15-25 Ton Foundation PKGD Cooling Rooftop (BPGDE) Consolidated Customer Package Submittal
15-25 Ton Foundation PKGD Cooling Rooftop (BPGDE) Consolidated Customer Package Submittal
15-25 Ton Foundation PKGD Cooling Rooftop (BPGDE) Consolidated Customer Package Submittal
Job Information
Name Escuela de Costa Rica Tag *** UNIT1-2, ***
v2 - 072220LC UNIT1-3, *** UNIT1-
4, *** UNIT1-5, ***
UNIT1-6, BPGDE-1
Address Quantity 6
Sales Team Model Number EBC300A3E0A--
A700000000000000
00000000000
Comments
General
Unit function Cooling Tonnage 25 Ton
Unit controls Electro-mechanical Design Airflow 10000 cfm
Fresh air selection Manual damper Elevation 0.00 ft
Airflow configuration Convertible Airflow Application Downflow
Cooling Entering Dry 80.00 F Cooling Entering Wet 67.00 F
Bulb Bulb
Ambient Temp 95.00 F Supply Two speed fan
fan/drive/type/motor standard motor
Voltage 208-230/60/3 Design ESP 0.800 in H2O
Evaporator Rows 4 Evaporator Face Area 26.00 sq ft
Evaporator Fin Spacing 180 Per Foot Evaporator Face 385 ft/min
Velocity
Min. Unit Operating 0.0 lb Max Unit Operating 0.0 lb
Weight Weight
Rated capacity (AHRI) 271.00 MBh ASHRAE 90.1 Yes
Main Cooling
Evap Coil Leav Air 60.39 F Evap Coil Leav Air 57.77 F
Temp (DB) Temp (WB)
Cooling Leaving Unit DB 62.21 F Cooling Leaving Unit 58.49 F
WB
Gross Total Capacity 288.08 MBh Gross Sensible Capacity 213.33 MBh
Gross Latent Capacity 74.75 MBh Net Total Capacity 271.49 MBh
Net Sensible Capacity 196.74 MBh Refrig charge (HFC- 13.2 lb
410A) - ckt 1
Refrig charge (HFC- 7.2 lb
410A) - ckt 2
Motor/Electrical
Field Supplied Drive Kit None Electric Heat Static 0.000 in H2O
Required Press Add
Component SP Add 0.485 in H2O Total Static Pressure 1.285 in H2O
Indoor Mtr. Operating 6.19 bhp Indoor RPM 1024 rpm
Power
Indoor Motor Power 4.61 kW EER @ AHRI Conditions 10.0 EER
MCA 133.00 A MOP 175.00 A
MCA (230 w/ Elec Heat) 0.00 A MOP (230 w/Elec Heat) 0.00 A
Compressor 1 RLA 50.50 A Compressor 2 RLA 35.70 A
Condenser Fan FLA 9.20 A Evaporator Fan FLA 24.20 A
IEER Rating 11.70
Baseunit
Height 59.313 in Width 86.938 in
Length 123.125 in
Fan
T24_SZVZV NA Indoor Fan Type FC Centrifugal
Indoor Fan Drive Type Belt Outdoor Fan Type Propeller
Page 1
Outdoor Fan Drive Type Direct Outdoor Fan Quantity 2.00 Number
Exhaust Fan Type FC Centrifugal Exhaust Drive Type Direct
Heat
Heating Type Electric Heating Stages 0
Page 2
NOTES:
1. THRU -THE -BASE ELECTRICAL IS NOT STANDARD ON
ALL UNITS.
2. VERIFY WEIGHT, CONNECTIONS, AND ALL DIMENSIONS
WITH INSTALLER DOCUMENTS BEFORE INSTALLATION
3127 mm
175 mm 455 mm
RETURN
1647 mm 1834 mm
1868 mm 1742 mm 2208 mm
173 mm
374 mm
3127 mm
PLAN VIEW OF UNIT
DIMENSION DRAWING
1489 mm
1507 mm
1011 mm
570 mm
114 mm
1292 mm
202 mm
331 mm
3127 mm
Page 3
CLEARANCE 1727 mm
CLEARANCE 914 mm
CLEARANCE 1524 mm
CLEARANCE 1219 mm
UNIT OUTLINE
ROOF OPENING
1943 mm
2057 mm
Page 4
INSTALLED ACCESSORIES NET WEIGHT DATA
ACCESSORY WEIGHTS
ECONOMIZER
OVERSIZED MOTOR
BAROMETRIC
ROOF CURB
POWER EXHAUST
HAIL GUARD
STATIC DRIVE
DISCONNECT
B A
CORNER WEIGHT
BASE UNIT WEIGHTS CORNER WEIGHTS CENTER OF GRAVITY
NOTE:
1. CORNER WEIGHTS ARE GIVEN FOR INFORMATION ONLY.
2. TO ESTIMATE SHIPPING WEIGHT OF OPTION/ACCESSORIES ADD 5 LBS TO NET WEIGHT.
3. NET WEIGHT OF OPTIONAL ACCESSORIES SHOULD BE ADD TO UNIT WEIGHT WHEN
ORDERING FACTORY INSTALLED ACCESSORIES.
4. WEIGHTS FOR OPTIONS NOT LISTED ARE < 5 LBS.
5. WEIGHT ARE OF BASE UNIT ONLY. FOR TOTAL WEIGHT, 10 DIGIT FACTORY INSTALLED
OPTION (ECONOMIZER AND/OR OVERSIZED MOTOR OR FIOP/ACCESSORY WEIGHT
MUST BE ADDED.
E
F
683 mm
631 mm 325 mm
Page 6
153 mm
34 mm
117 mm
84 mm
84 mm
TCONT802 - (3H/2C)
ACCESSORY - THERMOSTAT
Page 7
15 thru 25 Ton General
The units shall be dedicated downflow or horizontal airflow. The operating range shall be between 115°F and 40°F in cooling as
standard from the factory for all units. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall
be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check cooling operation, fan and
blower rotation and control sequence, before leaving the factory. Wiring internal to the unit shall be colored and numbered for
simplified identification. Units shall be UL listed and labeled, classified in accordance to UL 1995/C 22.2, 236-05 3rd Edition.
Page 9