MODEL 3005A /3007A: Instruction Manual
MODEL 3005A /3007A: Instruction Manual
MODEL 3005A /3007A: Instruction Manual
12 11:52 AM ページ 表4
KYORITSU ELECTRICAL
INSTRUMENTS DIGITAL INSULATION-CONTINUITY TESTER
WORKS, LTD.
No.5-20,Nakane 2-chome, Meguro-ku, Tokyo
152-0031 Japan
MODEL 3005A /3007A
Phone :(03) 3723-0131 Fax : (03) 3723-0152
URL : http://www.kew-ltd.co.jp
E-mail : [email protected] KYORITSU ELECTRICAL INSTRUMENTS
Factories : Uwajima & Ehime WORKS, LTD.
01-09 92-1492A
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 目1
―1―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 目1
―1―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 2
DANGER is reserved for conditions and actions that are likely to cause CAUTION
serious or fatal injury. ● Always make sure to set the function switch or range selector switch to
WARNING is reserved for conditions and actions that can cause the appropriate position before taking measurements.
serious or fatal injury. ● Do not expose the instrument to the direct sun, dew fall or extreme
CAUTION is reserved for conditions and actions that can cause minor temperature and/or humidity.
injury or instrument damage. ● When the instrument will not be in use for a long period of time, place it
in storage after removing batteries.
DANGER ● Use a damp cloth soaked in water or neutral detergent for cleaning the
● Do not use this instrument on energized (LIVE) circuits. instrument. Do not use abrasives or solvents.
● Do not take measurement in the presence of flammable gasses.
Otherwise, the use of the instrument may cause sparkling, which leads
to an explosion.
● Always keep your fingers behind the barrier on test probe during
measurement.
● Never use the instrument if its surface or your hand is wet.
● Never open the battery compartment cover while taking measurement.
WARNING
● Do not attempt to take any measurements, if any abnormal conditions
occur, such as broken test probe and cracked enclosure of the
instrument.
● Never change function switches with test probe connected to the
equipment under test.
● Do not install substitute parts, perform any unauthorized modification, or
disassemble the instrument. Return the instrument to Kyoritsu or your
distributor for service and repair so as to ensure the safety features are
maintained.
● Do not replace batteries when the surface of the instrument is wet.
● Make sure to disconnect the test probe from the instrument before
opening the battery compartment cover for battery replacement.
―2― ―3―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 2
DANGER is reserved for conditions and actions that are likely to cause CAUTION
serious or fatal injury. ● Always make sure to set the function switch or range selector switch to
WARNING is reserved for conditions and actions that can cause the appropriate position before taking measurements.
serious or fatal injury. ● Do not expose the instrument to the direct sun, dew fall or extreme
CAUTION is reserved for conditions and actions that can cause minor temperature and/or humidity.
injury or instrument damage. ● When the instrument will not be in use for a long period of time, place it
in storage after removing batteries.
DANGER ● Use a damp cloth soaked in water or neutral detergent for cleaning the
● Do not use this instrument on energized (LIVE) circuits. instrument. Do not use abrasives or solvents.
● Do not take measurement in the presence of flammable gasses.
Otherwise, the use of the instrument may cause sparkling, which leads
to an explosion.
● Always keep your fingers behind the barrier on test probe during
measurement.
● Never use the instrument if its surface or your hand is wet.
● Never open the battery compartment cover while taking measurement.
WARNING
● Do not attempt to take any measurements, if any abnormal conditions
occur, such as broken test probe and cracked enclosure of the
instrument.
● Never change function switches with test probe connected to the
equipment under test.
● Do not install substitute parts, perform any unauthorized modification, or
disassemble the instrument. Return the instrument to Kyoritsu or your
distributor for service and repair so as to ensure the safety features are
maintained.
● Do not replace batteries when the surface of the instrument is wet.
● Make sure to disconnect the test probe from the instrument before
opening the battery compartment cover for battery replacement.
―2― ―3―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 4
2. FEATURES 3. SPECIFICATIONS
MODEL-3005A/3007A are microprocessor controlled insulation-continuity ● Measuring Range and Accuracy (at 23±5°C, relative humidity 45 -75%)
testers.
