TEST REPORT ON 1x185 RM NYY 60011000 V CABLE

MANT]FACTURED BY SQ WIRE & CABLE CO., LTD.,


DHAI{A

BRTC REF. NO.: 1101- Date: 2411112018


CLIENT,S REF: NIL Date: 2011112018
e-

E&qeffiGfrrHfu{ Department of Electrical & Electronic Engineering


<tqqtcqrt e6fi.H ffi, El-iFt- ) o o o Bangladesh Univprsity of Engineering and Technology
Tlfq/ffi r beebocs (q-drTR)
Dhaka-l 000, Bangladesh
fltefree 8 bsscgco-bo/v> Go, g)8q Fax/Phone : 9668054 (Direct), PABX : 9665650-80 16150, 6142
TTfq 8 * bbo-a.-bg)eoqg Fax : + 880-2-8 613026, + 880-2-9668054
*Wo-q-bggboC8 E-mail : headee [email protected]

TEST REPORT ON lx 185. RM NYY 600/1000 V CABLE IYIANUFACTURED BY SQ WIRE


&
CABLE CO., LTD., DHAKA

Date: 2411112018
BRTC REF. NO.: I 1 0 l-73917 1EEE 12018-19
Date: 2011112018
CLIENT,S REF.: NIL,

Date:26 December,2018

The tests are conducted and the report is prepared by the Department of Electrical and Electronic
Engineering of Bangladesh University of Engineerin! and Technology (BUET), Dhaka-I205,
Bangladesh.

Head of the Department


Department of Electrical & Electronic Engineering
Bangladesh University of Engineering and Technology
Dhaka -1205, Bangladesh

U4
EGqsffiffi{nfu"f Department of Electrical & Electronic Engineering
q1qqfcq{ e[6-fi"H ffi , El-iFt- ) o o o Bangladesh Univgrsity of Engineering and Technology
TI'fq/mt{ s beebocs (q-{fuTR) Dhak L-1000, B angladesh
PteReg r bsscvco-bo/slco, g)8q Fa>/Phone : 9668054 (Direct), PABX :9665650-80/6150, 6142
TIrg 3 * bbo-q-ug)rrolg Fax : * 880-2-8 613026, + 880-2-9668054
* bbo-a.-b9gboCS E-mail : headee [email protected]

TEST REPORT ON 1xl85.RMNYY 600/1000 v CABLE IVANUFACTURED BY SQ WIRE &


CABLE CO., LTD., DHAKA

Date: 2411112018
BRTC REF. NO.: 11 0l-7 3917 lEEEl2018- 19
Date: 2011112018
CLIENT,S RE,F: NIL

1. Introduction
The Plant Manager, SQ Wire & Cable Co., Ltd., Corporate Office, Plot # 31,
I-ake Drive Road'
Engineering and
Nikunja t, pt uku-tZZql nur requested Director, BRTC, Bangladesh University of
NYY V cable
Technology (BUET), to carry ou! typg tests on one sampB of 1x185 rm 600/1000
were
manufachli.d Uy Sq Wir" a Cable Co., Ltd. In respgme to the request, the following
tests
of EEE,
carried out on the supplied cable sample of six -et".s in the laboratory of Department
BIIET according to the relevant standards:
1. Dimension and weight test
2. DC resistance test
3. Insulation resistance test
4. High voltage withstand test
5. Current carrYing capacitY test
2. Samples
A sample of cable was supplied by the is unknown. The
specification of this sample is presented

'i, .'

