5
Power requirements 1-phase 50Hz 230V (220–240V) / 1-phase 60Hz 220V (Separate power supply for indoor units required.)
Electrical
characteristics Power consumption
0.085 0.115 0.198 0.230 0.290 1.200/1.540 1.260/1.610
50 Hz/60 Hz (kW)
Standard air flow 800 1,200 1,920 2,100 2,400 3600 4200
(m3/h)
(Med./Low) (660/550) (970/800) (1,560/1,340) (1,740/1,420) (2,040/1,660)
Motor output (W) 250 350 370×3
Fan unit
External static pressure
100 137
(factory setting) (Pa)
1380
Air outle t Air inle t
100
Hanging bolt pitch 1288
1328
Electric parts box
Hole for hanging bolt (4- 12×92)
1250
200 150
470
31
45
624
698
Drain pipe
connecting port
190 250 250 250 250
MMD-AP0366HP-E to AP0566HP-E
29
406
Left side
35
Air outle t
Screw hole for
duct mounting (10-M6)
Z view
370
Screw hole for
65
duct mounting (10-M6)
or more
200
fo r inst allation space
and se rv icin g
Check port
1000
Service
or more
1000
space
Options
MMD-AP***6HP-E
TCB-PF3DE
TCB-UFM3DE
TCB-UFM7DE
52
Technical specifications
Model name MMD- AP0076BHP-E AP0096BHP-E AP0126BHP-E AP0156BHP-E AP0186BHP-E AP0246BHP-E AP0276BHP-E AP0306BHP-E AP0366BHP-E AP0486BHP-E AP0566BHP-E
Cooling/Heating capacity* 1
(kW) 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0 8.0/9.0 9.0/10.0 11.2/12.5 14.0/16.0 16.0/18.0
Power requirements 1-phase 50Hz 230V (220–240V) / 1-phase 60Hz 220V (Separate power supply for indoor units required.)
Electrical
characteristics Power consumption
0.038/0.038 0.043/0.043 0.062/ 0.062 0.077/0.077 0.094/ 0.094 0.172/ 0.172 0.198/0.198
50 Hz/60 Hz (kW)
Note 1 : The capacities are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 m height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
53
MMD-AP0076BHP-E to AP0566BHP-E
more
5 or
C (Outside)
275
Air outlet
1/100 or more downward
Ceiling
64 180(Outside)
At the time of natural drainage
25 25
more
70 or
750
275
100 or 700
or more
more or more
2500
Service door (Ceiling opening)
Refrigerant pipe
connecting port 6.4 Floor surface
(Liquid side)
Refrigerant pipe
connecting port 9.5
22
108 (Gas side)
50
Unit external dimension 750
Drain pipe
Hanging bolt pitch 650
connecting port
650
570
355
345
233
170
117.5
50
20 233 18
Electrical control box
20
136 125 knockout hole 37 Wires
18
(For air taking-in air) Air filter 232 drawing-out port Under air intake type
Model MMD- A B C D
AP0076BH-E, AP0096BHP-E,
AP0076BHP-E, AP0096BH-E, AP0126BH-E
AP0126BHP-E 765 700 640 654
229
AP0156BH-E,AP0186BHP-E
AP0156BHP-E, AP0186BH-E 765 700 640 654
AP0246BH-E, AP0276BHP-E,
AP0246BHP-E, AP0276BH-E, AP0306BHP-E
AP0306BH-E 1065 1000 940 953.5
* Standard filter is provided, but deeper filtration filter needs to be purchased locally.
Options
TCB-SF56C6BPE
TCB-SF80C6BPE
TCB-SF160C6BPE
54
Ceiling Type
MMC-AP***7HP-E
10 16 22 28 34 (C)
Technical specifications
Model name MMC- AP0157HP-E AP0187HP-E AP0247HP-E AP0277HP-E AP0367HP-E AP0487HP-E AP0567HP-E
Cooling/Heating capacity*1 (kW) 4.5/5.0 5.6/6.3 7.1/8.0 8.0/9.0 11.2/12.5 14.0/16.0 16.0/18.0
Power requirements 1-phase 50Hz 230V (220–240V) / 1-phase 60Hz 220V (Separate power supply for indoor units required.)