○ Insulation Resistance Ranges:
● Designed to safety standards: Nominal Output Voltage 250V 500V 1000V
IEC 61010-1 Overvoltage CAT III 300V Pollution Degree 2 0 ~19.99MΩ 0 ~19.99MΩ 0 ~19.99MΩ
Measuring
IEC 61010-2-31 (Safety requirements for hand-held probe assemblies) 0 ~ 199.9MΩ 0 ~ 199.9MΩ 0 ~ 199.9MΩ
Ranges
0 ~ 1999MΩ 0 ~ 1999MΩ 0 ~ 1999MΩ
● Display with back light function to facilitate work at night or dimly lit Open-Circuit 250V DC 500V DC 1000V DC
locations (Model 3007A only) Voltage +20%,-0% +20%,-0% +20%,-0%
1mA DC min. 1mA DC min. 1mA DC min.
Nominal Current
● Bar graph to indicate measured results at 0.25MΩ at 0.5MΩ at 1MΩ
Short-Circuit
1.5mA approx
● Strap belt to make both hands' operation easier Current
20MΩ
±1.5%rdg ±5dgt
● Live circuit warning indication and buzzer 200MΩ
Accuracy
2000 0~1GΩ ±3%rdg ±3dgt
MΩ 1G~2GΩ ±10%rdg ±3dgt
● Auto discharge function
When insulation resistance is measured, electric charges stored in
capacitive circuits are automatically discharged after testing. Discharge ○ Continuity Ranges:
can be checked with live circuit warning. Ranges 20Ω 200Ω 2000Ω
Measuring Ranges 0 ~ 19.99Ω 0 ~ 199.9Ω 0 ~ 1999Ω
● Auto power off function Open-Circuit
7 ~ 12V approx
To prevent the instrument from being left powered on and conserve Voltage
battery power, the instrument automatically turns off approx. 10 minutes Measuring Current
200mA min
after the last switch operation. at 0.2Ω ~ 2Ω
Accuracy ±1.5%rdg ±5dgt ±1.5%rdg ±3dgt
● LOK mode (Model 3007A only)
The test current is removed once a stable reading is reached to prevent ○ AC Voltage Indication
unnecessary battery consumption. 0 ~ 600V ±5%rdg ±3dgt
―4― ―5―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 4
2. FEATURES 3. SPECIFICATIONS
MODEL-3005A/3007A are microprocessor controlled insulation-continuity ● Measuring Range and Accuracy (at 23±5°C, relative humidity 45 -75%)
testers.
○ Insulation Resistance Ranges:
● Designed to safety standards: Nominal Output Voltage 250V 500V 1000V
IEC 61010-1 Overvoltage CAT III 300V Pollution Degree 2 0 ~19.99MΩ 0 ~19.99MΩ 0 ~19.99MΩ
Measuring
IEC 61010-2-31 (Safety requirements for hand-held probe assemblies) 0 ~ 199.9MΩ 0 ~ 199.9MΩ 0 ~ 199.9MΩ
Ranges
0 ~ 1999MΩ 0 ~ 1999MΩ 0 ~ 1999MΩ
● Display with back light function to facilitate work at night or dimly lit Open-Circuit 250V DC 500V DC 1000V DC
locations (Model 3007A only) Voltage +20%,-0% +20%,-0% +20%,-0%
1mA DC min. 1mA DC min. 1mA DC min.
Nominal Current
● Bar graph to indicate measured results at 0.25MΩ at 0.5MΩ at 1MΩ
Short-Circuit
1.5mA approx
● Strap belt to make both hands' operation easier Current
20MΩ
±1.5%rdg ±5dgt
● Live circuit warning indication and buzzer 200MΩ
Accuracy
2000 0~1GΩ ±3%rdg ±3dgt
MΩ 1G~2GΩ ±10%rdg ±3dgt
● Auto discharge function
When insulation resistance is measured, electric charges stored in
capacitive circuits are automatically discharged after testing. Discharge ○ Continuity Ranges:
can be checked with live circuit warning. Ranges 20Ω 200Ω 2000Ω
Measuring Ranges 0 ~ 19.99Ω 0 ~ 199.9Ω 0 ~ 1999Ω
● Auto power off function Open-Circuit
7 ~ 12V approx
To prevent the instrument from being left powered on and conserve Voltage
battery power, the instrument automatically turns off approx. 10 minutes Measuring Current
200mA min
after the last switch operation. at 0.2Ω ~ 2Ω
Accuracy ±1.5%rdg ±5dgt ±1.5%rdg ±3dgt
● LOK mode (Model 3007A only)
The test current is removed once a stable reading is reached to prevent ○ AC Voltage Indication
unnecessary battery consumption. 0 ~ 600V ±5%rdg ±3dgt
―4― ―5―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 6
● Typical Number of Measurements. IEC 60529 (IP54) Dust & drip proof
(central tendency for supply voltage up to 8V) ● Operating System: Dual integration
Insulation Resistance Ranges:
Approx. 1000 times min. at load 0.5MΩ ● Display: Liquid crystal display (maximum count: 1999),
Continuity Ranges: Unit, Mark
Approx. 700 times min. at load 1Ω Bar graph 30 points max. (20 points on Ω
range)
● Operating Errors (IEC 61557-2,-4)
Measuring range to keep Maximum percentage ● Over range Indication: "OL" is shown on the display.
