Enda Et2011 Pid Temperature Controller: Technical Specifications
Enda Et2011 Pid Temperature Controller: Technical Specifications
* Soft-Start feature.
* Zero point input shift.
* C/A2 Relay output programmable as alarm or control output. ENDA ET2011
* Selectable SSR control output.
* Selectable heating/cooling control.
* In the case of sensor failure, manual control can be selected.
* CE marked according to European Norms.
TECHNICAL SPECIFICATIONS
Input type Temperature range Accuracy
°C °F
PT100 Resistance thermometer EN 60751 -99.9...300.0 °C -99.9...543.0 °F 0,5% (of full scale) 1 digit
PT100 Resistance thermometer EN 60751 -200...600 °C -328...1112 °F 0,5% (of full scale) 1 digit
J (Fe-CuNi) Thermocouple EN 60584 0... 600 °C +32... +1112 °F 0,5% (of full scale) 1 digit
K (NiCr-Ni) Thermocouple EN 60584 0...1300°C +32... +2372 °F 0,5% (of full scale) 1 digit
T (Cu-CuNi) Thermocouple EN 60584 0... 400°C +32... +752 °F 0,5% (of full scale) 1 digit
S (Pt10Rh-Pt) Thermocouple EN 60584 0...1700°C +32... +3092 °F 0,5% (of full scale) 1 digit
R (Pt13Rh-Pt) Thermocouple EN 60584 0...1700°C +32... +3092 °F 0,5% (of full scale) 1 digit
ENVIRONMENTAL CONDITIONS
Ambient/storage temperature 0 ... +50°C/-25... +70°C (with no icing)
Max. Relative humidity Relative humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative humidity at 40°C.
According to EN 60529 Front panel : IP65
Rated pollution degree
Rear panel : IP20
Height Max. 2000m
Do not use the device in locations subject to corrosive and flammable gases.
ELECTRICAL CHARACTERISTICS
Supply 230V AC +%10 -%20, 50/60Hz or 24V AC %10, 50/60Hz
Power consumption Max. 5VA
Wiring Power connector: 2.5mm²' screw-terminal, Signal connector: 1,5mm² screw-terminal conenction.
Line resistance Max. 100ohm
Data retention EEPROM (minimum 10 years)
EMC EN 61326-1: 2012
Safety requirements EN 61010-1: 2010 (Pollution degree 2, overvoltage category II)
OUTPUTS
C/A2 output Relay : 250V AC, 8A (for resistive load), Selectable as NO+NC Control or Alarm2 output.
Relay : 250V AC, 16A (for resistive load), Selectable as NO Control or Alarm2 output.
SSR output Max 20mA 12Volt (as control output)
Life expectancy for relay
Mechanical 30.000.000; Electrical 100.000 operation. 250V AC, 8A and 16A (resistive load).
CONTROL
Control type Single set-point and alarm control
Control algorithm
A/D converter 12 bit
Sampling time 100ms
Proportional band Adjustable between 0% and 100%. If Pb=0%, On-Off control is selected.
Control period Adjustable between 1 and 250 seconds
Hysteresis Adjustable between 1 and 50°C/F
Output power The ratio of power at a set point can be adjusted between 0% and 100%
HOUSING
Housing type Suitable for flush-panel mounting according to DIN 43 700.
Dimensions W77xH35xD71mm
Weight Approx. 200g (after packing)
Enclosure material Self extinguishing plastics.
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
1/4 ET2011-E-06-201408
Entering from the programming mode to the run mode:
SET If no key is pressed within 20 seconds during programming mode, the data is stored automatically and the run mode is entered.
SET SET SET
If key is pressed while holding key, the programming mode is enabled.
Alternatively, the same function occurs first pressing key and F key is pressing programming mode is entered.Then and keys are pressing
together, data is recorded and running mode is entered.
Programming mode
SET SET SET SET SET
C.s.Hi. selected output) A2.S.H p10.r.= S type, If both keys are pressed, no nonE = Invisible.
Adjustable between A2.S.L message is displayed on the screen P.yEs = Modification can be done.
Adjustable between C.s.Lo. and Upper scale parameter value and upper scale P13.r.= R type thermocouple selection.
value. value.
and selftune process is stopped. P. no = Only visible.
