15-25 Ton Foundation PKGD Cooling Rooftop (BPGDE) Consolidated Customer Package Submittal

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

3-5T, 15-25Ton Pkgd Elec/Elec Rooftop - Foundation - (BPGDE)

Job Information
Name Escuela de Costa Rica Tag *** UNIT1-2, ***
v2 - 072220LC UNIT1-3, *** UNIT1-
4, *** UNIT1-5, ***
UNIT1-6, BPGDE-1
Address Quantity 6
Sales Team Model Number EBC300A3E0A--
A700000000000000
00000000000
Comments

General
Unit function Cooling Tonnage 25 Ton
Unit controls Electro-mechanical Design Airflow 10000 cfm
Fresh air selection Manual damper Elevation 0.00 ft
Airflow configuration Convertible Airflow Application Downflow
Cooling Entering Dry 80.00 F Cooling Entering Wet 67.00 F
Bulb Bulb
Ambient Temp 95.00 F Supply Two speed fan
fan/drive/type/motor standard motor
Voltage 208-230/60/3 Design ESP 0.800 in H2O
Evaporator Rows 4 Evaporator Face Area 26.00 sq ft
Evaporator Fin Spacing 180 Per Foot Evaporator Face 385 ft/min
Velocity
Min. Unit Operating 0.0 lb Max Unit Operating 0.0 lb
Weight Weight
Rated capacity (AHRI) 271.00 MBh ASHRAE 90.1 Yes

Main Cooling
Evap Coil Leav Air 60.39 F Evap Coil Leav Air 57.77 F
Temp (DB) Temp (WB)
Cooling Leaving Unit DB 62.21 F Cooling Leaving Unit 58.49 F
WB
Gross Total Capacity 288.08 MBh Gross Sensible Capacity 213.33 MBh
Gross Latent Capacity 74.75 MBh Net Total Capacity 271.49 MBh
Net Sensible Capacity 196.74 MBh Refrig charge (HFC- 13.2 lb
410A) - ckt 1
Refrig charge (HFC- 7.2 lb
410A) - ckt 2

Motor/Electrical
Field Supplied Drive Kit None Electric Heat Static 0.000 in H2O
Required Press Add
Component SP Add 0.485 in H2O Total Static Pressure 1.285 in H2O
Indoor Mtr. Operating 6.19 bhp Indoor RPM 1024 rpm
Power
Indoor Motor Power 4.61 kW EER @ AHRI Conditions 10.0 EER
MCA 133.00 A MOP 175.00 A
MCA (230 w/ Elec Heat) 0.00 A MOP (230 w/Elec Heat) 0.00 A
Compressor 1 RLA 50.50 A Compressor 2 RLA 35.70 A
Condenser Fan FLA 9.20 A Evaporator Fan FLA 24.20 A
IEER Rating 11.70

Baseunit
Height 59.313 in Width 86.938 in
Length 123.125 in

Fan
T24_SZVZV NA Indoor Fan Type FC Centrifugal
Indoor Fan Drive Type Belt Outdoor Fan Type Propeller

Page 1
Outdoor Fan Drive Type Direct Outdoor Fan Quantity 2.00 Number
Exhaust Fan Type FC Centrifugal Exhaust Drive Type Direct

Heat
Heating Type Electric Heating Stages 0

Field installed accessories


Thermostat 3H/2C 7-Day
Programmable
Touchscreen

Page 2
NOTES:
1. THRU -THE -BASE ELECTRICAL IS NOT STANDARD ON
ALL UNITS.
2. VERIFY WEIGHT, CONNECTIONS, AND ALL DIMENSIONS
WITH INSTALLER DOCUMENTS BEFORE INSTALLATION

