Kohler MPAC 1500 Operation Manual
Kohler MPAC 1500 Operation Manual
Kohler MPAC 1500 Operation Manual
Controls:
MPACt 1500
Software (Code) Version 2.0 or higher
TP-6714 4/10a
Table of Contents
5.7 Exerciser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
5.7.1 Setting the Exerciser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
5.7.2 Source/Source Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
5.8 Prime Power Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
5.8.1 Prime Power Mode Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
5.8.2 Prime Power Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
5.9 Time Delays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
5.9.1 Time Delays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
5.9.2 Load Control Time Delays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
5.9.3 Set S1 Time Delays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
5.9.4 Set S2 Time Delays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
5.10 Load Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5.10.1 Time-Based Load Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5.10.2 Current-Based Load Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5.11 Source Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
5.11.1 Phase Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
5.11.2 In-Phase Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
5.11.3 Preferred Source Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
5.11.4 System Voltage and Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
5.11.5 Voltage and Frequency Pickup and Dropout Settings . . . . . . . . . . . . . . . 75
5.11.6 Set Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
5.12 Programmable Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
5.12.1 Main Logic Board Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
5.12.2 Input/Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
5.12.3 Input Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
5.12.4 Output Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
5.12.5 User-Defined I/O Function Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . 82
5.13 Common Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
5.13.1 Common Alarm Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
5.13.2 Audible Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
5.13.3 Chicago Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
5.14 Set System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
5.14.1 Source Type/Source Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
5.14.2 Transition Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
5.14.3 Service Entrance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
5.14.4 Rated Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
5.14.5 Three Source Engine Start Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
5.14.6 Transfer Commit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
5.14.7 Remote Test Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
5.14.8 Peak Shave TD Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
5.14.9 USB Data Logger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
5.14.10 Min/Max Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
5.15 Three-Source Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
5.15.1 Three Source Engine Start Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
5.15.2 Preferred Source Toggle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
5.15.3 Three Source System Test and Exercise . . . . . . . . . . . . . . . . . . . . . . . . . 87
5.15.4 Three-Source System Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
5.15.5 ATS1 and ATS2 System Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
5.16 Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
5.17 Set Passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
5.18 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Section 6 Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
6.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
6.2 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
6.2.1 Serial Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
6.2.2 Ethernet Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
6.3 Communications Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
6.3.1 Serial Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
6.3.2 Ethernet Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
6.4 USB Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
6.4.1 File Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
6.4.2 Event History Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
6.4.3 Configuration files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
6.4.4 Controller Application Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
6.4.5 Data Logger Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
6.4.6 MinMax Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
6.4.7 SyncData Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Section 7 Scheduled Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
7.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
7.2 Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
7.2.1 Weekly Generator Set Exercise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
7.2.2 Monthly Automatic Control System Test . . . . . . . . . . . . . . . . . . . . . . . . . . 104
7.3 Inspection and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
7.3.1 General Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
7.3.2 Other Inspections and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
7.4 Service Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Section 8 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
8.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
8.2 Accessory Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
8.3 Accessory Module Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
8.4 Input/Output (I/O) Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
8.5 Alarm Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
8.5.1 Alarm Board DIP Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
8.5.2 External Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
8.5.3 Audible Alarm Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
8.5.4 Alarm Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
8.5.5 Alarm Silence Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
8.6 External Battery Supply Module (EBSM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
8.7 Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
8.8 Transient Voltage Surge Suppressor (TVSS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
8.8.1 Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
8.8.2 TVSS Remote Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
8.8.3 TVSS Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
8.9 Supervised Transfer Control Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
8.9.1 Automatic Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
8.9.2 Non-Automatic Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
8.10 Current Sensing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
8.11 Load Shed (Forced Transfer to OFF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
8.11.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
8.11.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
8.12 User Interface Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
8.13 Line-to-Neutral Voltage Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
8.14 Logic Disconnect Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
8.15 Monitoring Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Appendix A Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Appendix B Screen Summaries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
This manual provides operation instructions for Kohlerr operation and to avoid bodily injury. Read and follow the
MPACt 1500 automatic transfer switch controls and Safety Precautions and Instructions section at the
related accessories. beginning of this manual. Keep this manual with the
equipment for future reference.
This manual applies to MPACt 1500 controllers with
controller application code (software) version 2.0.0 or A separate transfer switch operation and installation
higher. To check the code version, go to the View manual provided with the unit contains instructions for
Control Parameters screen. See Section 4 for transfer switch installation, manual operation,
instructions. scheduled maintenance, and bypass/isolation
procedures, if applicable.
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to The equipment service requirements are very important
change this literature and the products represented to safe and efficient operation. Inspect parts often and
without notice and without any obligation or liability perform required service at the prescribed intervals.
whatsoever. Obtain service from an authorized service distributor/
dealer to keep equipment in top condition.
Read this manual and carefully follow all procedures
and safety precautions to ensure proper equipment
D Visit the Kohler Power Systems website at East China Regional Office, Shanghai
KohlerPower.com. Phone: (86) 21 6288 0500
Fax: (86) 21 6288 0550
D Look at the labels and stickers on your Kohler product India, Bangladesh, Sri Lanka
or review the appropriate literature or documents India Regional Office
included with the product. Bangalore, India
Phone: (91) 80 3366208
D Call toll free in the US and Canada 1-800-544-2444.
(91) 80 3366231
D Outside the US and Canada, call the nearest regional Fax: (91) 80 3315972
office. Japan, Korea
North Asia Regional Office
Headquarters Europe, Middle East, Africa Tokyo, Japan
(EMEA) Phone: (813) 3440-4515
Kohler Power Systems Fax: (813) 3440-2727
3 rue de Brennus
93200 Saint Denis Latin America
France Latin America Regional Office
Phone: (33) 1 49 178300 Lakeland, Florida, USA
Fax: (33) 1 49 178301 Phone: (863) 619-7568
Fax: (863) 701-7131
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 6264-6422
Fax: (65) 6264-6455
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening the enclosure. GM21079
2
NOTICE
3 4 5
Electrostatic discharge damage. Electrostatic discharge
(ESD) damages electronic circuit boards. Prevent 12 6
electrostatic discharge damage by wearing an approved
grounding wrist strap when handling electronic circuit boards 7
or integrated circuits. An approved grounding wrist strap
provides a high resistance (about 1 megohm), not a direct Main Logic
8
short, to ground. Board
Figure 1-1 shows the locations of the DIP switches and 1. Access openings to RJ-45 and USB connectors
connectors on the main logic board. It is not necessary 2. Latch
to open the cover to access the USB or Ethernet 3. RS-485 connection TB2
connectors. 4. I/O board connection P16
5. User interface connection P14
6. DIP switches SW1
7. RJ-45 Ethernet connection P13
8. USB connection P12
9. Programmed-transition interface board (PTIB) connection
(factory connection)
10. Ground wire
11. Contactor harness connection
12. Input/output terminal strip TB1
TB1
12
6
Output 2 NO
Output 1 NO
Output 2 C
Output 1 C
Output 2 NC
Output 1 NC
Input 2B
2
Input 1B 1
Input 2A
Input 1A
7
1
NC = normally closed
NO = normally open
C = common 6431
Figure 1-2 Logic Board Input and Output 1. Contactor Harness Connection
Connections to TB1 2. Ground Connection
Figure 1-4 Relay Transfer Time Settings If the available source is the preferred source, and
the contactor is in the standby position, the
contactor transfers to preferred, the engine
cooldown time delay runs, and then the engine
start contacts open.