This parameter varies when changing
a.2.sc. = Parameters of al2.o.
some parameters. When the self tune begins, PIdt. message a.2.sc. menu security access level code.
a2.Hy = Hysteresis of the Alarm2 and measurement value are shown
C. pb
C. Pb = Proportional band.(for selected A2.HY output. Unit Unit = The temperature unit.
alternately.
nonE = Invisible.
output) °C = °C, °F= °F P.yEs = Modification can be done.
Adjustable between %0.0 and %100.0. Adjustable between 1 and 50 °C. After the completion of the self tune process,
(This parameter varies when P. no = Only visible.
C. Pb = %0.0,On-Off control is selected. changing some parameters.) st.Co. parameter is automatically changed to
no and the device returns to working mode.
Cn.sc. Co.sc. = Parameters of Conf.
A2.tp = Function of Alarm2 type. fltr. fLtr. = Coefficient of digital filter. If the measured temperature is higher than
C.Hys = Hysteresis of the output.(for
A2.tP Four kinds of functions can be Filter for display value. 90% of the set value at the beginning of the
menu security access level code.
C.Hys selected output) selected. Adjustable between 1 and 200. If this parameter is 1, nonE = Invisible.
self tune process, then tE.Hi. message is P.yEs = Modification can be done.
Adjustable between 1 and 50 °C. indE. = Independdnt alarm digital filter runs most quick. If the parameter is 200,
the filter run most slow. The value of parameter should shown alternately and the measured P. no = Only visible.
C. Pb = 0,this parameter is active. (Independent)
be increased in interference. temperature is waited to go below %60 of
dE. = Deviation
the set value. After that, self tune operation S.t.Sc. = Parameters of S.tun.
C. ti = Integral time.(for selected output) bAnd = Band alarm (Band) is started automatically.
S.t.sc.
menu security access level code.
C. ti Adjustable between 0 and 100.0 minutes. bAn.i = Band with inhibition C.o.sE = Control output selection If it is intended to abort the self tune
C.o.sE C-A2 = C/A2 (Relay) output selection
nonE = Invisible.
C. ti = 0.0,integral impact is disable. process, St.Co. parameter is changed to P.yEs = Modification can be done.
C. Pb parameter is different from “0”,this A2.st. = The state of Alarm2 output. SSR = SSR output selection no and key is pressed.
parameter appears.
A2.St.
Hi = If A2 output is above the set Co.sc. = Parameters of Conf.
value. (on)
dEF.P. menu security access level code.
C. td = Derivative time.(for selected output)
C. td lo = If A2 output is above the set no = Parameter settings are not
Asjustable between 0.00 and 25.00 minutes. oFfS. = Offset value.
value (off). change.
C. td = 0.0, derivative time is disabled. offs. Offset value is added to the measurement value.
A2.Er. = State of Alarm2 output in the yEs = Parameter setting will be
C. Pb parameter is different from”0”,this A2.Er. Adjusted between -100 and +100°C.The normal value is 0. restored.
parameter appears. case of sensor failure.
on = A2 output is probe failure (on).
C. Ct. = Period time.(for selected output) off= A2 output is probe failure (off). F.k.E.C. F.kE.C. = Function key setting parameter
C. Ct. Adjustable between 1 and 250 second. nonE = Function key is off.
C. Pb parameter is different is different C2.S.A. = The function key with 2.set value is used.
from“0”,this parameter appears. manu. = Manual mode can be achieved with the function key.
dSP.o. = Only the temperature display mode is entered with
C.p.st = The ratio of output power at the function key.
C.p.st setpoint.Adjustable between %0 and %100.
Chys 6 5 6
DEFAULT PARAMETERS
C.typ. = Control output type SET
C.typ Set parameters Control output Alarm2 output Configuration Self tune Security When holding key, the value of parameter flashes and using
C.typ. = HEAt means heating control.
parameters parameters parameters parameters parameters
C.typ. = CooL means cooling control.
TC input PT100 input TC input PT100 input TC input PT100 input TC input PT100 input TC input PT100 input keys the requested value can be adjusted.
C1.sE. 400 C.s.lO. 0 -200 A2.s.l 0 -200 inp.t. FE.cn. Pt. a2.Er. no Co.sc. P.yEs
C2.SE. 400 C.s.Hi. 600 A2.s.H 600 Unit °C A2.Sc. P.yEs If key is pressed and held 0.6 seconds, the value of the selected
A2.SE. 500 C. PB 0 A2Hy. 2 Fltr. 25 Cn.Sc. P.yEs
2 C.o.SE. S.t.Sc. parameter changes rapidly. If waited enough,the value increases 100 at each
C.HyS A2.tp indE C-A2 P.yEs
step. After 1 second following the release of the key, initial condition is
C. ti 4.0 a2.st. Hi offs. 0 dEf.P. no returned.The same procedure is valid for the decrement key.
C. td 1.00 a2.Er. on f.k.E.C. nonE
C. Ct. 20 m.sEt. 50
While the parameter names appear, if and F
C.P.St. 0
keys are pressed together, returns to the program mode.
