DEC 550 Controller Operation
DEC 550 Controller Operation
DEC 550 Controller Operation
Models:
20--2000 kW
Controllers:
Decision-Makert 550
TP-6083 7/05a
California Proposition 65
WARNING
Engine exhaust from this product contains chemicals
known to the State of California to cause cancer, birth
defects, or other reproductive harm.
Engine Identification
Record the product identification information from the
engine nameplate.
Manufacturer
Model Designation
Serial Number
2 TP-6083 7/05
Table of Contents
This manual provides operation instructions for skilled and suitably-trained maintenance personnel
20--2000 kW generator sets equipped with the following familiar with generator set operation and service.
controller:
The disc supplied with this generator set is a backup
D Decision-Makert 550, Software (Code) Version copy of the generator set personality program
Prior to 2.10 containing data specific to the engine and alternator.
The engine and alternator data was preprogrammed in
Version 2.10 refers to the controller application the controller at the factory and no further use of the disc
software. To determine the generator set controller should be necessary. Typically, your authorized
software version, go to Menu 20—Factory Setup and distributor stores this disc for possible future use such as
scroll down to Code Version. The code version is the controller replacement or other circumstances requiring
controller software version. a backup.
D Visit the Kohler Power Systems website at East China Regional Office, Shanghai
KohlerPowerSystems.com Phone: (86) 21 6288 0500
Fax: (86) 21 6288 0550
D Look at the labels and stickers on your Kohler product India, Bangladesh, Sri Lanka
or review the appropriate literature or documents India Regional Office
included with the product Bangalore, India
Phone: (91) 80 3366208
D Call toll free in the US and Canada 1-800-544-2444 (91) 80 3366231
Fax: (91) 80 3315972
D Outside the US and Canada, call the nearest regional
office Japan, Korea
North Asia Regional Office
Headquarters Europe, Middle East, Africa Tokyo, Japan
(EMEA) Phone: (813) 3440-4515
Kohler Power Systems Fax: (813) 3440-2727
ZI Senia 122
Latin America
12, rue des Hauts Flouviers
Latin America Regional Office
94517 Thiais Cedex
Lakeland, Florida, USA
France
Phone: (863) 619-7568
Phone: (33) 1 41 735500
Fax: (863) 701-7131
Fax: (33) 1 41 735501
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 6264-6422
Fax: (65) 6264-6455
1 2 3 4 5 6
8 7 TP-6083-2
The following conditions cause a system shutdown: AM/PM key provides time of day data entries when
programming.
D Engine functions:
d Air damper closed (status), if equipped Enter ↵ key provides confirmation entry when selecting
d Coolant temperature signal loss menu or programming.
d High coolant temperature
d High oil temperature Lamp test key tests the controller indicator lamps, horn,
d Low coolant level and digital display. See Section 1.2.3, Switches and
d Low oil pressure Controls.
d Oil pressure signal loss
d Overcrank Menu down ↓ key provides navigation within menus
d Overspeed when necessary.
D General functions: Menu right → key provides navigation within menus
d Auxiliary—Analog up to 7 inputs each with a high when necessary.
and low programmable shutdown level
NOTE: Non-ECM models have 5 programmable Numeric 0--9 keys provide numeric data entries when
shutdowns selecting menus or programming.
d Auxiliary—Digital up to 21 programmable
Reset menu key exits a menu, clears incorrect entries,
shutdowns
and cancels the auto-scroll feature.
d ECM communications loss (ECM models only)
d Emergency stop Stop prog (program) run key allows the user to stop
d Internal fault any previously programmed generator set run
d Master switch in OFF/RESET position sequence. See Section 1.2.3, Switches and Controls.
d Master switch error
d Master switch open Yes/No keys provides data answer entries when
d NFPA 110 fault programming.
D Generator functions:
d AC output overvoltage
d AC output undervoltage
d Alternator protection against overload and short
circuits
d Field overvoltage (M4, M5, or M7 alternator only)
d Locked rotor (failed to crank)
d Overfrequency
d Underfrequency
AC Amps displays the generator output current. The Fuel Rate displays the calculated fuel consumption rate
display shows each line of 3-phase models. based on fuel injector outputs.
AC Volts displays the generator output voltages. The Fuel Temperature displays the fuel supply
display shows all line-to-neutral and line-to-line voltage temperature.
combinations.
Oil Level displays the engine oil level as a percent of full
Alternator duty level displays the actual load kW capacity.
divided by the nameplate kW rating as a percentage.
Oil Pressure displays the engine oil pressure.
Frequency displays the frequency (Hz) of generator
output voltage. Oil Temperature displays the engine oil temperature.
Hourmeter displays the generator set operating hours RPM (Tachometer) displays the engine speed.
loaded and unloaded for reference in scheduling
maintenance. Used Last Run displays the accumulated amount of
fuel used since last reset by the engine DDEC reader.
KVA displays the total and individual L1, L2, and L3 kVA.
Operational Record Displays
KVAR displays the total and individual L1, L2, and L3
kVAR. The operational record displays events since last reset.
See Section 2.9.4, Menu 4—Operational Records, for
Power factor displays the leading/lagging L1, L2, L3, resetting procedure.
and total power factor.
Engine Start Countdown displays the time remaining
Watts displays the total and individual L1, L2, L3 before the next generator set startup.
kilowatts.
Event History displays up to 100 stored system events
Engine Displays including status, warnings, and shutdowns.
Some engine displays are available with selected Last Start Date displays the date when the generator
generator set engines using engine electronic control set last operated.
modules (ECM) only. The controller display shows N/A
(not available) for items that are unavailable. See the Number of Starts displays the total number of
controller spec sheet for applicable generator set generator set startup events.
models.
Number of Starts (Since) Last Maintenance displays
Ambient Temperature displays the generator set area the total number of generator set startup events since
ambient temperature. the last maintenance date.
Coolant Level displays the engine coolant level. Operating Days (Since) Last Maintenance displays
the total number of days of operation since the last
Coolant Pressure displays the engine coolant maintenance date. A counted day of operation can be
pressure. 1--24 hours.
Coolant Temperature displays the engine coolant Run Time displays the total loaded hours, total
temperature. unloaded hours, and total kW hours.
Crankcase Pressure displays the engine crankcase Run Time Since Maintenance displays the total loaded
pressure. hours, total unloaded hours, and total kW hours.
1
2
3 TP-5829-2
1. Lamp test
2. Alarm horn silence
3. Stop program run
TP-6083-2
Stop Prog (Program) Run. Keypad switch allows the Digital Display Circuit Board provides the digital
user to stop any previously programmed generator set display for monitoring the generator set functions and
run sequence. output values.
2
TB4 Digital Input Connection Terminal Strips
connect external devices (engine ECM and user
supplied) to the generator set digital inputs.
1 2 3 4 5
ADV-6533-A
1. Interconnection circuit board
2. P2 ribbon connector
3. P12 ribbon connector
ADV-6533-A
1. TB1 terminal strip
2. TB2 terminal strip
3. P23 Connector
4. TB3 terminal strip
5. TB4 terminal strip
The engine ECM may limit the crank cycle even if the
controller is set to a longer time period.
6
ADV-6533-A
1. P19—unused ISO2, RS-485 port
2. P21—KBUS ISO1, RS-485 port
3. P18—KBUS or Modbus, RS-232 port
4. P20—Modbus, RS-485 port
5. P22—ECM connector
6. Main logic circuit board
* The controller-to-alternator interface circuit board was temporarily unavailable on early units. As a result, 350--2000 kW generator sets are
equipped with a Marathon DVR 2000 voltage regulator and not the internal controller voltage regulator. Refer to the Marathon voltage
regulator technical manual for specifications and all adjustments.
Power Factor (PF) Adjust Control. Power factor VAR Control. VAR control provides reactive current
adjust controls the generator reactive load. The PF flow adjustment in the generator during
adjustment controls the excitation level for maintaining generator-to-utility paralleling applications. The
the PF setting. The PF adjust control setting determines controller displays the total kVAR generator load while
the reactive current (VARs) amount in relation to the real running in parallel with the utility.
current (watts) as regulated by the load-sharing module.
The utility supply, not the controller, determines terminal
Power is the cosine of the electrical angle between voltage. Engine fueling determines real power
current and voltage. The cosine function is positive for measured in watts using load sharing module control.
angles between --90 degrees (lagging) and +90 degrees
(leading). This adjustment requires the user to Voltage Adjustment. The voltage adjustment allows
determine whether the current leads (positive angle) or the customer to enter the desired generator set output
lags (negative angle) the voltage. level. This regulated level setting is the average of the
three line-to-neutral voltages in wye configurations or
Reactive Droop. Reactive droop compensation L1-to-L2 in single phase and delta configurations.
provides reactive current flow adjustment in the
generator during generator-to-generator paralleling Submenus display the individual line-to-line voltages.
applications. Reactive droop reduces excitation levels These voltages are relevant in unbalanced load
with increasing reactive current. A reduced excitation conditions. The voltage adjust setpoint can be changed
level removes generator reactive current or generates to accommodate an important phase in an unbalanced
VARs, improving stability. system.
2.1 Prestart Checklist D Check for corroded or broken metal parts and replace
them as needed.
To ensure continued satisfactory operation perform the
following checks or inspections before or at each D Check for loose, corroded, or missing clamps and
startup, as designated, and at the intervals specified in hangers. Tighten or replace the exhaust clamps
the service schedule. In addition, some checks require and/or hangers as needed.
verification after the unit starts.
D Check that the exhaust outlet is unobstructed.
Air Cleaner. Check for a clean and installed air cleaner
D Visually inspect for exhaust leaks (blowby). Check
element to prevent unfiltered air from entering the
for carbon or soot residue on exhaust components.
engine.
Carbon and soot residue indicates an exhaust leak.
Air Inlets. Check for clean and unobstructed air inlets. Seal leaks as needed.
Battery. Check for tight battery connections. Consult Fuel Level. Check the fuel level and keep the tank(s)
the battery manufacturer’s instructions regarding full to ensure adequate fuel supply.
battery care and maintenance.
Oil Level. Maintain the oil level at or near, not over, the
Controller. After reconnecting the battery, set the full mark on the dipstick.
controller time and date. See Section 2, Menu 14—
Operating Area. Check for obstructions that could
Programming Mode On and Menu 6—Time and Date.
block the flow of cooling air. Keep the air intake area
Coolant Level. Check the coolant level according to clean. Do not leave rags, tools, or debris on or near the
the cooling system maintenance information. generator set.
Note: Block heater damage. The block heater will fail 2.2 Exercising Generator Set
if the energized heater element is not immersed
in coolant. Fill the cooling system before turning Operate the generator set under load once each week
on the block heater. Run the engine until it is for one hour. Perform the exercise in the presence of an
warm, and refill the radiator to purge the air from operator when the generator set does not have a
the system before energizing the block heater. programmed exercise mode or an automatic transfer
switch with an exercise option.
Drive Belts. Check the belt condition and tension of the
radiator fan, water pump, and battery charging During the exercise period apply a minimum of 35% load
alternator belt(s). based on the nameplate standby rating, unless
otherwise instructed in the engine operation manual.
Exhaust System. Check for exhaust leaks and
blockages. Check the silencer and piping condition and The operator should perform all of the prestart checks
check for tight exhaust system connections. before starting the exercise procedure. Start the
generator set according to the starting procedure in
Inspect the exhaust system components (exhaust Section 2.3, Controller Operation. While the generator
manifold, exhaust line, flexible exhaust, clamps, set is operating, listen for a smooth-running engine and
silencer, and outlet pipe) for cracks, leaks, and visually inspect the generator set for fluid or exhaust
corrosion. leaks.
Local Starting During the idle (speed) mode the controller continues to
monitor critical engine parameters such as oil pressure,
Move the generator set master switch to the RUN coolant temperature, and engine speed. The voltage
position to start the generator set at the controller. regulator, thermal protection feature, and AC metering
are disabled in the idle speed mode.
Note: The alarm horn sounds and the Not-In-Auto lamp
lights whenever the generator set master switch The controller overrides the idle speed function when
is not in the AUTO position. the generator set is signaled to start while in the AUTO
position. This override provides emergency generator
Note: The transient start/stop function of the controller
set power in the event of a utility power failure. When the
prevents accidental cranking of the rotating
utility power returns and the generator set is signalled to
engine. The generator set stops and recranks
stop, the generator set continues to run for the duration
when the generator set master switch is
of the idle mode period when the idle mode is active.
momentarily placed in the OFF/RESET position
When the idle mode is not active, the generator set will
and then returned to RUN.
shut down in the normal stopping mode including time
delays.
Auto Starting
See Menu 9—Input Setup to activate the idle speed
Move the generator set master switch to the AUTO function as a user-defined digital input. The idle speed
position to allow startup by the automatic transfer switch feature requires an ECM-equipped engine with the idle
or remote start/stop switch (connected to controller speed function.
terminals 3 and 4).
Idle (Speed) Mode Warmup and Cooldown Generator set connected to an automatic transfer
Function switch. Should a utility power failure occur while the
unit is in the run time mode, the controller will bypass the
The idle (speed) mode function provides the ability to run time mode and function in the standby (backup)
start and run the engine at reduced speed for a mode. When the utility power returns, the generator set
selectable time period (0--10 minutes) during warmup. continues to run for the duration of the run time period
See Section 6.1.5, Idle (Speed) Mode Feature, for when not timed out.
installation information.
Note: Press the STOP PROG RUN key, when
The controller will override the idle speed mode when necessary, to stop the generator set when it is in
the engine reaches the preprogrammed engine the run time mode.
warm-up temperature before the idle mode times out.
Run the generator set without load for 5 minutes to 1. Place the generator set master switch in the
ensure adequate engine cooldown. OFF/RESET position.
The controller has a programmable cooldown timer that 2. Investigate and correct the cause of the
functions only when the master switch is in the AUTO emergency stop.
position. To stop the generator set, place the generator
set master switch in the OFF/RESET position and wait 3. Reset the optional remote emergency stop switch by
until the generator set comes to a complete stop. replacing the glass piece, when equipped. Additional
glass rods are available as a service part. Reset the
Note: The cooldown cycle times out before the controller emergency stop switch by pulling the
generator set stops when a remote switch or switch knob outward.
automatic transfer switch initiates the generator
set start/stop sequence. 4. After resetting all faults using the Controller Reset
Procedure, toggle the generator set master switch
to RUN or AUTO to restart the generator set. The
Emergency Stopping generator set will not crank until the reset
Use the controller emergency stop switch or optional procedure completes.
remote emergency stop for immediate shutdown.
2.3.4 System Ready Lamp
The emergency stop switch bypasses the time delay
engine cooldown and immediately shuts down the System Ready. The green lamp illuminates when the
generator set. generator set master switch is in the AUTO position and
the system has no fault conditions.
Use the Alarm Off keypad switch to silence the alarm High Battery Voltage. The lamp illuminates when the
horn at the operator’s discretion. Place the generator battery voltage rises above the preset level for more
set master switch in the AUTO position before silencing than 10 seconds. The local display shows high battery
the alarm horn. The alarm horn cannot be silenced voltage. Figure 2-1 shows high battery voltage
unless the master switch is in the AUTO position. specifications. The high battery voltage feature
monitors the battery and battery charging system in the
Note: Text shown in italics in this manual represents generator set operating and off modes.
digital display messages.
