0% found this document useful (0 votes)
130 views1 page

SCADA Project Guide - 20 PDF

This document discusses the technical specifications for a SCADA/DMS system. It outlines requirements for the system to automatically integrate changes from a GIS database, support data exchange through CIM/XML and IEC 61850 standards, and interface with AMI, AMR, and smart grid systems. It also describes the information storage and retrieval functions, including periodically storing real-time SCADA data in a relational database for analysis, display, and report generation while maintaining previously stored data.

Uploaded by

renv
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
130 views1 page

SCADA Project Guide - 20 PDF

This document discusses the technical specifications for a SCADA/DMS system. It outlines requirements for the system to automatically integrate changes from a GIS database, support data exchange through CIM/XML and IEC 61850 standards, and interface with AMI, AMR, and smart grid systems. It also describes the information storage and retrieval functions, including periodically storing real-time SCADA data in a relational database for analysis, display, and report generation while maintaining previously stored data.

Uploaded by

renv
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Power Finance Corporation

SCADA/DMS, system under Part A –R-APDRP


Model Technical specification
MGVCL/RAPDRP/SIA/1140

Any Change in the electrical network system which will be captured in GIS
database (through IT system being procured under separate package under R-
APDRP) of the utility shall be automatically added/modified to SCADA system.
eg: A new asset addition, should be able to be exchanged through Model
Information between the IT System, and SCADA/DMS System without
programming or configuration effort automatically & adjust and accept the Model
and re-configure its databases, and should provide updated results.

SCADA/DMS Vendors shall provide CIM/XML Adapters for ICCP, OPC or ODBC
for their System and CIM/XML Model repository for data and model exchange
with IT Systems.

Further, system shall be able to interface with IEC61850 (GOOSE & GSSE
Models) & provide an Independent 3rd Party modeling tool that can support
multiple vendor IEC 61850 IED's and create IEC 61850 SCD files.

To enable to Migrate to Smart Grid, the SCADA/DMS Systems shall support the
following:
• Security – The SCADA/RTU/FRTU Network has to be secure over SSL
secure layer, and should be implemented as a VPN. Secure adapters
between end nodes on public networks should be considered with IPSec
or VPN.
•  Interface to AMI/AMR System where-by DSM can be implemented over
CIM/XML Interfaces
• The SCADA CFE should be able to integrate with Smart Grid gateway that
support ICCP / IEC 61850 / IEC 60870-5-101/104// DNP3, DLMS & ANSI
C12.18/21 & IEEE C37.118 .
--
1.3 Information Storage and Retrieval

Information Storage and Retrieval (ISR) function shall allow collection of data from
real-time SCADA/DMS system and storing it periodically in a Relational database
management system (RDBMS) database as historical information (HI) data. This
includes storing of data such as SOE, status data, Analog values, calculated
values, Energy values etc. Programmer shall also be able to set storage mode as
by exception in place of periodic storage.

Subsequently, the data shall be retrieved for analysis, display, trending and report
generation. All stored data shall be accessible from any time period regardless of
changes made to the database after storage of that data (e.g., it shall be possible
to retrieve stored data for a variable that no longer exists in the SCADA/DMS
computer system through back ups on storage medias viz. tapes /MO disks etc
and initialise study-mode DMS functions with stored data on the corresponding
power system model).

The addition, deletion, or modification of data to be collected and processed shall


not result in loss of any previously stored data during the transition of data
collection and processing to the revised database.