Electrical
characteristics Power consumption
0.033/0.033 0.034/0.034 0.067/0.067 0.083/0.083 0.111/0.111
50 Hz/60 Hz (kW)
Note 1 : The capacities are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 m height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
55
MMC-AP0157HP-E to AP0567HP-E
Z view
Options
TCB-KP13CE, TCB-KP23CE
Elbow piping
TCB-DP31CE
Drain pump kit
TCB-PCUC1E
Optional connecting kit
56
MMK-AP0073H to AP0243H
1050
228
320
73.5
73.5
50
7
50
c
c
Space re quir ed for installation and se rv icing
50
110 or mor
T 72 78
(Unit: mm)
Technical specifications
Model name MMK- AP0073H AP0093H AP0123H AP0153H AP0183H AP0243H
Cooling/Heating capacity*1 (kW) 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0
Power requirements 1-phase 50Hz 230V (220-240V) (Separate power supply for indoor units required.)
Electrical
characteristics Power consumption
0.018 0.021 0.043 0.050
50 Hz (kW)
Height (mm) 320
External
Width (mm) 1050
dimensions
Depth (mm) 228
Total weight (kg) 15
Standard air flow
570/450/390 600/480/390 840/660/540 1020/750/570
Fan unit (High/Mid/Low) (m3/h)
Motor output (W) 30
Gas side (mm) ø9.5 ø12.7 ø15.9
Connecting pipe Liquid side (mm) ø6.4 ø9.5
Drain port (nominal dia.) 16 (polyvinyl chloride tube)
Sound pressure level*2
35/31/28 37/32/28 41/36/33 46/39/34
(High/Mid/Low) (dB(A))
Note 1 : The capacities are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 m height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
57
Console Type
MML-AP***4NH-E
Features
Elegant & simple design makes this unit a perfect fit for shops,
office buildings, and luxury apartments.
Bottom flow functionality ensures comfortable air bi-flow for
an advantage in heating and floor warming.
Multi-function operation is convenient, making adjustments by
the user possible using the wireless remote controller. Remote controller
MML-AP0074NH-E to AP0184NH-E
700 Space required for installation
100 70 and servicing
Dia. 80mm
60
100
A
C C
Air inlet
Air inlet Air inlet
600
Connecting pipe
Gas side
Connecting pipe
Liquid side
104 146
90
90
85
60
Technical specifications
Model name MML- AP0074NH-E AP0094NH-E AP0124NH-E AP0154NH-E AP0184NH-E
Cooling/Heating capacity*1 (kW) 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3
Electrical Power requirements 1-phase 50Hz 230V (220–240V) / 1-phase 60Hz 220V (Separate power supply for indoor units required.)
characteristics Power consumption 50 Hz/60 Hz (kW) 0.021 0.025 0.034 0.052
Height (mm) 600
External
Width (mm) 700
dimensions
Depth (mm) 220
Total weight (kg) 17
Standard air flow (High/Mid/Low) (m3/h) 510/366/282 552/408/324 624/468/384 726/528/426
Fan unit
Motor output (W) 41
Gas side (mm) ø9.5 ø12.7
Connecting pipe Liquid side (mm) ø6.4
Drain port (nominal dia.) 16 (Polyvinyl chloride tube)
Sound pressure level*2 (High/Mid/Low) (dB(A)) 38/32/26 40/34/29 43/37/31 47/40/34
Note 1 : The capacities are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 m height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
58
Slim & compact design Slim & compact design Air blown from front panel Air blown from top
Under-window mounting does Distribution can be reversed (factory default)
not block lighting. to suit occupant preference.
MML-AP0074H-E to AP0244H-E
95 Refrigerant pipe
connecting port
(Gas)
28
(Liquid side)
35
Lower refrigerant piping port
(knockout hole 50x100)
mounting (2 - 10)
(Liquid)
400 120
162
Refrigerant pipe
106
connecting port
(Gas side)
130
150
130 (Drain)
5 138
Drain pipe connecting port 177
(Liquid) (Gas)
430
more
Air inle t Wal l
120
57
Technical specifications
Model name MML- AP0074H-E AP0094H-E AP0124H-E AP0154H-E AP0184H-E AP0244H-E
Cooling/Heating capacity*1 (kW) 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0
Electrical Power requirements 1-phase 50Hz 230V (220–240V) / 1-phase 60Hz 220V (Separate power supply for indoor units required.)