High Battery
AC Sensing Loss. The lamp illuminates when the
Engine Electrical High Battery Voltage Default
controller does not detect nominal generator set AC System Voltage Voltage Range Setting
output voltage after crank disconnect. The local display
12 14.5--16.5 16
shows AC sensing loss.
24 29--33 32
Battery Charger Fault. The lamp illuminates when the Figure 2-1 High Battery Voltage Specs
battery charger malfunctions. This fault feature requires
an optional battery charger with a malfunction output for High Coolant Temperature Warning. The lamp
the lamp to function. Local display shows battery illuminates and the alarm horn sounds when the engine
charger fault. coolant temperature approaches the shutdown range.
The local display shows high coolant temperature
Customer Auxiliary (Warning). The lamp illuminates warning.
and the alarm horn sounds when an auxiliary digital or
analog inputs signals the controller. The customer can Load Shed. The lamp illuminates when the generator
define inputs as shutdowns or warnings. The local set’s total kW load exceeds the programmed level for
display shows digital input 1-21 or analog input 1-7. more than the load shed time. When the load shed
alarm sounds and resets more than twice in 1 minute,
Using the remote communications package, the user the load shed warning lamp circuit latches and remains
can label the auxiliary functions. The controller displays on until the generator set shuts off. The local display
the selected name instead of digital input 1-21 or analog shows load shed kW over.
input 1-7.
When the generator set frequency drops to less than 59
EEPROM Write Failure. The lamp illuminates and the Hz on a 60 Hz system or 49 Hz on a 50 Hz system for
alarm horn sounds when the control logic detects a data more than 5 seconds, the local display shows load shed
save error. The local display shows EEPROM write under freq. When the load shed alarm sounds and
failure. resets more than twice in 1 minute, the load shed
warning lamp latches and remains on until the generator
set shuts down.
Note: The text shown in italics represents digital display High Oil Temperature. The lamp illuminates and the
messages. unit shuts down because of high engine oil temperature.
The shutdown occurs 5 seconds after the engine oil
Air Damper Indicator. The lamp illuminates and the reaches the temperature shutdown range. The high
unit shuts down when signaled by a closed air damper engine oil temperature shutdown does not function
circuit. The local display shows air damper indicator. during the first 30 seconds after startup. The local
display shows high oil temp.
Alternator Protection. The lamp illuminates and the
unit shuts down because of an alternator overload or Internal Fault. The lamp illuminates and the unit shuts
short circuit. The local display shows altrntr protect down when the internal diagnostic test detects a
sdwn. controller malfunction. The local display shows internal
fault.
Customer Auxiliary (Shutdown). The lamp
illuminates and the unit shuts down when an auxiliary Locked Rotor. If none of the speed sensing inputs
digital or analog input signals the controller. The show engine rotation within 5 seconds of initiating
customer can define inputs as shutdowns or warnings. engine cranking, the ignition and crank circuits turn off
The local display shows digital input 1-21 or analog input for 5 seconds and the cycle repeats. The unit shuts
1-7 when activated. down after the second cycle of 5 seconds of cranking.
The local display shows locked rotor.
Using the remote communications package, the user
can label the auxiliary functions. The controller displays Loss of ECM Communications. The lamp illuminates
the selected name instead of digital input 1-21 or analog and the unit shuts down when the ECM communication
input 1-7. link is disrupted. The local display shows loss of ECM
comm.
Emergency Stop. The lamp illuminates and the unit
shuts down when the local or optional remote
emergency stop switch activates. The local display
shows emergency stop.
Master Switch Open. The lamp illuminates and the unit Generator Set Overspeed Overspeed Default
shuts down when the controller detects an open circuit in Frequency Hz Range Hz Setting Hz
the master switch circuit. The local display shows 60 65--70 70
master switch open. 50 55--70 60
NFPA 110 Fault. The lamp illuminates and the unit Figure 2-5 Overspeed Specs
shuts down when NFPA 110 faults signal the controller.
The local display shows NFPA 110 fault. See Overvoltage. The lamp illuminates and the unit shuts
Section 2.4, Menu List Summary, Menu 10—Output down when the overvoltage setting exceeds the
Setup, for the NFPA 110 list. overvoltage setting for the time delay period. The local
display shows overvoltage. Overvoltage specifications
No Coolant Temperature Signal. The lamp follow. See Figure 2-6.
illuminates and the unit shuts down when the engine
coolant temperature sender circuit is open. The local Note: Overvoltage can damage sensitive equipment in
display shows no cool temp signal. less than one second. Install separate
overvoltage protection on online equipment
No Oil Pressure Signal. The lamp illuminates and the requiring faster than 2-second shutdown.
unit shuts down when the engine oil pressure sender
circuit is open. The local display shows no oil press Overvoltage Time Delay Overvoltage
signal. Setting Range Range Default Setting
105%--135% of nominal 2--10 sec. 115% at 2 sec.
Overcrank. The lamp illuminates and cranking stops
when the unit does not start within the defined cranking Figure 2-6 Overvoltage Specs
period. The local display shows overcrank. See
Section 2.3.1, Auto Starting, and Section 1,
Specifications and Features, for cyclic crank
specifications.
2.3.7 Controller Reset Procedure 11. Move the generator set master switch to the AUTO
position for startup by the remote transfer switch or
(Following System Shutdown or the remote start/stop switch.
Warning)
When equipped, move the remote annunciator
Use the following procedure to restart the generator set and/or audiovisual alarm switch to the NORMAL
after a system shutdown or to clear a warning lamp position.
condition. This procedure includes the resetting of the
optional remote annunciator and the audiovisual alarm.
2.4 Menu List Summary
Refer to Section 2.3.3, Emergency Stop Switch Reset
Procedure, to reset the generator set after an Use the Menu List Summary section on the following
emergency stop. pages after reading and understanding the features of
the keypad. See Section 1.2.2, Digital Display and
1. Move the generator set master switch to the AUTO Keypad.
position, if not already done.
The Menu List Summary provides a quick reference to
2. Silence the controller alarm horn by pressing the the digital display data. Some digital display data may
alarm off key. not be identical to your display due to generator set
application differences. The closed bullet items
When equipped, the optional remote annunciator represent main level data and the open bullet items are
and/or audiovisual alarm horn and lamp activate. sub-level data.
Move the alarm switch to the SILENCE position to
stop the alarm horn. The lamp stays lit. Section 2.8, Reviewing the Menu Displays, provides a
digital display menu overview and explains the
3. Disconnect the generator set load using the line navigation using the down and right arrow keys.
circuit breaker or automatic transfer switch.
Section 2.9, Local Programming Mode On, contains the
4. Correct the cause of the fault shutdown or warning. keystroke details of each menu when programming.
See Safety Precautions and Instructions section of
this manual before proceeding.
Note: Pressing the menu down ↓ key locks the user into
the levels of that main menu. Press the reset
menu key to access other main menus.
Note: After energizing the controller by reconnecting Reset Menu Key. The reset menu key exits a menu,
the battery, set the controller time and date. See clears incorrect entries, and cancels the auto-scroll
Section 2.9.6, Local Programming Mode On, function. Press the reset menu key to exit a menu or any
Menu 6—Time and Date. layer within that menu.
Pressing any key on the keypad activates the controller Stop Prog Run Key. Press the stop prog run key to end
panel display. The panel lamps and display turn off the generator set programmed exercise run created in
5 minutes after the last keypad entry. Menu 4—Operational Records. The generator set
shuts down after the time delay for engine cooldown
2.6.1 Keypad Operation ends. The stop prog run key does not affect the
programmed transfer switch exercise function.
Use the keypad to input information into the controller.
Some of the keys have two functions. The following Yes/No Keys. When the controller asks a question
gives keypad definitions and functions. during programming requiring a nonnumeric answer (yes
or no), the controller accepts the secondary key function
Alarm (Horn) Off Key. Press the alarm off key to
and ignores the numeric value of the key.
silence the horn at the user’s discretion. Place the
generator set master switch in the AUTO position before
silencing the alarm horn. The alarm horn cannot be 2.6.2 Auto-Scroll Function
silenced unless the master switch is in the AUTO
position. See Section 2.3.7, Controller Reset The auto-scroll function continuously shows voltage
Procedure, for more information on turning the alarm and current data from Menu 1—Generator Monitoring,
horn off. V & A Summary without the need to press the down
arrow for each display.
AM/PM Key. When the controller asks a question during
programming requiring a nonnumeric answer (am or For auto-scroll function press ENTER at the V & A
pm), the controller accepts the secondary key function Summary menu. Press the Reset Menu key or Menu
and ignores the numeric value of the key. Right → key to stop the auto-scroll function.
Display messages require additional data, confirm the Cannot Change Preset appears when the user
previous entry or require time to process as described attempts to change the preset factory digital input or
below. input parameter.
Entry Accepted appears for several seconds after Entry Unacceptable appears when the user attempts
pressing the Enter key during the programming mode. an invalid input to the voltage regulator setup.
The display then shows the new data.
Func(Function) Used by (RDO) XX Reassign?
Reset Complete indicates the user: appears when the user attempts to assign an RDO to a
function already assigned.
D Reset the maintenance records or
Invalid Code appears when the user attempts to enter:
D Restored the AC analog inputs to the default settings.
D An invalid access code for programming mode setup,
Right Arrow → directs the user to the next menu.
or
Menus loop; press the right arrow key to the next menu.
D An invalid access code for setup unlock.
Setup Complete indicates the completion of the analog
No Input Assigned appears when the user attempts to
input setup.
assign any of the following system faults to an RDO
(Question) ? asked by the control firmware; answer the where the digital input is not defined. See digital input
question by pressing the yes/no, numeric digit, or scale requirements in Menu 12—Calibration.
am/pm key.
D Air damper indicator
Wait for System Reset (6 Sec) appears while the D Battery charger fault
EEPROM initializes. D Ground fault
D High oil temperature shutdown
Error Messages D Low coolant level
Access Denied Idle Mode Active appears when the D A numeric input that is not within the required
user attempts to modify the voltage regulator setup parameters of system settings, time delays,
while the idle mode is active. addresses, etc.
Alarm Active appears when the user attempts to D An invalid analog or digital input number or date/time.
modify an active digital input. See Menu 9—Input
Setup. Setpoint Values Cannot be Equal appears when the
user attempts to enter the same value for both setpoints
during the analog input calibration.
User Operating Mode Selection Menu 13—Communications Settings Menu 14—Programming Mode
Remote Local Remote
Single or Programming Programming Programming
User Activity Access Source On Line? Local LAN? LAN? Mode Off? Mode? Mode?
Controller No No No Yes No No
Monitor only Direct PC Yes Yes No Yes No No
PC via Telephone Lines Yes No Yes Yes No No
Controller No No No No Yes No
Monitor and Direct PC Yes Yes No No No Yes
Program
PC via Telephone Lines Yes No Yes No No Yes
Generator Set
RS-232 to RS-485 Controller or
port converter Transfer Switch
Control
RS-485
up to
Personal 1220 m
Computer (4000 ft.)
Generator Set
Modem Modem Controller or
Transfer Switch
Control
RS-232 RS-232
up to Telephone up to
Personal 15 m (50 ft.) Lines 15 m (50 ft.)
Computer
Menu 1 Overview
MENU 1
GENERATOR MONITORING
VOLTS & AMPS → V & A SUMMARY → POWER KW → POWER KVAR → POWER KVA →
L1-L2 VOLTS # V L1-L2 L2-L3 L3-L1 TOTAL KW # TOTAL KVAR # TOTAL KVA #
L1 AMPS # (3 PH) # # # PF # LEADING/LAGGING ABSORBING/GENERATING
L3-L0 VOLTS #
L3 AMPS (3 PH) # Use the MENU→ key to
stop the auto-scroll function.
FREQUENCY # HZ
Menu 2 Overview
MENU 2
ENGINE MONITORING
OIL PRESSURE # PSI ENGINE FUEL → ENGINE COOLANT → ENGINE OIL → ENGINE MISC →
COOLANT TEMP #F
ENGINE RPM # FUEL PRES # PSI COOLANT PRES # PSI OIL PRES # PSI ECM BATT VDC #
LOCAL BATT VDC # FUEL TEMP #F COOLANT TEMP #F OIL TEMP #F AMBIENT TEMP #F
FUEL RATE # GPH COOLANT LEVEL #% OIL LEVEL #% ENGINE MODEL NO.
CRANKCASE PRES # PSI #
UNIT NO. #
ECM S/N #
Menu 3 Overview
MENU 3
ANALOG MONITORING
ANALOG 03 #
(USER DEFINED DESC)
ANALOG 04 #
(USER DEFINED DESC)
ANALOG 05 #
(USER DEFINED DESC)
ANALOG 06 #
(USER DEFINED DESC)
ANALOG 07 #
(USER DEFINED DESC)
Menu 4 Overview
MENU 4 NO. OF STARTS #
OPERATIONAL RECORDS LAST MAINT ##-###-##
NO. OF STARTS #
OPERATING DAYS #
LAST MAINT ##-###-##
Menu 5 Overview
MENU 5
EVENT HISTORY
(MESSAGE TEXT)
##-###-## ##:## AM/PM
Menu 6 Overview
MENU 6
TIME AND DATE
DATE ??-???-??
Menu 7 Overview
MENU 7
GENERATOR SYSTEM
SYSTEM VOLTAGE
LINE-LINE ?
SYSTEM FREQ # HZ
KW RATING ?
RATED CURRENT #
OVERFREQUENCY
?% # HZ
UNDERFREQUENCY
?% # HZ
OVERSPEED
? HZ # RPM
TO GENERATOR SYSTEM
MENU ON NEXT PAGE
Menu 8 Overview
MENU 8
TIME DELAYS
OVERCRANK SHUTDOWN
CRANK CYCLES ?
Menu 9 Overview
MENU 9
INPUT SETUP
DIGITAL INPUT 01 → DIGITAL INPUT 01 → DIGITAL INPUT 01 → DIGITAL INPUT 01 → DIGITAL INPUT 01 →
(USER DEFINED DESC) (see Group A) YES/NO ENABLED YES/NO INHIBIT TIME ?:?? DELAY TIME ?:??
Note: Some data require entry using a PC in the Relay Driver Outputs (RDOs)
Remote Programming mode. See the Software
Operation Manual for details. Up to 31 RDOs are available using the system, digital,
and analog status events and faults. RDOs provide only
Common Faults the driver. The contact relays that interface with other
equipment are optional.
The user can program a single fault comprised of faults
from 3 common fault programs—system, digital, and Note: Func(tion) Used By (RDO) XX Reassign? error
analog faults. message appears when the user attempts to
duplicate an existing RDO selection.
Up to 46 user-defined system status events and faults
are available. See Group B on the following pages for Note: Cannot Change NFPA is Enabled. error message
specific descriptions. The NFPA-110 faults are part of appears when the user attempts to modify RDO
the system fault program and are comprised of 15 setting defaulted as NFPA 110 requirement.
individual faults shown on the next page.