1
If the available source is the preferred source and
the contactor is already in the preferred position,
the engine start contacts open immediately,
bypassing the engine cooldown time delay.
TP-6714
Enter Password Use the open arrow buttons to enter the Test
Time to Enter #:## password. See Section 3.4 for instructions. Then
>????<
press the OK button.
OK
Type of Test
Auto Load Press the down arrow button to step to the
Time :## min loaded test screen.
B Main " Start
B Main Start
3.2 User Interface Panel D Time and date of next scheduled exercise
1 2 3 4
6
8
GM46892
7
Back Save
Press the open UP arrow button to
increase the first digit of the
password from 0 through 9.
Press the open up arrow
Note: The default password is 0000. button to increase the first
digit. (Use 00:00 to 23:59 for
time.)
3 Enter Password
Time to Enter #:##
0???
OK
8
Set Time 1#:##
Set Time/Date
5
Press Save.
B Y " Main
B Y " Main B Y " Back B Y " Back B Y " Back Back Save
For closed-transition models, the setup password is Note: The factory default password is 0000.
required to initiate a transfer when the programmed
Enter Password
transition override function is set to manual. See Time to Enter #:##
Section 3.10.3. >????<
System Ready
B Y Main
LD Exer 12/14 @ 16:00
Norm 480V Emer 480V
Emer AB BC AC
B View Set Test ##Hz ###V ###V ###V
Norm L1 L2 B Y Main
##Hz ###V ###V
Lamp Emer AN BN CN
B Y Test Main ##Hz ###V ###V ###V
B Y Main
Emer L1 L2
##Hz ###V ###V
Amps LA LB LC
#### #### ####
B Y Main
B Y Main
Amps L1 L2
#### ####
Time/Date
09:10 DST 01/13/06
B Y Main
B Y Main
Time/Date
09:10 DST 01/13/06
Daylight Saving Time
Clock Ahead 1 Hour
B Y Main
Sun 03/12/06
B Y Main
Daylight Saving Time
Clock Ahead 1 Hour
Daylight Saving Time
Sun 03/12/06
Clock Back 1 Hour
B Y Main
Sun 11/05/06
B Y Main
Daylight Saving Time
Clock Back 1 Hour Normal Preferred
Sun 11/05/06 Util-Gen Operation
B Y Main No Commit Transfer
B Y Main
Normal Preferred
Util-Gen Operation Standard Transition
No Commit Transfer Phase Rotation ABC
B Y Main In Phase Enabled
B Y Main
Standard Transition
The Sequence of Operation descriptions in Sections 3.6 Unloaded Exercise Sequence Starts
through 3.9 describe the transfer switch normal
operation for standard, programmed, and closed 1. Exerciser timer begins.
transition models, and for service entrance models.
2. The generator is signaled to start.
Operation can be affected by faults such as the normal
or emergency contacts failing to open or close when 3. The generator starts and the standby source
signaled to do so. becomes available.
3.6.1 Preferred Source Loss and 4. The load bank control is activated.
Return, Standard Transition
Unloaded Exercise Sequence Ends
Following is an explanation of the transfer switch
sequence of operation when Preferred Source failure is 1. The load bank control is deactivated.
detected.
2. Engine cooldown time delay expires.
Preferred Source Fails 3. The engine start contacts open, signaling the
generator to stop.
1. Load control contacts open.
4. The generator starts and the standby source 2. The generator is signaled to start.
becomes available.
3. The generator starts and the standby source
5. Preferred-to-standby time delay expires. becomes available.
6. The engine start contacts open, signaling the 4. Immediate failure to acquire standby alarm.
generator to stop.
5. Post-transfer load control sequences and engine
cooldown time delay expire.
5. Load control contacts close. 5. Post-transfer load control sequences and engine
cooldown time delay expire.
6. The engine start contacts open, signaling the
generator to stop. 6. Load control contacts close.
3. The load bank control is activated. 4. Post-transfer load control sequences and engine
cooldown time delay expire.
Unloaded Test Function is Ended
5. Load control contacts close.
1. The load bank control is deactivated.
6. The engine start contacts open, signaling the
2. Engine cooldown time delay expires. generator to stop.
Preferred Source Fails 2. The engine start contacts close, signaling the
generator set to start.
1. Load control contacts open.
3. The generator starts and the standby source
2. Engine start time delay expires. becomes available.
3. The generator is signaled to start (engine start 4. Preferred-to-standby time delay and pre-transfer
contacts close). load control sequences run.
4. The generator starts and the standby source 5. Load control contacts open.
becomes available.
6. Contactor transfers to Off position.
5. Preferred-to-standby time delay expires.
7. Off-to-standby time delay expires.
6. Contactor transfers to Off position.
8. Contactor transfers to standby source.
7. Off-to-standby time delay expires.
9. Post-transfer load control sequences run.
8. Contactor transfers to standby source.
10. Load control contacts close.
9. Post-transfer load control sequences run.
Emergency Source Fails (Normal Source is
10. Load control contacts close. available)
1. Standby-to-preferred and pre-transfer load control 2. Immediate failure to acquire standby alarm.
time delays expire.
3. Load control contacts open.
2. Load control contacts open.
4. Contactor transfers to Off position.
3. Contactor transfers to Off position.
5. Off-to-preferred time delay expires.
4. Off-to-preferred time delay expires.
6. Contactor transfers to preferred source.
5. Contactor transfers to preferred source.
7. Post-transfer load control sequences and engine
6. Post-transfer load control sequences and engine cooldown time delay expire.
cooldown time delay expire.
8. Load control contacts close.
7. Load control contacts close.
9. Engine start contacts open.
8. The generator is signaled to stop (engine start
contacts open).
7. Load control contacts close. 7. Post-transfer load control sequences and engine
cooldown time delay expire.