characteristics Power consumption 50 Hz/60 Hz (kW) 0.056/0.053 0.092/0.092 0.102/0.113
Height (mm) 630
External
Width (mm) 950
dimensions
Depth (mm) 230
Total weight (kg) 37 40
Standard air flow (High/Mid/Low) (m3/h) 480/420/360 900/780/650 1080/930/780
Fan unit
Motor output (W) 45 70
Gas side (mm) ø9.5 ø12.7 ø15.9
Connecting pipe Liquid side (mm) ø6.4 ø9.5
Drain port (nominal dia.) 20 (Polyvinyl chloride tube)
Sound pressure level*2 (High/Mid/Low) (dB(A)) 39/37/35 45/41/38 49/44/39
Note 1 : The capacities are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 m height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
59
Easy maintenance
Simplified design of fan and drainage pipe eases
maintenance.
MML-AP0074BH-E to AP0244BH-E
and se rv icing
50
145
25
10
Electric parts box (earth terminal (for mounting rear side) (Gas side)
2−12×18 long hole
274
Air filter
80
B 110
Model MML- A B C D E 85 55 155
220
AP0074BH-E to AP0124BH-E 610 580 550 4 5
AP0154BH-E to AP0244BH-E 910 880 850 7 8 (Unit: mm)
Technical specifications
Model name MML- AP0074BH-E AP0094BH-E AP0124BH-E AP0154BH-E AP0184BH-E AP0244BH-E
Cooling/Heating capacity*1 (kW) 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0
Electrical Power requirements 1-phase 50Hz 230V (220–240V) / 1-phase 60Hz 220V (Separate power supply for indoor units required.)
characteristics Power consumption 50 Hz/60 Hz (kW) 0.056/0.058 0.090/0.096 0.095/0.110
Height (mm) 600
External
Width (mm) 745 1045
dimensions
Depth (mm) 220
Total weight (kg) 21 29
Standard air flow (High/Mid/Low) (m3/h) 460/400/300 740/600/490 950/790/640
Fan unit
Motor output (W) 19 70
Gas side (mm) ø9.5 ø12.7 ø15.9
Connecting pipe Liquid side (mm) ø6.4 ø9.5
Drain port (nominal dia.) 20 (Polyvinyl chloride tube)
Sound pressure level*2 (High/Mid/Low) (dB(A)) 36/34/32 42/37/33
Note 1 : The capacities are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 m height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
60
200 or
more
20
Wall
Wall
25
210
500 or
1000 or more
(Front side)
more Wall
(Front side)
815
Model MMF-MMF- A B C D E F
AP0154H-E to AP0274H-E 200 107 132 157 210 50
1750
Pipe holes on side AP0364H-E to AP0564H-E 380 125 120 160 390 40
(both sides)
(knockout hole) MMF-AP0151H MMF-AP0361H
50
Liquid Liquid
Rear side pipe hole side
Drain pipe port side
(φ130 knockout hole)
(both sides)
631
(knockout hole)
358
380
Gas
165
side
120
180
floor mounting B Refrigerant pipe connecting port (Gas side)
Floor fixing bracket Drain pipe Earth screw (M4)
(both sides) A
screw positions 640 connecting port Refrigerant piping position
(Unit: mm)
Note 1 : The capacities are measured under the conditions specified by JIS B 8615 based on the reference piping.
The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 m height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
61
(Unit: mm)
control of the air conditioner difficult, or placing large loads on Indoor unit
the system and its cooling performance.
Therefore it is frequently adopted to handle the fresh air to
a certain condition before the fresh air will enter in the main
air conditioner.
Fresh air
NOTE: The fresh air intake indoor unit is an air conditioner provided to handle the fresh air load and is not to control the room temperature.
For correspondence to the load of the indoor air controller, set an air conditioner separately.
