Onyxworks® Gateways: NFN Fire Monitoring

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

dn-7060:b1

ONYXWorks® Gateways
NFN Fire Monitoring

Network Systems

General 7060cov1.jpg

The NOTI•FIRE•NET™ Gateway is an intelligent gateway


interface for the ONYXworks® fire monitoring workstation.
This gateway facilitates complete monitoring and control of a
NOTI•FIRE•NET™ network and is available in a PC version
and an embedded version. In addition, it supports full panel
programming and network diagnostics.
The PC version of the gateway is the network interface for a
true peer-to-peer network and resides in ONYX® Series
workstations. The embedded version is a standalone gateway
and is equipped with IP capability thus enabling ONYX®
Series users to monitor multiple sites over an Ethernet
network without the need for remote workstations.
NFN-GW-PC-W
Features
• Enables ONYX® Series workstation to monitor alarm, pre-
alarm, trouble, and disabled events for Notifier fire alarm
control panels on a NOTI•FIRE•NET™ network.
• Adds acknowledge, silence, reset, enable/disable, and
activate/deactivate control capability to the workstation.
• Supports fire alarm control panel programming upload/
downloads and modifications.
• Standalone embedded version for: ability to scale, remote
IP connections.
• Supervised IP connections for remote workstations and
gateways.
• Multiple workstations can access the gateway at the same
time.
• PC versions support wire or multimode fiber options.
NFN-GW-EM-3
• Gateway redundancy for network survivability.
• Operating temperature: 0°C to 49°C (32°F to 120°F).
Compatibility • Mounts on a CHS-4L chassis in a CAB-4 Series cabinet
The NOTI•FIRE•NET™ Gateway is compatible with (see data sheet DN-6857).
ONYXWorks® and ONYX FirstVision and interfaces to • Direct connection to NFS2-640, NFS-640, NFS-320,
NOTI•FIRE•NET™ version 5.0 and higher for the following NFS2-3030, and NFS-3030 fire alarm control panels.
panels and devices: NCM-W or NCM-F required for connection to
• ONYX Series NOTI•FIRE•NET™ (see data sheet DN-6861).
• AM2020/AFP1010 (version 5.0 SIB-NET)
Standards and Codes
• AFP-200 (version 5.0 NAM)
• AFP-300/AFP-400 (version 5.0 NAM) The NOTI•FIRE•NET™ Gateway complies with the following
UL/ULC Standards and NFPA 72 Fire Alarm Systems
• BACnet Gateway requirements:
• NCA-2/NCA Network Control Annunciator
– UL 864
• NOTI•FIRE•NET™Web Server
– UL 1076
– UL 2017
Specifications
– ULC S559-04
PC version:
– ULC S527-99
• Requires an ONYXworks® Workstation (see ONYXworks®
data sheet DN-7048). Listings and Approvals
• Operating temperature: 0°C to 49°C (32°F to 120°F).
Embedded version: These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications
• Input current: 450 mA @ 24 VDC. may not be listed by certain approval agencies, or listing may
• Input voltage range: 19 VDC to 29 VDC. be in process. Consult factory for latest listing status.
• UL / ULC: S5697
• CSFM: 7300-1525:103

dn-7060:b1 • 09/21/09 — Page 1 of 2


• MEA: 286-07-E • ONYXWorks® Workstation.
*If adding to an existing system, please provide Customer Ser-
Ordering Information vice with the 5 digit software key number of your workstation.
An upgrade authorization will be provided for you.
NFN-GW-EM-3: NOTI•FIRE•NET™ Gateway, embedded.
Includes PC board, Surge Suppressor (PNET-1). Additional EMBEDDED VERSION Gateway required
components:
NFN-GW-PC-W: NOTI•FIRE•NET™ Gateway PC card for wire
media (PCI card). Included in ONYXWORKS-NW (UL-listed • NCM-W or NCM-F for connection to NOTI•FIRE•NET™.
workstation) • IBM®-compatible PC with Windows® XP.
NFN-GW-PC-F: NOTI•FIRE•NET™ Gateway PC card for • For Gateway versions 3.0 and above, the Gateway is
multimode fiber media (PCI card). Included in configured over IP or through a cross-over ethernet cable.
ONYXWORKS-NF (UL-listed workstation) • Standard Ethernet network cable with RJ45 connectors.
Additional PC VERSION Gateway required components: • CHS-4L with a CAB-4 Series cabinet (for standalone
mounting).

Local Monitoring

7060ap1.wmf
NOTI•FIRE•NET
Network version 5.0

NFS-3030
ONYXWORKS-NW/-NF
ONYXWorks
(NFN-PC-W/F)

Remote Monitoring
NFN-GW-EM

7060ap2a.wmf
NOTI•FIRE•NET
Network version 5.0

INTERNET/ NFN GATEWAY


INTRANET* (embedded)
NFS2-3030
ONYXWORKS

* A UL Listed ethernet (TCP/IP) switch is required between a shared-IP network and the ONYXWORKS equipment. Contemporary Control Systems, Inc.
(www.ctrlink.com) has several UL864 recognized switching hubs.

NION®, NOTIFIER®, ONYX® and ONYXWorks® are registered trademarks


and NOTI•FIRE•NET™, NOTIFIY-IP™, and ONYX FirstVision™ are
trademarks of Honeywell International Inc. Windows® is a registered
trademark of Microsoft Corporation.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com

Page 2 of 2 — dn-7060:b1 • 09/21/09