Abb 267CS
Abb 267CS
Abb 267CS
01
Base accuracy Fewer transmitters, less wiring and fewer shut-off valves
— ± 0.075 % / ± 0.04 % — Reduce installation costs
One transmitter replaces three separate transmitters Full compliance with PED category III
— Saving initial purchase costs
Series 2600T Pressure Transmitters SS/267CS/269CS
Model 267CS/269CS Multivariable
For orifices:
dp
4 dp
Y 1 = 1 – ( 0.41 + 0.35 ⋅ β ) --------------
p⋅ κ
F
DP p
Meet For nozzles:
the
2 κ – 1- 1
Future ⎛ ---⎞ ⎛ ⎞⎛ ----------- ⎞ ---
⎜ ⎛ dp⎞ κ⎟ ⎜ κ ⎟ 2
P T ⎟⎜ ⎛ ------⎞
dp
κ ------
⎜ ⎝ p ⎠ ⎟⎜ 4 ⎟⎜ 1 – ⎟
Flow
Flow
1–β ⎝ p⎠
Y 1 = ⎜⎜ --------------------⎟⎟ ⎜⎜ ---------------------------------⎟⎟ ⎜⎜ -----------------------------------⎟⎟
κ–1 2
⎜ ⎟⎜ ---⎟ ⎜ 1 – ⎛ dp ------⎞ ⎟
4 ⎛ dp⎞ κ⎟ ⎜ ⎝ p⎠ ⎟
T Qm ⎜ ⎟⎜
⎝ ⎠ ⎝ 1 – β ⎝ ------ p ⎠ ⎠⎝ ⎠
Qv
β = ratio of diameters (Beta ratio)
15_d0030 dp = differential pressure
p = static pressure
κ = Isentropic exponent
The dynamic mass flow compensation of 267C./269C. is based on Velocity of approach factor
the following formula (according to EN ISO 5167/AGA 3:
Is dependent on the Beta ratio as defined by the following equation:
2
Qm ≈ C ⋅ Ev ⋅ Y1 ⋅ d dp ⋅ ρ 1
E v = --------------------
4
1–β
Qm = mass flowrate
C = discharge coefficient Beta ratio is dependent on bore diameter and pipe diameter which in
Ev = velocity of approach factor turn are functions of temperature. The material of the process pipe
Y1 = gas expansion factor and primary flow element expands or contracts with changes in
d = bore diameter temperature of the fluid being measured. The thermal expansion
dp = differential pressure coefficients are dependent on the the material of the pipe and flow
ρ = fluid density element and are used for calculating the change in diameters.
This ensures high flowrate accuracy during low and high temperature
The following standards are used for flow calculation: applications.
– AGA 3
– DIN EN ISO 5167
2
Series 2600T Pressure Transmitters SS/267CS/269CS
Model 267CS/269CS Multivariable
Span limits
Maximum span = URL = upper range limit
(with the flow measurement shut off, can be adjusted up to ± URL
within the measurement span.
Example: -400 ... +400 mbar)
In order to optimize performance characteristics, it is recommended
to select the transmitter sensor providing the lowest turndown ratio.
Zero suppression and elevation
No suppression or elevation, but zero-based range if:
– calibrated span ≥ minimum span
Process temperature range
-50 °C to +650 °C (-58 °F to 1200 °F) with external four-wire RTD.
Damping
Adjustable time constant: 0 to 60 sec
This is in addition to sensor response time.
Warm-up period
Operation within specifications: ≤ 2.5 sec with minimal damping
Insulation resistance
> 100 MΩ at 1000 V DC (between terminals and ground)
3
Series 2600T Pressure Transmitters SS/267CS/269CS
Model 267CS/269CS Multivariable
Hazardous atmospheres
Pressure limits
Transmitter of protection type "Intrinsically safe EEx ia"
Overpressure limits (without damage to the transmitter)
according to Directive 94/9/EC (ATEX)
Lower limit
– 0.5 kPa abs, 5 mbar abs, 0.07 psia for silicone oil For applications in explosive areas, the connected RTD must also
– 40 kPa abs, 400 mbar abs, 5.8 psia for carbon fluoride have the respective Ex protection class as the transmitter.
