Primary Windings: Understanding Vector Group of Transformer (Part 1)
Primary Windings: Understanding Vector Group of Transformer (Part 1)
Three phase transformer consists of three sets of primary windings, one for each phase,
and three sets of secondary windings wound on the same iron core. Separate single-
phase transformers can be used and externally interconnected to yield the same results
as a 3-phase unit.
It’s important to remember that the secondary voltage waveforms are in phase with the
primary waveforms when the primary and secondary windings are connected the same
way. This condition is called “no phase shift.”
But when the primary and secondary windings are connected differently, the secondary
voltage waveforms will differ from the corresponding primary voltage waveforms by 30
electrical degrees. This is called a 30 degree phase shift. When two transformers are
connected in parallel, their phase shifts must be identical; if not, a short circuit will occur
when the transformers are energized.”
Basic Idea of Winding
An ac voltage applied to a coil will induce a voltage in a second coil where the two are
linked by a magnetic path. The phase relationship of the two voltages depends upon
which ways round the coils are connected. The voltages will either be in-phase or
displaced by 180 degree.
When 3 coils are used in a 3 phase transformer winding a number of options exist. The
coil voltages can be in phase or displaced as above with the coils connected in star or
delta and, in the case of a star winding, have the star point (neutral) brought out to an
external terminal or not.
Polarity
An AC voltage applied to a coil will induce a voltage in a second coil where the two are
linked by a magnetic path. The phase relationship of the two voltages depends upon
which way round the coils are connected. The voltages will either be in-phase or
displaced by 180 deg.
When 3 coils are used in a 3 phase transformer winding a number of options exist. The
coil voltages can be in phase or displaced as above with the coils connected in star or
delta and, in the case of a star winding, have the star point (neutral) brought out to an
external terminal or not.
Additive and substractive polarity of
transformer
When Pair of Coil of Transformer have same direction than voltage induced in both coil
are in same direction from one end to other end. When two coil have opposite winding
direction than Voltage induced in both coil are in opposite direction.
IS: 2026 (Part 1V)-1977 gives 26 sets of connections star-star, star-delta, and star
zigzag, delta-delta, delta star, delta-zigzag, zigzag star, zigzag-delta. Displacement of the
low voltage winding vector varies from zero to -330° in steps of -30°, depending on the
method of connections.
Hardly any power system adopts such a large variety of connections. Some of the
commonly used connections with phase displacement of 0, -300, -180″ and -330° (clock-
hour setting 0, 1, 6 and 11).
Symbol for the high voltage winding comes first, followed by the symbols of windings in
diminishing sequence of voltage. For example a 220/66/11 kV Transformer connected
star, star and delta and vectors of 66 and 11 kV windings having phase displacement of
0° and -330° with the reference (220 kV) vector will be represented As Yy0 – Yd11.
The digits (0, 1, 11 etc) relate to the phase displacement between the HV and LV
windings using a clock face notation. The phasor representing the HV winding is taken as
reference and set at 12 o’clock. Phase rotation is always anti-clockwise. (International
adopted).
Use the hour indicator as the indicating phase displacement angle. Because there are 12
hours on a clock, and a circle consists out of 360°, each hour represents 30°.Thus 1 =
30°, 2 = 60°, 3 = 90°, 6 = 180° and 12 = 0° or 360°.
The minute hand is set on 12 o’clock and replaces the line to neutral voltage (sometimes
imaginary) of the HV winding. This position is always the reference point.
Example
Digit 0 =0° that the LV phasor is in phase with the HV phasor
Digit 1 =30° lagging (LV lags HV with 30°) because rotation is anti-clockwise.
Digit 11 = 330° lagging or 30° leading (LV leads HV with 30°)
Digit 5 = 150° lagging (LV lags HV with 150°)
Digit 6 = 180° lagging (LV lags HV with 180°)
When transformers are operated in parallel it is important that any phase shift is the
same through each. Paralleling typically occurs when transformers are located at one site
and connected to a common bus bar (banked) or located at different sites with the
secondary terminals connected via distribution or transmission circuits consisting of
cables and overhead lines.
The phase-bushings on a three phase transformer are marked either ABC, UVW or 123
(HV-side capital, LV-side small letters). Two winding, three phase transformers can be
divided into four main categories
Group O’clock TC
Group I 0 o’clock, 0° delta/delta,
star/star
Group II 6 o’clock, delta/delta,
180° star/star
Group III 1 o’clock, -30° star/delta,
delta/star
Group IV 11 o’clock, star/delta,
+30° delta/star
Minus indicates LV lagging HV, plus
indicates LV leading HV
Clock Notation 0 (Phase Shift 0)
Clock
Notation 0 (Phase Shift 0)
Clock Notation 1 (Phase Shift -30)
Clock
Notation 1 (Phase Shift -30)
Clock Notation 2 (Phase Shift -60)
Clock Notation 2 (Phase Shift -60)
Clock Notation 4 (Phase Displacement -120)
Clock
Notation 6 (Phase Shift +180)
Clock Notation 7 (Phase Shift +150)
Clock
Notation 7 (Phase Shift +150)
Clock Notation 11 (Phase Shift +30)
Clock
Notation 11 (Phase Shift +30)
To be continued…