CONDENSATE DRAIN REFRIGERANT GAUGE ACCESS


CONNECTION (25 mm) NPT
CUSTOMER POWER
DISCONNECT CONDUIT CONNECTION (ALTERNATE)
SWITCH ACCESS

PACKAGED COOLING DOWNFLOW


DIMENSION DRAWING

3127 mm

365 mm 365 mm SUPPLY

175 mm 455 mm

RETURN

1647 mm 1834 mm
1868 mm 1742 mm 2208 mm

173 mm

374 mm

177 mm 917 mm 490 mm 1076 mm

3127 mm
PLAN VIEW OF UNIT
DIMENSION DRAWING

1489 mm
1507 mm
1011 mm
570 mm

114 mm
1292 mm
202 mm

331 mm
3127 mm

FRONT VIEW OF UNIT RIGHT VIEW OF UNIT


DIMENSION DRAWING DIMENSION DRAWING

Page 3
CLEARANCE 1727 mm

CLEARANCE 914 mm

CLEARANCE FROM THE


TOP OF UNIT 1829 mm

CLEARANCE 1524 mm

CLEARANCE 1219 mm

DOWNFLOW-PACKAGED COOLING WITH ELECTRIC CLEARANCE

UNIT OUTLINE

ROOF OPENING

1943 mm
2057 mm

DOWNFLOW-PACKAGED COOLING WITH ELECTRIC ROOF OPENING CLEARANCE

Page 4
INSTALLED ACCESSORIES NET WEIGHT DATA
ACCESSORY WEIGHTS

ECONOMIZER

MOTORIZED OUTSIDE AIR DAMPER

C MANUAL OUTSIDE AIR DAMPER 6.8 kg


D
HEATER

OVERSIZED MOTOR

MULTI-SPEED WITH DRIVE 29.5 kg

THROUGH THE BASE ELECTRICAL

BAROMETRIC

ROOF CURB

POWER EXHAUST

HAIL GUARD

STATIC DRIVE

DISCONNECT

B A

CORNER WEIGHT
BASE UNIT WEIGHTS CORNER WEIGHTS CENTER OF GRAVITY

SHIPPING NET A 301.2 kg C 156.5 kg (E) LENGTH (F) WIDTH

1001.5 kg 856.4 kg B 207.3 kg D 191.4 kg 1346 mm 889 mm

NOTE:
1. CORNER WEIGHTS ARE GIVEN FOR INFORMATION ONLY.
2. TO ESTIMATE SHIPPING WEIGHT OF OPTION/ACCESSORIES ADD 5 LBS TO NET WEIGHT.
3. NET WEIGHT OF OPTIONAL ACCESSORIES SHOULD BE ADD TO UNIT WEIGHT WHEN
ORDERING FACTORY INSTALLED ACCESSORIES.
4. WEIGHTS FOR OPTIONS NOT LISTED ARE < 5 LBS.
5. WEIGHT ARE OF BASE UNIT ONLY. FOR TOTAL WEIGHT, 10 DIGIT FACTORY INSTALLED
OPTION (ECONOMIZER AND/OR OVERSIZED MOTOR OR FIOP/ACCESSORY WEIGHT
MUST BE ADDED.

E
F

RIGGING AND CENTER OF GRAVITY


Page 5
NOTES:
1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION
WITH INSTALLER DOCUMENTS BEFORE INSTALLATION

MANUAL DAMPER HOOD

PLAN VIEW OF UNIT


DIMENSION DRAWING

PACKAGED MANUAL DAMPER


DIMENSION DRAWING

FAN MANUAL DAMPER HOOD

683 mm

631 mm 325 mm

3127 mm 463 mm 2208 mm

BACK VIEW OF UNIT LEFT VIEW OF UNIT


DIMENSION DRAWING DIMENSION DRAWING

Page 6
153 mm

34 mm

117 mm

84 mm

84 mm

TCONT802 - (3H/2C)
ACCESSORY - THERMOSTAT

Page 7
15 thru 25 Ton General
The units shall be dedicated downflow or horizontal airflow. The operating range shall be between 115°F and 40°F in cooling as
standard from the factory for all units. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall
be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check cooling operation, fan and
blower rotation and control sequence, before leaving the factory. Wiring internal to the unit shall be colored and numbered for
simplified identification. Units shall be UL listed and labeled, classified in accordance to UL 1995/C 22.2, 236-05 3rd Edition.

