Assignment 2 PSM
Assignment 2 PSM
Example. 1. A load having a peak value of 50 MW and 45% load factor is to be supplied by a
steam power station in conjunction with a hydro-power station, the latter supplying 60 million
units of energy per annum with a maximum output of 20 MW.
Cost of fuel Coal Rs 150 per metric ton ; consumption being 0·5
Solution:
Unit supplied by Hydro Power Station= 60 × 106 kWh (As 1 kWh= 1 unit)
Unit supplied by Steam power Station = (197.1×106) - (60 × 106) = 137.1× 106 kWh
Since the maximum output of hydro station is 20 MW, the balance 50 − 20 = 30 MW shall be
150×.5×197.1 ×10 6
Cost of fuel= =Rs 14.7825 × 106
1000
= Rs 27.4422 × 106
6
27.4422 ×10
∴ Overall cost/ kWh = Rs 6
= 13.9 paise (Ans.)
197.1 ×10
Example. 2. The energy cost of a 100 MW steam station working at 40% load factor comes out
to be 12 paise/kWh of energy generated. What will be the cost of energy generated if the load
factor is improved to 60%? The fuel cost of the power station due to increased generation
increase the annual generation cost by 5%.
Solution:
Thus, Total annual cost = Overall cost per unit × Unit generated per annum
Then, increased generation cost= x+ .05x =1.05 x = 1.05 × 42.048× 10 6 =44.1504× 106 Taka
44.1504×106
Overall cost per unit = = 8.4 paise (Ans.)
525.6×10 6
Example. 3. The load duration curve of a system for the whole year of 8760 hours is as shown in
Fig. The system is supplied by two stations A and B having the following annual costs:
Station A = Rs (75,000 + 80 kW + 0·02 kWh)
Station B = Rs (50,000 + 50 kW + 0·03 kWh)
Determine the installed capacity required for each station and for how many hours per year peak
load station should be operated to give the minimum cost per unit generated.
Solution:
Let x = Installed capacity of station B in kW
y = Hours of operation of station B
∴ Installed capacity of station A = (50,000 − x) kW
1 1 8760×x 2
Units generated/ annum by station B = xy= × =0 ·0876 x
2 2 50,000
1 2
Unit generated/ annum by station A = ×50000×8760−0 ·0876 x
2
Annual cost of station A, CA = Rs (75,000 + 80 (50,000 − x) + 0·02 (219 × 106 − 0·0876 x2)
C = CA + CB
= Rs (50,000 + 50 x + 0·00262 x2) + (8·455 × 106 − 80 x − 0·00175 x2)
= Rs (85,05,000 − 30 x + 0·00087 x2)
dC
For minimum annual operating cost, =0
dx
dC
∴ = 0 − 30 + 2 × 0·00087 x
dx
or 0 = −30 + 0·00174 x
30
or x= =17,241 kW
0.00174