8. The engine start contacts open, signaling the
generator to stop. 8. Load control contacts close.
1. The generator is signaled to start (engine start 4. Off-to-preferred time delay expires.
contacts close).
5. Contactor transfers to preferred.
2. The generator starts and the standby source
becomes available. 6. Post-transfer load control sequences and engine
cooldown time delay expire.
3. Pre-transfer load control time delays expire and
load control contacts open. 7. Load control contacts close.
4. Preferred-to-standby time delay expires. 8. The engine start contacts open, signaling the
generator to stop.
5. Contactor transfers to the Off position.
3.8.1 Preferred Source Loss and 2. The engine start contacts close, signaling the
Return, Service Entrance Models generator set to start.
4. The generator starts and the standby source 7. Source 1 circuit breaker opens.
becomes available.
8. Off-to-standby time delay expires.
5. Preferred-to-standby time delay expires.
9. Source 2 circuit breaker closes.
6. Source 1 circuit breaker opens.
10. Post-transfer load control time delays expire.
7. Off-to-standby time delay expires.
11. Load control contacts close.
8. Source 2 circuit breaker closes.
Emergency Source Fails (Normal Source is
9. Post-transfer load control time delays expire. available)
10. Load control contacts close. 1. Immediate failure to acquire standby alarm.
2. Exerciser is deactivated.
Preferred Source Returns
1. Pre-transfer load control time delays expire. 3. Load control contacts open.
5. Off-to-preferred time delay expires. 7. Post-transfer load control time delays expire and
load control contacts close.
6. Source 1 circuit breaker closes.
8. Engine cooldown time delay expires and engine
7. Post-transfer load control sequences and engine start contacts open.
cooldown time delay expire.
7. Engine cooldown time delay expires. 7. Post-transfer load control sequences and engine
cooldown time delay expire.
8. The engine start contacts open, signaling the
generator to stop. 8. Load control contacts close.
1. The engine start contacts close, signaling the 4. Off-to-preferred time delay expires.
generator set to start.
5. Source 1 circuit breaker closes.
2. The generator starts and the standby source
becomes available. 6. Post-transfer load control sequences and engine
cooldown time delay expire.
3. Pre-transfer load control time delays expire and
load control contacts open. 7. Load control contacts close.
4. Preferred-to-standby time delay expires. 8. The engine start contacts open, signaling the
generator to stop.
5. Source 1 circuit breaker opens.
6. Check/wait for source synchronization. 2. The generator is signaled to start (engine start
contacts close).
Note: If the sources do not synchronize before the
Fail to Sync time delay expires, the 3. The generator starts and the standby source
programmed-transition override function becomes available.
operates. See Section 3.9.2.
4. Load control contacts open.
7. When sources are synchronized, emergency
source contacts close. 5. Check/wait for source synchronization.
8. Normal source contacts open within 100 Note: If the sources do not synchronize before the
milliseconds. Fail to Sync time delay expires, the
programmed-transition override function
Note: If the normal contacts do not open, the operates. See Section 3.9.2.
emergency contacts will be signaled to open
and a Fail to Transfer fault will be activated. 6. When sources are synchronized, emergency
source contacts close.
Loaded Exercise Sequence Ends
7. Normal source contacts open within 100
1. Pre-transfer load control sequences run. milliseconds.
2. Load control contacts open. Note: If the normal contacts do not open, the
emergency contacts will be signaled to open
3. Check/wait for source synchronization. and a Fail to Transfer fault will be activated.
Type of Test
Press the Test button to enter the
Loaded
Test mode. A password is required.
B Main Start
Type of Test
Unloaded
B Main Start
Type of Test
Sync Check
B Main Start
System on Test
Norm ###V Emer ###V
3.10.4 Auto-Loaded System Test
Synced
End
The auto-loaded test feature is a timed, loaded test. The Main >< Test
auto-loaded time delay determines how long after the
transfer to standby to terminate the test and transfer Figure 3-15 Sync Check Screens
back to the preferred source. The time is defaulted to
30 minutes and can be adjusted from 1 minute to
60 minutes. See Figure 3-14.
1 3 2
Figure 3-20 Fault Reset If one or more accessory modules are disconnected
from the controller, the message Module Status Change
appears. See Figure 3-23. Pressing the Reset button
3.14 Accessory Module Faults displays the message Check Module Setup to Clear
Fault. Use the following Module Uninstall Procedure to
uninstall modules after disconnection.
3.14.1 Module Status Change
Connecting or disconnecting one or more accessory Module Status Change
modules can cause the Module Status Change Press Reset.
Norm ###V Emer ###V
message to be displayed.
Reset View Set Test
Module Connection (new or reconnected module)
Check Module Setup Press Main and follow
Installing or reconnecting one or more accessory to Clear Fault Module Uninstall
modules triggers the Module Status Change message. Procedure.
See Figure 3-21. Press the Reset button to display B Y Reset Main
Reset New Module. Press the Reset button from that
screen. The controller recognizes the module type(s).
Figure 3-23 Screens after Module Disconnection
See Figure 3-22.
4. Press the down arrow to step to the Set Inputs/ Procedure to Clear a Module Status Conflict
Outputs screen.
1. Disconnect power to the transfer switch.
5. Navigate to the Set Auxiliary I/O screen. See
Figure 3-24. Press the right arrow button to see the 2. Disconnect the module.
status of module 1. Press the down arrow to step to 3. Close the enclosure door and reconnect power to
the next module, if necessary, until the screen
the ATS. The display will show Module Status
shows Status: Lost.
Change.
6. Press the right arrow button to move to the 4. Press the button labeled Reset. The display will
Uninstall Module screen. Verify that the screen
show Check Module Setup to Clear Fault.
says Uninstall Module Yes. (Press the open arrow
button to toggle no/yes, if necessary.) 5. Follow the procedure in Section 3.14.1 to uninstall
the module through the ATS controller keypad.
7. When Yes is displayed, press Save to uninstall the
module. 6. Disconnect power to the ATS.
8. Repeat the uninstall procedure for additional 7. Connect the new module.
modules, if necessary.
8. Close the enclosure door and reconnect power to
Other Module Status Change Conditions the ATS. The display will show Module Status
Change. See Figure 3-21.
A Module Status Change message that cannot be
cleared as described in this section may indicate a 9. Press the button labeled Reset to display Reset
failure of the controller’s real-time clock. Carefully follow New Module. Press the reset button from that
the Module Connection or Module Uninstall procedures screen. The controller will now recognize the new
to attempt to reset the fault. If the fault cannot be reset, module type.
the controller’s logic board may need to be replaced.