COMMON FAULT Y/N COMMON FAULT Y/N COMMON FAULT Y/N COMMON FAULT Y/N
(see Group B) (see Group C) (see Group D)LO WARNING→ HI WARNING→
Press down arrow to scroll Press down arrow to scroll Press down arrow to scroll COMMON FAULT Y/N
through available faults. through digital auxiliary through analog auxiliary LO SHUTDOWN→
inputs. inputs.
Group E
Choose up to 31 status Press down arrow to scroll Press down arrow to scroll Press down arrow to scroll
event and fault RDOs RELAY DRV OUT Y/N
through available RDO through RDO digital auxiliary through RDO analog
from the following: LO SHUTDOWN→
faults. inputs. auxiliary inputs.
SYSTEM FAULTS
(see Group B, 46 Items)
DIGITAL INPUTS RELAY DRV OUT Y/N
(see Group C, 21 Items) HI SHUTDOWN→
ANALOG INPUTS
(see Group D, 7 Items)
Menu 11 Overview
MENU 11
VOLTAGE REGULATOR
AVG L-L V # → L1-L2 VOLTS → L2-L3 VOLTS (3 PHASE) → L3-L1 VOLTS (3 PHASE) →
VOLT ADJ ?.? # # #
The user must enable the programming mode to edit the Note: Press the Menu Right → key prior to entering
display. decimal values where necessary.
Connect a meter with a minimum accuracy of ᐔ1% to Note: ECM engines have user-defined analog inputs
the output leads to calibrate the voltage-sensing logic. A01--A07. Non-ECM engines have user-defined
Configure the generator set controller for the system analog inputs A03--A07 where analog inputs 01
operating configuration using Menu 7—Generator and 02 are reserved for engine oil pressure and
System. If the generator set has a digital voltage coolant temperature displays.
Menu 12 Overview
MENU 12
CALIBRATION
GEN L2 AMPS #
CALIB REF ?.?
RESTORE
DEFAULTS?
Menu 13 Overview
MENU 13
COMMUNICATIONS
PROTOCOL → PROTOCOL →
KBUS MODBUS
SYSTEM ID ?
(Remote Connections)
Menu 14 Overview
MENU 14
PROGRAMMING MODE
Menu 20 Overview
MENU 20
FACTORY SETUP
FINAL ASSEMBLY
CLOCK NO ?
OPERATING DAYS #
MODEL NO #
SPEC NO #
GENSET SERIAL NO #
ALTERNATOR PART NO #
ENGINE PART NO #
SERIAL NO #
CONTROLLER SERIAL NO
CODE VERSION #
COPYRIGHT XXXX
The programming feature alters stored settings and Note: Use the generator set controller to initially set up
changes characteristics of the logic. Do not operate the the remote programming. Set the controller for
controller with the program mode on unless there is a remote programming using Menu 14 and remote
need to edit program logic or clear stored data. Limit communication using Menu 13 before attempting
programming responsibilities to individuals with training remote programming.
and authority.
Note: Press any key on the keypad to activate the
The product application requires expertise in the design controller panel display. The panel display turns
and programming of control systems. Only qualified off 5 minutes after the last keypad entry.
personnel should program, install, alter, and apply this
Note: Press the Reset Menu key to clear the Error
product.
display.
Use Section 2.8, Reviewing the Menu Displays, to view
Note: Press the Menu Right → key prior to entering
the generator set operation data and review previously
decimal values where necessary.
programmed information and to review the data when
no programming is necessary.
MENU 1
GENERATOR MONITORING
Displays the menu number and name.
L1-L2 VOLTS #
L1 AMPS #
Displays L1 and L2 volts and L1 amps.
L2-L3 VOLTS #
Displays L2 and L3 volts and L2 amps. (3 ph. only)
L2 AMPS #
L1-L2 VOLTS #
L2 AMPS #
Displays L1 and L2 volts and L2 amps. (1 ph. only)
L3-L1 VOLTS #
L3 AMPS #
Displays L3 and L1 volts and L3 amps. (3 ph. only)
L1-L0 VOLTS #
L1 AMPS #
Displays L1-L0 volts and L1 amps.
L2-L0 VOLTS #
L2 AMPS #
Displays L2 and L0 volts and L2 amps.
L3-L0 VOLTS #
L3 AMPS #
Displays L3-L0 volts and L3 amps. (3 ph. only)
MENU 1
Returns the user to the menu number and name.
GENERATOR MONITORING
V & A SUMMARY →
Displays the volts and amps summary heading.
A L1 L2 L3
# # # Displays L1, L2, and L3 amps. (3 ph. only)
A L1 L2
# # Displays L1 and L2 amps. (1 ph. only)
V & A SUMMARY →
Returns the user to the volts and amps summary heading.
POWER KW →
Displays the power kilowatt heading.
TOTAL KW #
Displays total kilowatts and leading or lagging power factor.
PF # LEADING/LAGGING
L1 KW #
PF # LEADING/LAGGING
Displays total L1 kilowatts and leading or lagging power factor.
L2 KW #
Displays total L2 kilowatts and leading or lagging power factor.
PF # LEADING/LAGGING
TOTAL KW #
% OF RATED KW # Displays the total kW and percent of rated kilowatts.
POWER KW →
Returns the user to the power kilowatt heading.
POWER KVAR →
Displays the power kVAR heading.
TOTAL KVAR #
ABSORBING/GENERATING
Displays total kVAR, absorbing or generating.
L1 KVAR #
ABSORBING/GENERATING
Displays L1 kVAR, absorbing or generating.
L2 KVAR #
ABSORBING/GENERATING Displays L2 kVAR, absorbing or generating.
L3 KVAR #
ABSORBING/GENERATING
Displays L3 kVAR, absorbing or generating. (3 ph. only)
POWER KVAR →
Returns the user to power kVAR heading.
POWER KVA →
Displays the power kVA heading.
TOTAL KVA #
Displays total kVA.
L1 KVA #
Displays L1 kVA.
L2 KVA #
Displays L2 kVA.
L3 KVA #
Displays L3 kVA. (3 ph. only)
POWER kVA →
Returns the user to power kVA heading.
MENU 2
Displays the menu number and name.
ENGINE MONITORING
ENGINE MONITORING →
Displays the basic engine monitoring heading.
BASIC
ENGINE RPM #
Displays engine rpm and local battery VDC.
LOCAL BATT VDC #
MENU 2
ENGINE MONITORING Returns the user to the menu number and name.
ENGINE MONITORING →
Returns the user to basic engine monitoring heading.
BASIC
ENGINE MONITORING → Displays the detailed engine monitoring heading. Note: The detailed
DETAILED engine monitoring feature requires an ECM-equipped engine.
ENGINE FUEL →
Displays the engine fuel subheading.
ENGINE MONITORING →
Returns the user to the detailed engine monitoring heading.
DETAILED
ENGINE FUEL →
Displays the engine fuel subheading.
ENGINE COOLANT →
Displays the engine coolant subheading.
COOLANT LEVEL #%
Displays the coolant level as a percent of full capacity.
ENGINE COOLANT →
Returns the user to engine coolant subheading.
ENGINE OIL →
Displays the engine oil subheading.
OIL LEVEL #%
CRANKCASE PRES # PSI Displays the oil level as a percent of full capacity and crankcase
pressure.
ENGINE OIL →
Returns the user to engine oil subheading.
ENGINE MISC →
Displays the miscellaneous engine subheading.
UNIT NO. #
ECM S/N # Displays the unit number and ECM serial number.
ENGINE MISC →
Returns the user to the miscellaneous engine subheading.
MENU 3
Displays the menu number and name.
ANALOG MONITORING
NO. OF STARTS #
Displays the number of engine starts.
RUN TIME HR:MN→ Displays the run time (hours:minutes) feature. When required, use the
??:?? numeric keys to enter the selected run time (hours:minutes) and press
the Enter key.
RUN TIME HR:MN→ Confirms entry and displays the selected run time (hours:minutes). The
##:## generator set will start after activation. Note: Activate the generator set
run time feature by pressing the Yes and Enter keys. See the following
steps.
ENGINE START? Y/N→ Returns the user to the start and countdown subheading. Enter Yes to
COUNTDOWN ##:## start the generator set.
RUN TIME HR:MN→ Confirms the entry. The generator set will begin cranking and run based
##:## on the run time (hours:minutes) period and all previously established
time (hours:minutes) delays from Menu 8—Time Delays. Note: Press
the STOP PROG RUN key to stop the generator set when in the run time
mode, if necessary.
RESET RECORDS? → Displays the reset records option. After performing maintenance or
when required, enter Yes to reset.
RECORDS MAINT →
Returns the user to records maintenance subheading.
OPERATING DAYS #
LAST MAINT ##-###-##
Displays the operating days since the last maintenance.
NO. OF STARTS # Displays the number of starts since the last maintenance date
LAST MAINT ##-###-## (day-month-year).
LAST START ##:## AM/PM Displays last the start time (hours:minutes) and date (day-month-year).
DATE ##-###-##
LENGTH OF RUN
Displays the length of last run in (un)loaded hours.
(UN)LOADED HRS #
MENU 4
OPERATIONAL RECORDS Returns the user to the operational records heading.
(MESSAGE TEXT) Displays the message text, date (day-month-year) and time
##-###-## ##:## AM/PM (hours:minutes). Scroll through up to100 stored events. See
Section 2.3.5, System Warning Lamp, for fault descriptions.
MENU 5
Returns the user to event history heading.
EVENT HISTORY
MENU 6
Displays the menu number and name.
TIME AND DATE
DAY OF WEEK ##-###-## Displays the day of the week, date (day-month-year), and time
##:## AM/PM (hours:minutes).
TIME ??:?? AM/PM Displays the time (hours:minutes) of day entry. When required, use the
numeric and am/pm keys to set the time (hours:minutes) of day and press
the Enter key.
DAY OF WEEK ##-###-##
##:## AM/PM
Displays the corrected time (hours:minutes) of day.
DATE ??-???-?? Displays the date (day-month-year) entry. When required, use the
numeric keys to set the day of the month.
AND
DATE ??-???-?? Use the Menu Right → key to select the month.
AND
DATE ??-???-?? Use the numeric keys to set the two-digit year and press the Enter key.
AND
DAY OF WEEK ##-###-##
##:## AM/PM
Displays the corrected date (day- month-year).
OPERATING MODE → Displays the operating mode selection. Note: The display sample may
(see note) YES differ depending upon previous entries. The previously selected
operating mode appears first, either standby or prime power.
OPERATING MODE → Displays the optional operating mode selection. When required, enter
STANDBY NO YES for standby operating mode. Note: This display indicates the
generator set application.
OPERATING MODE → Enter YES to change the operating mode selection to standby and press
STANDBY YES the Enter key.
OPERATING MODE →
STANDBY YES
Confirms the entry.
OR
OPERATING MODE → Displays the optional operating mode selection. When required, enter
PRIME POWER NO YES for the prime power operating mode. Note: This display indicates
the generator set application.
OPERATING MODE → Enter YES to change the operating mode selection to prime power and
PRIME POWER YES press the Enter key.
OPERATING MODE →
PRIME POWER YES
Confirms the entry.
SYSTEM VOLTAGE Displays the line-to-line system voltage as entered data. When required,
LINE-LINE ? use the numeric keys to set new value. Press the Enter key.
SYSTEM VOLTAGE
LINE-LINE # Displays the corrected line-to-line system voltage.
SYSTEM FREQ # HZ Displays the system frequency as entered data. When required, use the
numeric keys to set the new value. Press the Enter key.
SYSTEM FREQ # HZ
Displays the corrected system frequency.
PHASE → Displays the phase configuration selection. Note: The display sample
(see note) YES may differ depending upon previous entries. The user-selected phase
appears first, either wye, delta, or single phase.
PHASE → Displays the optional phase configuration selection. When required, use
3 PHASE DELTA NO the YES key to choose the delta phase configuration.
PHASE →
3 PHASE DELTA YES Confirms the entry.
OR
PHASE → Displays the optional phase configuration selection. When required, use
3 PHASE WYE NO the YES key to choose the wye phase configuration.
PHASE → Enter YES to change the phase configuration to a wye phase
3 PHASE WYE YES configuration and press the Enter key.
PHASE →
3 PHASE WYE YES Confirms the entry.
OR
PHASE → Displays the optional phase configuration selection. When required, use
SINGLE-PHASE NO YES key to choose the single-phase configuration.
PHASE → Enter YES to change the phase configuration to a single-phase
SINGLE-PHASE YES configuration and press the Enter key.
PHASE →
SINGLE-PHASE YES Confirms the entry.
KW RATING ? Displays the generator set kW rating as entered data. When required,
use the numeric keys to set the new value. Press the Enter key.
KW RATING #
Displays the corrected system kilowatt rating.
RATED CURRENT # Displays the generator set rated current as entered data. Note: This is
a read-only display.
LOAD SHED OUTPUT → Displays the load shed output setting. When required, use the numeric
?% # KW keys to set the new value. Press the Enter key.
TIME DELAY MIN:SEC → Displays the load shed time (minutes:seconds) delay setting. When
??:?? required, use the numeric keys to set the new value. Press the Enter key.
OVERVOLTAGE → Displays the overvoltage setting. When required, use the numeric keys
?% # VAC to set the new value. Press the Enter key.
OVERVOLTAGE →
Displays the corrected overvoltage setting.
#% # VAC
TIME DELAY MIN:SEC → Displays the overvoltage time (minutes:seconds) delay setting. When
??:?? required, use the numeric keys to set the new value. Press the Enter key.
TIME DELAY MIN:SEC → Displays the corrected overvoltage time (minutes:seconds) delay
##:## setting.
OVERVOLTAGE →
#% # VAC
Returns the user to the overvoltage setting.
UNDERVOLTAGE → Displays the undervoltage setting. When required, use the numeric keys
?% # VAC to set the new value. Press the Enter key.
UNDERVOLTAGE →
#% # VAC
Displays the corrected undervoltage setting.
TIME DELAY MIN:SEC → Displays the undervoltage time (minutes:seconds) delay setting. When
??:?? required, use the numeric keys to set the new value. Press the Enter key.
TIME DELAY MIN:SEC → Displays the corrected overvoltage time (minutes:seconds) delay
##:## setting.
UNDERVOLTAGE →
Returns the user to the undervoltage setting.
#% # VAC
OVERFREQUENCY Displays the overfrequency setting. When required, use the numeric
?% # HZ keys to set the new value. Press the Enter key.
OVERFREQUENCY
#% # HZ Displays the corrected overfrequency setting.
UNDERFREQUENCY Displays the underfrequency setting. When required, use the numeric
?% # HZ keys to set the new value. Press the Enter key.
UNDERFREQUENCY
Displays the corrected underfrequency setting.
#% # HZ
OVERSPEED
Displays the overspeed setting. When required, use the numeric keys
? HZ # RPM
to set the new value. Press the Enter key.