Technical specifi cations
Model name MMD- AP0481HFE AP0721HFE AP0961HFE
Cooling/Heating capacity (Note 1) (kW) 14.0/8.9 22.4/13.9 28.0/17.4
Electrical Power supply (kW) 1-phase 50 Hz 230 V (220–240 V)/60 Hz 220 V
characteristics Power consumption (kW) 0.28/0.34 0.45/0.55 0.52/0.65
Height (mm) 492
External
Main unit Width (mm) 892 1392
dimensions
Depth (mm) 1262
Total weight (kg) 93 144
Standard air flow (m3/h) 1080 1680 2100
Motor output (kW) 0.160 0.160×2
Fan unit
External static pressure 50 Hz/60 Hz (Pa) 170-210-230 / 115-215-260 140-165-180 / 150-210-235 160-190-205 / 80-180-220
Air flow limit Lower limit/Upper limit (m3/h) 756/1188 1176/1848 1470/2310
Gas side (mm) ø15.9 ø22.2
Connecting pipe Liquid side (mm) ø9.5 ø12.7
Drain port (mm) 25
Sound pressure level (Note 2) (High/Med./Low) (dB(A)) 45/43/41 46/45/44
Cooling (Note 3) (°C) 5 – 43
Operation range
Heating (Note 4) (°C) –5 – 43
* The setting temperature is 16 – 27°C (standard FCU…18 – 29°C).
* An optional humidifier is not available with fresh air intake indoor unit.
* Height difference between fresh air intake indoor units must be within 0.5 m. Height difference between fresh air intake indoor unit and standard FCU must be within 30 m.
NOTE 1 Rated conditions Cooling: Outdoor air temperature 33°C DB/28°C WB setting temperature 18°C
Heating: Outdoor air temperature 0°C DB/–2.9°C WB setting temperature 25°C
Piping: Length 7.5 m / Height 0 m
NOTE 2 Normally, the values measured in the actual operating environment become large than the indicated values due to the effects of external sound.
NOTE 3 * When supply air temperature is “setting temperature + 3°C” or less, fresh air intake indoor unit operates as FAN mode.
* When supply air temperature is 19°C or less, Fresh Air Intake Indoor unit operates as FAN mode.
NOTE 4 * When supply air temperature is “setting temperature –3°C” or over, fresh air intake indoor unit operates as FAN mode.
63
Use Conditions
• In COOL mode, if temperature of the fresh air • In HEAT mode, if temperature of the fresh air is above
is below the setup temp. of +3°C, FAN status is the setup temp. –3°C, FAN status is automatically made.
automatically made. When temperature of the fresh When temperature of the fresh air is above 15°C, FAN
air is below 19°C, FAN status is also made regardless status is also made regardless of the setup temperature.
of the setup temperature.
Fresh air temp. (°C) −10 0 10 20 30 40 50 Fresh air temp. (°C) −10 0 10 20 30 40 50
Setup temp. Setup temp.
5 43 −5 43
MMD-AP0481HFE to AP0961HFE
Long hole for M10 hanging bolt
Type
1328 Spac e re quir ed fo r inst allation an d se rv icin g
Hole dia.-Width x Length
Hanging bolt pitch 1288
0481 4-φ12 x 40
Over
Service space
200
4-φ12 x 92 1262
0721, 0961
Fresh air
intake
indoor
unit
Hanging bolt pitch B
Over 1000
200
A
600
600
406
216 150
370
492
51
47
Model MMD- A B C D E F G H I J K L M N
AP0961HFE 1392 1260 250 250 250 250 250 250 250 250 10-M6 10-M6 φ22.2 brazin g φ12.7 flare
AP0721HFE 1392 1260 250 250 250 250 250 250 250 250 10-M6 10-M6 φ22.2 brazin g φ12.7 flare
(Unit: mm) AP0481HFE 892 810 215 107.5 107.5 215 250 250 8-M6 6-M6 φ15.9 flare φ9.5 flare
Options
Filter chamber
TCB-FCY51DFE
TCB-FCY100DE
Long life prefilter
TCB-PF3DE
TCB-PF4D-1E
High-efficiency filter 65
TCB-UFM3DE, TCB-UFM4D-1E
Drain pump kit High-efficiency filter 90
TCB-UFH7DE, TCB-UFH8D-1E
TCB-DP32DFE
64
efficiency.
(*1) Cooling and heating capacities are based on the following conditions:
Cooling capacities are based on : indoor temperature :27 °CDB/19°CWB, Outdoor temperature : 35°CDB
Heating capacities are based on : indoor temperature :20 °CDB, Outdoor temperature : 7 °CDB/6°CWB
Fan is based on High and Middle
( ): The figures in ( ) indicate the heat reclaimed from the heat recovery ventilator.
