Power Supply System, Battery

Charger or DC/DC Converter


The Integrated 19” 2U power supply is built around the
Flatpack2 rectifier and designed for applications such as
switchgear, telecom, emergency lighting and alarm
systems.

The rectifier’s wide DC output range makes it suitable for


parallel operation with all types of stationary batteries,
including lead acid, or nickel cadmium types.

As additional options the measuring and signaling can be


widely extended by incorporating the Eltek Flexi-Monitor and
Relay Board see details in specific Data sheet.

Flatpack2 Integrated 19” 2U


24VDC, 48 VDC, 60 VDC, 110 VDC, 125 VDC & 220 VDC Systems
DOC. NO: CTO30402.400.DS3, rev3

MODULAR ARCHITECTURE APPLICATIONS KEY FEATURES


RECTIFIER MODULE  COMPACT DESIGN AND SIMPLE
The most efficient power conversion Power Utilities INSTALLATION
module in the industry!  Low & High voltage switchgear  85-300 VAC OR DC INPUT
Since the launch the Flatpack 2 family has  Transformer & substations  HOUSE UP TO 4 RECTIFIER
expanded into a wide selection of power MODULES
 Power generation & distribution
ratings and voltages. 24-220 VDC SYSTEMS
 Control & protection 
 Scada system  BULK FEED OUTPUT
The modular architecture, industry-leading
efficiency, compact size, innovative design  Communication equipment  GRAPHICAL 3.2” TFT HIGH
and comprehensive monitoring and control CONTRAST, HIGH RESOLUTION
features provide significant benefits over Railway & Metro infrastructure COLOR DISPLAY FOR EASY
the current industry standard. NAVIGATION IN USER MENU
 Control & protection
 ETHERNET FOR REMOTE OR
 Signaling
LOCAL MONITORING AND
 Safety Systems CONTROL VIA WEB BROWSER
 SNMP PROTOCOL WITH TRAP,
Telecom-mobile SET AND GET ON ETHERNET.
 LTE/4G/WiMAX EMAIL OF TRAP ALARMS
 Distributed antenna system  DIGITAL PROGRAMMABLE RELAY
 Broadband OUTPUTS
 Radio base stations/cell sites  PROGRAMMABLE
MULTIPURPOSE INPUTS
(“DIGITAL INPUTS” OR ANALOG
FP2 Rectifier Module SIGNALS).

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com
Flatpack2 Integrated 19” 2U
Doc CTO30402.400.DS3 – rev3

FRONT VIEW FLATPACK 2 INTEGRATED 19” 2U


MODEL 24-125 VDC-12 KW
Part number CIO30402.4xxx
INPUT DATA
Voltage (nominal) 185-275 VAC or VDC
Voltage (operating range) 85-305 VAC or VDC
Maximum current AC (per input) 11,6-19,2 A
Frequency 45-66 Hz / 0 Hz
Power factor > 0.99
OUTPUT DATA
Voltage (nominal) DC 24, 48, 60, 110, 125 V
REAR VIEW FLATPACK 2 INTEGRATED 19” 2U
Adjustable range DC See module type
Max output power DC 12 kW
Static Voltage regulation +/- 0,5%
CONTROLLER TYPE
Smartpack 2 Master
Basic unit Standard basic
I/O unit Type 2

Specifications are subject to change without notice

AVAILABLE RECTIFIERS & DC/DC CONVERTERS FP2 HE


Models 24/1800 HE 48/3000 SHE 48/2000 HE 48/3000 HE 48-60/2000 HE 110/2000 HE
Part number 241115.205 241119.106 241115.105 241119.105 241115.705 241115.805
INPUT DATA
Voltage AC (nominal) 185-275 VAC 206-264 VAC 185-275 VAC 176-277 VAC 185-275 VAC 185-275 VAC
Voltage DC (nominal) 185-275 VDC - 185-275 VDC - 185-275 VDC 185-275 VDC
Voltage AC (range) 85-300 VAC 85-264 VAC 85-300 VAC 85-305 VAC 85-305 VAC 85-305 VAC
Voltage DC (range) 85-300 VDC - 140-275 VDC - 80-300 VDC 85-300 VDC
Frequency 0-66 Hz 45-66 Hz 45-66 Hz / 0 Hz 45-66 Hz 45-66 Hz / 0 Hz 0-66 Hz
Current (maximum) 11,25 ARMS 16 ARMS 11,6 ARMS 19,2 ARMS 11,6 ARMS 11,9 ARMS
Protection Fuse Fuse Fuse Fuse Fuse Fuse
OUTPUT DATA
Nominal output voltage 24 VDC 48 VDC 48 VDC 48 VDC 48-60 VDC 110-125 VDC
Voltage (default) 26,7 VDC 53,5 VDC 53,5 VDC 53,5 VDC 53,5 VDC 122,5 VDC
Voltage (adjustable range) 21,7-28,8 VDC 43,2-57,6 VDC 43,5-57,6 VDC 43,5-57,6 VDC 39,9-72 VDC 89,2-171,6 VDC
Power (maximum) 1800 W 3000 W 2000 W 3000 W 2000 W 2000 W
Power @ 85 VAC 750 W 1000 W 850 W 1380 W 750 W 850 W
Current (maximum) 75 A 62,5 A 41,7 A 62,5 A 41,6 A 16,7 A
Protection Fuse Fuse Fuse Fuse Fuse Diode
OTHER SPECIFICATIONS
Efficiency @ nominal input 95,4 % 97,8 % 96,5 % 96,2 % 96,1 % 94,4 %