OVERSPEED
# HZ # RPM Displays the corrected overspeed setting.
BATTERY VOLTAGE → Displays the battery voltage selection. Note: The display sample may
(see note) YES differ depending upon previous entries. The user-selected battery
voltage appears first, either 12 VDC or 24 VDC.
BATTERY VOLTAGE → Displays the 12 VDC battery voltage selection. When required, use the
12 VDC NO YES key to choose the 12 VDC battery voltage.
BATTERY VOLTAGE → Enter YES to change the battery voltage to 12 VDC and press the Enter
12 VDC YES key.
BATTERY VOLTAGE →
12 VDC YES Confirms the entry.
OR
BATTERY VOLTAGE → Displays the 24 VDC battery voltage selection. When required, use the
24 VDC NO YES key to choose the 24 VDC battery voltage.
BATTERY VOLTAGE → Enter YES to change the battery voltage to 24 VDC and press the Enter
24 VDC YES key.
BATTERY VOLTAGE →
24 VDC YES Confirms the entry.
LOW BATTERY VOLTAGE Displays the low battery voltage setting. When required, use the numeric
?.? VDC keys to set the new value. Press the Menu Right → key prior to entering
the decimal value.
AND
LOW BATTERY VOLTAGE
?.? VDC Use the numeric keys to enter the decimal value. Press the Enter key.
HIGH BATTERY VOLTAGE Displays the high battery voltage setting. When required, use the
?.? VDC numeric keys to set the new value. Press the Menu Right → key prior
AND to entering the decimal value.
HIGH BATTERY VOLTAGE Use the numeric keys to enter the decimal value. Press the Enter key.
?.? VDC
OR
METRIC UNITS NO
Enter NO to change to English displays and press the Enter key.
METRIC UNITS NO
Confirms the entry.
SET NFPA-110 Y/N Displays the NFPA 110 default selection. Note: See Menu 10—Output
DEFAULTS Setup, Overview for a list of the NFPA-110 faults.
SET NFPA-110 YES Enter YES to select the NFPA 110 default selection and press the Enter
DEFAULTS key.
OR
SET NFPA-110 NO Enter NO to deselect the NFPA 110 default selection and press the Enter
DEFAULTS key.
SET NFPA-110 NO
Confirms the entry.
DEFAULTS
MENU 7
Returns the user to the generator system heading.
GENERATOR SYSTEM
TIME DELAY MIN:SEC Displays the engine start time delay in minutes:seconds. When required,
ENGINE START ??:?? use the numeric keys to set the new value. Press the Enter key.
TIME DELAY MIN:SEC Displays the corrected engine start time (minutes:seconds) delay
ENGINE START ##:## setting.
TIME DELAY MIN:SEC Displays the starting aid time delay in minutes:seconds. When required,
STARTING AID ??:?? use the numeric keys to set the new value. Press the Enter key.
TIME DELAY MIN:SEC Displays the corrected starting aid time (minutes:seconds) delay setting.
STARTING AID ##:##
TIME DELAY MIN:SEC Displays the crank on time delay in minutes:seconds. When required,
CRANK ON ??:?? use the numeric keys to set the new value. Press the Enter key.
TIME DELAY MIN:SEC Displays the crank pause time delay in minutes:seconds. When
CRANK PAUSE ??:?? required, use the numeric keys to set the new value. Press the Enter key.
TIME DELAY MIN:SEC Displays the engine cooldown time delay in minutes:seconds. When
ENG COOLDOWN ??:?? required, use the numeric keys to set the new value. Press the Enter key.
OVERCRANK SHUTDOWN Displays the engine crank cycles before overcrank shutdown. When
CRANK CYCLES ? required, use the numeric keys to set the new value. Press the Enter key.
OVERCRANK SHUTDOWN Displays the corrected engine crank cycles before overcrank shutdown
CRANK CYCLES # setting.
TIME DELAY MIN:SEC Displays the overvoltage time delay in minutes:seconds. When required,
OVERVOLTAGE ??:?? use the numeric keys to set the new value. Press the Enter key.
TIME DELAY MIN:SEC Displays the corrected overvoltage time (minutes:seconds) delay
OVERVOLTAGE ##:## setting.
TIME DELAY MIN:SEC Displays the undervoltage time delay in minutes:seconds. When
UNDERVOLTAGE ??:?? required, use the numeric keys to set the new value. Press the Enter key.
TIME DELAY MIN:SEC Displays the corrected undervoltage time (minutes:seconds) delay
UNDERVOLTAGE ##:## setting.
TIME DELAY MIN:SEC Displays the load shed time delay in minutes:seconds. When required,
LOAD SHED KW ??:?? use the numeric keys to set the new value. Press the Enter key.
TIME DELAY MIN:SEC Displays the corrected load shed time (minutes:seconds) delay setting.
LOAD SHED KW ##:##
MENU 8
Returns the user to the time delays heading.
TIME DELAYS
Digital and Analog Inputs. After the user selects the Figure 2-18 Analog Input Logistics
input, the setup requires entering the following choices
or values: enabled (yes/no), inhibit time, and delay time.
Battle Switch/Fault Shutdown Override Switch. The
D Enabled. This menu entry enables the input. The battle switch function forces the system to ignore normal
previous yes/no selection does not activate the input. fault shutdowns such as low oil pressure and high
Digital inputs have three tier groups: the selection engine temperature. The battle switch does not
group (25 total), the chosen group (up to 21 total), and override the emergency stop and overspeed shutdown.
the enabled group (up to 21 total based on the chosen When the battle switch function is enabled the generator
group). Analog inputs have separate warning and set continues to run regardless of shutdown signals
shutdown enabled choices. where potential engine/generator damage can occur.
SETUP DIGITAL →
AUXILIARY INPUTS
Displays the setup of digital auxiliary inputs heading.
DIGITAL INPUT 01 → Displays the digital input 01 with the user-defined description.
(USER DEFINED DESC) Note: Press the down arrow to move to the start of the next input setup.
DIGITAL INPUT 01 → Identifies the signal source for digital input 01. Use the menu down ↓ key
(see Group A) YES/NO to select the digital input.
Group A Group A, continued
The preprogrammed FIELD OVERVOLTAGE Y/N
selections include the IDLE MODE ACTIVE Y/N
following: (ECM engine only)
WARNING Y/N BATTLE SWITCH Y/N
SHUTDOWN TYPE A Y/N (see Battle Switch/Fault
SHUTDOWN TYPE B Y/N Shutdown Override Switch
VOLTAGE RAISE Y/N on the previous page.)
VOLTAGE LOWER Y/N GROUND FAULT Y/N
VAR PF MODE Y/N BAT CHGR FAULT Y/N
REMOTE SHUTDOWN Y/N HI OIL TEMP Y/N
REMOTE RESET Y/N LOW COOLANT LVL Y/N
AIR DAMPER Y/N LOW COOLANT TEMP Y/N
LOW FUEL Y/N (not user selectable)
DIGITAL INPUT 01 →
Displays the digital input 01, enabled yes or no selection.
ENABLED YES/NO
DIGITAL INPUT 01 →
Entering YES enables digital input 01.
ENABLED NO
DIGITAL INPUT 01 →
Press the Enter key.
ENABLED YES
DIGITAL INPUT 01 →
Confirms the entry.
ENABLED YES
OR
DIGITAL INPUT 01 →
ENABLED YES Entering NO disables digital input 01.
DIGITAL INPUT 01 →
ENABLED NO Press the Enter key.
DIGITAL INPUT 01 →
Confirms the entry.
ENABLED NO
DIGITAL INPUT 01 → Displays the digital input 01 inhibit time (minutes:seconds) setting. When
INHIBIT TIME ?:?? required, use the numeric keys to set the new values. Press the Enter
key.
DIGITAL INPUT 01
Displays the corrected inhibit time (minutes:seconds) setting.
INHIBIT TIME #:##
DIGITAL INPUT 01 → Displays the digital input 01 delay time (minutes:seconds) setting. When
DELAY TIME ?:?? required, use the numeric keys to set the new values. Press the Enter
key.
DIGITAL INPUT 01 →
Displays the corrected delay time (minutes:seconds) setting.
DELAY TIME #:##
DIGITAL INPUT 01 →
(USER DEFINED DESC) Returns the user to digital input 01.
DIGITAL INPUT XX → Displays digital inputs 02 to 21. Note: Press the down arrow to scroll
(USER DEFINED DESC) through additional digital auxiliary inputs or enter the input number.
Note: Press the right arrow at each digital auxiliary input to enable the
selection, inhibit time setting, and delay time setting. See Digital Input
01 instructions for complete procedure and Group A selections.
MENU 9
Returns the user to the menu number and name.
INPUT SETUP
SETUP DIGITAL →
AUXILIARY INPUTS Returns the user to setup digital auxiliary inputs.
SETUP ANALOG →
AUXILIARY INPUTS Displays the setup of analog auxiliary inputs heading.
ANALOG INPUT 01 →
Entering YES enables the warning analog input 01.
WARNING ENABLED NO
ANALOG INPUT 01 →
Press the Enter key.
WARNING ENABLED YES
AND
ANALOG INPUT 01 →
Confirms the entry.
WARNING ENABLED YES
OR
ANALOG INPUT 01 →
WARNING ENABLED YES Entering NO disables the warning analog input 01.
ANALOG INPUT 01 →
WARNING ENABLED NO Press the Enter key.
AND
ANALOG INPUT 01 →
Confirms the entry.
WARNING ENABLED NO
ANALOG INPUT 01 →
SHUTDOWN ENABLED Y/N
Displays the analog input 01, shutdown enabled selection.
ANALOG INPUT 01 →
SHUTDOWN ENABLED NO Entering YES enables the shutdown analog input 01.
ANALOG INPUT 01 →
SHUTDOWN ENABLED YES Press the Enter key.
AND
ANALOG INPUT 01 →
Confirms the entry.
SHUTDOWN ENABLED YES
OR
ANALOG INPUT 01 →
Entering NO disables the shutdown analog input 01.
SHUTDOWN ENABLED YES
ANALOG INPUT 01 →
Press the Enter key.
SHUTDOWN ENABLED NO
AND
ANALOG INPUT 01 →
Confirms the entry.
SHUTDOWN ENABLED NO
ANALOG INPUT 01 → Displays the analog input 01, inhibit time (minutes:seconds) setting.
INHIBIT TIME ?:?? When required, use the numeric keys to set the new values. Press the
Enter key.
ANALOG INPUT 01 →
Displays the corrected inhibit time (minutes:seconds) setting.
INHIBIT TIME #:##
ANALOG INPUT 01 → Displays the analog input 01, warning time (minutes:seconds) delay
WARN DELAY TIME ?:?? setting. When required, use the numeric keys to set the new values.
Press the Enter key.
ANALOG INPUT 01 → Displays the corrected warning time (minutes:seconds) delay setting.
WARN DELAY TIME #:##
ANALOG INPUT 01 → Displays the analog input 01, shutdown time (minutes:seconds) delay
SDWN DELAY TIME ?:?? setting. When required, use the numeric keys to set the new values.
Press the Enter key.
ANALOG INPUT 01 →
SDWN DELAY TIME #:##
Displays the corrected shutdown time (minutes:seconds) delay setting.
ANALOG INPUT 01 → Displays the analog input 01, low shutdown value. When required, use
LO SDWN VALUE ? the numeric keys to set the new values. Press the Enter key.
Note: The user must scale the analog input value in order to calculate the
low/high warning and shutdown values based on a 0--5 VDC scale. See
Menu 12—Calibration.
ANALOG INPUT 01 →
LO SDWN VALUE #
Displays the corrected low shutdown value.
ANALOG INPUT 01 → Displays the analog input 01, low warning value. When required, use the
LO WARN VALUE ? numeric keys to set the new values. Press the Enter key.
Note: The user must scale the analog input value in order to calculate the
low/high warning and shutdown values based on a 0--5 VDC scale. See
Menu 12—Calibration.
ANALOG INPUT 01 →
Displays the corrected low warning value.
LO WARN VALUE #
ANALOG INPUT 01 → Displays the analog input 01, high warning value. When required, use
HI WARN VALUE ? the numeric keys to set the new values. Press the Enter key.
Note: The user must scale the analog input value in order to calculate the
low/high warning and shutdown values based on a 0--5 VDC scale. See
Menu 12—Calibration.
ANALOG INPUT 01 →
Displays the corrected high warning value.
HI WARN VALUE #
ANALOG INPUT 01 → Displays the analog input 01, high shutdown value. When required, use
HI SDWN VALUE ? the numeric keys to set the new values. Press the Enter key.
Note: The user must scale the analog input value in order to calculate the
low/high warning and shutdown values based on a 0--5 VDC scale. See
Menu 12—Calibration.
ANALOG INPUT 01 →
Displays the corrected high shutdown value.
HI SDWN VALUE #
ANALOG INPUT 01 →
Returns the user to analog input 01.
(USER DEFINED DESC)
ANALOG INPUT XX → Displays analog inputs A02 to A07. Note: Press the down arrow to scroll
(USER DEFINED DESC) through additional analog auxiliary inputs or enter the input number.
Note: ECM engines have inputs A01--A07 and non-ECM engines have
inputs A03--A07.
Note: Press the right arrow at each analog auxiliary input for the following
selections and settings:
Warning enabled
Shutdown enabled
Inhibit time
Warning delay time
Shutdown delay time
Low shutdown value
Low warning value
High warning value
High shutdown value
See the Analog Input 01 instructions for the complete procedure.
SETUP ANALOG →
AUXILIARY INPUTS
Returns the user to the setup analog auxiliary input heading.
SETUP DIGITAL →
Returns the user to the setup digital auxiliary input heading.
AUXILIARY INPUTS
DEFINE COMMON →
FAULTS
Displays the common faults heading.
SYSTEM EVENTS →
Displays the system events heading.
COMMON FAULT Y/N Gives the user the option to add or delete the selection from the defined
(see Group B) system events group. Press the Menu Down key to continue to the next
selection (repeat as necessary).
COMMON FAULT NO
(see Group B)
Entering YES adds the selection to the defined system event group.
OR
COMMON FAULT YES Entering NO removes the selection from the defined system event group.
(see Group B)
COMMON FAULT NO
Press the Enter key.
(see Group B)
COMMON FAULT NO
(see Group B)
Confirms the entry.
DIGITAL INPUTS →
Displays the digital inputs heading.
COMMON FAULT Y/N Gives the user the option to add or delete selection from the defined
Dxx (see Group C) digital faults starting with D01. Note: Press the Menu Down key to
continue to the next selection D02--D21 (repeat as necessary).
COMMON FAULT NO Entering YES adds the selection to the defined digital fault group.
Dxx (see Group C)
COMMON FAULT YES
Dxx (see Group C) Press the Enter key.
COMMON FAULT NO
Dxx (see Group C)
Press the Enter key.
COMMON FAULT NO
Confirms the entry.
Dxx (see Group C)
Group C
Up to 21 PC user-defined digital
status and fault inputs designated
as D01 to D21 can result in an
digital input common fault.
ANALOG INPUTS →
Displays the analog inputs heading.