Contact an authorized distributor/dealer for service. 10. Navigate to the Set Auxiliary I/O screen to check
the status and settings for the new module. See
Figure 3-24. Press the right arrow button to see the
status of module 1. Press the down arrow to step to
the next module, if necessary,
Set
Set Inputs/Outputs Main Board I/O
1. Use the black arrow buttons to step to the desired 3.15.3 Reset Default Parameters
screen.
Resetting to the default parameters will reset all
parameters, including the system voltage and
2. Press the open up arrow button to toggle Yes or No
until Yes is displayed. frequency, to a factory default setting. The default
system voltage and frequency settings may not match
3. Press Save to reset the records or parameters to the settings for your application.
the factory defaults. Pressing Back exits the
screen without resetting. The transfer switch will not operate correctly if the
system voltage and frequency do not match the
sources. Use the Set Sources screen to set the system
3.15.1 Reset Maintenance Records voltage and frequency after resetting to the default
parameters. See Section 6 for instructions.
Reset the maintenance records after transfer switch
service to update the last maintenance date and totals Check the system operation to verify the settings after
since reset that are displayed in the maintenance resetting.
records screen.
Reset
Event History
Yes/No
B Save Back
Reset
Test Password
Yes/No
B Save Back
Delete Files
File Maintenance Filename
Save Back
View
4.2 Main Screen View
Source2 Time Delays
Exerciser Setup
The main screen appears at system startup. See
B Y " Main B Y " Main
Figure 4-1.
Press the View button to navigate to the View screens View View
Inputs/Outputs
shown in the following sections. Prime Power Setup
The display returns to the main screen after 30 minutes B Y " Main B Y " Main
of no activity (no buttons pressed).
View View
System Setup Common Alarm
System Setup
View Enabled/Disabled Rated Current
Prime Power Setup S1 Duration DD:HH:MM 225 Amps
S2 Duration DD:HH:MM B Y Back
B Y " Main B Y Back
System Setup
Press the right arrow 3 Src Eng Start Mode
(") button to view Mode 1/Mode 2
source S1 and S2 run B Y Back
settings.
System Setup
Remote Test Loading
Loaded/Unloaded
B Y Back
System Setup
Peak Shave TD Bypass
Enabled/Disabled
B Y Back
B Y Back
B Y Back
B Y Back
B Y Back
Current-based load control screens, continued from Source 1 time delay screens.
Current-Based Contrl B
Amps Lvl Remove Srce1 Current-Based Contrl
Amps: #### Load # Add Source1
Priority: #
B Y " Back
B Y " Back
Current-Based Contrl
Amps Lvl Add Source1 B
Amps: ####
Current-Based Contrl
B Y " Back Load # Remove Source1
####
B Y " Back
B
Current-Based Contrl
Load # Remove Source1
Priority: #
B Y Back
B Y Back
B Y Back
B Y Back
B Y Back
Current-based load control screens, continued from Source 2 time delay screens.
Current-Based Contrl B
Amps Lvl Remove Srce2 Current-Based Contrl
Amps: #### Load # Add Source2
B Y " Back Priority: #
B Y " Back
Current-Based Contrl
Amps Lvl Add Source2
Amps: #### B
Current-Based Contrl
B Y " Back Load # Remove Source2
####
B Y " Back
B
Current-Based Contrl
Load # Remove Source2
Priority: #
B Y Back
Module #1
Output ##
Function Description
See Section 5.12 for input and output function descriptions. B Y Back
5.1 Introduction The test password is not affected by this DIP switch.
Use the Reset Data screen to disable the test password.
This section contains setup instructions, including:
SW1-2, Maintenance. The maintenance DIP switch
D Controller DIP switch settings
inhibits transfer. Use it to prevent transfers while
D Default settings servicing the ATS. When this switch is in the ON
D Passwords position, sensing, timing, engine start and contactor
D Changing parameter settings using the setup menus functions are disabled. A preferred source failure will be
ignored. The Not in Auto LED flashes red and the
message Maintenance Mode is indicated on the LCD
5.2 Source Names screen. In addition, a programmable digital output is
turned on and an entry in the event log indicates that the
The controller uses various designations for the maintenance mode has been activated. System
sources. Source S1 is connected to the Normal side of
monitoring and setup are allowed while in maintenance
the transfer switch. Source S2 is connected to the mode.
Emergency side of the transfer switch. In a typical
application, Source S1 is the utility source, and source Switch SW1-2 should be ON only during
S2 is the standby generator set. Other applications may maintenance or service. It must be OFF during
use different configurations, such as the gen-gen normal operation.
configuration which uses two generator set sources and
no utility. Close and lock the enclosure door before energizing the
transfer switch.
The Preferred Source is the source that will be used if
both sources are available. Typically, this is the normal
utility source, S1. The Set Preferred Source menu
1
allows the operator to select either source as the
preferred source. Source S2 (connected to the
emergency side of the contactor) can be set as the
preferred source using this menu. See Section 5.11.3
for more information about preferred source selection. Main Logic
Board
In the load control setup menus, N is the preferred
source and E is the standby source.
System Ready
LD Exer ##/## @ ##:## Press the Set button in the main screen to enter the Setup screens.
Norm ###V Emer ###V The setup password is required.
B View Set Test
Enter Password
Time to Enter #:## Appears if the password disable DIP
Incorrect Password Password Disabled switch is set. Press OK to proceed.
>????<
OK OK
Set Time/Date
Press the down arrow B button to step to the next screen.
B Y " Main Press the right arrow " button to enter the detailed setup screen.
Set Exerciser
B Y " Main
B Y " Main
<
<
Enable Daylight Saving
Example:
2nd Sun of Mar Time
YES/NO
Back Save
Interval Daily, weekly, monthly, or day/month. This setting works with the repeat rate to set the time interval between
exercise runs.
The day/month selection allows you to set the exerciser to run on the same day every month. For example, the
exerciser can be set to run the first Sunday of every month. Use caution with the day/month selection. For
example, selecting day/month on the 5th Friday of the month will cause the exerciser to run only during months
that have five Fridays.
Repeat Rate The repeat rate works with the interval to set the time interval between exercise runs. For example, if Day is
selected as the interval, and 5 is selected as the repeat rate, then the exercise will repeat every 5 days. Select
a number between 1 and 12.
Duration Enter the exercise run duration in hours:minutes. For example, a run time of 00:30 will run the generator set for
30 minutes. The maximum run time is 24 hours.
