Seismic Load Considered Is As Per SAES-A-112. If Calculated The Value Shall Be 0.02 (See The Calculation Below.)

1. The seismic load for the structure is calculated according to ASCE 7-10. The calculated seismic load is 0.02. 2. Key parameters like the mapped spectral acceleration, site coefficients, design spectral response acceleration, seismic design category, structural system properties, and calculation of the seismic response coefficient are determined. 3. All calculations show the seismic design category is C and the seismic response coefficient Cs used is 0.02, which is the minimum allowed value.

Uploaded by

Mohamed Rafik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
170 views2 pages

Seismic Load Considered Is As Per SAES-A-112. If Calculated The Value Shall Be 0.02 (See The Calculation Below.)

1. The seismic load for the structure is calculated according to ASCE 7-10. The calculated seismic load is 0.02. 2. Key parameters like the mapped spectral acceleration, site coefficients, design spectral response acceleration, seismic design category, structural system properties, and calculation of the seismic response coefficient are determined. 3. All calculations show the seismic design category is C and the seismic response coefficient Cs used is 0.02, which is the minimum allowed value.

Uploaded by

Mohamed Rafik
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

1. Seismic Load considered is as per SAES-A-112. If calculated the value shall be 0.

02 (see the
calculation below.)

ASCE 7 Seismic Load (12.8 Seismic Equivalent Lateral Force Procedure)


Code Version: ASCE 7-10

1.Seismic Ground Motion Values(Section 11.4):


Occupancy category = I (Table 1-1)
Mapped spectral response acceleration: (from USGS)
at short periods, Ss = 0.204 2 2
at 1-second period, S1 = 0.058 2 2
(From Geo
Site class = C report)
1.20
Site coefficient (Table 11.4-1), Fa = 1.200 1.200 0
1.70
Site coefficient (Table 11.4-2), Fv = 1.700 1.700 0
Design spectral response acceleration: (Section 11.4.4)
at short periods, Sds=2/3FaSs = 0.163
at 1-second period, Sd1=2/3FvS1 = 0.066

2.Seismic Design Category(Section


11.6):
SDC as per table 11.6-1: A
SDC as per table 11.6-2: A
(choose more severe value
Seismic design category = C above)
*Exception of SDC Ditermination:
Ts=Sd1/Sds = 0.40
Check Ta < 0.8Ts No
Check S1 < 0.75 Yes
Exception of SDC NOT APPLY

Final SDC defined : C

3.Structural System Selection(Section


12.2):
Seismic Force-Resisting System:
(Table 12.2-1)
Light-framed Steel
Structure
Response modification coeffieient, R = 3 (Table 12.2-1)

4.Seismic Resoponse Coefficient Cs(Section 12.8.1.1):


Importance factor, I = 1 (Table 1.5-2)
(Equation
Cs=Sds/(R/I) = 0.054 12.8-2)
*Maximum value of Cs
Structure Type = stl M frame (Table 12.8-2)
Ct = 0.028 (Table 12.8-2)
x= 0.80 (Table 12.8-2)
Total building height, h = 100 ft.
Approximate foundamental period, Ta = secon (Section
Ct hx = 1.115 d 12.8.2.1)
Coefficient, Cu = 1.7 (Table 12.8-1)
secon (Section
Tmax = CuTa = 1.895 d 12.8.2)
secon (Section
Foundamental period (T<=Tmax), T=Ta = 1.115 d 12.8.2)
secon
Long-period transition period, TL = 12 d (Figure 22-12)
(Equation
If T<=TL, Cs max=SD1/(T(R/I)) = 0.020 12.8-3)
(Equation
If T>TL, Cs max=SD1TL/(T2(R/I)) = 0.212 12.8-4)
Cs max = 0.020
Cs min = 0.01
Cs used= 0.020