65
MMD-VN502HEXE
1690
1601 4-13 x 30 oval hole 173
550 (Hangling bracket)
25
EA RA
(Exhaust (Return Air)
Air)
400
Outdoor
1197
1140
800
side Indppr Side
250
SA
(Supply Air)
OA
(Outdoor Air) Power supply wire intake
152
200
25
600
( (
Heat exchange element Filter Motors,
Fans, Maintenance space
(Magnetic
Humidification element Maintenance space (
valve Decompression magnetic valve Water inlet
connecting
port (R1/2)
46
476
350
454
430
194 53
195
212
343
350
175
175
496 80
80 26 Refrigerant pipe connecting port (Liquid) 6.4
Drain pipe connecting port
Duct size (Nominal Diameter): 200 (VP25) Refrigerant pipe connecting port (Gas) 9.5
(Unit: mm)
MMD-VN802HEXE to VN1002HEXE/2
1739
1650 4-13 x 30 oval hole
550 (Hangling bracket)
25
RA
EA (Return Air)
(Exhaust
400
Air)
Outdoor
1246
1189
800
SA
(Supply Air)
OA
(Outdoor Air) Power supply wire intake
200
25
245
262
430
400
343
200
200
496 85
26
80 Drain pipe connecting port Refrigerant pipe connecting port (Liquid) 6.4
Duct size (Nominal Diameter): 250 (VP25) Refrigerant pipe connecting port (Gas) 12.7
(Unit: mm)
Options
VN-M***HE
* Does not connect to refrigerant piping from outdoor unit. Control wires can be connected.
Power (Extra high) 68-78/76 123-138/131 165-182/209 214-238/260 262-290/307 360-383/446 532-569/622 751-786/928 1084-1154/1294
consumption High 59-67/65 99-111/105 135-145/162 176-192/206 240-258/283 339-353/408 494-538/589 708-784/830 1032-1080/1220
50Hz/60Hz (W) Low 42-47/45 52-59/54 82-88/94 128-142/144 178-191/206 286-300/333 353-370/411 570-607/660 702-742/818
(Extra high) 150/150 250/250 350/350 500/500 650/650 800/800 1000/1000 1500/1500 2000/2000
Air volume (m3/h) High 150/150 250/250 350/350 500/500 650/650 800/800 1000/1000 1500/1500 2000/2000
Low 110/110 155/155 210/210 390/390 520/520 700/700 755/755 1200/1200 1400/1400
(Extra high) 82-102/99 80-98/97 114-125/167 134-150/181 91-107/134 142-158/171 130-150/185 135-156/165 124-143/165
External static
High 52-78/59 34-65/38 56-83/33 69-99/63 58-82/68 102-132/102 97-122/120 103-129/108 92-116/102
pressure (Pa)
Low 47-64/46 28-40/22 65-94/39 62-92/44 61-96/52 76-112/58 84-127/55 112-142/109 110-143/87
(Extra high) 26-28/27.5 29.5-30/31.5 34-35/35.5 32.5-34/33.5 34-36/35.5 37-38.5/38 39.5-40.5/41.5 38-39/39.5 41-42.5/42.5
Sound pressure
High 24-25.5/24.5 25-27/25 30-32/29.5 29.5-31/29 33-34/34 35.5-37/35 38.5-40/39 36.5-37.5/36.5 39.5-41/40
level (dB(A))
Low 20-22/20 21-22/21 27-29/23.5 26-29/24.5 31-32.5/29.5 33.5-35/32.5 34-35.5/33.5 36-37.5/35.5 37-38/36.5
Temperature (Extra high) 81.5/81.5 78/78 74.5/74.5 76.5/76.5 75/75 76.5/76.5 73.5/73.5 76.5/76.5 73.5/73.5
exchange High 81.5/81.5 78/78 74.5/74.5 76.5/76.5 75/75 76.5/76.5 73.5/73.5 76.5/76.5 73.5/73.5
efficiency (%) Low 83/83 81.5/81.5 79.5/79.5 78/78 76.5/76.5 77.5/77.5 77/77 79/79 77.5/77.5
(Extra high) 74.5/74.5 70/70 65/65 72/72 69.5/69.5 71/71 68.5/68.5 71/71 68.5/68.5
for heating High 74.5/74.5 70/70 65/65 72/72 69.5/69.5 71/71 68.5/68.5 71/71 68.5/68.5
Enthalpy exchange Low 76/76 74/74 71.5/71.5 73.5/73.5 71.5/71.5 73.5/73.5 72/72
efficiency (%) (Extra high) 69.5/69.5 65/65 60.5/60.5 64.5/64.5 61.5/61.5 64/64 60.5/60.5 64 /64 60.5/60.5
for cooling High 69.5/69.5 65/65 60.5/60.5 64.5/64.5 61.5/61.5 64/64 60.5/60.5 64/64 60.5/60.5
Low 71/71 69/69 67/67 66.5/66.5 64/64 65.5/65.5 64.5/64.5 67/67 65.5/65.5
Dimensions (Length x Width x Height) (mm) 900 x 900 x 290 1140 x 1140 x 350 1189 x 1189 x 400 1189 x 1189 x 810
Weight (kg) 36 38 53 70 143
Duct diameter (mm) 100 150 200 250 inside: 250, outside: 283 x 730
Around unit -10°C – 40°C 80% RH or less
Operating range Outdoor Air (OA) -15°C (*1) – 43°C RH
Return Air (RA) 5°C – 40°C 0% RH or less
* Air volume can be changed over to high (extra high) mode or low mode.