Functions Range
operating error operating error
20MΩ 0.50 ~ 19.99MΩ ● Sample Rate: Approx. 0.5 ~ 2.5 times per second
1000V 200MΩ 1.0 ~ 199.9MΩ
2000MΩ 10 ~ 1000MΩ ● Operating Temperature 0 ~ +40°C, relative humidity up to 85%
20MΩ 0.50 ~ 19.99MΩ & Humidity:
500V 200MΩ 1.0 ~ 199.9MΩ
2000MΩ 10 ~ 100MΩ ● Storage Temperature -20 ~ +60°C, relative humidity up to 75%
20MΩ 0.25 ~ 19.99MΩ ±30% & Humidity:
250V 200MΩ 1.0 ~ 199.9MΩ
2000MΩ 10 ~ 100MΩ ● Insulation Resistance: More than 50MΩ at 1000V DC between electrical
20Ω 0.20 ~ 19.99Ω circuit and housing case
Ω 200Ω 1.0 ~ 199.9Ω
2000Ω 10 ~ 1999Ω ● Withstand Voltage: 3700V AC for one minute between electrical
The influencing variations used for calculating the operating error are circuit and housing case
denoted as follows;
Temperature: 0℃ and 35℃ ● Overload Protection
Supply voltage : 8V to 13.8V Insulation resistance ranges:
1000V Range 1200V (DC+AC p-p) for 10 seconds
● Applicable Standards 500V Range 600V (DC+AC p-p) for 10 seconds
IEC 61010-1 Over voltage CAT III 300V Pollution Degree 2 250V Range 300V (DC+AC p-p) for 10 seconds
IEC 61010-2-31 Safety requirements for hand-held probe Continuity ranges:
assemblies 20/200/2000Ω 280V (DC+AC p-p) for 10 seconds
IEC 61557-1/2/4 Measuring equipment for low voltage Range (Protection by fusing)
distribution systems
IEC 61326-1 EMC
―6― ―7―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 6
● Typical Number of Measurements. IEC 60529 (IP54) Dust & drip proof
(central tendency for supply voltage up to 8V) ● Operating System: Dual integration
Insulation Resistance Ranges:
Approx. 1000 times min. at load 0.5MΩ ● Display: Liquid crystal display (maximum count: 1999),
Continuity Ranges: Unit, Mark
Approx. 700 times min. at load 1Ω Bar graph 30 points max. (20 points on Ω
range)
● Operating Errors (IEC 61557-2,-4)
Measuring range to keep Maximum percentage ● Over range Indication: "OL" is shown on the display.
Functions Range
operating error operating error
20MΩ 0.50 ~ 19.99MΩ ● Sample Rate: Approx. 0.5 ~ 2.5 times per second
1000V 200MΩ 1.0 ~ 199.9MΩ
2000MΩ 10 ~ 1000MΩ ● Operating Temperature 0 ~ +40°C, relative humidity up to 85%
20MΩ 0.50 ~ 19.99MΩ & Humidity:
500V 200MΩ 1.0 ~ 199.9MΩ
2000MΩ 10 ~ 100MΩ ● Storage Temperature -20 ~ +60°C, relative humidity up to 75%
20MΩ 0.25 ~ 19.99MΩ ±30% & Humidity:
250V 200MΩ 1.0 ~ 199.9MΩ
2000MΩ 10 ~ 100MΩ ● Insulation Resistance: More than 50MΩ at 1000V DC between electrical
20Ω 0.20 ~ 19.99Ω circuit and housing case
Ω 200Ω 1.0 ~ 199.9Ω
2000Ω 10 ~ 1999Ω ● Withstand Voltage: 3700V AC for one minute between electrical
The influencing variations used for calculating the operating error are circuit and housing case
denoted as follows;
Temperature: 0℃ and 35℃ ● Overload Protection
Supply voltage : 8V to 13.8V Insulation resistance ranges:
1000V Range 1200V (DC+AC p-p) for 10 seconds
● Applicable Standards 500V Range 600V (DC+AC p-p) for 10 seconds
IEC 61010-1 Over voltage CAT III 300V Pollution Degree 2 250V Range 300V (DC+AC p-p) for 10 seconds
IEC 61010-2-31 Safety requirements for hand-held probe Continuity ranges:
assemblies 20/200/2000Ω 280V (DC+AC p-p) for 10 seconds
IEC 61557-1/2/4 Measuring equipment for low voltage Range (Protection by fusing)
distribution systems
IEC 61326-1 EMC
―6― ―7―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 8
⑩
● Power Source: 8 x R6P, 1.5V AA or equivalent
⑤
● Auto-power-off Function: Automatically turns off approx. 10 minutes after ①
⑪
the last switch operation.
