Uniandes - CRS560CW - Data Sheet PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Data sheet

Project: UNIANDES
Editor: Areateam4
Date : 25.03.2020

Unit
Unit type: CRS 560 CW
Cooling capacity (total): 31,2 kW Airflow: 10.700 m³/h
Cooling capacity (sensible): 31,2 kW Air velocity: 2,5 m/s
Net total cooling capacity: 29,6 kW Return air temperature: 34 °C
Net sensible cooling capacity: 29,6 kW Return air humidity: 25 rel.%
EER: 19,50 kW/kW Supply air temperature: 22 °C
AER: 0,15 W/(m³/h) Altitude above sea level: 2.600 m
Sound power level: 89,8 dB(A) Height: 1.950 mm
LpA (2m freefield): 69,8 dB(A) Width: 600 mm
Total power consumption: 1,6 kW Depth: 1.175 mm
Weight: 254 kg
Power supply: 460V/60Hz/3Ph/N/PE

Fan (Data per unit)


Supply air direction: Supply air left/right Power consumption: 1,6 kW
Fan type: R3G355 ESP external static pressure: 0 Pa
Number: 3 Total pressure drop: 294 Pa
Max. revolutions: 2.067 U/min Control voltage: 9,4 V
Nominal power: 2,2 kW Motor-efficiency: 81 %
Revolutions: 2.050 rpm

Hydraulics (Data per unit)


Pressure drop CW Coil: 7 kPa Medium inlet temperature: 12,0 °C
Pressure drop 2-way valve: 9 kPa Medium outlet temperature: 18,0 °C
Pressure drop pipework: 5 kPa Medium volume flow: 4,6 m³/h
Total pressure drop: 21 kPa Percentage of glycol: 20 %
Type of Medium: Ethylenglycol
Nominal size 2-way valve: DN32
Information with ''Standard coil (A)''!
Caution: Unit capacity is calculated with reduced airflow to meet a valid fan working point due to changed altitude above sea level !

The above mentioned data are determined and rated in accordance to EN 14511 and therefore are subject to measuring tolerances. Unless otherwise stated, all data Page 1 of 1
refer to a product in basic version.
StulzSelect Vers. 3.3.2 - New Project: 1 x CRS 560 CW

You might also like