Uniandes - CRS560CW - Data Sheet PDF
Uniandes - CRS560CW - Data Sheet PDF
Uniandes - CRS560CW - Data Sheet PDF
Project: UNIANDES
Editor: Areateam4
Date : 25.03.2020
Unit
Unit type: CRS 560 CW
Cooling capacity (total): 31,2 kW Airflow: 10.700 m³/h
Cooling capacity (sensible): 31,2 kW Air velocity: 2,5 m/s
Net total cooling capacity: 29,6 kW Return air temperature: 34 °C
Net sensible cooling capacity: 29,6 kW Return air humidity: 25 rel.%
EER: 19,50 kW/kW Supply air temperature: 22 °C
AER: 0,15 W/(m³/h) Altitude above sea level: 2.600 m
Sound power level: 89,8 dB(A) Height: 1.950 mm
LpA (2m freefield): 69,8 dB(A) Width: 600 mm
Total power consumption: 1,6 kW Depth: 1.175 mm
Weight: 254 kg
Power supply: 460V/60Hz/3Ph/N/PE
The above mentioned data are determined and rated in accordance to EN 14511 and therefore are subject to measuring tolerances. Unless otherwise stated, all data Page 1 of 1
refer to a product in basic version.
StulzSelect Vers. 3.3.2 - New Project: 1 x CRS 560 CW