C.EP.S. 0
S.s.t.S. 0
C.typ. HEat
2/4 ET2011-E-06-201408
TERMS
(5) ( 1 ) Measurement value and set value indicator Running mode)
Parameter name and value (Programming mode)
°F C/A2 A1 SSR ( 2 ) Value increment key (Programming mode)
If only this key is pressed in normal operation,software version
F
°C number is seen. (F.k.E.C. parameter processing)
( 3) Value decrement and parameter selection key.
SET (Programming mode)
ENDA ET2011
( 4 ) Control ve Alarm set selection key (Running mode)
Parameter set key (Programming mode)
ON ON ON
SV+ASV SV+ASV
SV SV
SV-ASV SV-ASV
ON ON
OFF OFF
SV =Set point of CONT output ASV = Set point of AL2 output (ASV min. = 0, ASV max. = 300 )
3/4 ET2011-E-06-201408
DIMENSIONS
Depth
77mm
73mm 5mm
For removing mounting clamps ;
°F C/A2 A1 SSR - Push flush mounting clamps in
direction 1 as shown in the figure below.
F
°C Then pull out the clamps in direction 2 .
35mm
SET
ENDA ET2011
Connection 2
cable Flush mounting Panel
clamp
-
SSR OUT
RESISTIVE LOAD
250V AC 8A
29,5mm
TC C/A2
50/60Hz 5VA
1
MADE IN TURKEY 230V AC +10% -20%
8 680407 711246 1
PID DIGITAL THERMOSTAT
ET2011-T-230
SN: XXXXXXXXX ENDA INDUSTRIAL ELECTRONICS
Note :
1) Panel thickness should be maximum 7mm.
2) If there is no 60mm free space at back side of the
device, it would be difficult to remove it from the panel.
Order Code : ET2011- - - 1- Input selection 2 - Supply Voltage 3- Contact current selection
1 2 3 RT....PT100 input 230VAC...230V AC None......8A contact output
T....TC input 110VAC....110V AC P....16A contact output
024VAC......24V AC
SM...........9-30V DC / 7-24V AC
CONNECTION DIAGRAM
ENDA ET2011 is intended for installation within control panels. Make sure that the device is used only for intended
purpose. The shielding must be grounded on the instrument side. During an installation, all of the cables that are
connected to the device must be free of electrical power. The device must be protected against inadmissible humidity,
vibrations, severe soiling. Make sure that the operation temperature is not exceeded. All input and output lines that are
not connected to the supply network must be laid out as shielded and twisted cables. These cables should not be close
to the power cables or components. The installation and electrical connections must be carried out by a qualified staff
and must be according to the relevant locally applicable regulations.
ENDA INDUSTRIAL ELECTRONICS SN: XXXXXXXXX ENDA INDUSTRIAL ELECTRONICS SN: XXXXXXXXX
ET2011-T-230 ET2011-RT-230
PID DIGITAL THERMOSTAT PID DIGITAL THERMOSTAT
8 680407 711246 8 680407 711321
SSR OUT
-
+
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12
ENDA INDUSTRIAL ELECTRONICS SN: XXXXXXXXX ENDA INDUSTRIAL ELECTRONICS SN: XXXXXXXXX
ET2011-T-230-P ET2011-RT-230-P
PID DIGITAL THERMOSTAT PID DIGITAL THERMOSTAT
8 680407 711284 8 680407 711369
MADE IN TURKEY
SSR OUT
-
+
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12
NOTE : Fuse Note 1) Mains supply cords shall meet the requirements
SUPPLY: F 100 mA of IEC 60227 or IEC 60245.
Switch
250V AC
Phase 2) In accordance with the safety regulations, the
184-253V AC 5 230V AC power supply switch shall bring the identification of
50/60Hz 5VA 6 Neutral Supply
the relevant instrument and it should be easily
Fuse should
accessible by the operator.
be connected. Cable size: 1,5mm²
4/4 ET2011-E-06-201408