* Sound pressure level is measured 1.5m below the center of the unit.
*Sound pressure level is the value which was measured at the acoustic room.
*The actual values in an external operating environment are generally higher than the indicated values due to the contribution from
ambient noise.
* Sound pressure level is less than 70 dBA
67
VN-M150HE to VN-M350HE
1050 350
25
1140
170 EA(Exhaust Air) 454
RA(Return Air)
Earth Terminal
195
212
1140
1197
800
OA(Outdoor Air)
SA(Suppiy Air)
150~250 170
200
600 or more
25
175
4-13 × 30 Oval hole(Hanging Bracket)
Inspection Opening 450 × 450 or more
VN-M500HE, VN-M650HE
1050 25 350
1140
170
195
212
1140
1197
800
OA(Outdoor Air)
SA(Suppiy Air)
150~250 170
25
175
4-13 × 30 Oval hole(Hanging Bracket)
Inspection Opening 450 × 450 or more
(Unit: mm)
Heat Exchange Element Filter Motor,Fans Maintenance Space
Duct size (Nominal Diameter): 200
VN-M800HE, VN-M1000HE
1099 400
25
1189
195
85 Connecting Diagram 85
25
200
4-13 × 30 Oval hole(Hanging Bracket)
Inspection Opening 450 × 450 or more
VN-M1500HE, VN-M2000HE
1099 810
25
195
50 1189
EA(Exhaust Air) RA(Return Air) 454
730
262
245
1246
1189
800
262
245
Connecting Diagram 85
200
600 or more
25
Combination Pattern
1) Accessory for 4-way air discharge cassette type: 1 2 3 4 5 6
combination pattern
Fresh air inletbox
+ Fresh air filter Auxiliary fresh air Spacer for height Air discharge
Ceiling panel
Fresh air filter chamber flange adjustment direction kit
chamber
1 Ceiling panel OK OK OK OK OK
Remote controllers
TCB-IFCB640TLE
Analog I/F (DCvoltage)
TCB-IFLN642TLE/TCB-IFLN642UL
LonWorks®
Open
Network
System
TCB-IFMB640TLE
Modbus® RS485
RS485
Energy monitoring
Relay I/F Power Meter
Touch-screen Controller
BMS-CT5120E
Digital I/O Relay I/F
I/O
Device
MiNi-SMMS
TCC-LINK
Remote ON/OFF
TCB IFCB-4E2
Lite-Vision plus Remote Controller Wired remote controller Wired remote controller Simple remote controller Wireless remote Remote Sensor
RBC-AMS51E-ES with Weekly timer RBC-AMT32(31)E RBC-AS41E2 controller TCB-TC41LE
RBC-AMS51E-EN RBC-AMS41E
72
RBC-AX23UW(W)-E
Integral receiver (For 2-way air discharge cassette)
(MMU-AP ∗∗∗2WH)
73
Schedule timer
TCB-EXS21TLE
• Schedule timer mode
– 6 programmings per day
– Enabling 8 groups to be programmed
– A maximum of 64 indoor units can be controlled
– A maximum of 100 hours back-up power supply
• Weekly timer mode
– 7 types of weekly schedule and 3 programmings
per day
Other
Remote sensor Wired remote controller for air to air heat exchanger
TCB-TC41LE NRC-01HE
Install this sensor when outside • Up to 8 units of the Air to Air Heat Exchanger can be operated using
air has been introduced or when this remote controller.
overcooling and overheating are to • Control by 2 remote controllers is available.
be minimised. Two remote controllers can operate a single Air to Air Heat
Exchanger.