COMMON FAULT Y/N Gives the user the option to add or delete selection from the defined
Axx(see Group D)LO WARNING→ analog faults starting with A01. Note: Press the Menu Down key to
continue to the next selection A02--A07 (repeat as necessary).
Group D
Up to 7 analog inputs, PC user-
defined status events and faults
designated as A01 to A07. Each
of the 7 is assignable as a
shutdown or warning with high
and low settings.
COMMON FAULT NO Entering YES adds the low warning selection to the defined analog fault
A01 LO WARNING→ group.
COMMON FAULT YES Press the Enter key.
A01 LO WARNING→
OR
COMMON FAULT YES Entering NO removes the low warning selection from the defined analog
A01 LO WARNING→ fault group.
COMMON FAULT NO
A01 LO WARNING→ Press the Enter key.
COMMON FAULT NO
Confirms the entry.
A01 LO WARNING→
COMMON FAULT Y/N Indicates whether the previously user-defined analog output was
A01 HI WARNING→ selected (yes or no) as a high warning fault.
COMMON FAULT NO Entering YES adds the high warning selection to the defined analog fault
A01 HI WARNING→ group.
OR
COMMON FAULT YES Entering NO removes the high warning selection from the defined analog
A01 HI WARNING→ fault group.
COMMON FAULT NO
A01 HI WARNING→ Press the Enter key.
COMMON FAULT NO
Confirms the entry.
A01 HI WARNING→
COMMON FAULT Y/N Indicates whether the previously user-defined analog output was
A01 LO SHUTDOWN→ selected (yes or no) as a low shutdown fault.
COMMON FAULT NO Entering YES adds the low shutdown selection to the defined analog fault
A01 LO SHUTDOWN→ group.
COMMON FAULT YES Press the Enter key.
A01 LO SHUTDOWN→
OR
COMMON FAULT YES Entering NO removes the low shutdown selection from the defined
A01 LO SHUTDOWN→ analog fault group.
COMMON FAULT NO
A01 LO SHUTDOWN→ Press the Enter key.
COMMON FAULT NO
A01 LO SHUTDOWN→ Confirms the entry.
COMMON FAULT Y/N Indicates whether the previously user-defined analog output was
A01 HI SHUTDOWN→ selected (yes or no) as a high shutdown fault.
COMMON FAULT NO Entering YES adds the high shutdown selection to the defined analog
A01 HI SHUTDOWN→ fault group.
COMMON FAULT YES Press the Enter key.
A01 HI SHUTDOWN→
OR
COMMON FAULT YES Entering NO removes the high shutdown selection from the defined
A01 HI SHUTDOWN→ analog fault group.
COMMON FAULT NO Press the Enter key.
A01 HI SHUTDOWN→
COMMON FAULT Y/N Returns the user to common fault (analog inputs) heading.
A01 LO WARNING→ Press the Menu Down key to continue to the next selection A02--A07
(repeat as necessary).
COMMON FAULT Y/N Gives the user the option to add or delete selection from the next defined
Axx(see Group D)LO WARNING→ analog fault. Note: Use the A01 common fault analog input setup
procedure shown above for A02--A07. To go
Group D
Up to 7 analog inputs, PC user-
defined status events and faults
designated as A01 to A07. Each
of the 7 is assignable as a
shutdown or warning with high
and low settings.
DEFINE COMMON →
FAULTS
Returns the user to the define common faults heading.
RELAY DRV OUT 01 → Gives the user previously selected items for relay driver outputs (RDO)
(user defined) starting with 01. Note: Press the down arrow to continue to the next relay
driver output 02--31 or enter the RDO number.
Note: The RDO can be assigned from the SYSTEM EVENTS, DIGITAL
INPUTS, or ANALOG INPUTS groups. The start of each of these groups
are highlighted on the following pages.
SYSTEM EVENTS →
Displays the system events heading.
RELAY DRV OUT 01 Y/N Gives the user the option to assign a system event to an RDO. Press the
(see Group B) Menu Down key to continue to the next selection (repeat as necessary).
RELAY DRV OUT 01 NO Entering YES adds the selection to the RDO group.
(see Group B) Note: Func(Function) Used by (RDO) XX Reassign? appears when the
user attempts to assign an RDO to a function already assigned.
Note: Cannot Change (because the) NFPA is Enabled appears when the
user attempts to modify the RDO setting that is a NFPA 110 default
requirement.
DIGITAL INPUTS →
Displays the digital inputs heading.
RELAY DRV OUT 01 Y/N Gives the user the option to assign a digital input to an RDO starting with
Dxx (see Group C) D01. Press the Menu Down key to continue to the next selection
D02--D21 (repeat as necessary).
Note: Func(Function) Used by (RDO) XX Reassign? appears when the
user attempts to assign an RDO to a function already assigned.
RELAY DRV OUT 01 NO Entering YES adds the selection to the RDO group.
Dxx (see Group C) Note: Func(Function) Used by (RDO) XX Reassign? appears when the
user attempts to assign an RDO to a function already assigned.
Note: Cannot Change (because the) NFPA is Enabled appears when the
user attempts to modify the RDO setting that is a NFPA 110 default
requirement.
Group C
Up to user-defined digital status
and fault inputs designated as
D01 to D21 can result in a digital
input common fault.
ANALOG INPUTS →
Displays the analog inputs heading.
RELAY DRV OUT 01 Y/N Gives the user the option to assign an analog input to an RDO starting
Axx(see Group D)LO WARNING→ with A01. Note: Press the Menu Down key to continue to the next
selection A02-A07 (repeat as necessary).
Group D
Up to 7 analog inputs, user-
defined status events and
faults designated as A01 to
A07. Each of the 7 is
assignable as a shutdown or
warning with high or low
settings.
RELAY DRV OUT 01 Y/N Indicates whether the previously user-defined analog RDO was selected
A01 LO WARNING→ (yes or no) as a low warning fault.
RELAY DRV OUT 01 NO Entering YES adds the low warning selection to the defined analog RDO
A01 LO WARNING→ group.
OR
RELAY DRV OUT 01 YES Entering NO removes the low warning selection from the defined analog
A01 LO WARNING→ RDO group.
RELAY DRV OUT 01 Y/N Indicates whether the previously user-defined analog RDO was selected
A01 HI WARNING→ (yes or no) as a high warning fault.
RELAY DRV OUT 01 NO Entering YES adds the high warning selection to the defined analog RDO
A01 HI WARNING→ group.
OR
RELAY DRV OUT 01 YES Entering NO removes the high warning selection from the defined analog
A01 HI WARNING→ RDO group.
RELAY DRV OUT 01 Y/N Indicates whether the previously user-defined analog RDO was selected
A01 LO SHUTDOWN→ (yes or no) as a low shutdown fault.
RELAY DRV OUT 01 NO Entering YES adds the low shutdown selection to the defined analog
A01 LO SHUTDOWN→ RDO group.
RELAY DRV OUT 01 YES
A01 LO SHUTDOWN→ Press the Enter key.
OR
RELAY DRV OUT 01 YES Entering NO removes the low shutdown selection from the defined
A01 LO SHUTDOWN→ analog RDO group.
RELAY DRV OUT 01 Y/N Indicates whether the previously user-defined analog RDO was selected
A01 HI SHUTDOWN→ (yes or no) as a high shutdown fault.
RELAY DRV OUT 01 NO Entering YES adds the high shutdown selection to the defined analog
A01 HI SHUTDOWN→ RDO group.
RELAY DRV OUT 01 YES
A01 HI SHUTDOWN→ Press the Enter key.
OR
RELAY DRV OUT 01 YES Entering NO removes the high shutdown selection from the defined
A01 HI SHUTDOWN→ analog RDO group.
RELAY DRV OUT 01 Y/N Returns the user to the analog RDO (analog inputs) heading. Press the
A01 LO WARNING→ Menu Down key to continue to the next selection A02--A07 (repeat as
necessary).
RELAY DRV OUT 01 Y/N Gives the user the option to add or delete a selection for the next analog
Axx(see Group D)LO WARNING→ RDO. Note: Use the A01 analog RDO setup procedure shown above for
A02--A07. Go to
ANALOG INPUTS → Returns the user to the analog inputs heading. Press the Menu Right key.
RELAY DRV OUT XX → Gives the user the option to add or delete a selection for the next RDO.
(user defined) Note: Use the RDO 01 setup procedure shown above for RDOs 02--31.
Go to
DEFINE COMMON →
FAULTS
Displays the common faults heading.
RELAY DRV OUT XX → Gives the user previously selected items for the relay driver outputs
S’WARE CONTROLLED #X (RDO). Press the down arrow to scroll through relay driver outputs 1--31
or enter the RDO number. Locate the SCRDO display.
DEACTIVATE RDO? → When required (SCRDO is currently active), enter the YES key to
deactivate the SCRDO.
AVG L-L V # → Displays the average line-to-line volts and voltage adjustment. Enter the
VOLT ADJ ?.? desired nominal voltage using the numeric keys. Press the Menu Right
→ key prior to entering the decimal value.
AND
AVG L-L V # →
VOLT ADJ ?.? Use the numeric keys to enter the decimal value. Press the Enter key.
AVG L-L V # →
Confirms the entry.
VOLT ADJ #.#
L1-L2 VOLTS →
Displays L1-L2 volts.
#
L3-L1 VOLTS →
Displays L3-L1 volts (3 phase only).
#
AVG L-L V # → Returns the user to the average line-to-line volts and voltage adjustment
VOLT ADJ # heading.
UNDER FREQ UNLOAD → Displays the under frequency (volts per Hz) unloading (yes or no)
ENABLED N/Y selection.
AND
FREQUENCY # HZ →
Use the numeric keys to enter the decimal value. Press the Enter key.
SETPOINT ?.? HZ
FREQUENCY # HZ →
SETPOINT #.# HZ
Confirms the entry.
SLOPE →
#.# VOLTS-PER-CYCLE Confirms the entry.
REACTIVE DROOP →
Displays the reactive droop selection (yes or no).
ENABLED N/Y
REACTIVE DROOP →
ENABLED NO
Entering YES enables the reactive droop feature.
REACTIVE DROOP →
ENABLED YES Press the Enter key.
REACTIVE DROOP →
ENABLED YES
Confirms the entry.
OR
REACTIVE DROOP →
Entering NO disables the reactive droop feature.
ENABLED YES
REACTIVE DROOP →
Press the Enter key.
ENABLED NO
.8 PF RATED LOAD → Displays the reactive (voltage) droop as a percentage of the rated
VOLTAGE DROOP ?.?% voltage at rated load. When required, enter the desired reactive droop
using the numeric keys. Press the Menu Right → key prior to entering
the decimal value.
AND
.8 PF RATED LOAD →
Use the numeric keys to enter the decimal value. Press the Enter key.
VOLTAGE DROOP ?.?%
.8 PF RATED LOAD →
Confirms the entry.
VOLTAGE DROOP #.#%
REACTIVE DROOP →
ENABLED N/Y Returns the user to reactive droop selection heading.
VAR CONTROL →
Displays the VAR control selection (yes or no).
ENABLED N/Y
VAR CONTROL →
Confirms the entry.
ENABLED YES
OR
VAR CONTROL →
ENABLED YES Entering NO disables the VAR control feature.
VAR CONTROL →
ENABLED NO Press the Enter key.
VAR CONTROL →
Confirms the entry.
ENABLED NO
TOTAL KVAR # → Displays total kVAR (running) and kVAR adjustment settings. Enter the
KVAR ADJ ?.? desired kVAR adjustment using the numeric keys. Press the Menu Right
→ key prior to entering the decimal value.
AND
TOTAL KVAR # →
KVAR ADJ ?.? Use the numeric keys to enter the decimal value. Press the Enter key.
TOTAL KVAR # →
KVAR ADJ #.# Confirms the entry.
GENERATING YES → Displays the generating kVAR selection. When required, use the NO key
to choose absorbing kVAR.
GENERATING YES →
Confirms the entry.
VAR CONTROL →
Returns the user to VAR control selection heading.
ENABLED N/Y
PF CONTROL →
ENABLED N/Y
Displays the power factor control selection (yes or no).
PF CONTROL →
Confirms the entry.
ENABLED YES
OR
PF CONTROL → Entering NO disables the power factor conrol feature.
ENABLED YES
PF CONTROL →
Press the Enter key.
ENABLED NO
PF CONTROL →
Confirms the entry.
ENABLED NO
AVERAGE PF # → Displays the average power factor and power factor adjustment settings.
PF ADJ ?.? Enter the desired kVAR adjustment using the numeric keys. Press the
Menu Right → key prior to entering the decimal value.
AND
AVERAGE PF # →
Use the numeric keys to enter the decimal value. Press the Enter key.
PF ADJ ?.?
AVERAGE PF # →
PF ADJ #.# Confirms the entry.
LAGGING YES → Displays the lagging PF selection. When required, use the NO key to
choose leading PF.
LAGGING YES →
Confirms the entry.
PF CONTROL →
Returns the user to the power factor control selection heading.
ENABLED N/Y
Menu 12—Calibration
Menu 12 Displays with Key Entries
Key
Entry Display Description
SCALE AC ANALOG
Displays the scale AC analog inputs heading.
INPUTS
GEN L1-L0 V # Measure the generator set output voltage for single and three-phase
CALIB REF ?.? models between L1-L0 using a voltmeter and enter the result using the
numeric keys. Press the Menu Right → key prior to entering the decimal
value.
Note: The generator set must be running for the following steps.
AND
GEN L1-L0 V #
CALIB REF ?.?
Use the numeric keys to enter the decimal value. Press the Enter key.
GEN L1-L0 V #
Confirms the entry.
CALIB REF #.#
GEN L2-L0 V # Measure the generator set output voltage for three-phase models
CALIB REF ?.? between L2-L0 using a voltmeter and enter the result using the numeric
keys. Press the Menu Right → key prior to entering the decimal value.
AND
GEN L2-L0 V # Use the numeric keys to enter the decimal value. Press the Enter key.
CALIB REF ?.?
GEN L2-L0 V #
Confirms the entry.
CALIB REF #.#
GEN L3-L0 V # Three-Phase Models only. Measure the generator set output voltage
CALIB REF ?.? for three-phase models between L3-L0 using a voltmeter and enter the
result using the numeric keys. Press the Menu Right → key prior to
entering the decimal value.
AND
GEN L3-L0 V # Use the numeric keys to enter the decimal value. Press the Enter key.
CALIB REF ?.?
GEN L3-L0 V #
Confirms the entry.
CALIB REF #
GEN L1 AMPS # Measure the generator set output current for single- and three-phase
CALIB REF ?.? models at L1 using an AC ammeter and enter the result using the numeric
keys. Press the Menu Right → key prior to entering the decimal value.
AND
GEN L1 AMPS # Use the numeric keys to enter the decimal value. Press the Enter key.
CALIB REF ?.?
GEN L1 AMPS #
CALIB REF # Confirms the entry.
GEN L2 AMPS # Measure the generator set output current for three-phase models at L2
CALIB REF ?.? using an AC ammeter and enter the result using the numeric keys. Press
the Menu Right → key prior to entering the decimal value.