Specifications are subject to change without notice

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com
Flatpack2 Integrated 19” 2U
Doc CTO30402.400.DS3 – rev3

FRONT VIEW FLATPACK 2 INTEGRATED 19” 2U


MODEL 110-220 VDC-8 KW
Part number CIO20402.4xxx
INPUT DATA
Voltage (nominal) 185-275 VAC or VDC
Voltage (operating range) 85-305 VAC or VDC
Maximum current AC (per input) 11,9 A
Frequency 0-66 Hz
Power factor > 0.99
OUTPUT DATA
Voltage (nominal) DC 110, 125, 220 V
REAR VIEW FLATPACK 2 INTEGRATED 19” 2U
Adjustable range DC See module type
Max output power DC 8 kW
Static Voltage regulation +/- 0,5%
CONTROLLER TYPE
Smartpack 2 Master
Basic unit Industrial basic
I/O unit (option) Fleximonitor/relay box

Specifications are subject to change without notice

AVAILABLE RECTIFIERS & DC/DC CONVERTERS FP2 HE


Models 110/2000 HE 220/2000 HE
Part number 241115.805 241115.815
INPUT DATA
Voltage AC (nominal) 185-275 VAC 185-275 VAC
Voltage DC (nominal) 185-275 VDC 185-275 VDC
Voltage AC (range) 85-300 VAC 85-300 VAC
Voltage DC (range) 85-300 VDC 85-300 VDC
Frequency 0-66 Hz 0-66 Hz
Current (maximum) @ nominal input, full load 11,9 ARMS 11,9 ARMS
Protection Fuse Fuse
OUTPUT DATA
Nominal output voltage 110-125 VDC 220 VDC
Voltage (default) 122,5 VDC 245,3 VDC
Voltage (adjustable range) 89,2-171,6 VDC 178,5-297 VDC
Power (maximum) 2000 W 2000 W
Power @ 85 VAC 850 W 850 W
Current (maximum) @ nominal input, full load 16,7 A 9,16 A
Protection Diode Diode
OTHER SPECIFICATIONS
Efficiency @ nominal input 94,4 % 95 %

Specifications are subject to change without notice

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com
Flatpack2 Integrated 19” 2U
Doc CTO30402.400.DS3 – rev3

Models / ordering information 24-125 VDC-12 kW 110-220 VDC-8 kW


Product family CIO30402.4xxx CIO20402.4 xxx
INPUT DATA
Voltage (range), see respective module 85-300 VAC/DC
Individual AC input 4* (L,N,PE)
Current (maximum) @ nominal input, full load 19,2 A (3 kW module) 11,9 A
Recommended input breaker (2 kW module) 16 A for each individual input, 25 A connected as TN net 400VAC + N, 3phase
Protection Individual fuse in rectifiers modules
Connection Individual screw terminal 6 mm 2 for L, N, PE
OUTPUT DATA
Nominal output voltage 24-125 VDC 110-220 VDC
Power (maximum @ nominal input) 12kW 8 kW
Current (maximum) See previous page or applicable Flatpack2 HE rectifier datasheet
Pb, number of cells supported 12-60 50-120
NiCd, number of cells supported 18-104 82-180
Unprotected bulk output connection M5 bolt
Output protection in rectifiers Fuse Blocking OR-ring diode
CONTROL AND MONITORING
Monitoring master unit Smartpack2
Monitoring basic unit Standard basic Industrial basic
Local operations Display and keys, WEB interface via standard browser
Remote operations Web interface, SNMP protocol, Modbus
Alarm relays 6*potential free NO-C-NO 3*potential free NO-C-NO
Inputs 6*NO/NC See option fleximonitor
Current measurements Rectifier current and if battery shunt is used; battery current and load current
Low & high output voltage alarms (Minor and major levels), Earth fault alarm,
Alarms Temperature alarm, Mains outage alarm, Battery remaining capacity/low quality
alarms, Battery/load breaker tripped alarm and much more
OPTIONS (see Fleximonitor datasheet)
Fleximonitor - option
Relay extension board 4 outputs - option
Relay extension board 8 outputs - option
OTHER SPECIFICATION
3.0 kVAC - input to output
Isolation 1.5 kVAC - input to earth
0.5 kVDC - output to earth
Protection Class IP 20
Operating temperature -40 to +55°C (-40 to +131°F), humidity 5 - 95% RH non-condensing
Storage temperature -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxDxH] 482 x 432 x 89mm (2U) (19 x 17 x 3,5”) 482 x 470 x 89mm (2U) (19 x 18,5 x 3,5”)
Weight 10 kg (1 module) 16 kg (4 module)
DESIGN STANDARDS
Electrical safety UL 60950-1, EN 60950-1 EN 60950-1
EMC ETSI EN 300 386 V.1.6.1, FCC CFR 47 Part 15
EN 61000-6-1 /-2/-3/-4/-5 (depending on module)
ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)
Environment
RoHS (2011/65/EU) and WEEE (2002/96/EC) compliant

Specifications are subject to change without notice

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2017 – www.eltek.com