N1040i Indicator Communication Protocol - V10x: RS485 Interface
N1040i Indicator Communication Protocol - V10x: RS485 Interface
The MOSBUS RTU slave is implemented, available in most SCADA Status Word Read: Status bits. See table 2.
0009
softwares in the market. 2 Write: not allowed.
All configurable parameters can be accessed (for reading or writing) Status Word Read: Status bits. See table 2.
through the Registers Table. Broadcast commands are supported as 0010
3 Write: not allowed.
well (address 0).
0011~0015 Reserved Internal use.
The available Modbus commands are:
03 - Read Holding Register Mains frequency.
0016 Freq 0→ 60 Hz;
05 - Force Single Coil (Force Digital Output state)
1→ 50 Hz;
06 - Preset Single Register
16 - Preset Multiple Registers (Block write to multiple holding 0017 Reserved
registers) PV digital filter gain.
0018 FLtr
The registers are arranged in a table in such a way that several Range: 0 – 20
registers can be read in the same request.
0019 Reserved Internal use.
1.2 CONFIGURATION OF SERIAL COMMUNICATION Controls the presence of the parameter SPA1 in
PARAMETERS the indicator operation cycle.
0020 SP1.E
Two parameters must be configured in the device for serial 0→ Disables (hides SPA1);
communication: 1→ Enables (shows SPA1);
bavd: Baud rate. All devices with same baud rate. Controls the presence of the parameter SPA2 in
the indicator operation cycle.
addr: Device communication address. Each device must have an 0021 SP2.E
exclusive address. 0→ Disables (hides SPA2);
prty: Paraty. 1→ Enables (shows SPA2);
0022 Reserved Internal use.
1.3 REGISTERS TABLE
Serial number first four digits.
Equivalent to the registers referenced as 4XXXX. Serial
0023 Write: no allowed.
number H
The holding registers are basically a list of the internal indicator Read: 0 to 9999.
parameters. All registers above address 12 can be read or written. The
registers up to this address in more are read only. Please verify each Serial number last four digits.
Serial
case. Each table parameter is a 16 bits two complement signed word. 0024 Write: no allowed.
number L
Read: 0 to 9999.
Holding 0025 Reserved Internal use.
Parameter Register Description
Registers
Defines the minimum PV indication value for
Diferential alarm reference.. 0026 iNLL analog input types (used to scale the analog
0000 ALrf
Range: SPLL to SPkL (or the sensor span), inputs).
Defines the indication higher limit of the PV
0027 iNkL indication (used to scale the analog inputs).
0028 Reserved Internal use.
PV offset. 0079 rtll Retransmission low limit of PV.
0029 OFFS
Range: from iNLL to iNkL. 0088 rtkl Retransmission high limit of PV.
PV decimal point position Allows visual signalization of an alarm
0030 DP.PO Range: 0 to 3 occurrence by flashing the indication of PV in
0→X.XXX; 1→XX.XX; 2→XXX.X; 3→XXXX the operation level.
0081 FLSH
0031 SP.A1 Alarm 1 Setpoint. 0→ Disables
0032 SP.A2 Alarm 2 Setpoint. 1→ Enables