Optimization of Pipe Diameter & Insulation Thickness
Optimization of Pipe Diameter & Insulation Thickness
net/publication/303544076
CITATIONS READS
0 2,318
3 authors:
N. S. Senanayake
The Open University of Sri Lanka
38 PUBLICATIONS 49 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by N. S. Senanayake on 28 May 2016.
19
SLEMA Journal, Volume 18, No. 1, March 2015
higher pressure drop, and steam starvation. The pressure drops owing to pipe friction
On the other hand, oversized pipes lead to along the pipe length at minimum and
higher installation cost and higher heat loss maximum recommended velocities were
due to the heat transfer through larger surface calculated next, using Darcy Weisbach
area. Further, the higher heat loss causes Equation (2) [3].
increased condensate that increases the size of
4
fittings needed such as steam traps and …………………………... 2
condensate recovery pipe lines. 2
With regard to insulation, proper thickness of The equation (2) can be rearranged in the form
insulation needs to be established in a given of pressure drop as follows.
situation that would save money. The higher
the insulation is, the lower is the heat loss,
hence saving energy. However, in economic 2
∆ ………………………..……. 3
terms, insulation costs money and need to be
optimized so that investment on insulation is
recovered through energy savings. Where,
Therefore, there should be an optimization
when deciding on both pipe diameter as well
as insulation thickness. In this paper, savings
of energy as a result of using proper thickness
of insulation and the pipe sizes are
investigated.
The pressure range from 2 bar to 30 bar and
An unknown parameter in the Darcy equation,
pipe bore diameter from 50 mm to 150 mm,
the friction factor (f) was obtained from the
which are the most frequently used in the
Moody Chart [4] or for accurate figure (when
industry, are considered in this paper for
the flow is turbulent) f was calculated using
analysis.
the equation (4).
Selection of Pipe Size for a Given Steam
Flow Rate 1 2 9.3
3.48 1.74 ……….. 4
Methodology
Where
As mentioned above, pipes for steam
distribution networks are sized based on two
methods, called velocity method and the
pressure drop method. For wet steam, the
recommended velocity range is between 15 The Reynolds number that is to be substituted
and 30 m/s. into equation (3) was calculated using
equation (5).
Then the minimum and maximum mass flow
rates the pipe can deliver are calculated using ……………………………..…… 5
the equation (1).
Where
……………………… 1
4
Where,
Calculations were performed for different pipe
sizes (50 mm to 150 mm) at different
pressures, from 2bar to 30bar, while the flow
For different pipe sizes (50 mm to 150 mm) at velocity is at lowest and highest recommended
different pressures in the range of 2 bar to 30 values.
bar, the steam mass flow rate through the
pipes were calculated (Table 1).
Page 20
SLEMA Journal, Volume 18, No. 1, March 2015
21
SLEMA Journal, Volume 18, No. 1, March 2015
The Tables 1 and 2 are useful for the industry
in selecting pipes in the distribution system. If
the required flow rate, for example is
4000kgh -1 at 10bar, then the required pipe size
can be selected from Table 1. In this case, pipes
with diameters 100 mm and 125 mm can be
used as the required flow rate could be
achieved within the recommended velocity
range. From the pressure drop in bar per 100m U is expressed as given in equation (7).
can be extracted from Table 2. At 10 bar, the
pressure drop along 100 mm pipe is between 1 1
0.1364 and 0.4938 bar. For 125 mm pipe, it is …… 7
2 2
between 0.1032 and 0.3741bar. A general
industry norm is that the pressure drop along Where
the steam pipeline should not exceed 20% of
boiler pressure. Based on this, the optimum
pipe can be selected. In Table 2, the pressure
drop values are given per 100m pipe length Suffixes, i, o, in and p refer to inner, outer,
and when calculating the total pressure drop insulation, and pipe respectively.
the total length of the pipe should be The reduction in heat loss with different
considered and also equivalent length should insulation thickness values, compared to non-
be added to compensate for the fittings (This is insulated pipe, were computed, hence the
normally obtained by multiplying the length savings in terms of energy, mass of steam,
by a factor varying from 1.1 to 1.15). fuel for the boiler, and money for a period of
Selection of Insulation Thickness 10 years.
23
SLEMA Journal, Volume 18, No. 1, March 2015
The convective heat transfer coefficient from system operating about 5 hours a day and 250
outer insulation surface to the surrounding air days a year, for a period of 10 years.
was assumed as 10Wm-2K-1.
