Ficha Tecnica Terminales Tipo Codo 200A 15KV Elastimold

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Issue Date: 07/25/2016

Page: 1 of 4
File: PSS-162LR-W5X

15kV 200A Loadbreak Elbow w/ Test Point 162LR-W5X

162LR
Loadbreak Elbow
Connector

Applications:
The Elastimold® 162LR Elbow Connector is a fully
rated 15kV, 200 Amp Class loadbreak connector. It
includes provisions for energized operation using
standard hotstick tools allowing loadmake/loadbreak
operation and a visible disconnect. It has a
standard interface for connecting to 15kV, 200 Amp
bushing inserts, junctions, and operating
accessories. The 162LR is designed for connecting
to and operating 15kV Class, 200 Amp distribution
apparatus. It provides a convenient method to
connect/disconnect cable and equipment on power
distribution systems. The 162LR allows the
connection of cables with insulation diameters from
.575’’ (14,6mm) to 1.220’’ (31,0mm) with only four
elbow sizes. (#4 solid, 175 mil to 4/0 stranded, 260
mil)

Features:

 15kV, 200 Amp Loadbreak Elbow


Ratings:
 Fully shielded, fully submersible molded rubber housing
Meets ANSI/IEEE Standard 386, Latest Revision
 100% peroxide-cured construction includes insulation For 15kV Voltage Class:

and conductive EPDM materials 8.3kV Max Phase-to-Ground – Operating Voltage


14.4kV Max Phase-to-Phase
95kV BIL – Impulse Withstand (1.2 x 50
 Provision for hot stick operation microsecond wave)
34kV AC – One minute withstand
 Provision for ground wire connection 53kV DC – 15 minutes withstand
11kV AC – Corona Extinction @ 3pC sensitivity
200 Amp – Continuous and Loadbreak
 Wide cable range with minimum number of sizes 10kA Sym – 10 Cycles Momentary & Fault Close

 Long bi-metal compression lug is standard

 Non-corrosive capacitive test point


Issue Date: 07/25/2016
Page: 2 of 4
File: PSS-162LR-W5X

15kV 200A Loadbreak Elbow w/ Test Point 162LR-W5X

CATALOG NUMBER SELECTION


Step 1 (W)
Determine the insulation diameter of the cable.
Select the insulation letter code that best straddles the insulation
diameter from W table below. Insert code into catalog number.

Step 2
Insert conductor material code from the Material Code table.
Code 5 is standard.

Step 3 (X)
Choose the proper compression lug code according to the
conductor size from the Conductor Code Table. Insert code into
catalog number.

Material Code

2 Copper*

5 Bi-metal**

W Code XXX Code

162LR -

Cable Insulation Cable Insulation


Conductor Size AWG or
XXX Code

Diameter in Inches Diameter in mm Connector only


Symbol
MIN. MAX. MIN. MAX. for W kcmil
0.575 0.740 14.61 18.80 A Strand./ Solid/ Bi-
Copper
Compr. Comp. mm 2 Metal
0.635 0.905 16.13 22.99 B
190 - #4 16.76 02500190 02702190
0.805 1.060 20.45 26.92 C
200 #4 #3 21.14 02500200 02702200
0.890 1.220 22.61 30.99 D
210 #3 #2 26.67 02500210 02702210
Example: #2 #1 33.62 02500220 02702220
220
The ordering number for an Elbow Connector
for a 1/0 compressed/stranded, 220 mil wall 230 #1 1/0 42.41 02500230 02702230
cable with an insulation diameter of .805’’ to
.895’’ and capacitive test point is 162LR- 240 1/0 2/0 53.49 02500240 02702240
B5240. 2/0 3/0 67.43 02500250 02702250
250
Each kit contains the following: 260 3/0 4/0 85.01 02500260 02702260