3. Test Results
3.1 Dimension il dimension and weight of the cable were
measured and
3.2 DC resistance test: of the single strand from the sample are measured at
,L)C),,resistances
room temperature unU th.n converted to resistance at20" C'
3.3 Insulation resistance test: The sample was immersed in saline water at room temperature'
The insulation resistance of the sample was measured after 24 hours at room temperature.
3.4 High voltage withstand test: The sample was immersed in saline water for 24 hours and
tt * t ign ,oltuge withstand test appropriate for the sample was carried out between the
conductor and the ground. The voliage was raised slowly and kept for 5 minutes at the
desired rms level 3.5 kV. No breakdown of insulation in the cable occurred.
3.5 Current carrying capacity test: The rated current for the cable was passed through the
conductor and malntained until the temperature of the conductor became stable. Increase in
the ternperature of the conductor and of the insulator was measured at regular intervals.
The
measurement was carried out at room temperature. The temperature rise in the conductor
and in the insulation was within acceptable limit'

214
-o&qsffiffirHfu"t Department of Electrical & Electronic Engineering
<tqqtcq'f efufr"H ffi, EIS1- ) o o o Bangladesh Un[versity of Engineering and Technology
Tlrg/m]{ 8 beebocs ({flrTR) Dhak L-1000, Bangladesh
fteReg t bsscsco-bo/vlco, s)8q Fax/Phone : 9668054 (Direct), PABX :9665650-80/6150, 6142
Tlfq t *tst.o-q-Ug)so\tg Fax : + 880-2-8 613026, + 880-2-9668054
* bbo-q-bg9boG8 E-mail :[email protected]

TEST REPORT ON 1xl85 RM Nyy 600/1000 v CABLETMANUFACTURED BY SQ WIRE &


CABLE CO., LTD., DHAKA

Date: 2411112018
BRTC REF. NO.: 1101-73917 IEEE 12018-19
Date: 2011112018
CLIE,NT,S REF.: NIL

Table 1: Nameplate Data of 1x185 rm NYY 600/1000 V cable


Manufacturer SQ CABLES BANGLADESH
Voltage Grade
Type
Length
Description ISO 9001 Certified

Table 2: Test 000 V Copper cable

Nominal Test Result


Value
No. I
30 37
Number of wires in each core No.
(minimum)
Overall diameter of the cable 24.4 2s.s7
tT[Tl
(avg.) (approx.)
Thickness of sheath (PVC) mm 2.0 2.32 (average)
7.78 (rninimum)
Thickness of insulation (PVC) mm 2.0
1 .92 (average)

Overall diameter of conductor mm 16.26


2026 2082
Weight of the cable kg/km
(approx.)
DC resistance of the conductor at 0.0991 0.0970
O/km (max)
20" c
Insulation resi stance between >1000
MO
core and the body
Satisfactory
High Voltage Withstand test
Current Carrying Capacity Test Satisfactory

314
EGqsffi6ftEfu1"f Department of Electrical & Electronic Engineering
<tqql-cE-f eft'fi"H ffi , El-<Ft- )ooo Bangladesh Univprsity of Engineering and Technology
+ll-q/mFr e beeboc8 (q-drTR) Dhak a-1000, Bangladesh
farefteg B bsvcsco-bo/s>co, s)8q Fa>/Phone : 9668054 (Direct), PABX : 9665650-80 16150, 6142
Tlfg 8 * bbo-q-bg)rro{9 Fax : + 880-2-8 613026, + 880-2-9668054
* Ebo-q-bggboG8 E-mail : headee [email protected]

BY SQ WIRE &
TEST REPORT ON 1Xl85 RM NYY 600/1000 V CABLE MANUFACTURED
CABLE CO., LTD., DHAKA

Date:2411112018
BRTC REF. NO.: 11 0l-73917 lEEEl20l8-19
Date: 2011112018
CLIENT,S REF: NIL

4. Comments

l) physical dimensions of the supplied sample are wilhin acceptable limits. Though the
range and
minimum insulation thickness is less than nominal value, it is within acceptable
conforms to the related standard.
2) DC resistan ce at20" c of the supplied sample is within acceptable
limit'
3) The insulation resistance of the supplied cable is satisfactory.
4) The cable Sample withstood the high voltage test.
s) The temperatuie rise due to flow of the rated current in the su cable was within
acceptable limit. r'i