0% found this document useful (0 votes)
345 views2 pages

PSC Pole Calculation Sheet PDF

This document provides design calculations for a 9 meter pole with a pole height of 9000 mm and a 12 meter pole with a pole height of 12000 mm. It includes calculations for tensile stress, force applied, self weight, grade of concrete, maximum permitted compressive and tensile stresses, diameter and number of tension wires, pole top and bottom diameters, section properties, prestress force applied, bending stress, and checks that the resulting stresses do not exceed allowable limits. Design parameters and calculations are provided for two sections of each pole.

Uploaded by

gopi nowpada
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
345 views2 pages

PSC Pole Calculation Sheet PDF

This document provides design calculations for a 9 meter pole with a pole height of 9000 mm and a 12 meter pole with a pole height of 12000 mm. It includes calculations for tensile stress, force applied, self weight, grade of concrete, maximum permitted compressive and tensile stresses, diameter and number of tension wires, pole top and bottom diameters, section properties, prestress force applied, bending stress, and checks that the resulting stresses do not exceed allowable limits. Design parameters and calculations are provided for two sections of each pole.

Uploaded by

gopi nowpada
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Design Calculation Sheet

Pole 9 mtr 5 kN
Tensile Stress 1570 N/sqmm
Force applied 0.75 times tensile stress Keeping a margin of 25%, conservatively
Pole height 9000 mm
Load from top 300 mm
Self weight 916.5 kg
Grade of Concrete 50 N/mm2 (fc) 7251.9 Psi)

Max. perm compressive stress = 0.6 fc x 1.33 39.9 N/mm2 Table 24.5.4.1 & increase by one third for Transient loads, ACI 318
Max. perm. tensile stress = 12 x Sqrt(fc) in psi 7.046 N/mm2 1021.8971 Psi Table 24.5.2.1 for Cracked Section, ACI 318
Dia. Of Tension wire 7 mm
No. of wires 18 Nos
Total cross section of wires 692.7 sqmm
Pole top dia. 220 mm
Pole Bottom dia 340 mm

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
P/A (loss-
Total loss of Stress in 'T'
Planting Length from Force @ 300 Area of 'T' Area of 'UT' Effective Area Prestress force Area of 'T' steel Bending Self weight P/A (before elastic P/A (after P'/A due to SIGMA1 (19 + SIGMA2 (19 +
Section ID OD Thickness Z- provided Working Moment 'M' prestress in wire after
Depth Bottom mm from top provided provid ed provided applied 'P' required stress M/Z P' losses) shortening of all losses) self weight 20 +15) 20 -15)
% transfer
conc)
(mm) (mm) (Newton) (mm) (mm) (mm) (mm2) (mm2) (mm2) (mm3) (Newton) (mm2) (N.mm) (N/mm2) (Newton) (N/mm2) (N/mm2) (N/mm2) (N/mm2) (N/mm2) (N/mm2) (N/mm2)

1500 Base 0 5000 240 340 50

GL 1500 5000 220 320 50 692.7 0 42411.5 2498302 815654 36,000,000 14.41 8990.865 19.23 17.307 14.19 0.21 28.81 -0.01 25% 1177.5

Pole ht. 9 220 mm OD at top Comp Tension Allowable 39.9 -7.046

28.81 -0.01 PASS PASS

39.9 -7.046

PASS PASS

Page 1 of 1
Design Calculation Sheet

Pole 12 mtr 6 kN
Tensile Stress 1570 N/sqmm
Force applied 0.75 times tensile stress Keeping a margin of 25%, conservatively
Pole height 12000 mm
Load from top 300 mm
Self weight 1654.5 kg
Grade of Concrete 50 N/mm2 (fc) 7251.9 Psi)

Max. perm compressive stress = 0.6 fc x 1.33 39.9 N/mm2 Table 24.5.4.1 & increase by one third for Transient loads, ACI 318
Max. perm. tensile stress = 12 x Sqrt(fc) in psi 7.046 N/mm2 1021.8971 Psi Table 24.5.2.1 for Cracked Section, ACI 318
Dia. Of Tension wire 7 mm
No. of wires 20 Nos
Total cross section of wires 769.7 sqmm
Pole top dia. 220 mm
Pole Bottom dia 380 mm

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
P/A (loss-
Effective Area of 'T' Stress in 'T'
Planting Length from Force @ 300 Area of 'T' Area of 'UT' Prestress force Working Bending Self P/A (before elastic P/A (after P'/A due to SIGMA1 (19 + SIGMA2 (19 + Total loss of
Section ID OD Thickness Area Z- provided steel wire after
Depth Bottom mm from top provided provid ed applied 'P' Moment 'M' stress M/Z weight P' losses) shortening of all losses) self weight 20 +15) 20 -15) prestress in %
provided required transfer
conc)
(mm) (mm) (Newton) (mm) (mm) (mm) (mm2) (mm2) (mm2) (mm3) (Newton) (mm2) (N.mm) (N/mm2) (Newton) (N/mm2) (N/mm2) (N/mm2) (N/mm2) (N/mm2) (N/mm2) (N/mm2)

2000 Base 0 6000 260 380 60

GL 2000 6000 233 353 60 769.7 0 55229.2 3498723 906322 58,200,000 16.63 16230.65 16.41 14.769 12.11 0.29 29.03 -4.23 25% 1177.5

Pole ht. 12 220 mm OD at top Comp Tension Allowable 39.9 -7.046

29.03 -4.23 PASS PASS

39.9 -7.046

PASS PASS

Page 1 of 1

You might also like