AND
GEN L2 AMPS # Use the numeric keys to enter the decimal value. Press the Enter key.
CALIB REF ?.?
GEN L3 AMPS # Three-Phase Models only. Measure the generator set output current
CALIB REF ?.? for three-phase models at L3 using an AC ammeter and enter the result
using the numeric keys. Press the Menu Right → key prior to entering
the decimal value.
AND
GEN L3 AMPS # Use the numeric keys to enter the decimal value. Press the Enter key.
CALIB REF ?.?
GEN L3 AMPS #
CALIB REF #
Confirms the entry.
RESTORE
DEFAULTS?
Displays the restore defaults selection (yes or no).
RESTORE When required, enter YES to activate the restore calibration defaults
DEFAULTS? YES setting. Press the Enter key. Note: Entering Yes will delete all of the
previously entered voltage and current data based on system voltage
and kW and restore the calibration default settings.
RESTORE
Confirms the entry.
DEFAULTS? YES
SCALE AC ANALOG →
INPUTS
Returns the user to the scale AC analog inputs heading.
ZERO AUX. ANALOG Gives the user the option to calibrate the auxiliary analog inputs for zero
INPUTS? input signals. Note: ECM engines have inputs A01--A07 and non-ECM
engines have inputs A03--A07.
ZERO AUX. ANALOG When required, enter YES to activate the auto-zero auxiliary analog
INPUTS? YES inputs feature. Press the Enter key.
ANALOG 01 # Displays the analog 01 and scale value 1 settings. Use the numeric keys
SCALE VALUE 1 ? to enter the minimum value based on the previously calculated 5 VDC
analog input value. Note: There is no calibration available on analogs
inputs 01 and 02 with non-ECM engines.
SCAL 1 #--#.#V Note: Press the Menu Right → key to review both the scale value 1 and
SCAL 2 #--#.#V scale value 2 settings any time during the setup procedure.
ANALOG 01 # Displays analog 01 and scale value 2 settings. Use the numeric keys to
SCALE VALUE 2 ? enter the maximum value based on the previously calculated 5 VDC
analog value.
SCALE AUX. ANALOG →
Returns the user to the scale auxiliary analog inputs heading.
INPUTS
Menu 13—Communications
Menu 13 Displays with Key Entries
Key
Entry Display Description
MENU 13
COMMUNICATIONS Displays the menu number and name.
PROTOCOL →
Displays the KBUS protocol heading.
KBUS
OR
KBUS ONLINE YES Entering NO deactivates the online KBUS selection.
KBUS ONLINE NO
Confirms the entry.
CONNECTION TYPE → Displays the user-defined connection type. Press the Down arrow key
(USER DEFINED) Y/N if the correct connection type is displayed. If the desired connection type
is not displayed, press the Right arrow key until the desired connection
type appears.
CONNECTION TYPES
LOCAL SINGLE Y/N
LOCAL LAN N/Y
LOCAL LAN CONV N/Y Entering YES selects the connection type shown. Note: Selecting one
REMOTE SINGLE N/Y connection type deselects any previously selected choice.
REMOTE LAN N/Y
REMOTE LAN CONV N/Y
CONNECTION TYPE →
(USER DEFINED) YES
Confirms the entry.
PRIMARY PORT → Displays the user-defined primary port subheading. Press the Down
(USER DEFINED) Y/N arrow key if the correct primary port type is displayed. If the desired
primary port type is not displayed, press the Right arrow key until the
desired primary port type appears.
PRIMARY PORTS Entering YES selects the primary port shown. Note: Selecting one
RS-232 Y/N primary port deselects any previously selected choice.
RS-485 ISO 1 N/Y
PRIMARY PORT →
Confirms the entry.
(USER DEFINED) YES
ADDRESS ? Displays the LAN connection address number. Use the numeric keys to
(LAN Connections) enter the desired address 1--128. Use one address number per unit and
use consecutive numbers. Individual addresses are necessary for the
software to call up the desired unit.
ADDRESS #
Confirms the entry.
(LAN Connections)
SYSTEM ID ? Displays the system ID request. Use the numeric keys to enter the
(Remote Connections) required system ID of remote connections. The system ID is a password.
The user must use the same password for all devices at a site.
SYSTEM ID #
Confirms the entry.
(Remote Connections)
BAUD RATE → Displays the user-defined baud rate selection. Press the Down arrow
(USER DEFINED) Y/N key if the correct baud rate is displayed. If the desired baud rate is not
displayed, press the Right arrow key until the desired baud rate appears.
BAUD RATES
1200 Y/N
Entering YES selects the baud rate shown. Note: Selecting one baud
2400 N/Y
9600 N/Y
rate deselects any previously selected choice.
BAUD RATE →
Press the Enter key.
(USER DEFINED) YES
BAUD RATE →
Confirms the entry.
(USER DEFINED) YES
MENU 13
COMMUNICATIONS Returns the user to the menu number and name.
PROTOCOL →
Returns the user to kBUS protocol heading.
KBUS
PROTOCOL →
MODBUS
Displays the Modbus protocol heading.
OR
MODBUS ONLINE YES Entering NO de-activates the online Modbus selection.
MODBUS ONLINE NO
Confirms the entry.
CONNECTION TYPE → Displays the user-defined connection types. Press the Down arrow key
(USER DEFINED) Y/N if the correct connection type is displayed. If the desired connection type
is not displayed, press the Right arrow key until the desired connection
type appears.
CONNECTION TYPES
Entering YES selects the connection type shown. Choices are a single
SINGLE Y/N
or RS-232 to RS-485 convertor. Note: Selecting one connection type
CONVERTOR N/Y
deselects any previously selected choice.
CONNECTION TYPE →
Confirms the entry.
(USER DEFINED) YES
PRIMARY PORT → Displays the user-defined primary ports. Press the Down arrow if the
(USER DEFINED) Y/N correct primary port is displayed. If the desired primary port is not
displayed, press the Right arrow key until the desired primary port
appears.
PRIMARY PORTS
RS-232 Y/N Entering YES selects the primary port shown. Note: Selecting one
RS-485 N/Y primary port deselects any previously selected choice.
PRIMARY PORT →
Press the Enter key.
(USER DEFINED) YES
PRIMARY PORT →
(USER DEFINED) YES Confirms the entry.
ADDRESS ? Displays the address number. Use the numeric keys to enter the desired
address 1--128. Use one address number per unit and use consecutive
numbers. Individual addresses are necessary for the software to call up
the desired unit.
ADDRESS #
Confirms the entry.
BAUD RATE → Displays the user-defined baud rate. Press the Down arrow key if the
(USER DEFINED) Y/N correct baud rate is displayed. If the desired baud rate is not displayed,
press the Right arrow key until the desired baud rate appears.
BAUD RATES
9600 N/Y Entering YES selects the baud rate shown. Note: Selecting one baud
19200 N/Y rate deselects any previously selected choice.
BAUD RATE →
Confirms the entry.
(USER DEFINED) YES
PROTOCOL →
Returns the user to Modbus protocol heading.
MODBUS
Menu 14 allows altering controller data either locally D Local—using the controller keypad
using the keypad or remotely using a PC or other device. D Remote—using a PC
The user must enter a password (access code) to D Off—no programming is permitted
enable the programming mode.
Enter Yes to one mode to change the other two choices
Local Programming. Local programming is data to No.
alteration using the controller keypad and display.
Note: Use the generator set controller to initially set up
Remote Programming. Remote programming is data remote programming. Remote programming is
alteration using devices connected to a communication not allowed from a PC unless the controller is first
port using KBUS or Modbusr. set for remote programming using Menu 14.
Note: Log into the local programming mode to edit Note: After completing the programming always place
the programming access code. The factory the controller back in the Programming Mode Off
default access code is the number 0. position to prevent inadvertent program changes.
Use Menu 14 to change the access code. Record the Modbusr is a registered trademark of Schneider
new number and give the access code to authorized Electric.
individuals only. Should the controller logic not accept
the access code or if the new code number is lost,
contact your local authorized distributor/dealer for
password information.
PROGRAMMING MODE → Displays the user-defined programming mode. Press the Down arrow
(USER DEFINED) Y/N key if the correct programming mode is displayed. If the desired
programming mode is not displayed, press the Right arrow key until the
desired programming mode appears.
PROGRAMMING MODES
OFF Y/N Entering YES selects the programming mode shown.
LOCAL N/Y Note: Selecting one programming mode deselects any previously
REMOTE N/Y selected choice.
PROGRAMMING MODE Changing the programming mode requires entering the access code.
ENTER CODE * Enter the access code and press the Enter key.
Note: The factory default access code is the number 0.
PROGRAMMING MODE →
Confirms the entry.
(USER DEFINED) YES
PROGRAMMING MODE → Displays the programming mode and changes the access code. Press
CHANGE ACCESS CODE the Down arrow key if you do not wish to change the access code. To
change the access code, press the Right arrow key.
PROGRAMMING MODE
Enter the old access code and press the Enter key.
ENTER OLD CODE *
PROGRAMMING MODE
Enter the new access code and press the Enter key.
ENTER NEW CODE *
PROGRAMMING MODE →
Confirms the entry.
CHANGE ACCESS CODE
MENU 14
PROGRAMMING MODE
Returns the user to the programming mode heading.
FINAL ASSEMBLY
Displays the final assembly clock number at the factory.
CLOCK NO #
OPERATING DAYS #
Displays the generator set operating days.
MODEL NO #
Displays the generator set model number.
SPEC NO #
Displays the generator set specification number.
GENSET SERIAL NO #
Displays the generator set serial number.
ALTERNATOR PART NO #
Displays the alternator part number.
ENGINE PART NO #
Displays the engine part number.
SERIAL NO #
Displays the generator set serial number.
CONTROLLER SERIAL NO #
Displays the controller serial number.
CODE VERSION #
Displays the controller software (code) version.
COPYRIGHT XXXX
Under normal operating conditions, the generator set’s Disabling the generator set. Accidental starting can
alternator requires no normal service. Consult cause severe injury or death. Before working on the
Section 2.1, Prestart Checklist, for a list of routine generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
checks.
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
3.1 Alternator Service battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
When operating the generator set under dusty or dirty start/stop switch, or engine start command from a remote
conditions, use dry compressed air to blow dust out of computer.
the alternator while the generator set is running. Direct
the stream of air through openings in the generator set
WARNING
end bracket.
WARNING WARNING
3.4.2 350--2000 kW Models with 4. Tighten the bleed screw. Wipe up any fuel leakage.
Single-Bearing Alternator 5. Place the fuel valves in the normal operation
The alternator bearing requires lubrication at intervals position. Open the fuel valve located between the
specified in the generator set technical manual. Use pipe tee and the engine. Close the fuel valves on
Chevron SRI or equivalent antifriction, high-quality each side of the fuel prime pump.
grease with a lubrication temperature range of --30° to
+175°C (--22° to +350°F).
Note: Bleed air from the fuel system according to the Valve Open Valve Closed PK-272000-H
Pushbutton Description
Off Pushbutton disables the ECM for routine
maintenance to the tank system.
On Pushbutton activates the ECM after the
OFF pushbutton is depressed. On
power-up after a power outage, the ECM
automatically turns on.
Test Pushbutton lights front panel LEDs for
3 seconds and activates the pump/motor
for as long as the pushbutton is depressed.
The alarm relays maintain their original
positions.
Internal test Pushbutton (located inside the ECM) tests
224825
each alarm LED and remote annunciation
relay in sequential order (high fuel to ECM
Figure 3-2 ECM Front Panel Layout functional).
Servicing the day tank. Hazardous voltage can cause Figure 3-4 ECM Pushbuttons
severe injury or death. Service the day tank electrical control
module (ECM) as prescribed in the equipment manual.
Disconnect the power to the day tank before servicing. Press ECM Alarms
the day tank ECM OFF pushbutton to disconnect the power.
The ECM has five standard alarm conditions indicated
Notice that line voltage is still present within the ECM when the
POWER ON light is lit. Ensure that the generator set and day locally by LEDs and remotely by relays. Figure 3-5
tank are electrically grounded. Do not operate the day tank describes the five alarm conditions. Make customer
when standing in water or on wet ground because these connections to the normally open and normally closed
conditions increase the risk of electrocution. relay contacts provided.
Alarm Float
Switch Switch
Leak Alarm Panel Position Position Observation
Normal Open The alarm horn and the lamp are not
energized.
Normal Closed The alarm horn and lamp activate when a
fuel leak occurs. If the alarm switch is
moved to the silence position the lamp
stays on until the fuel leak fault is
corrected.
Silence Open The alarm horn sounds to alert the user
that the alarm horn switch is not in the
normal position and that the alarm horn
will not sound should a fuel leak occur.
FF-273000-D
1
3.6.2 LP Liquid Withdrawal Fuel System
Concept
With the LP liquid withdrawal fuel system, pressurized 2
liquid LP fuel passes from the tank to a vaporizer. The
vaporizer converts the liquid fuel to gas before sending it
to the carburetor. The system also includes a fuel valve
that shuts off the fuel flow when the engine stops.
Contact an authorized service distributor/dealer for
availability. 4 3
135--180 kW
Detroit Diesel
1.2--5 (2.9--11.6) 13--51 (5--20) 3.6.5 Carburetor Adjustment
Series 50
200--275 kW
Detroit Diesel
1.2--5 (2.9--11.6) 13--51 (5--20)
Before adjusting the carburetor, verify that the engine
Series 60 compression and the ignition system meet
Figure 3-10 Recommended Fuel Supply Pressures specifications. Do not adjust the carburetor to
compensate for other engine disorders. If the engine
4. Adjust the fuel supply pressure with the generator speed is incorrect, adjust the electronic governor to
set running at full load. Rotate the adjustment achieve 1800 rpm (at 60 Hz) or 1500 rpm (at 50 Hz).
screw on the fuel regulator until the pressure Adjust the carburetor if governor adjustment alone does
indicated by the manometer matches the specified not result in the desired engine speed.
pressure. Use the lower pressure value if the
generator set still provides good response and full Adjusting the carburetor affects the engine fuel mixture.
power. Lower-than-specified pressures may result Routine carburetor adjustment is not necessary.
in poor response to load changes or lack of power. However, if the carburetor is removed or tampered with,
the carburetor may require adjustment to achieve
5. Reinstall the cover plug. optimum engine performance. Some engines have
sealed carburetors that are not adjustable.
3.6.4 Fuel System Changeover Kits
Gasoline Carburetor Adjustment
Automatic Changeover Refer to the engine operation manual or engine service
manual for gasoline carburetor adjustment information.
