Single Phase Core & Coil Assembly: General Information
Single Phase Core & Coil Assembly: General Information
General Information
ERMCO single phase distribution transformers are designed and
manufactured in compliance with all applicable ANSI, and RUS
standards. All transformers are oil filled, 65°C rise, and designed for
usual service conditions per ANSI C57.12.00.
Capabilities
• kVA sizes 5 through 250 kVA
• High voltages 2.4 through 19.9 kV (150 kV BIL)
• Low voltages 120 through 600 volts
• Shell form construction (two core loops and one coil)
Special design emphasis:
• Overload
• Fault current
• Extreme transient performance
• Electrical efficiency
• Thermal performance
• Material standardization
Core Cores
• Designed for low watts loss
• High quality grain oriented silicon steel
• Step lap joint construction
• State-of-the-art core forming
• Quality inspection procedure requires 100% loss testing
Coils
• Constructed to pass the next higher BIL ANSI impulse test
• Dual voltage coils are rated at highest BIL in both switch positions
• High voltage taps are wound in two sections for optimum
Coil
magnetic balance
• Wound in a low-high-low configuration in concentric layers
Coil Insulation:
• Each layer is insulated with thermally upgraded 65°C
rise paper
• Layer insulation is coated with an epoxy adhesive in
a diamond pattern for mechanical bonding
• Cooling ducts are rectangular with a flat surface to prevent
pressure damage on layer insulation
ERMCO
2225 Industrial Rd.
Dyersburg, TN 38024
1.800.238.5587
Clamping Structure
• Rigid steel frames
• clamps the coil through high density press board shims
• No pressure is applied to the core
• stress free construction
• assures low core losses remain stable for the life
of the transformer
• The core and coil assembly is securely banded to the top
and bottom frames
• provides excellent short circuit strength
Coil Leads
Assembly Process
High Voltage Leads:
• Leads are stranded copper
• eliminates the possibility of breakage associated
with solid wire
• Leads are joined to coil conductor with insulation piercing
clamp connector
• eliminates the need to abrade the film which would
weaken the conductor
• Leads are attached to a rigid terminal block before connection
to the HV bushing
• provides increased reliability
Quality Assurance
Low Voltage Leads:
• Leads are hardened aluminum alloy
• prevents cold flow at the copper bushing connection
• extends the full length inside the coil body to the low
voltage bushing
• improves reliability by eliminating a welded joint for
a hard alloy tab