Start Date Enter the date, month/date/year, of the first exercise event. Subsequent events will be scheduled based on the
interval and repeat rate.
Start Time Enter the desired start time of the exercise run in hours:minutes. The time settings range from 00:00 to 23:59,
with 00:00=midnight.
Weekly
Monthly
Day/Month Exerciser Event ##
Daily Start Time ??:??
Back Save
D Connect the engine start leads of the source 1 During a prime power sequence, the preferred source
generator set to output 1. Connect to a different selection alternates so that the generator set operating
output on the main logic board or accessory I/O at the time is designated as the preferred source.
module if output 1 is not available. Assign the Source
N Start Signal function to the output connected to the Press the end button to start the other generator set and
source 1 generator set engine start leads. See transfer the load. The generator set run time may be
Section 5.12, Programmable Inputs and Outputs. ended by pushing the end time delay button. This will
start the alternate source, transfer the source, and run
D Check the overfrequency and underfrequency pick on the alternate source for the programmed period of
up and drop out settings for both sources, and adjust if time. The first generator set will run for the programmed
necessary. engine cooldown time and then be signaled to stop.
D Set the normal source engine start and engine To stop the prime power run sequence, enter the Set
cooldown time delay settings. menus (password required), navigate to the Set Prime
Power Run menu, Prime Power Event Sequence
D Navigate to the Set Prime Power Run menu. Enable Start/Stop. Use the up arrow button if necessary to
the prime power event and program the S1 and S2 switch to Stop, and press Save.
Set Prime Power Run Prime Power Event Duration at Source1 Duration at Source2
Enable/Disable ??:??:?? DD:HH:MM ??:??:?? DD:HH:MM
Back Save
Load # Add Source1/Source2 For current-based load control. See Section 5.10.2. 0 sec
0--60 min
Load # Remove Srce1/Srce2 For current-based load control. See Section 5.10.2.
* The optional external battery module allows extended engine start time delays from 0--60 min.
Back Save
B
Current-Based Control
Load #? Add Source1
Priority : ?
Back Next
B
Load #? Remove Src1
??:??
Back Next
B
Current-Based Control
Load #? Remove Src1
Priority : ?
Back Next
B
Current-Based Control
Source1 Load Cntrl#?
Enable/Disable
Back Save
B
Current-Based Control Set Hi Current Level
Set Hi Current Level Amps: ????
Load Remove Source1
B
Load #? Rec N>E
??:??
Back Save
B
Current-Based Control
Load #? Add Source2
Priority : ?
Back Next
B
Load #? Remove Src2
??:??
Back Next
B
Current-Based Control
Load #? Remove Src2
Priority : ?
Back Next
B
Current-Based Control
Source2 Load Cntrl#?
Enable/Disable
Back Save
B
Current-Based Control Set Hi Current Level
Set Hi Current Level Amps: ????
Load Remove Source2
The controller allows control of up to 9 separate loads. Setting up the load control function requires the
Two load control modes allow selected loads to be following steps:
disconnected and reconnected to the source:
1. Connect each selected load to an output terminal
D Time-based load control adds and removes loads on the main logic board or one of the input/output
according to a timed sequence before and after modules. The high power module accessory is
transfer. available for high voltage or high current loads.
D Current-based load control adds or removes loads 2. Use the Set Inputs/Outputs screen to assign the
according to the current measured through the connected output to one of the load control outputs
transfer switch. This mode allows load control based 1--9. See Section 5.12.
on power usage.
3. Proceed to step 4 to set time-based load control for
The load control function is not activated if the controller source 1, if required. Skip to step 7 if time-based
detects no available source. load control is only needed for source 2 (standby
source).
Note that the load control can be set up to operate during
transfer to Source1 and/or Source2. Your application 4. In the Set S1 Time Delays menu, select Time as the
may require load control during transfer to one source load control mode.
(e.g. a generator set) but not the other source (e.g. the
5. Enter the number of loads to control, which is equal
utility).
to the number of loads connected to outputs in
Two types of load control are available: time-based load step 1.
control and current-based load control. Load Control
6. Use the Set S1 Time Delays menu to set the
setup parameters are found in the Set Time Delays
following associated time delays.
menus.
a. Load # Disc N>E: pre-transfer time delay
Note: The load control setup parameters are found in
disconnects loads a programmed time before
the Set S1 Time Delays and Set S2 Time Delays
transfer from Normal to Emergency. The
menus.
pre-transfer delays operate during loaded test,
loaded exercise, or programmed transfers for
5.10.1 Time-Based Load Control peak shave operation when the transfer is
controlled.
The time-based load control function allows selected
loads to be disconnected from the source before b. Load # Rec E>N: post-transfer time delay
transfer and reconnected to the source after transfer at reconnects loads a programmed time after
different time intervals. The loads can be connected and transfer to Normal. The post-transfer time
disconnected at different times for each source. The delay allows delayed or staggered addition of
pre-transfer signals are active only when both sources selected loads to avoid starting numerous large
are available. motors or other large loads at the same time.
Staggering the loads can minimize voltage dips
When the load control function is activated, the contacts as large loads come online.
open a programmed length of time before transfer to
allow controlled disconnection of selected loads. After c. Loads to Add: Enter the number of loads that
transfer, the contacts remain open for a programmed have been connected to load control outputs for
length of time and then close to allow controlled pre-transfer disconnect and delayed
application of selected loads. For example, large motor reconnect.
loads such as an air conditioner can be delayed to start
after other essential loads have been transferred. Repeat for source 2 if time-based load control is
required for source 2:
The pre-transfer signals overlap the preferred-to-
standby and the standby-to-preferred time delays. See 7. In the Set S2 Time Delays menu, select Time as the
Figure 5-11. The longer delay determines the time load control mode.
delay before transfer.
Example 1:
Example 2:
The add priority and remove priority settings are set d. Load # Add Source1 (Source2) Priority: Assign
separately and can be different for the same load. Add a priority to each load. This number will be used
Priority #1 loads are added first. Remove Priority #1 to determine the order in which loads are added
loads are removed first. if the current drops below the low limit.
Example: If you have four loads, with one load that e. Load # Remove Src1 (Src2): Enter the time to
should be added first and removed last, set wait before the load is removed. This prevents
Add Priority = 1 and Remove Priority = 4 for that load. nuisance changes caused by brief current
Prioritize the other loads according to the order in which spikes. See Figure 5-12.
they should be added and removed.
f. Load # Remove Src1 (Src2) Priority: Assign a
Adjustable time delays prevent load addition and priority to each load. This number will be used
removal caused by momentary current variations. to determine which loads are removed first if
There are three time delays associated with each load. the current rises above the high limit. (The
See Figure 5-12 for time delays and other load control priority 1 load is removed first.)
parameters.
g. Source1 Load Ctrl # Enable/Disable: Toggle to
Enable and press Save to enable load control
Current-Based Load Control Setup Procedure: for the selected load.