A changeover fuel system kit provides automatic
changeover from natural gas to LP gas vapor or from
LP gas vapor to natural gas. The primary and backup Gaseous Carburetor (Fuel Mixer) Adjustment
fuels each have a secondary fuel regulator and a fuel Procedure
valve. Typically, the primary fuel is natural gas; the Use the following procedure to adjust the carburetor
backup fuel is LP gas vapor. When the generator set (fuel mixer).
starts, the primary fuel valve opens and the backup fuel
valve closes. The primary fuel line has a vacuum 1. Start the generator set and run it at approximately
switch in series with a relay connected to the start/run half load.
circuit. When the primary fuel pressure drops below
0.6 kPa (1.4 oz./in.2) or 6.4 cm (2.5 in.) water column , a 2. Adjust the engine fuel mixture screw (Figure 3-11)
relay opens the backup fuel valve and closes the until the engine runs smoothly.
primary fuel valve. When the primary fuel pressure
rises above 0.6 kPa (1.4 oz./in.2) or 6.4 cm (2.5 in.) 3. Apply varying loads and readjust the carburetor as
water column, the generator set uses the primary fuel. necessary to achieve smooth engine performance
Contact an authorized service distributor/dealer for kit at all load levels.
availability.
4. Stop the generator set.
2. Remove the pressure cap to allow the entire Note: A coolant solution of 50% ethylene glycol
system to drain and prevent air pockets from provides freezing protection to --37°C
restricting coolant flow through the engine block. (--34°F) and overheating protection to
129°C (265°F). A coolant solution
3. Open the radiator and/or engine block coolant containing less than 50% ethylene glycol
drain valve(s) and allow the system to drain. may not provide adequate freezing and
overheating protection. A coolant solution
4. If the inside of the radiator has mineral deposits or containing more than 50% ethylene glycol
the used coolant contains dirt or grease, refer to can cause engine or component damage.
Section 3.7.4, Procedure to Flush and Clean the Do not use alcohol or methanol antifreeze
Cooling System. If the cooling system does not or mix them with the specified coolant.
have mineral deposits, go to Section 3.7.5, Refer to the engine operation manual for
Procedure to Refill the Cooling System. recommendations regarding the coolant
mixture to use in extreme temperatures.
3.7.4 Cooling System Flushing and
6. Replace the pressure cap.
Cleaning Procedure
7. Fill the coolant recovery tank to the low mark.
Use the instructions in the engine operation manual
when available to flush and clean the cooling system. 8. Operate the generator set until the thermostat
Otherwise, use the following procedure and the cooling opens when the upper cooling system hose
system cleaner manufacturer’s instructions. warms.
1. Flush the cooling system with clean water. 9. Stop the engine and allow it to cool.
2. If the inside of the radiator still has mineral 10. Remove the pressure cap.
deposits, use a radiator cleaner to remove the
remaining deposits following the manufacturer’s 11. Add coolant to bring the coolant level to just below
instructions. the overflow tube opening of the filler neck.
3. Drain, clean, and flush the coolant recovery tank. 12. Replace the pressure cap.
2. Close the radiator and/or engine block coolant 14. Reenergize the block heater, if equipped.
drain valve(s) and tighten the cooling system hose
clamps.
4 5
2
1
2
3
TP-5353-3 4
1. Air flow
2. Expansion joint nuts for rear tank, left side 2
3. Expansion joint nuts for front tank, left side
4. Top front of radiator 3
TP-5353-3
Figure 3-12 Expansion Joint Nuts, Top Left Side of 1
Radiator, Typical 1. Grease fittings
2. Pressure relief port
3. Radiator assembly
3.9 Fan Bearing Lubrication 4.
5.
Idler shaft grease fittings
Fan shaft grease fittings
The following procedure applies only to 1200--2800 kW Figure 3-13 Radiator Fan Bearings and Pressure
generator sets. Lubricate the radiator fan shaft and idler Relief Ports, Typical
shaft bearings at every engine oil change to avoid
bearing damage. Lubricate the bearings every Note: The fan shaft and idler shaft bearings have
200 hours of operation when the generator set runs in pressure relief ports to prevent bearing
ambient temperatures below 29°C (85°F) or when the damage caused by overlubrication.
generator set runs in a dusty and/or humid environment.
5. Remove excess grease from the bearing pressure
Lubrication and Drive Belt Adjustment Procedure relief ports.
Lubricate the fan shaft and idler shaft bearings with a 6. Inspect the fan drive belt and replace if it is damaged
lithium-complex base, multi-purpose grease with or worn. Check the fan belt tension using a poly
antirust, antifoam, and extreme-pressure additives V-belt tension gauge and adjust the tension, if
having a minimum dropping point of 204°C (400°F). necessary. See Figure 3-14.
Use Mobil Mobilith AW2 NLGI Grade 2 or equivalent.
If the belt slips after the belt tension procedure, clean the
1. Place the generator set master switch in the pulley surfaces and repeat the belt tension procedure. If
OFF/RESET position. slippage continues, replace the fan belt.
2. Disconnect the generator set engine starting Generator Set New Belt, Used Belt*,
battery(ies), negative (--) lead first, and disconnect Model N (lbf.) N (lbf.)
power to the battery charger.
2450--2890 1650--1910
1200-2800 kW
(550--650) (370--430)
3. Remove the belt guards to expose the fan shaft and
* A belt is considered used after 50 hours of service.
idler shaft bearings.
Figure 3-14 Poly V-Belt Tension Specifications
3.10 Battery Battery acid cleanup. Battery acid can cause severe
injury or death. Battery acid is electrically conductive and
corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking
WARNING soda) to a container with 4 L (1 gal.) of water and mix the
neutralizing solution. Pour the neutralizing solution on the
spilled battery acid and continue to add the neutralizing
solution to the spilled battery acid until all evidence of a
chemical reaction (foaming) has ceased. Flush the resulting
liquid with water and dry the area.
Sulfuric acid in batteries. Refer to this section for general battery information and
Can cause severe injury or death. maintenance. All generator set models use a negative
ground with a 12-volt or 24-volt engine electrical system.
Wear protective goggles and
Consult the generator set nameplate for the engine
clothing. Battery acid may cause
blindness and burn skin. electrical system voltage. Consult the generator spec
sheet for battery capacity recommendations for
replacement purposes. The wiring diagrams provide
battery connection information. See Figure 3-15,
Battery gases. Explosion can cause severe injury or
death. Battery gases can cause an explosion. Do not smoke
Figure 3-16, and Figure 3-17 for typical battery
or permit flames or sparks to occur near a battery at any time, connections, including multiple battery configurations.
particularly when it is charging. Do not dispose of a battery in a
fire. To prevent burns and sparks that could cause an 1 2
explosion, avoid touching the battery terminals with tools or
other metal objects. Remove all jewelry before servicing the 1 2
equipment. Discharge static electricity from your body before
touching batteries by first touching a grounded metal surface
away from the battery. To avoid sparks, do not disturb the
battery charger connections while the battery is charging.
Always turn the battery charger off before disconnecting the 1 2
battery connections. Ventilate the compartments containing
batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury
or death. Short circuits can cause bodily injury and/or
equipment damage. Disconnect the battery before generator
set installation or maintenance. Remove all jewelry before
servicing the equipment. Use tools with insulated handles.
Remove the negative (--) lead first when disconnecting the
battery. Reconnect the negative (--) lead last when
reconnecting the battery. Never connect the negative (--) EZ-273000-J
battery cable to the positive (+) connection terminal of the 1. To positive (+) terminal on starter solenoid.
starter solenoid. Do not test the battery condition by shorting 2. To ground (--) terminal on or near starter motor.
the terminals together.
Figure 3-15 12-Volt Engine Electrical System Single
Starter Motor Typical Battery Connection
1 2 3 4
KW-272000-B
1. To positive (+) terminal on starter solenoid. 2
2. To ground (--) terminal on or near starter motor.
3. To positive (+) terminal on second starter solenoid. 1-046
4. To ground (--) terminal on or near second starter motor.
1. Filler caps
2. Electrolyte level
Figure 3-17 24-Volt Engine Electrical System Dual
Starter Motors Typical Battery Figure 3-18 Battery Electrolyte Level Inspection
Connections
caps. Holding the hydrometer vertically, read the 65.6 150 + .028
Example No. 1
number on the glass bulb at the top of the electrolyte + .026
temperature in Figure 3-20 and correct the specific 48.9 120 + .016 Subtract .024 Specific Gravity
+ .014
Corrected Specific Gravity is 1.226
gravity by the amount shown. The battery is fully
charged if the specific gravity is 1.260 at an electrolyte 43.3 110 + .012 1.250 -- .024 = 1.226
temperature of 26.7_C (80_F). Maintain the specific + .010
gravities between cells within ±0.01 of each other. 37.8 100 + .008
Charge the battery if the specific gravity is below 1.215 + .006 Example No. 2
at an electrolyte temperature of 26.7_C (80_F). 32.2 90 + .004
Temperature above 26.7°C (80°F)
+ .002
Note: Some battery testers have four or five beads in a 26.7 80 0 Hydrometer Reading 1.235
test tube. Draw electrolyte into the tube as with -- .002
Acid Temperature 37.8°C (100°F)
the battery hydrometer described in this section 21.1 70 -- .004
or use the manufacturer’s instructions. Use --. 006 Add .008 Specific Gravity
Corrected Specific Gravity is
Figure 3-19 to interpret typical test results. 15.6 60 -- .008
1.243
-- .010
-- 1.1 30 -- .020
3 A good charge
-- .022
1 or 2 A low charge
-- 6.7 20 -- .024
0 A dead battery -- .026
3.10.4 Charging
Use a battery charger to maintain a fully charged battery
when the generator set is used in a standby application.
The engine battery-charging alternator charges the The temperature correction amounts to about .004 (4 points) of
battery while the generator set is running. specific gravity for each 5.5°C (10°F) change in temperature.
1-787
Note: If the generator set is in a temporary prime power
application in which the generator set has periods Figure 3-20 Specific Gravity Temperature Correction
of inactivity, the controller circuitry may drain the
battery. If there is no power source for a battery
charger, place the controller in the prime power
mode, if equipped, or disconnect the battery from
the generator set.
3.11.1 DDEC Features Active code. A code flashing on the SEL lamp indicates
a fault currently exists.
The DDEC system optimizes control of critical engine
functions and protects against serious engine damage Inactive code. A code flashing on the CEL lamp
resulting from conditions such as the following: indicates a previous fault occurrence. The ECM
memory stores inactive codes with time/date
D Low coolant level identification and the following information:
D Low coolant pressure
D First occurrence of each diagnostic code in engine
D High coolant temperature
operating hours.
D Low oil pressure
D High oil temperature D Last occurrence of each diagnostic code in engine
operating hours.
The major components of the DDEC system include the
electronic control module (ECM), engine sensors, and D Total time in seconds that the diagnostic code was
control box, located in the generator set junction box. active.
A-343591-C
Diesel-Fueled Engines
A-364162-B
1. Fill the fuel tank with #2 diesel fuel.
Figure 3-22 Deutz Control Box 2. Condition the fuel system with compatible
additives to control microbial growth.
3.13 Storage Procedure 3. Change the fuel filter/separator and bleed the fuel
system. See the engine owner’s manual.
Perform the following storage procedure before taking a
generator set out of service for three months or longer. Gasoline-Fueled Engines
Follow the engine manufacturer’s recommendations, if
available, for fuel system and internal engine 1. Add stabilizer to the fuel system. Follow the
component storage. manufacturer’s recommended procedure.
If a fogging agent is not available perform the following: 5. Spread a light film of oil over unpainted metallic
surfaces to inhibit rust and corrosion.
1. Remove the spark plugs.
4. Reinstall the spark plugs and torque them to 4. Place the battery in a cool, dry location.
specifications.
5. Connect the battery to a float/equalize battery
charger or charge it monthly with a trickle battery
charger. Refer to the battery charger
manufacturer’s recommendations.
This section contains generator set troubleshooting, Battle Switch/Fault Shutdown Override Switch. The
diagnostic, and repair information. battle switch function forces the system to ignore normal
fault shutdowns such as low oil pressure and high
Use the following charts to diagnose and correct engine temperature. The battle switch does not
common problems. First check for simple causes such override the emergency stop and overspeed shutdown.
as a dead engine starting battery or an open circuit When the battle switch function is enabled, the
breaker. The charts include a list of common problems, generator set continues to run regardless of shutdown
possible causes of the problem, recommended signals where potential engine/generator damage can
corrective actions, and references to detailed occur.
information or repair procedures.
When this input is enabled, the yellow warning lamp
Maintain a record of repairs and adjustments performed illuminates and stored warning/shutdown events that
on the equipment. If the procedures in this manual do are ignored continue to log in Menu 5— Event History.
not explain how to correct the problem, contact an
authorized distributor/dealer. Use the record to help See Section 2.9.9, Menu 9—Input Setup, for information
describe the problem and repairs or adjustments made on how to enable the battle switch feature.
to the equipment.
Section or
Publication
Starts hard
Excessive or
abnormal noise
Cranks but
does not start
No or low
output voltage
Stops
suddenly
Lacks power
Overheats
Low oil
pressure
High fuel
consumption
Does not
crank
Probable Causes Recommended Actions Reference*
Controller
x x Controller circuit board(s) inoperative Replace the controller circuit board. Gen. S/M
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual; S/M—Service Manual;
S/S—Spec Sheet; W/D—Wiring Diagram Manual
[ Have an authorized service distributor/dealer perform this service.
TP-6083 7/05
Trouble Symptoms
TP-6083 7/05
Section or
Publication
Starts hard
Excessive or
abnormal noise
Cranks but
does not start
No or low
output voltage
Stops
suddenly
Lacks power
Overheats
Low oil
pressure
High fuel
consumption
Does not
crank
Probable Causes Recommended Actions Reference*
Engine
x x x x Air cleaner clogged Clean or replace the filter element. Eng. O/M
x x x x x Compression weak Check the compression.[ Eng. S/M
x x x x x Engine overload Reduce the electrical load. See the generator set spec sheet for S/S
wattage specifications.
x Exhaust system leak Inspect the exhaust system. Replace the inoperative exhaust I/M
TP-6083 7/05 system components.[
x Exhaust system not securely installed Inspect the exhaust system. Tighten the loose exhaust system I/M
components.[
x x x x Governor inoperative Adjust the governor.[ Gen. S/M
x x Valve clearance incorrect Adjust the valves.[ Eng. S/M
x Vibration excessive Tighten all loose hardware. —
x x x Ignition system inoperative Check the ignition system (spark plugs, spark plug wires, etc.). Eng. O/M
(gas/gasoline only)
Fuel System
x x x Air in fuel system (diesel only) Bleed the diesel fuel system. Eng. O/M
x x Ether canister empty or system Replace or repair the ether starting system. Eng. O/M
inoperative, if equipped (diesel only)
x x Fuel tank empty or fuel valve shut off Add fuel and move the fuel valve to the ON position. —
x x x Fuel feed or injection pump inoperative Rebuild or replace the injection pump.[ Eng. S/M
(diesel only)
x x x Fuel or fuel injectors dirty or faulty Clean, test, and/or replace the inoperative fuel injector.[ Eng. S/M
(diesel only)
x x x x Fuel filter restriction Clean or replace the fuel filter. Eng. O/M
x Fuel solenoid inoperative Troubleshoot the fuel solenoid.[ Eng. S/M
x x Fuel pressure insufficient (gas only) Check the fuel supply and valves.[ S/S, Gen. O/M
x x x x Fuel injection timing out of adjustment Adjust the fuel injection timing.[ Eng. S/M
(diesel only)
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual; S/M—Service Manual;
S/S—Spec Sheet; W/D—Wiring Diagram Manual
[ Have an authorized service distributor/dealer perform this service.