1 Elbow connector housing 162BLR-W 270 4/0 250 107.20 02500270 02702270
1 Bi-metal compression lug 02500XXX
1 Probe 162LRF
1 Probe wrench 271-94 Notes:
1 Tube, lubricant 82-08
* Copper compression lug suitable for all copper conductor sonly.
1 Crimp chart CC-0020 ** Bi-metal compression lug with universal aluminum barrel suitable for copper or aluminum conductors.
1 V.D Cap-Peroxide 156-7
1 Installation Instruction IS-1378
Issue Date: 07/25/2016
Page: 3 of 4
File: PSS-162LR-W5X

15kV 200A Loadbreak Elbow w/ Test Point 162LR-W5X

IMPORTANT:
For safety purposes, a sealing & grounding kit with the loadbreak elbow is HIGHLY
RECOMMENDED. Please choose from the sealing and grounding kit below:

Jacket Concentric Copper Tape


Neutral Cable Shield Cable

200ECS 200ECSG3

For Jacketed Concentric For Copper Tape Shield


Neutral Cables, the sealing Cables, the sealing &
kit part number will be: grounding kit part number will
200ECS or add suffix “-S” to be:
part number for cables with 200ECS or add suffix “-S” to
nominal O.D. within the range part number for cables with
of .80”-1.50” nominal O.D. within the range of
.80”-1.50”
Example:
The ordering number for an Elbow Example:
Connector for a 1/0 The ordering number for an Elbow
compressed/stranded, jacketed Connector for a 1/0
concentric neutral, 220 mil wall compressed/stranded, copper tape
cable with an insulation diameter of shield, 220 mil wall cable with an
.805’’ to .895’’, overall cable insulation diameter of .805’’ to
diameter is 1.03” and capacitive .895’’, overall cable diameter is
test point is 1.05” and capacitive test point is
162LR-B5240-S. 162LR-B5240-SG3.
For installation instruction for the For installation instruction for the
200ECS, please see IS-459 200ECSG3, please see IS-460
Issue Date: 07/25/2016
Page: 4 of 4
File: PSS-162LR-W5X

15kV 200A Loadbreak Elbow w/ Test Point 162LR-W5X

Unishield
Cable

For Unishield Cables, the shield


10TL-W adapter part number will be:
10TL-W, where the “W” letter code will
be determined by the insulation
diameter of the Unishield cable. Please
see W Table below for W code. Or add
suffix “-TL” to the part number. Copper Tape Concentric
Shield Cable Neutral Cable
W Code

10TL -

Cable Insulation
Cable Insulation
Diameter in Symbol
Diameter in mm
Inches for W
MIN. MAX. MIN. MAX.
0.495 0.585 12.6 14.9 EB
0.525 0.635 13.3 16.1 EF
0.575 0.685 14.6 17.4 FA
0.625 0.735 15.9 18.7 FAB
0.675 0.785 17.1 19.9 FB
0.725 0.835 18.4 21.2 FG
0.775 0.885 19.7 22.5 GA
0.825 0.935 21.0 23.7 GAB
0.875 0.985 22.2 25.0 GB
0.930 1.040 23.6 26.4 GH
0.980 1.115 24.9 28.3 HA
1.040 1.175 26.4 29.8 HAB
1.095 1.240 27.8 31.5 HB
1.160 1.305 29.5 33.1 HJ
1.220 1.375 31.0 34.9 JA
1.285 1.395 32.6 35.4 JAB
1.355 1.520 34.4 38.6 JB
1.485 1.595 37.7 40.5 KA
1.530 1.640 38.9 41.7 KAB
1.575 1.685 40.0 42.8 KB
1.765 1.875 44.8 47.6 PB

Example: Example: Example:


Partial installation example of Partial installation example of
The ordering number for an
162LR-B5240-SG3 for copper 162LR-B5240-S for
Elbow Connector for a 1/0
tape shield cables. concentric neutral cables.
compressed/stranded Uni-shield,
For full instruction please see For full instruction please see
220 mil wall cable with an
IS-460. IS-459.
insulation diameter of .825’’ to
.9.35’, overall cable diameter is
1.03” and capacitive test point is
162LR-B5240-TL.