Partial Safety Factor On Material and Load Based On IS456, Eurocode &ACI
Partial Safety Factor On Material and Load Based On IS456, Eurocode &ACI
Partial Safety Factor On Material and Load Based On IS456, Eurocode &ACI
&ACI”
-Sudip Shrestha
Introduction:
Partial factor of safety is the certain factor that are usually introduced in order to design a
structure with larger load or reduced strength of material. It is very important to use partial
safety factor in the design as we are designing the structure for the future use and due to
uncertainties of anticipated load and strength of material.Hence, Use of the partial factor of
safety keeps the structure safe in future anticipated load as well as the responsibility of engineer
towards the designed structure is safeguarded.
The design strength of concrete and reinforcing steel is reduced and obtained by dividing the
characteristic strength by the appropriate partial safety factor. the characteristic strength of a
material as obtained from the statistical approach is the strength of that material below which not
more than five per cent of the test results are expected to fall. However, such characteristic
strengths may differ from sample to sample also.
Clause 36.4.2 of IS 456 states that partial factor of safety concrete and steel should be taken as
1.5 and 1.15, respectively when determining the strength of the structures or structural members
employing limit state of collapse. However, when assessing the deflection, the material
properties such as modulus of elasticity should be taken as those associated with the
characteristic strength of the material.
The partial safety factor for steel (1.15) is comparatively lower than that of concrete (1.5)
because the steel for reinforcement is produced in steel plants and commercially available in
specific diameters with expected better-quality control than while mixing of concrete is done in
site.
Moreover, In the concrete the characteristic strength is calculated on the basis of test results on
150 mm standard cubes. But the concrete in the structure has different sizes. To take the size
effect into account, it is assumed that the concrete in the real-world structure develops a strength
of 0.67 times the characteristic strength of cubes.
Characteristic strength of concrete in structure = 0.67 x characteristic strength of cube
Note: It has been observed in experiments conducted on beams or columns that the strength of
concrete in the compression zone at failure is approximately 0.85 times the strength of cylinders
cast and tested in laboratories (Hognestad, et al. 1955; Rüsch 1960). Furthermore, the cylinder
strength (fc) is about 0.80 of the cube strengths(fck)
Characteristic strength of concrete in structure=0.85xcharacteristic strength of cylinder specimen(fc)
= 0.85*0.8 fck (∴ fc/fck =0.8 )
=0.67 fck
The above expression accounts the size effect. The reason behind reducing the characteristic
strength of concrete used in beam and column is due to the size effect as in reality structural
member or concrete is subjected to the sustained load while the cube or cylindrical specimen are
subjected to the short-term load only.
Design load (Pu) = Characteristic load (P) X Partial safety factor for load γf
Respective values of γf for loads in the two limit states as given in Table 18 of IS 456 for
different combinations of loads are listed below:
Most of the value of factor of safety of load in limit state of collapse is greater than unity (1)
which overestimate the possible load and ensure the safe design. As the multiplication of service
load or characteristic load which has only 5% probability to exceed in the design life of the
structure with partial factor of safety increases the design load.
The dead load factor γdf, which is taken as 0.9 to encounter the two factors:
Dead load contributes to stability against overturning or sliding, or
While considering reversal stresses when dead loads are combined with wind or earthquake
loads. In such cases, underestimating the counteracting effects of dead load results in greater
safety.
The partial load factor γf should be taken as unity for all serviceability limit state calculations,
since they relate to the criteria governing normal use.
The characteristic value of an action (load) is its main representative value defined by a nominal
value which is normally expected to have a 95% probability of not being exceeded
Note that combination factor ψ is a device for reducing the design value of variable loads when
they act in combination.
The design value of an action is a product of the representative value and a load factor γFi.
Then, For Permanent actions,
∴Design value = γFi Gk.
For variable actions,
∴Design value = γFi ψi Qk
Combining the design loads will vary with the design situations. Partial safety factors are used to
combine loads and produce the worst design situation for a building or element
In the above the symbols denote as follows
ξ = reduction factor for unfavorable permanent actions G
ASCE/SEI 07–16 2019, Minimum Design Loads for Buildings and Other structures, American
Society of Civil Engineers
ACI 318-19 2019, Building Code Requirements for Structural Concrete and Commentary,
American Concrete Institute,
Pillai, S.U. and D. Menon 2003, Reinforced Concrete Design, 2nd edition, Tata McGraw-Hill
Publishing Company Ltd, New Delhi
Bhatt, Choo, Machginley,2014, Reinforced Concrete Design to Eurocodes Design Theory and
Examples, 4rth edition, CRC press
Explanatory Handbook on Indian Standard Code of Practice for Plain and Reinforced Concrete
(IS 456:1978), Special Publication SP:24, Bureau of Indian Standards, New Delhi, 1983