1. Connect each selected load to an output terminal
on the main logic board or one of the input/output 6. Set Hi Current Level, Load Remove
Source1/Source2: Set the high current level. If the
modules. The high power module accessory is
current rises above this limit, loads will be removed
available for high voltage or high current loads.
in order of their remove priority settings until the
2. Use the Set Inputs/Outputs screen to assign the current falls back to an acceptable level.
connected output to one of the load control outputs
7. Set Lo Current Level, Load Add Source1/Source2:
1--9. See Section 5.12.
Set the low current level. If the current drops below
3. In the Set S1 or Set S2 Time Delays menu, select this level and some loads are not connected, loads
Current as the load control mode. will be added in the order of their add priority
settings. (The add priority and remove priority
settings for a load may be different.)
Figure 5-14 Preferred Source Selection Effect on System Parameters and Time Delays
Set Synchronization
Voltage Differential ? ? Percent
Set Synchronization
Frequency Differential ? ? Hz
Preferred Source
Set Preferred Source Normal/Emergency
Normal Source
Set Normal Source Set Number of Phases ? Phase
Emergency
B Y " Back B Y " Back Save Back
Inputs and outputs are unassigned (except as noted in There are two programmable inputs and two
Figure 5-17) until the installer or operator assigns a programmable outputs on the controller’s main logic
function to the I/O. board. Additional inputs and outputs are available
through the installation of optional input/output
The programmable inputs and outputs on the modules.
controller’s main logic board and input/output (I/O)
modules can be assigned to the functions shown in See the Installation Section for connection information
Figure 5-18 and Figure 5-19. Use the Input/Output for main logic board inputs and outputs.
Setup Screen to assign input and output functions . See
Figure 5-16. 5.12.2 Input/Output Modules
Input and output functions can also be assigned over Input/output (I/O) modules are optional accessories.
Modbus using Monitor III software. Refer to the Monitor The standard I/O Module has two inputs and six outputs.
III operation manual for instructions. The high-power I/O module has two inputs and three
outputs. The I/O modules specifications are shown in
Each programmable input and output requires a Section 8.4.
connection to the transfer switch. Do not change the
programmable input/output assignments without See Section 8.4 for I/O module connection information.
verifying the transfer switch input and output
connections.
Set Inputs/Outputs Press the right arrow button to enter the Set Inputs/Outputs screen.
B Y " Main
<
Module #?
Uninstall Module?
Yes/No
Save Back
«
Programmable Inputs * LED LED Display Message
Bypass Contactor Disable* None Flashing Bypass Contactor Disable *
Forced Transfer to OFF* (programmed-transition None Flashing Forced Off
models only; requires load shed accessory; not
applicable to bypass/isolation switches)
Inhibit Transfer* (maintenance mode) None Flashing Inhibit Transfer
Low Battery Voltage Steady None Low Battery Voltage
Peak Shave Mode None None Peak Shave
Remote End Time Delay None None None
Remote Common Alarm Steady None Remote Common Alarm
Remote Test None None Normal test sequence screens. See
Section 3.10.
Remote Monitor In #1--4 None None None
Three-Source System Disable None None None
* See Figure 5-17 for factory-set input functions for selected models. Do not change the factory settings.
Figure 5-18 Available Programmable Inputs
Emergency (standby)
source available
Engine cooldown
Set Common Alarms Set Common Alarms Modify Alarm Alarm Description Alarm Description
Alarm Group 1 Common Y Audible N Common Y Audible N
B Y " Main B Y " Back B Y " Back B Y " Back Back Save
3 Src Eng Start Mode 3 Src Eng Start Mode Pref Source Toggle
Mode 1/Mode 2 Enable/Disable
B Y " Back Back " Save Back Save
Min/Max Values
?? Days/Weeks
Back Next
2. Three-source systems require the following input/ 4. Set voltage selector switch SW11-1 on the battery
output connections to control the engine start module (EBSM) to 12 or 24VDC.
commands for generator sets 1 and 2. Observe the
polarity of all connections shown in Figure 5-28. Note: See Section 8.6 for more information on the
Use wire sizes from #14 AWG to #20 AWG for EBSM.
EBSM and I/O module connections.
5. Assign the ATS1 programmable output connected
a. Connect the ATS2 engine start contacts to the in step 2b. to Three-Source System Disable.
engine start circuit on generator set 2 (G2).
6. Assign the following inputs and outputs for the
Note: See the Installation Section for the engine second transfer switch.
start contact locations. Engine start
contacts are labeled with a decal. a. Assign ATS2 main logic board programmable
input 1 to Three-Source System Disable.
b. Connect one ATS1 main logic board
programmable output to one ATS2 main logic b. Assign the ATS2 main logic board
board programmable input as shown in programmable output connected in step 2c. to
Figure 5-28. This I/O connection will be set to Source N Start Signal.
Three-Source System Disable.
3. Connect battery power. Use #14-28 AWG wire to ATS2: Set the source type to Util-Gen-Gen. Set the
connect the generator set engine starting battery 3 Src Engine Start Mode to Mode 1 or Mode 2 as
(or batteries) to the BATT1 terminals on terminal described in Section 5.15.1.
block TB13 on the external battery supply module
(EBSM). (Another battery(ies) can be connected The transfer switch settings are summarized in
to terminals BATT2 but is not required.) Follow the Figure 5-26.
ATS2
N E
TO G2
N E
NOTE: THE CLOSED IN EMERGENCY AUXILLIARY
ENGINE START
L CONTACT THAT IS USED IN THE ENGINE START CIRCUIT
OF THE ATS MUST BE REMOVED FROM THE CIRCUIT
WHEN USED WITH THIS THREE SOURCE CONTROL SCHEME.
N/C REFERENCE ATS WIRING DIAGRAM FOR CONNECTIONS.
LOAD
LEGEND
OPERATION
WHEN UTILITY FAILS ATS2 STARTS G1. ATS1 TRANSFERS TO THE EMERGENCY POSITION. IF G1 FAILS ATS2
WILL START G2 AND ATS2 WILL TRANSFER TO EMERGENCY. IF G1 RETURNS THEN ATS2 WILL RE--TRANSFER
BACK TO NORMAL. ATS1 WILL RE--TRANSFER BACK TO NORMAL AFTER THE UTILITY RETURNS. WHEN THE
UTIITY IS AVAILABLE, THE BATTERY SUPPLY MODULE WILL PROVIDE POWER TO THE CONTROLLER ON ATS2.