15 thru 25 Ton Casing


Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and
finished with a weather-resistant baked enamel finish. Unit's surface shall be tested 672 hours in a salt spray test in compliance with
ASTM B117. Cabinet construction shall allow for all maintenance on one side of the unit. In order to ensure a water and air tight seal,
service panels shall have lifting handles and no more than three screws to remove. All exposed vertical panels and top covers in the
indoor air section shall be insulated with a 13 mm, 0.5 kgdensity foil-faced, fire-resistant, permanent, odorless, glass fiber material.
The base of the downflow unit shall be insulated with 13 mm, 0.5 kgdensity foil-faced, closed-cell material. The downflow unit base
pan shall have no penetrations within the perimeter of the curb other than the raised 29 mmhigh supply/return openings to provide an
added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane
lifting.

15 thru 25 Ton Compressors


All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled
and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Internal overloads shall be provided with
the scroll compressors.
All models shall have phase monitors and low and high pressure control as standard.

15 thru 25 Ton Controls


Unit shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit
shall provide an external location for mounting a fused disconnect device.

15 thru 25 Ton Discharge Line Thermostat


A bi-metal element discharge line thermostat is installed as a standard option on the discharge line of each system. This standard
option provides extra protection to the compressors against high discharge temperatures in case of loss of charge, extremely high
ambient and other conditions which could drive the discharge temperature higher. Discharge line thermostat is wired in series with
high pressure control. When the discharge temperature rises above the protection limit, the bi-metal disc in the thermostat switches
to the off position, opening the 24 Vac circuit. When the temperature on the discharge line cools down, the bi-metal disc closes the
contactor circuit, providing power to the compressor.

15 thru 25 Ton Evaporator and Condenser Coils


Microchannel coils will be burst tested by the manufacturer. Internally finned, 8 mmcopper tubes mechanically bonded to a configured
aluminum plate fin shall be standard for evaporator coils. Microchannel condenser coils shall be standard on all units. Coils shall be
leak tested to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 225 psig and pressure
tested to 450 psig. Sloped condensate drain pans are standard.

15 thru 25 Ton Filters


51 mm standard filters shall be factory supplied on all units.

15 thru 25 Ton High Pressure Control


All units include High Pressure Cutout as standard.

15 thru 25 Ton Indoor Fan


Units above shall have belt driven, FC centrifugal fans with adjustable motor sheaves. Units with standard motors shall have an
adjustable idler-arm assembly for quick-adjustment of fan belts and motor sheaves. All motors shall be thermally protected.
Oversized motors shall be available for high static application. All indoor fan motors meet the U.S. Energy Policy Act of 1992
(EPACT).

15 thru 25 Ton Low Pressure Control


All units include Low Pressure Cutout as standard.

15 thru 25 Ton Outdoor Fans


The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position. The fan
motor(s) shall be permanently lubricated and shall have builtin thermal overload protection.

15 thru 25 Ton Phase Monitor


Page 8
The Phase Monitor is a three-phase line monitor module that protects against phase loss, phase reversal and phase unbalance. It is
intended to protect compressors from reverse rotation. It has an operating input voltage range of 190-600 Vac, and LED indicators
for ON and FAULT. There are no field adjustments and the module will automatically reset from a fault condition.

15 thru 25 Ton Refrigerant Circuits


Each refrigerant circuit shall have independent fixed orifice, service pressure ports, and refrigerant line filter driers factory installed as
standard. An area shall be provided for replacement suction line driers.

15 thru 25 Ton Unit Top


The top cover shall be double hemmed and gasket sealed to prevent water leakage.

15 thru 25 Ton Multi-Speed Indoor Fan System


Multi-speed indoor fan system is designed for use in applications for meeting the minimum requirement of CA Title 24. This system
incorporates a multi-speed fan control to change the speed of the fan to 67% of full airflow based off of compressor stages.

15 thru 25 Ton Manual Outside Air Damper


The rain hood and screen shall provide up to 50% outside air.

Page 9