Page No. 1 1: Why Tot Some Feeder Consider Very Poor Power Factor 2 6
The document discusses several issues with the electrical design of a catering load:
1. The design does not account for critical loads only being supplied by the generator during a grid outage.
2. The interconnecting circuit breaker 2 is shown closed during grid operation when it should generally remain open.
3. The voltage profiles for some UPS panels and loads are not correctly shown as being referenced to the UPS output voltage of 415V instead of the main panel voltage.
It then asks several clarifying questions about terminology, load assumptions, and power factors used in the design.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
31 views1 page
Page No. 1 1: Why Tot Some Feeder Consider Very Poor Power Factor 2 6
The document discusses several issues with the electrical design of a catering load:
1. The design does not account for critical loads only being supplied by the generator during a grid outage.
2. The interconnecting circuit breaker 2 is shown closed during grid operation when it should generally remain open.
3. The voltage profiles for some UPS panels and loads are not correctly shown as being referenced to the UPS output voltage of 415V instead of the main panel voltage.
It then asks several clarifying questions about terminology, load assumptions, and power factors used in the design.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1
B
——
ir.No. points page no.
DG catering all load not only critical loads 1 1 2 I/C 2 shown closed but generally it is not closed during grid operation 12 UPS Process panel 3 and 250 KVA UPS ??? 17 In volt ag e profile UPS process 1,2 and ups process panel n ot sh own.at so for ups HvAC panel,UPS general and ups parallel for OG shown voltge referance from main panel 5 instead of ups output voltage referance which is 415 v. 22 what is N1,N2 and N 25 Wha t is co ns ta nt K VA and c on st an t Z l oa d( Co ns ta nt k va mean s( in du ct iv e) w it h v o l t a g e f l u c t u a t i o n K V A re m a i n s s a m e eg . m o t o r an d c o n s t a n t Z ( s t a t i c ) m ea n s i t s voltage decrease current decrease. 25 Wh y f o r h v a c pa ne l co ns id er 8 0 % i nd uc ti ve and 20 % s tat ic lo ad bc oz in th is pane l only motor load 25 why tot some feeder consider very poor power factor 2 6