THE 3 SOURCE SYSTEM DISABLE INPUT AND OUTPUT WILL PREVENT ATS2 FROM STARTING EITHER GENSET
WHILE THE UTILITY SOURCE IS AVAILABLE.
THE BATTERY SUPPLY MODULE USES UP TO TWO BATTERY INPUTS (9--36VDC) AND PROVIDES A 12V
OUTPUT THAT POWERS THE ATS CONTROLLER. THIS IS CONNECTED TO THE CONTROLLER BY SNAPPING IT
TO AN EXISTING I/O MODULE OR THROUGH A HARNESS TO P3 ON THE CONTROLLER (WHEN AN I/O
MODULE IS NOT USED). THE BATTERY SUPPLY MODULE WILL CONTINUALLY PROVIDE POWER TO THE
CONTROLLER UNLESS THE ON/OFF INPUT ON THE BATTERY SUPPLY MODULE IS ENABLED.
THE ON/OFF INPUT ON TB1 OF THE BATTERY SUPPLY MODULE CAN BE USED IN CONJUNCTION WITH THE
NORMALLY OPEN CONTACT OF A PROGRAMMABLE OUTPUT FROM AN INPUT/OUTPUT MODULE TO TURN THE
BATTERY SUPPLY MODULE OFF WHEN A SOURCE IS AVAILABLE.
GM28627B
12
3 Source System Disable
6
Connect Output 1 terminals
TB1-5 and TB1-6 on ATS 1 to
Input 1 terminals TB1-1 and
TB1-2 on ATS2.
7
1
Assign ATS 1 main logic board
output 1 to 3 Source System ATS1 TB1
Disable. on logic board
12
6
Connect one normally closed G1 ES
output from ATS2 to G1 engine
start (ES) connections. Assign to
Engine Start Source N.
7
1
ATS2 TB1
Connect the ATS2 engine start contacts (on on logic board
6446
PC Terminating resistor
may be required
Input
RS-232 RS-485
GND1
B1 (+)
RS-232 to RS-485
A1 (--)
In Device
port converter
Out
RS-485
PC
1 3
In Device
Out
TB2
RS-485
4 6
In Last
GND1
B1 (+)
Out Device
A1 (--)
Terminating
resistor, 121 Ohms
Customer connections
6431
Modbusr TCP/IP
Ethernet Modbusr TCP/IP ATS 1500
Category 5e Network Category 5e Controller IP
xx.xx.xx.03
PC with network
interface card Note: The PC and the ATS must be on the same subnet.
IP xx.xx.xx.02 Note: A crossover cable can be used to connect the PC
to the ATS controller through the Ethernet port.
Device
RS-485
PC with network
interface card
Last device
IP xx.xx.xx.01 Terminating
resistor
Remote
Serial
Setting Range Serial (modem) Ethernet Notes
Modbus Server TCP Enabled or X Enable for network communication through the ethernet
Disabled port.
Modbus Server Enabled or X X Enable for Modbus communication through the serial port
Disabled on the main logic board. See Section 6.2.
Modbus Addr 001-247 X X Address for the RS-485 serial port (on the logic board).
default 1
Baud Rate 9600, 19200, X X Baud rate in bits per second for serial communication
57600 between the controller and a personal computer’s COM
port.
Modbus TCP Unit ID — — — X Factory-set to 3. A unit ID is required for Modbus over
TCP communication. The unit ID for TCP communication
is analogous to the Modbus address for serial
communication through the RS-485 ports.
IP Address — — — X Obtain from your local network administrator. Every device
on the network must have a unique IP address.
Subnet Mask — — — X Obtain from your local network administrator.
MAC Address Factory-set — — X Hardware address, entered at the factory. Not adjustable.
Appears only in the Communications View screen.
2. Press the Download button to load new files from a A message on the display indicates when file
memory device to the controller. Or, press the transfer is complete.
Download Upload
D Transfer (upload) the file from the controller to a USB D Communications settings
storage device as instructed in Section 6.4.1. D Calibration factors
D Use a personal computer to select the The configuration file is automatically updated when the
presentyymmdd.his file on the storage device. Save operator changes the transfer switch settings. A backup
the file to the computer, if desired. configuration file is also created automatically.
D Use a spreadsheet program to open the file on the Configuration files from one transfer switch can be
computer. saved to a mass storage device and then loaded onto
other transfer switches for quick setup of multiple
The resulting file includes the events with time and date switches. Serial numbers and descriptions entered
formatted into spreadsheet columns. See Figure 6-11 through Monitor III software (or other Modbus
for an example of an event history file viewed with application) are not changed by downloading
spreadsheet software. configuration files to a transfer switch.
Replace all barriers and close and lock the enclosure Only authorized personnel should
door after maintenance or service and before reapplying open the enclosure.
power.
WARNING
WARNING
Contact an authorized distributor/dealer to inspect and 7.3.2 Other Inspections and Service
service the transfer switch if any of the following
conditions are found inside the transfer switch. Have an authorized distributor/dealer perform
scheduled maintenance, service, and other
D Accumulations of dirt, dust, moisture, or other maintenance that ensures the safe and reliable
contaminants operation of the transfer switch. See Section 7.4,
Service Schedule, for the recommended maintenance
D Signs of corrosion items and service intervals.
Adjust,
See Visually Repair,
System Component or Procedure Section Inspect Check Replace Clean Test Frequency
Electrical System
Check for signs of overheating or loose connections:
7.3.1 X X Y
discoloration of metal, melted plastic, or a burning odor
Check the contactor’s external operating mechanism D (clean
7.3.1 X Y
for cleanliness; clean and relubricate if dirty * and lube)
Inspect wiring insulation for deterioration, cuts, or
abrasion. Repair or replace deteriorated or damaged 7.3.1 X D D Y
wiring
Tighten control and power wiring connections to
2 D D Y
specifications
Check the transfer switch’s main power switching
contacts’ condition; clean or replace the main contacts S/M D D D Y
or replace the contactor assembly as necessary
Control System
Exercise the generator set under load 7.2.1 X W
Test the transfer switch’s automatic control system 7.2.2
X X M
2.5
Test all indicators (LEDs) and all remote control
2.4 X D D D Y
systems for operation
General Equipment Condition
Inspect the outside of the transfer switch for any signs
of excessive vibration, leakage, high temperature, 7.3.1 X X M
contamination, or deterioration *
Check that all external hardware is in place, tightened,
7.3.1 X X X M
and not badly worn
Inspect the inside of transfer switch for any signs of
excessive vibration, leakage, high temperature, 7.3.2 D D D Y
contamination, or deterioration*
Check that all internal hardware is in place, tightened,
7.3.2 X D D Y
and not badly worn
* Service more frequently if the transfer switch is operated in dusty or dirty areas.