• Air conditioning units may be controlled in addition to controlling
the Air to Air Heat Exchanger.
• Central control allows linked ON/OFF operation of air conditioner
and Air to Air Heat Exchanger.
• Central control can be set to allow standalone operation of the Air to
Air Heat Exchanger.
• Switchable ventilation modes (Automatic/Air to Air/Normal)
• Switchable ventilation air volume (Extra-high/High-Low)
74
Power Supply
1-phase
Power unit
220-240V
50Hz
1-phase
220V
60Hz
TCC-LINK TCC-LINK
SMART BMS MANAGER
BMS-SM1280HTLE
or
Local Supply SMART BMS MANAGER
RS-485
WITH DATA ANALYSER
SMMS-e MiNi-SMMS
BMS-SM1280ETLE
Interface
Energy Monitoring Relay Interface
Digital I/O Relay Interface
Interfaces
TCC-LINK
RS-485
Interface
Energy Monitoring Relay Interface
Digital I/O Relay Interface
TOUCH SCREEN CONTROLLER
BMS-CT5120E
75
• Power meter
TOUCH SCREEN CONTROLLER
BMS-CT5120E (Local Supply)
1 kWh/pulse or 10 kWh/pulse
(Pulse duration 50 to 1000 ms)
(Maximum 8 power meters per interface)
FEATURES
• Icon display
BACnet® system
BACnet®/ IP
BMS-STBN10E TCC-LINK
RS-485
Local supply
Intelligent server
(BACnet® server software
required) BMS-LSV10E TCS-NET Relay
Interface
BMS-IFLSV4E
LonWorks®
TCC-LINK
Local supply
LN Interface
TCB-IFLN642TLE
Modbus®
Local supply
TCC-LINK
RS-485
Modbus® Interface
TCB-IFMB641TLE
77
• BACnet®
The BACnet® system operates in conjunction with the BACnet®.
Server uses object signals to provide the following functions:
• Control • Monitoring
– ON/OFF – ON/OFF
– Temperature setting – Operation mode
– Fan speed – Temperature setting
Intelligent Server – Room temperature
BMS-LSV10E – Local remote controller : permit / prohibit
• LonWorks® LN Interface
The LonWorks® interface manages the MiNi-SMMS air conditioning system
as a Lon device to communicate with the custormer’s Building Management
System and to monitor operational status.
A maximum of 64 units / groups are controllable per interface.
• SNVT signal
Signals and provides the following functions:
• Control • Monitoring
– ON/OFF – ON/OFF
LN Interface – Temperature setting – Operation mode
TCB-IFLN642TLE – Fan speed – Temperature setting
– Room temperature
– Local remote controller : permit / prohibit
• Modbus®
The Modbus® interface manages the MiNi-SMMS air conditioning system as a
Modbus® device to communicate with the custormer’s Building Management
System.
Accessible to 64 units / groups per one TCB-IFMB641TLE, 15 TCB-IFMB641TLEs
on one Modbus® Master (prepared by user).
Signals and provides the following functions:
• Control • Monitoring
– ON/OFF – ON/OFF
Modbus® Interface – Temperature setting – Operation mode
TCB-IFMB641TLE – Fan speed – Temperature setting
– Room temperature
– Local remote controller : permit / prohibit
1. LonWorks®: Registered trademark Echelon corporation.
2. BACnet®: ANSI/ASHRAE 135-2008, A data Communication Protocol for Building Automation and Control Networks.
3. Modbus® is a registered trademark of Schneider E.
78
Application controls
TCB-PCDM4E
TCB-PCMO4E
TCB-PCIN4E
TCB-IFCB-4E2
Size: 200 × 170 × 66 (mm) Remote location ON/OFF control box Monitoring
• Feature ON/OFF status (for indoor unit)
Start and stop of the air conditioner is possible Alarm status (system & indoor unit stop)
by an external signal and indication of operation/ ON/OFF command
alarm externally. Air conditioner can be turned ON/OFF by the
external signals.
Operation The external ON/OFF signals will initiate the
signals shown below.