The insulation material selected was Rockwool 55.78 12500 3600
and its thermal conductivity was taken as 2510
0.045Wm-1K-1[8] and the thermal conductivity
of carbon steel (pipe) was taken as 21 Wm-1K-1
[9]. 10.56 12500 3600
475
From the standard pipe chart [6], the inner and
the outer diameters of 100 mm pipe were Energy saving due to insulation = 2510 – 475
taken as 102.26 and 114.3 mm respectively. =2035GJ
The heat loss through the pipe wall causes
102.26
some amount of steam in the pipe to condense.
114.3
Hence, the energy saving in terms of the
3000
10 amount of steam can be computed by dividing
21 the heat loss, by the enthalpy of vaporization
0.045 of water at 10bar pressure (1999. 67 kJkg-1).
Therefore,
Assuming an initial value for insulation
thickness of 25mm, Steam saved = 2035 GJ/1999.67 kJ kg-1
=1017.67 tons
2 114.3 2 25 164.3
Equivalent savings in fuels can be computed
From equation (7), assuming the fuel consumption to produce
one ton of steam is equal to 75 liters.
1.310
Fuel saving = 1017.67x 75
Heat Loss in an Insulated Pipe = 76,325 liters
The heat loss through insulated pipe was then Price of one 1liter furnace oil = 82 LKR
estimated from the equation (6) with the
following data. Fuel cost saving = 76,325 x 82 = 6,258,650 LKR
Page 24
SLEMA Journal, Volume 18, No. 1, March 2015
25
SLEMA Journal, Volume 18, No. 1, March 2015
Figure 2 – Variation of Net Savings with Insulation Thickness
6,700,000
6,600,000
Net Saving (LKR) 6,500,000
6,400,000
6,300,000
6,200,000
6,100,000
6,000,000
0 20 40 60 80 100 120 140
Insulation Thickness (mm)
Table 5 - Optimum Insulation Thickness for Different Pipe Diameters at Different Pressures
Pipe size Optimum Insulation Thickness at Different Pressure (mm)
(mm) 5 bar 10 bar 12 bar 15 bar 20 bar 25 bar 30 bar
50 60 60 70 70 70 70 70
65 60 70 70 70 70 80 80
80 60 70 80 80 80 90 90
100 70 80 80 90 90 90 100
125 80 90 90 90 100 110 110
150 80 90 90 100 110 110 110
Discussion and Conclusion performance and save energy. Tables 3 and 4
give the expected cost savings when different
Sizing of pipe diameters and selection of
values of insulation thickness are used with
optimum level of insulation are very important
100mm pipe diameter and 10bar line
aspects in the design of steam distribution pipe
pressure. It was proven that optimum
networks in order to save energy. Improper
insulation thickness should be 80mm, which
piping and insulation lead to heavy losses in
gives a net saving of 6,589,154 LKR for a 10
terms of steam generated, and finally additional
year period. Table 5 presents optimum
fuel and associated high costs as demonstrated
insulation thickness when different pipe sizes
in this paper.
and pressure are used.
The analysis related to the selection of optimum
pipe diameters and insulation thickness for a
given application with known steam mass flow Reference
rate and line pressure requirements is presented
[1] S. Anand , N.K. Bansal, S.R. Park and
in this paper, and these provide guidelines in
S.K. Tyagi ( 2011). Comparative study of
sizing steam distribution systems. Table 1 gives
different insulating materials for
information on possible pipe sizes to match the
reducing the heat losses in steam pipes: a
pressure and mass flow requirements in a given
technical study. International Journal of
application. Further, expected pressure drops
Sustainable Energy, Vol. 31, Issue 2, 2012,
per 100m length for different pipe sizes and line
133 – 141.
pressure are given in Table 5.
The pipes selected need to be insulated properly [2] Pipe Sizing Steam Supply and
with optimum thickness to obtain the maximum Condensate Return Lines, Available at
https://www.armstronginternational.co
Page 26
SLEMA Journal, Volume 18, No. 1, March 2015
m/files/products/traps/pdf/N1_4550.p
df ( Accessed on 14 November 2014)
[6] http://www.engineeringtoolbox.com/st
eam-viscosity-d_770.html( Accessed on
20 November 2014)
27