Tip Sheet #14 • May 2001 Steam Motors Compressed Air

Use Low-Grade Waste Steam to Power


Absorption Chillers

Reduce Demand Absorption chillers use heat, instead of mechanical energy, to provide cooling. The
Charges mechanical vapor compressor is replaced by a thermal compressor (see figure) that
consists of an absorber, a generator, a pump, and a throttling device. The refrigerant vapor
Absorption chillers can from the evaporator is absorbed by a solution mixture in the absorber. This solution is
reshape facility thermal then pumped to the generator where the refrigerant is revaporized using a waste steam
and electric load profiles heat source. The refrigerant-depleted solution is then returned to the absorber via a
by shifting cooling from an throttling device. The two most common refrigerant/absorbent mixtures used in
electric to a thermal load. If absorption chillers are water/lithium bromide and ammonia/water.
you are served by an electric
utility with a ratcheted demand
charge, you may be able to Comparison of Mechanical and Thermal Vapor Compression Systems*
reduce demand charges
throughout the year by
Waste Heat from Process
reducing your summer peak or Low-Pressure Steam
loads. Refrigerant
Vapor to High Pressure Refrigerant
Condenser Vapor to
Utility Incentives Generator Condenser
Some gas utilities offer
reduced rates during the Electric/
summer. In some areas, Engine- Pump Thermal Throttle
electric utilities provide
Driven Vapor Compression Valve
Compressor
rebates or incentives to
replace mechanical chillers Low Pressure
with steam absorption units. Refrigerant Refrigerant
Vapor from Absorber Vapor from
Evaporator Evaporator
Mechanical
Vapor Compression Rejected Heat

* The evaporator and the condenser, required for both systems, are not shown in the figure.

Steam Tip Sheet information Compared to mechanical chillers, absorption chillers have a low coefficient of
adapted from material provided performance (COP = chiller load/heat input). Nonetheless, they can substantially
by the Industrial Energy reduce operating costs because they are energized by low-grade waste heat, while
Extension Service of Georgia vapor compression chillers must be motor- or engine-driven.
Tech and reviewed by the
DOE BestPractices Steam Low-pressure, steam-driven absorption chillers are available in capacities ranging
Technical Subcommittee. For from 100 to 1,500 tons. Absorption chillers come in two commercially available
additional information on steam designs: single-effect and double-effect. Single-effect machines provide a thermal
system efficiency measures,
COP of 0.7 and require about 18 pounds of 15-psig steam per ton-hour of cooling.
contact the OIT Clearinghouse
at (800) 862-2086. Double-effect machines are about 40 percent more efficient, but require a higher
grade of thermal input, using about 10 pounds of 100- to 150-psig steam per
ton-hour.

OFFICE OF INDUSTRIAL TECHNOLOGIES


ENERGY EFFICIENCY AND RENEWABLE ENERGY • U.S. DEPARTMENT OF ENERGY
Example
In a plant where low-pressure steam is currently being exhausted to the atmosphere, a
mechanical chiller with a COP of 4.0 is used 4,000 hours per year to produce an average
of 300 tons of refrigeration. The cost of electricity at the plant is $0.05 per kilowatt-hour.
An absorption unit requiring 5,400 lbs/hr of 15-psig steam could replace the mechanical
chiller, providing annual electrical cost savings of:
Annual = 300 tons x (12,000 Btu/ton / 4.0) x 4,000 hrs/year x $0.05/kWh x kWh/3,413 Btu
Savings = $52,740 BestPractices is part of the Office of
Industrial Technologies’ (OIT’s) Industries
of the Future strategy, which helps the
Suggested Actions country’s most energy-intensive
industries improve their competitiveness.
BestPractices brings together the best-
Determine the cost-effectiveness of displacing a portion of your cooling load with available and emerging technologies
a waste steam absorption chiller by taking the following steps: and practices to help companies begin
improving energy efficiency, environmental
• Conduct a plant survey to identify sources and availability of waste steam. performance, and productivity right now.

• Determine cooling load requirements and the cost of meeting those requirements BestPractices focuses on plant systems,
with existing mechanical chillers or new installations. where significant efficiency improvements
and savings can be achieved. Industry
• Obtain installed cost quotes for a waste steam absorption chiller. gains easy access to near-term and
long-term solutions for improving the
• Conduct a life cycle cost analysis to determine if the waste steam absorption chiller performance of motor, steam, compressed
meets your company’s cost-effectiveness criteria. air, and process heating systems. In
addition, the Industrial Assessment Centers
provide comprehensive industrial energy
evaluations to small and medium-size
manufacturers.

F OR A DDITIONAL I NFORMATION ,
P LEASE C ONTACT:

Peter Salmon-Cox
About DOE’s Office of Industrial Technologies Office of Industrial Technologies
Phone: (202) 586-2380
The Office of Industrial Technologies (OIT), through partnerships with industry, Fax: (202) 586-6507
government, and non-governmental organizations, develops and delivers advanced [email protected]
energy efficiency, renewable energy, and pollution prevention technologies for www.oit.doe.gov/bestpractices
industrial applications. OIT is part of the U.S. Department of Energy’s Office of
Energy Efficiency and Renewable Energy. OIT Clearinghouse
OIT encourages industry-wide efforts to boost resource productivity through a Phone: (800) 862-2086
Fax: (360) 586-8303
strategy called Industries of the Future (IOF). IOF focuses on the following nine [email protected]
energy- and resource-intensive industries:
• Agriculture • Forest Products • Mining Please send any comments,
• Aluminum • Glass • Petroleum questions, or suggestions to
• Chemicals • Metal Casting • Steel [email protected]

OIT and its BestPractices program offer a wide variety of resources to industrial
Visit our home page at
partners that cover motor, steam, compressed air, and process heating systems. www.oit.doe.gov
For example, BestPractices software can help you decide whether to replace or
rewind motors (MotorMaster+), assess the efficiency of pumping systems (PSAT),
or determine optimal insulation thickness for pipes and pressure vessels (3E Plus). Office of Industrial Technologies
Energy Efficiency
Training is available to help you or your staff learn how to use these software and Renewable Energy
programs and learn more about industrial systems. Workshops are held around the U.S. Department of Energy
country on topics such as “Capturing the Value of Steam Efficiency,” “Fundamentals Washington, DC 20585-0121
and Advanced Management of Compressed Air Systems,” and “Motor System
Management.” Available technical publications range from case studies and tip
sheets to sourcebooks and market assessments. The Energy Matters newsletter, for
example, provides timely articles and information on comprehensive energy systems
for industry. You can access these resources and more by visiting the BestPractices DOE/GO-102001-1277
Web site at www.oit.doe.gov/bestpractices or by contacting the OIT Clearinghouse at May 2001
800-862-2086 or via email at [email protected]. Steam Tip Sheet #14