Consumption current: approx. 75µA
● Accessories ②
Test Probe MODEL7122 x 1 set ⑥
Strap belt x1
Test probe pouch x1 ③
Batteries (R6P) x8 ⑧ ⑨
Instruction manual x1
④
Spare fuse F600V/500mA x1
①… LCD DISPLAY
②… TRAC-LOKSWITCH (Model 3007A only)
③… RANGE SELECTOR SWITCH
④… TEST BUTTON
⑤… CONNECTOR
⑥… BACK LIGHT SWITCH (Model 3007A only)
⑦… FUNCTION SWITCH
⑧… TEST PROBE (RED)
⑨… TEST PROBE (BLACK)
⑩… ALLIGATOR CLIP (BLACK)
⑪… PLOBE CAP (BLACK & RED)
―8― ―9―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 8
⑩
● Power Source: 8 x R6P, 1.5V AA or equivalent
⑤
● Auto-power-off Function: Automatically turns off approx. 10 minutes after ①
⑪
the last switch operation.
Consumption current: approx. 75µA
● Accessories ②
Test Probe MODEL7122 x 1 set ⑥
Strap belt x1
Test probe pouch x1 ③
Batteries (R6P) x8 ⑧ ⑨
Instruction manual x1
④
Spare fuse F600V/500mA x1
①… LCD DISPLAY
②… TRAC-LOKSWITCH (Model 3007A only)
③… RANGE SELECTOR SWITCH
④… TEST BUTTON
⑤… CONNECTOR
⑥… BACK LIGHT SWITCH (Model 3007A only)
⑦… FUNCTION SWITCH
⑧… TEST PROBE (RED)
⑨… TEST PROBE (BLACK)
⑩… ALLIGATOR CLIP (BLACK)
⑪… PLOBE CAP (BLACK & RED)
―8― ―9―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 10
5… TRACK/LOK MODE
6… AUTONULL OPERATION
7… BATTERY VOLTAGE WARNING
8… CONTINUITY/INSULAATION RESISTANCE RANGE SETTING
9… UNIT
― 10 ― ― 11 ―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 10
5… TRACK/LOK MODE
6… AUTONULL OPERATION
7… BATTERY VOLTAGE WARNING
8… CONTINUITY/INSULAATION RESISTANCE RANGE SETTING
9… UNIT
― 10 ― ― 11 ―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 12
CAUTION
● Never press the test button if the live circuit warning is indicated or the
warning buzzer sounds. This may damage the circuit.
Voltage check can be made with the function switch at any position except "OFF".
Be sure to turn off the breaker for the circuit under test.
① Connect the test probe (black) to the earth side and the test probe (red) to
the line side of the circuit under test.
② Ensure that the live circuit warning is not lit and the audible warning is not
5-2 Battery Voltage Check present. When the live circuit warning is lit and the buzzer sounds, never
① Set the function switch to any position except "OFF". press the test button. Voltage is generated in the circuit under test.
② When the battery voltage warning symbol ( ) is lit, the batteries are Recheck that the breaker for the circuit under test is "OFF".
exhausted. Replace all of them with new ones according to section 8
for battery & fuse replacement.
― 12 ― ― 13 ―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 12
CAUTION
● Never press the test button if the live circuit warning is indicated or the
warning buzzer sounds. This may damage the circuit.
Voltage check can be made with the function switch at any position except "OFF".
Be sure to turn off the breaker for the circuit under test.
① Connect the test probe (black) to the earth side and the test probe (red) to
the line side of the circuit under test.