Section or
Publication
Starts hard
Excessive or
abnormal noise
Cranks but
does not start
No or low
output voltage
Stops
suddenly
Lacks power
Overheats
Low oil
pressure
High fuel
consumption
Does not
crank
Probable Causes Recommended Actions Reference*
Alternator
x AC output circuit breaker open Reset the breaker and check for AC voltage at the generator —
* Sec./Section—numbered section of this manual; ATS—Automatic Transfer Switch; Eng.—Engine; Gen.—Generator Set; I/M—Installation Manual; O/M—Operation Manual; S/M—Service Manual;
S/S—Spec Sheet; W/D—Wiring Diagram Manual
[ Have an authorized service distributor/dealer perform this service.
bp #
TP-6083 7/05
Section 5 Generator Set Reconnection
5. Go to Menu 14—Programming Mode and select 11. Replace the controller cover.
the Program Mode—Local. See Section 2.9.14,
12. Place the generator set master switch in the AUTO
Menu 14—Programming Mode, for the complete
or RUN position.
procedure.
GM13984-
C-294301
GM13984-
CHARGER MALFUNCTION
LV HV CM BATTERY CHARGER
ALARM TERMINAL STRIP
GM16088A-A
1
PRIME POWER
SWITCH 2
GM20652-
Figure 6-8 Idle (Speed) Mode Switch Figure 6-11 Prime Power Switch Installation Location
Remote Annunciator
A-258782
NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C NO C
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14
P
42B
P
FBA--1 10 AMP
A-293983
354246B-
Figure 6-14 Remote Annunciator with 14-Relay Dry Contact Kit Connections
A-222654
TP-5352-1
GM16088A-A-
Use the single glass piece located inside the switch for
replacement and order additional glass pieces as
service parts. See Section 2.3.3, Emergency Stop
Switch Reset Procedure. See Section 6.2, Accessory
Connections, for terminal identifications.
alerts the operator through visual and audible signals. Overspeed Battery Voltage
On=High, Blink=Low
The remote serial annunciator kit includes components Emergency Stop User Input #1
for flush and surface mounting. One RSA (master) can Low Coolant Level User Input #2
support up to a maximum of three additional RSAs Low Coolant Temp. User Input #3
(slaves). The RSA will function as master or slave by Low Fuel Alarm Silenced
changing the DIP switch position on the RSA board. If a
generator set fault occurs, the RSA 1000 horn activates
and the corresponding LED illuminates.
System Ready
Figure 6-20 shows the status of the system ready LED,
Generator Running
generator set running LED, communication status LED,
common fault LED, common fault output, and horn for
each fault or status condition. See Figure 6-21 for RSA
wiring connections.
The RSA requires connection to the controller Modbusr
RS-485 port. If the RS-485 port is needed for switchgear
monitoring or a wireless monitor, the RSA cannot be Figure 6-19 Remote Serial Annunciator (RSA 1000)
connected to the controller. If the RS-485 port is
Modbusr is a registered trademark of Schneider Electric.
unavailable, please select an alternate annunciator kit.
550 CONTROLLER
16--LIGHT CONTROLLER
273705
TB10
BR-273000-C GM16088A-A
1. Optional Remote Speed Pot
Figure 6-24 Run Relay Connections
Figure 6-22 Remote Speed Adjustment
Potentiometer Connection, Typical
GM16088A-A
GM13984-/354246B-
GM16759D-C
Note: The 550 controller supports only one connection Upon power loss, a rechargeable battery powers the
for Modbusr communication. If the controller’s wireless monitor. The monitor continues to transmit
RS-485 connection is already used for Modbusr messages for 15 minutes, then transmits a loss of power
communication with other equipment, use signal and enters the sleep mode. The sleep mode can
wireless monitor model GM23409-KP1 or -KP3 last up to 18 hours, until the battery completely
with hardwire inputs through a customer discharges or power is restored. The wireless monitor
connection board for monitoring. continues to send scheduled heartbeat messages
during the sleep mode until the battery discharges
Typical messages might include: completely.
D Overcrank
D Low oil pressure
86
D Overspeed [3.4]
D Common fault
2
4
GM16088A-A/GM10193B-A
1. TB1 terminal strip 4. TB4 terminal strip
2. TB2 terminal strip 5. P23 Connector
3. TB3 terminal strip
Figure 6-32 Terminal Strips on Controller Interconnection Circuit Board (Controller Back Panel Folded Down)
Figure 6-34 Terminal Strips TB6, TB7, TB8, and TB9 on the Controller Connection Kit in the Junction Box
Figure 6-35 Controller (Customer) Connection Kit Terminal Strip Identification with Relay Driver Outputs (RDOs)
The following list contains abbreviations that may appear in this publication.
A, amp ampere cfm cubic feet per minute ext. external
ABDC after bottom dead center CG center of gravity F Fahrenheit, female
AC alternating current CID cubic inch displacement fglass. fiberglass
A/D analog to digital CL centerline FHM flat head machine (screw)
ADC analog to digital converter cm centimeter fl. oz. fluid ounce
adj. adjust, adjustment CMOS complementary metal oxide flex. flexible
ADV advertising dimensional substrate (semiconductor) freq. frequency
drawing cogen. cogeneration FS full scale
AHWT anticipatory high water com communications (port) ft. foot, feet
temperature coml commercial ft. lb. foot pounds (torque)
AISI American Iron and Steel Coml/Rec Commercial/Recreational ft./min. feet per minute
Institute conn. connection
ALOP anticipatory low oil pressure g gram
cont. continued ga. gauge (meters, wire size)
alt. alternator CPVC chlorinated polyvinyl chloride
Al aluminum gal. gallon
crit. critical gen. generator
ANSI American National Standards CRT cathode ray tube
Institute genset generator set
(formerly American Standards CSA Canadian Standards GFI ground fault interrupter
Association, ASA) Association
CT current transformer GND, ground
AO anticipatory only
Cu copper gov. governor
API American Petroleum Institute
cu. in. cubic inch gph gallons per hour
approx. approximate, approximately
cw. clockwise gpm gallons per minute
AR as required, as requested
CWC city water-cooled gr. grade, gross
AS as supplied, as stated, as
suggested cyl. cylinder GRD equipment ground
ASE American Society of Engineers D/A digital to analog gr. wt. gross weight
ASME American Society of DAC digital to analog converter HxWxD height by width by depth
Mechanical Engineers dB decibel HC hex cap
assy. assembly dBA decibel (A weighted) HCHT high cylinder head temperature
ASTM American Society for Testing DC direct current HD heavy duty
Materials DCR direct current resistance HET high exhaust temperature,
ATDC after top dead center high engine temperature
deg., ° degree
ATS automatic transfer switch hex hexagon
dept. department
auto. automatic Hg mercury (element)
dia. diameter
aux. auxiliary HH hex head
DI/EO dual inlet/end outlet
A/V audiovisual HHC hex head cap
DIN Deutsches Institut fur Normung
avg. average e. V. (also Deutsche Industrie HP horsepower
AVR automatic voltage regulator Normenausschuss) hr. hour
AWG American Wire Gauge DIP dual inline package HS heat shrink
AWM appliance wiring material DPDT double-pole, double-throw hsg. housing
bat. battery DPST double-pole, single-throw HVAC heating, ventilation, and air
BBDC before bottom dead center DS disconnect switch conditioning
BC battery charger, battery DVR digital voltage regulator HWT high water temperature
charging E, emer. emergency (power source) Hz hertz (cycles per second)
BCA battery charging alternator EDI electronic data interchange IC integrated circuit
BCI Battery Council International EFR emergency frequency relay ID inside diameter, identification
BDC before dead center e.g. for example (exempli gratia) IEC International Electrotechnical
BHP brake horsepower Commission
EG electronic governor
blk. black (paint color), block IEEE Institute of Electrical and
EGSA Electrical Generating Systems Electronics Engineers
(engine) Association
blk. htr. block heater IMS improved motor starting
EIA Electronic Industries
BMEP brake mean effective pressure Association in. inch
bps bits per second EI/EO end inlet/end outlet in. H2O inches of water
br. brass EMI electromagnetic interference in. Hg inches of mercury
BTDC before top dead center emiss. emission in. lb. inch pounds
Btu British thermal unit eng. engine Inc. incorporated
Btu/min. British thermal units per minute EPA Environmental Protection ind. industrial
C Celsius, centigrade Agency int. internal
cal. calorie EPS emergency power system int./ext. internal/external
CARB California Air Resources Board ER emergency relay I/O input/output
CB circuit breaker ES engineering special, IP iron pipe
cc cubic centimeter engineered special ISO International Organization for
ESD electrostatic discharge Standardization
CCA cold cranking amps
est. estimated J joule
ccw. counterclockwise
E-Stop emergency stop JIS Japanese Industry Standard
CEC Canadian Electrical Code
etc. et cetera (and so forth) k kilo (1000)
cert. certificate, certification, certified
exh. exhaust K kelvin
cfh cubic feet per hour
Use the table below to record user-defined settings Note: The engine ECM may limit the crank cycle even if
during the generator set controller setup and calibration. the controller is set to a longer time period.
The controller default settings and ranges provide
guidelines. The table contains all faults with ranges and
time delays including items that do not have
adjustments.
Relay Inhibit
Refer Driver Time Time
Status or to Digital Output Default Delay* Delay
Fault Menu Display (RDO) Range Setting Selection (sec.) (sec.) User-Defined Settings
AC Sensing 10 AC Sensing RDO-25 Not adjustable
Loss Loss
Access Code 14 0 (zero)
(password)
Analog Aux. 9 User-Defined Default values with 30 sec. 0--60 0--60
Inputs 1--7 A1--A7 Warning Enabled: inhibit, 5
HI warning 90%, sec. delay
LO warning 10%,
HI shutdown 100%,
LO shutdown 1%
Analog Aux. 9 Coolant Default values with 30 sec. 0--60 0--60
Input 1 Temperature Warning Enabled: inhibit, 0
HI/LO warning and sec. delay
HI/LO shutdown are
all engine dependant
Analog Aux. 9 Oil Pressure Default values with 30 sec. 0--60 0--60
Input 2 Warning Enabled: inhibit,
HI/LO warning and 0 sec. delay
HI/LO shutdown are warning,
all engine dependant 5 sec. delay
(255 psi max.) shutdown
Cyclic Cranking 8 1--6 crank cycles 3 cycles
10--30 sec. crank on 15 sec.
1--60 sec. pause 15 sec.
Defined 10 User-Defined RDO-18 Default shutdowns 30 sec. 0--60 0--60
Common Faults include: inhibit,
Emergency stop 5 sec. delay
High coolant temp
Low oil pressure
Overcrank
Overspeed
Digital Aux. 9 User-Defined 30 sec. 0--60 0--60
Inputs 1--21 D1--D21 inhibit, 5
sec. delay
EPS 10 EPS RDO-15 5% of rated
(Emergency Supplying line current
Power System) Load
Supplying Load
High Battery 10 High Battery RDO-13 14.5--16.5 (12V) 16 (12V) 10
Voltage Voltage 29--33 (24V) 32 (24V)
High Coolant 10 Hi Cool RDO-03 30 5 Not adjustable
Temperature Temp
Shutdown Shutdown
High Coolant 10 Hi Cool RDO-06 30 Not adjustable
Temperature Temp
Warning Warning
High Oil 10 Hi Oil Temp RDO-17 30 5 Not adjustable
Temperature Shutdown
Shutdown
* Inhibited time delay is the time delay period after crank disconnect.
The following Definitions and Adjustment and since it is the power in the alternator that translates into
Setting Specifications are intended for users planning engine torque, the engine load is also reduced.
to adjust the voltage regulator beyond the default
settings in order to customize the voltage regulator for a By changing various parameters of this compensation
specific application. technique, the controlling system can be tailored to
match the performance capabilities of nearly any
This information is not intended to be a comprehensive combination of engine and alternator. The point at
explanation of all the terms mentioned. There are which the unloading begins to act or how much
numerous documents available that define these terms unloading occurs can be adjusted to impact such things
more completely than described herein. Any user as maximum voltage droop, maximum speed droop, or
planning to change the generator set controller time to recover. Some applications may not need any
adjustment settings or to apply the generator set to unloading and, in these cases, set the unloading
these types of applications should understand these parameter to disable the function. These parameters
terms. are further described below. An example is provided to
help clarify the relationship between these parameters.
This appendix contains references to other sections of
this manual. Please refer to these sections for further
information and explanation. Underfrequency Unload Slope
Paralleling generator sets can be a complicated and Underfrequency unload slope is the term used to
dangerous exercise. Application programming must be describe the amount that the voltage is reduced,
performed by appropriately skilled and suitably-trained per-cycle-per-second or per-hertz (Hz), when in an
personnel. underfrequency condition. The slope or schedule is
sometimes called the volts-per-hertz slope. When the
electrical frequency drops below the cut-in point (see
Definitions below), the excitation control system temporarily
reduces the regulated voltage to reduce the subsequent
torque on the engine. The amount that the control
Underfrequency Unloading system reduces voltage is defined as the product or
multiplication of the slope and the amount of frequency
Underfrequency unloading is a function used in the
generator excitation control system to improve the or speed below the cut-in point. For every Hz below the
cut-in point, the control system reduces the line-to-line
overall generator set system (engine and alternator)
voltage by an amount equal to the slope.
response. In particular, underfrequency unloading
relates to large-block load applications. When applied
Because each engine responds differently to the
to engine-driven generators, large-block loads cause a various loads encountered, the slope may be adjusted
subsequent transient torque load on the engine. This
to improve the system response. If, when large loads
torque load can reduce the engine’s speed below the
are applied to the generator set, the engine speed drops
normal operating point. Typically, the engine speed below the acceptable limit (as determined by the
controller or governor will compensate for this by
particular loads applied), the slope may need to be
commanding an increase in fuel. If, however, the fuel increased. Increasing the slope will cause the voltage to
system is inadequate to recover from a relatively large droop more during load applications, consequently
load, the speed may never recover. In these instances,
reducing the load torque on the engine and allowing the
other measures must be taken. This is where the speed to increase. If, however, the voltage drops below
underfrequency unloading occurs.
an acceptable lower limit (as determined by the
When the excitation control system detects a drop in the particular loads connected to the generator set), a lower
slope may work better. The underfrequency unloading
speed or electrical frequency below some
predetermined point, the control system enters an function may be disabled by setting the slope to zero.
unloading condition. This can be described as moving
to a lower voltage regulation point. By reducing the Frequency Setpoint or Cut-In Point
output voltage of the alternator, the load on the
generator set is, in effect, reduced. This can be shown The point at which the underfrequency unloading begins
mathematically by Ohm’s law, which states that power is to take effect is adjustable, allowing the system to be
equal to the voltage squared divided by the impedance. tailored for each application. Because the
As the voltage is reduced, the power delivered by the characteristics of the engine have the largest effect on
alternator decreases by a squared relationship and the system’s performance, the engine’s response