See Section: Read these sections carefully for additional information before attempting maintenance or service.
Visually Inspect: Examine these items visually.
Check: Requires physical contact with or movement of system components, or the use of nonvisual indications.
Adjust, Repair, Replace: Includes tightening hardware and lubricating the mechanism. May require replacement of components depending
upon the severity of the problem.
Clean: Remove accumulations of dirt and contaminants from external transfer switch’s components or enclosure with a vacuum cleaner or by
wiping with a dry cloth or brush. Do not use compressed air to clean the switch because it can cause debris to lodge in the components and
cause damage.
Test: May require tools, equipment, or training available only through an authorized distributor/dealer.
Symbols used in the chart:
X= The transfer switch operator can perform these tasks. W=Weekly
D=An authorized distributor/dealer must perform these tasks. M=Monthly
S/M = Service Manual. An authorized distributor/dealer must perform Q=Quarterly
these tasks. S=Semiannually (every six months)
Y=Yearly (annually)
1 2
2
3
GM40764
4 3
There are four DIP switches on the alarm module board. Chicago Alarm mode requires the horn to sound and a
Two of the switches are not used at this time. See lamp or LED to light when the switch is in the emergency
Figure 8-11. To enable the preferred source selection (non-preferred) position. The horn continues to sound
function, set DIP switch 1 to ON. If the supervised unless the alarm silence button is pressed. When the
transfer switch is installed on the ATS, set DIP switch 2 fault is cleared, the alarm silence is ended and reset for
to ON. the next alarm.
DIP Switch Function For Chicago Alarm Mode, use the Common Alarm
1 Preferred source selection enable Setup screen to assign the necessary faults and
conditions to the audible alarm. See Section 5.13. Be
2 Supervised transfer enable
sure to assign the Contactor in Standby condition to
3 Not used trigger the audible alarm.
4 Not used
A remote alarm or indicator light can also be connected
Figure 8-11 Alarm Board DIP Switches
to the alarm board to indicate the alarm condition. See
Section 8.5.2.
8.5.2 External Alarm
A customer-supplied external alarm horn can be 8.5.5 Alarm Silence Mode
connected to the alarm module at terminal block TB14.
Connect to the normally open or normally closed contact In Alarm Silence Mode, the horn is disabled. Alarm
as recommended by the alarm manufacturer’s Silenced appears on the display and the system alert
LED lights.
instructions.
The Alarm Silenced condition can be assigned to a
Item Specification programmable output. See Section 5.12 for instructions
Wire Size #12-22 AWG Cu
to assign outputs.
D Three-source systems. Three-source systems use The battery voltage selection DIP switch SW11-1 allows
two transfer switches and two standby power sources selection between 12-volt and 24-volt systems for low
in addition to the preferred power source. The EBSM battery voltage sensing and indication. Connect one or
provides power to the second ATS controller when two batteries to the external battery supply module. Use
the preferred source (connected to ATS1) is a battery charger to maintain the battery(ies) connected
supplying the load. See Section 5.15 for instructions to the EBSM.
to set up a three-source system.
DIP Switch SW11-1 Setting Battery Voltage
D Installations with frequent utility power outages. OFF 12 VDC
The EBSM provides power to the ATS controller when ON 24 VDC
neither source is available, preserving the controller’s
backup battery. Figure 8-15 Battery Voltage Selection
The EBSM produces 2 amps at 12 VDC with 9--36 VDC Connection and Voltage Setting
input. The EBSM input is reverse-polarity protected.
The EBSM outputs a low battery voltage signal when the 1. Use #14-28 AWG wire to connect one or two
external battery voltage falls below 11 VDC for a 12-volt batteries to terminal block TB13. (A second battery
system or 22 VDC for a 24-volt system. can be connected but is not required.) Follow the
marking on the board for the positive (+) and
negative (--) connections. See Figure 8-14 and
1 Figure 8-15.
4
2
GM42227-A
1. Connector P20
2. LED indicators
3. Battery input connection terminal block TB13
4. 12/24 volt DIP switch SW11-1. OFF=12 VDC, ON = 24 VDC
1
Right Side View
GM69824
HYGROSTAT
GM71056 CIRCUIT
BREAKER
GM71278
1
1
GM69824
1. TVSS assembly
8.8.2 TVSS Remote Status Indicator
Figure 8-20 TVSS Location, Typical A customer-supplied indicator for the optional transient
voltage surge suppressor (TVSS) can be connected to
provide remote indication when the TVSS needs to be
8.8.1 Diagnostic LEDs replaced. The contact changes state when the TVSS
Red and green indicators on each Transient Voltage module needs replacement.
Surge Suppression (TVSS) module indicate protection
Connect customer-provided indicators or alarms to the
status and TVSS condition (good or needs
normally open (NO) or normally closed (NC) auxiliary
replacement). See Figure 8-21 and Figure 8-22.
8.8.3 TVSS Replacement Note: Utility power is still present at the inlet side of
the normal source circuit breaker.
The green indicator light goes out if the suppressor
capability is exceeded or if there is an internal safety b. All other models: Open the normal and
component failure in the TVSS module. See emergency source circuit breakers upstream of
Figure 8-21. Replace the module if the green indicator the transfer switch.
is off and the red indicator is on. Follow the replacement
procedure in this section. 3. Remove the enclosure’s inner panel , if equipped.
1. Disable the generator set to prevent starting as 14. Reconnect power to the battery charger.
follows:
15. Close and lock the ATS enclosure door.
a. Move the generator set master switch to the
OFF position. 16. Move the generator set master switch to the AUTO
position.
1
GM47965
1. Current transformers on load bus 2. Terminal block TB1 (see wiring diagram GM47803)
TB1
12
6
Main Logic
Board
Power
Board
MLB Input 2
Forced Transfer to OFF
7
1
Figure 8-29 Forced Transfer to Off Input Connection (for factory-installed load shed kits)
Figure 8-30 Load Shed Accessory (for The line-to-neutral monitoring kit is available
identification) factory-installed or as a loose kit. Refer to the
instructions provided with the kit for field installation.
For reference, this section lists the items displayed during normal operation, and the information and settings shown in
the View and Setup screens.