② Ensure that the live circuit warning is not lit and the audible warning is not
5-2 Battery Voltage Check present. When the live circuit warning is lit and the buzzer sounds, never
① Set the function switch to any position except "OFF". press the test button. Voltage is generated in the circuit under test.
② When the battery voltage warning symbol ( ) is lit, the batteries are Recheck that the breaker for the circuit under test is "OFF".
exhausted. Replace all of them with new ones according to section 8
for battery & fuse replacement.
― 12 ― ― 13 ―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 14
6-2 Insulation Resistance Measurement ④ Read the resistance value from the LCD.
DANGER
● Always test the circuit or equipment to ensure it is surely de-energized
before measurement according to the instruction of 6-1.
● To avoid electrical shock, measurements must be performed on de-
energized circuits only.
● When the test button is pressed with the function switch in the MΩ
position, take care not to touch the tip of the test probe and the circuit
under test where a high voltage is present in order to avoid possible
shock hazard.
● Never make measurement with the battery compartment cover removed.
⑤ With the test probe still connected to the circuit under test, release the test
CAUTION button to discharge capacitance in the circuit after measurement.
● Never press the test button if the live circuit warning is indicated or the
warning buzzer sounds. This may damage the circuit. DANGER
●Conduct the voltage warning check before measurement to ensure that Do not touch the circuit under test immediately after testing. Capacitance
the circuit under test is de-energized. stored in the circuit may cause electric shock.
① Check the voltage which can be applied to the circuit under test and set Leave test probes connected to the circuit and never touch the circuit until
the function switch and the range selector switch to the desired range. the discharge is completed.
② Connect the test probe (black) to the earth terminal of the circuit under ●Principle of Insulation Resistance Measurement
test. Resistance value can be obtained by applying a certain high voltage to the
③ Put the tip of the test probe (red) to the circuit under test and press the resistance (insulation resistance) and measuring the flowing current.
test button.
The buzzer sounds intermittently during measurement. Resistance Value = Voltage / Current
RX = V / I
Current outputs from the earth terminal, and returns to the line terminal.
― 14 ― ― 15 ―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 14
6-2 Insulation Resistance Measurement ④ Read the resistance value from the LCD.
DANGER
● Always test the circuit or equipment to ensure it is surely de-energized
before measurement according to the instruction of 6-1.
● To avoid electrical shock, measurements must be performed on de-
energized circuits only.
● When the test button is pressed with the function switch in the MΩ
position, take care not to touch the tip of the test probe and the circuit
under test where a high voltage is present in order to avoid possible
shock hazard.
● Never make measurement with the battery compartment cover removed.
⑤ With the test probe still connected to the circuit under test, release the test
CAUTION button to discharge capacitance in the circuit after measurement.
● Never press the test button if the live circuit warning is indicated or the
warning buzzer sounds. This may damage the circuit. DANGER
●Conduct the voltage warning check before measurement to ensure that Do not touch the circuit under test immediately after testing. Capacitance
the circuit under test is de-energized. stored in the circuit may cause electric shock.
① Check the voltage which can be applied to the circuit under test and set Leave test probes connected to the circuit and never touch the circuit until
the function switch and the range selector switch to the desired range. the discharge is completed.
② Connect the test probe (black) to the earth terminal of the circuit under ●Principle of Insulation Resistance Measurement
test. Resistance value can be obtained by applying a certain high voltage to the
③ Put the tip of the test probe (red) to the circuit under test and press the resistance (insulation resistance) and measuring the flowing current.
test button.
The buzzer sounds intermittently during measurement. Resistance Value = Voltage / Current
RX = V / I
Current outputs from the earth terminal, and returns to the line terminal.
― 14 ― ― 15 ―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 16
●Terminal connection of insulation resistance test ● Principle of Continuity Measurement (Resistance Test)
In case of testing insulation of insulated wire and cable against the earth Resistance value can be obtained by applying a certain current to the
at direct current, connecting - pole of power to cable conductor, + to the resistance under test and measuring the voltage generated on the both
earth obtains smaller measuring value, compared with connecting the sides of the resistor under test.
other way round. This connecting method is generally acknowledged
relevant to detect defective insulation. Resistance value = Voltage / Current
RX = V / I
6-3 Continuity Measurement (Resistance Tests)
DANGER
● Always test the circuit or equipment to ensure it is surely de-energized
before measurement according to the instruction of 6-1.
