Functional Test Sheet For Current Transformer

This document provides a functional test sheet for a current transformer. It lists 8 inspection and test items to check the current transformer's mechanical condition, connections, wiring, insulation resistance, polarity, ratio accuracy, and magnetization characteristics. The test sheet collects location information, manufacturer details, and test results for the current transformer.

Uploaded by

aslam shaikh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
133 views2 pages

Functional Test Sheet For Current Transformer

This document provides a functional test sheet for a current transformer. It lists 8 inspection and test items to check the current transformer's mechanical condition, connections, wiring, insulation resistance, polarity, ratio accuracy, and magnetization characteristics. The test sheet collects location information, manufacturer details, and test results for the current transformer.

Uploaded by

aslam shaikh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

FUNCTIONAL TEST SHEET FOR CURRENT TRANSFORMER

LOCATION: SYSTEM/PURPOSE:
SWITCHBOARD/EQUIPMENT NO: FEEDER/CIRCUIT:
MANUFACTURER:
CT SERIAL NO: TYPE: DRAWING NO:
CT RATIO: VA: CLASS:
INSPECTION/TEST RESULT
1. Inspect the current transformer for mechanical damage.
2. Check and ensure that connections are clean and tight.
3. Check and ensure that the wiring is cleated and core marking is correct.
4. Test and record the insulation resistance between phases (M).
5. Test and record the insulation resistance between phase and earth (M).
6. Polarity Check:
Winding R-phase Y-phase B-phase

7. Ratio Check:
Secondary Current Secondary Current (Amps)
Primary Current
CT Ratio measured between winding
(Amps) R-phase Y-phase B-phase
points

8. CT Magnetisation and Winding Resistance Test:

Winding Measured magnetising current in mA with


Measured following applied voltages (V)
Core CT Resistance
between Phase
No Ratio () at V at 1
terminals
___C A
R-ph
Y-ph
B-ph
R-ph
Y-ph
B-ph
R-ph
Y-ph
B-ph