Interface
Display
Remote Controller
80
Safety precautions
Concept
General purpose interface
• Controls the operation status of each indoor unit.
TCB-IFCG1TLE Modbus®
control • ON/OFF control of peripheral equipment via the
Optional devices
relay point of Toshiba's BMS. (1pt only)
Modbus®
I/F
Standard function
Central remote controller and Building
Management System devices can control ON/OFF
TCC-LINK function via digital I/O ports.
Optional function
Control using the following channels: 4-channel
relay control, 6-channel digital input, 2-channel
(HA) analog voltage input and output, and 2-channel
Sensors Switches Pump/ Lights
Daiseikai temperature measurement functions via Modbus®
motor
I/F.
Analog Interface
Concept
Analog interface
• Provides access to 64 indoor units.
TCB-IFCB640TLE
• Does not require special network knowledge.
Toshiba refrigeration and air-conditioning units are designed and The type of the refrigerant used for each of our products is shown in the
manufactured on the assumption that the product is used with a accompanying owners manual, or on the product label attached on the
product itself.
We have recently seen some cases where the type of refrigerant Toshiba Carrier Corporation shall not assume any liability for failures,
SAFETY PRECAUTIONS
For operation:
• Before use, read through the operating instructions to ensure proper use.
Concerning the purpose for which the air conditioners are to be used
• The air conditioners presented in this catalogue are air conditioning/heating units to be used solely by general consumers.
– Do not use these air conditioners for special applications such as for the storage of food items, animals, plants, precision machines or works
of art. Doing so may degrade the quality of the items.
– Do not use these air conditioners for air-conditioning applications in vehicles or ships. Doing so may cause water and/or power leakages.
Concerning the automatic defrosting unit • Locations where power is supplied from independent power
When the outdoor air temperature drops, frost may form on the generators. The power line frequency and/or voltage may
heat exchanger of the outdoor unit. In such cases, the automatic
defrosting unit will be activated, and it will take 5 to 8 minutes for the • Locations where high frequencies or electrical noise is
heating operation to be restored. generated (from high-frequency welders used for vinyl welding
and processing, high-frequency therapeutic devices used
Concerning the air conditioner's operating conditions and their for thermotherapy, etc.) The electronic components may be
selection
(1) Avoid using the air conditioner in the following locations. malfunction.
• Locations with acidic or alkaline atmospheres (locations at which • Locations where electronic equipment is installed. Electrical
highly acidic or alkaline air is directly drawn in, such as in hot
equipment.
The heat exchangers and other parts may become corroded. (3) Concerning use in locations with high ceilings
• • In locations with high ceilings, use of circulators for improving
oil or steam exhaust (such as at food preparation factories or the temperature distribution during heating is recommended.
machine plants). The heat exchangers may corrode; frost may
form as a result of heat exchanger malfunction; air conditioner (4) Concerning use in high-humidity environments
operating performance may be compromised or condensation • When the ceiling-recessed type of indoor unit is installed in a
location, such as those described below, and it is very hot and
damage; heat-insulation materials may become separated, etc. humid inside the ceiling, condensation may form on the external
surfaces of the indoor unit and drip down. In such cases, add
(2) Before using an air conditioner in any of the following locations, external heat-insulating materials.
– Locations such as food preparation sites in which the areas
• above the ceilings are hot and humid
as in bakeries or kitchens and restaurants that use edible – Locations in which outside air is drawn in and routed above the
oils) ...The air conditioner's operating performance may be ceiling
compromised or condensation may form as a result of clogged – Above ceilings with a slate roof or tiled roof overhead
prevailing conditions, take countermeasures such as tailoring the (5) Even when an air conditioner is shut down, it will still consume a
installation conditions in accordance with the conditions, using small amount of power to protect the unit. If the air conditioner
will not be used for a prolonged period, turn OFF the main switch
• Locations with disinfectant-induced chlorine atmospheres (water
(ground fault circuit breaker). However, before the unit is to be
tanks, etc.) The metal parts in the heat exchangers, motors, etc.,
used again, turn ON the main switch (ground fault circuit breaker)
may become corroded.
• Locations with high salinity (coastal areas, etc.) Corrosion for at least 12 hours in order to prevent trouble.
may occur so use outdoor units specifically designed to
withstand exposure to salt.
T201510C-ASIA/CO