● To avoid electrical shock, measurements must be performed on de-
energized circuits only.
● Never make measurement with the battery compartment cover
removed. 6-4 Continuous Measurement
A lock down feature is incorporated on the test button. Pressing and
CAUTION turning it clockwise, lock the test button in the continuous operating
● Never press the test button if the live circuit warning is indicated or the position.
warning buzzer sounds. This may damage the circuit. To release the lock, turn the test button counterclockwise.
● When an additional circuit is connected in parallel with the circuit under
test , inaccurate reading may be taken. NOTE:
① Set the function switch to the "AUTO NULL" position. Model 3007A has TRAC/LOK function. When "LOK" mode is selected,
② Short the test probes (red) and (black) and press the test button. Then the sampling is conducted only once, even though the test button is locked
resistance of the test probes is displayed and memorized with down for continuous measurement.
microprocessor. To make continuous measurement, select "TRAC" mode.
③ Set the function switch to "Ω" position.
④ Connect the test probes to the circuit under test and press the test button. DANGER
⑤ Read the resistance value from the LCD. Be extremely careful not to get electric shock during insulation resistance
measurement as high voltage is present on the tip of test probes
●NULL symbol ( ) is displayed while AUTO NULL function is working. continuously.
●AUTO NULL will be cancelled when the instrument is powered off.
― 16 ― ― 17 ―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 16
●Terminal connection of insulation resistance test ● Principle of Continuity Measurement (Resistance Test)
In case of testing insulation of insulated wire and cable against the earth Resistance value can be obtained by applying a certain current to the
at direct current, connecting - pole of power to cable conductor, + to the resistance under test and measuring the voltage generated on the both
earth obtains smaller measuring value, compared with connecting the sides of the resistor under test.
other way round. This connecting method is generally acknowledged
relevant to detect defective insulation. Resistance value = Voltage / Current
RX = V / I
6-3 Continuity Measurement (Resistance Tests)
DANGER
● Always test the circuit or equipment to ensure it is surely de-energized
before measurement according to the instruction of 6-1.
● To avoid electrical shock, measurements must be performed on de-
energized circuits only.
● Never make measurement with the battery compartment cover
removed. 6-4 Continuous Measurement
A lock down feature is incorporated on the test button. Pressing and
CAUTION turning it clockwise, lock the test button in the continuous operating
● Never press the test button if the live circuit warning is indicated or the position.
warning buzzer sounds. This may damage the circuit. To release the lock, turn the test button counterclockwise.
● When an additional circuit is connected in parallel with the circuit under
test , inaccurate reading may be taken. NOTE:
① Set the function switch to the "AUTO NULL" position. Model 3007A has TRAC/LOK function. When "LOK" mode is selected,
② Short the test probes (red) and (black) and press the test button. Then the sampling is conducted only once, even though the test button is locked
resistance of the test probes is displayed and memorized with down for continuous measurement.
microprocessor. To make continuous measurement, select "TRAC" mode.
③ Set the function switch to "Ω" position.
④ Connect the test probes to the circuit under test and press the test button. DANGER
⑤ Read the resistance value from the LCD. Be extremely careful not to get electric shock during insulation resistance
measurement as high voltage is present on the tip of test probes
●NULL symbol ( ) is displayed while AUTO NULL function is working. continuously.
●AUTO NULL will be cancelled when the instrument is powered off.
― 16 ― ― 17 ―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 18
CAUTION
Never use any solvent which may transmute plastics, for example, organic
solvent such as benzene, acetone, etc.
11. SERVICING
― 20 ― ― 21 ―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 20
CAUTION
Never use any solvent which may transmute plastics, for example, organic
solvent such as benzene, acetone, etc.
11. SERVICING
― 20 ― ― 21 ―
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]
3007A-E 01.9.12 11:52 AM ページ 表4
KYORITSU ELECTRICAL
INSTRUMENTS DIGITAL INSULATION-CONTINUITY TESTER
WORKS, LTD.
No.5-20,Nakane 2-chome, Meguro-ku, Tokyo
152-0031 Japan
MODEL 3005A /3007A
Phone :(03) 3723-0131 Fax : (03) 3723-0152
URL : http://www.kew-ltd.co.jp
E-mail : [email protected] KYORITSU ELECTRICAL INSTRUMENTS
Factories : Uwajima & Ehime WORKS, LTD.
01-09 92-1492A
Quality Kyoritsu Products Online at: www. GlobalTestSupply.com [email protected]