4
Series 2600T Pressure Transmitters SS/267CS/269CS
Model 267CS/269CS Multivariable
Fieldbus transmitters (PROFIBUS PA / FOUNDATION fieldbus) Transmitter of protection type "Intrinsically safe EEx ia"
Identification: II 1/2 GD T 50 °C EEx ia IIC T6 according to Directive 94/9/EC (ATEX), or
II 1/2 GD T 95 °C EEx ia IIC T4
protection type "flameproof enclosure EEx d" according to
Power supply and signal circuit with protection type Intrinsic Safety Directive 94/9/EC (ATEX), or
EEx ib IIB/IIC or EEx ia IIB/IIC for connection to supply units with
maximum values: protection type "Limited energy equipment EEx nL" according to
II 1/2 GD T 50 °C EEx ia or ib IIC T6 Ui = 17.5 V Directive 94/9/EC (ATEX) (alternate certification)
II 1/2 GD T 95 °C EEx ia or ib IIC T4 Ii = 360 mA
Pi = 2.52 W Transmitter with 4 to 20 mA output signal and HART communication
Identification: II 1/2 GD T50 °C EEx ia IIC T6
II 1/2 GD T 50 °C EEx ia or ib IIB T6 Ui = 17.5 V II 1/2 GD T95 °C EEx ia IIC T4;
II 1/2 GD T 95 °C EEx ia or ib IIB T4 Ii = 380 mA (refer to "EEx ia" for additional data)
Pi = 5.32 W or
or connection to supply units or barriers with linear characteristics: Identification: II 1/2 GD T85 °C EEx d IIC T6
Maximum values:
II 1/2 GD T 50 °C EEx ia or ib IIC T6 Ui = 24 V Ambient temperature range:
II 1/2 GD T 95 °C EEx ia or ib IIC T4 Ii = 250 mA -40 °C to +75 °C (-40 °F to +167 °F)
Pi = 1.2 W or
Transmitter of protection type "flameproof enclosure EEx d" Transmitter with 4 to 20 mA output signal and HART communication
according to Directive 94/9/EC (ATEX) and fieldbus transmitter (PROFIBUS PA/FOUNDATION fieldbus)
Transmitter with 4 to 20 mA output signal and HART communication Explosion Proof: Class I, Division 1, Groups A, B, C, D;
and fieldbus transmitter (PROFIBUS PA/FOUNDATION fieldbus) Class II/III, Division 1, Groups E, F, G
Identification: II 1/2 G EEx d IIC T6 Degree of protection:NEMA Type 4X (indoor or outdoor)
5
Series 2600T Pressure Transmitters SS/267CS/269CS
Model 267CS/269CS Multivariable
6
Series 2600T Pressure Transmitters SS/267CS/269CS
Model 267CS/269CS Multivariable
8
Series 2600T Pressure Transmitters SS/267CS/269CS
Model 267CS/269CS Multivariable
9
Series 2600T Pressure Transmitters SS/267CS/269CS
Model 267CS/269CS Multivariable
70 (2.76)
114 (4.49) 23 (0.91) LCD display
(1.02)
26
Additional tag plate,
e.g., for indicating
measuring points
(optional)
Housing rotating
186 (7.32)
108 (4.25)
Threaded bore
stop-screw
(optional) ¼-18 NPT
Drain/vent valve (optional) for drain/vent valve
Transducer
61 (2.40)
(1.63)
plate
41.3
(1.18)
-+
30
Process
connection
54 (2.13) Threads for fixing screws 90 (3.54)
(see process flange data)
96 (3.78)
71 (2.80)
Type plate
∅ 83 (3.27)
140 (5.51)
Housing cover
15_0085x1
11
Series 2600T Pressure Transmitters SS/267CS/269CS
Model 267CS/269CS Multivariable
70 (2.76)
140 (5.51)
83 (3.27)
Space must be available
to rotate the keyboard
cover 43
(1.69)
Electrical connection
Additional tag plate, e.g., for
indicating measuring points Housing rotating Captive screw for
(optional) stop-screw keyboard cover
61 (2.40)
96 (3.78) 20 (0.79)
107 (4.21)
Transducer 54 (2.13)
plate 138 (5.43)
168 (6.61) 23 (0.91)
Process LCD display
connection
(1.63)
41.3
Type plate
Electrical connection
12
Series 2600T Pressure Transmitters SS/267CS/269CS
Model 267CS/269CS Multivariable
∅ 11 (0.43)
∅ 10 (0.4)
72 (2.83)
60(2.36) 135.5 (5.33)
72 (2.83)
57(2.24)
72 (2.83)
136 (5.35)
56(2.20) 110 (4.33)
214 (8.43)
M01517x1
Vertical pipe mounting Horizontal pipe mounting Vertical pipe mounting and Horizontal pipe mounting and
transmitter above the mounting transmitter above the
bracket mounting bracket
M01520x1 M01521x1
M01518x1 M01519x1
13
Series 2600T Pressure Transmitters SS/267CS/269CS
Model 267CS/269CS Multivariable
Electrical connections
Grounding/potential
Test sockets for 4 to 20 mA equalizing terminal Output signal/power supply Fieldbus plug connector
(not with Fieldbus
transmitters) 7/8 in connector
1 3
M12 x 1 connector
14 12 Connection for Pt 100 2
13 TEST 11
SIGNAL
- + - +
3 1
Screw terminals for leads with 0.5
to 2.5 mm² cross-section
4 15_0066x1
1 2
- +
Harting Han 8D (8U) pin assignment
(socket view)
15_0079x1
14
Series 2600T Pressure Transmitters SS/267CS/269CS
Model 267CS/269CS Multivariable
Ordering information
Multivariable transmitter, for mass flow Variant digit No. 1- 6 7 8 9 10 11 Code
267CS Base accuracy: 0.075 % Catalog No. 267CS-
269CS Base accuracy: 0.04 % Catalog No. 269CS-
Sensor - Span limits
1 kPa 10 mbar 4 in. H2O A
6 kPa 60 mbar 24 in. H2O (45 mm Hg) C
40 kPa 400 mbar 160 in. H2O (300 mm Hg) F
250 kPa 2500 mbar 1000 in. H2O (1875 mm Hg) L
2000 kPa 20 bar 290 psi N
100 kPa 1000 mbar 400 in. H2O Y
Static pressure
0 ... 0.6 MPa 0 ... 6 bar 0 ... 87 psi 1) 1
0 ... 2 MPa 0 ... 20 bar 0 ... 290 psi 2) 2
0 ... 10 MPa 0 ... 100 bar 0 ... 1450 psi 2) 3
0 ... 41 MPa 0 ... 410 bar 0 ... 5945 psi 2) 4
Diaphragm material / Fill fluid
AISI 316L SST (1.4435) Silicone oil NACE S
Hastelloy C-276 Silicone oil NACE K
Monel 400 Silicone oil NACE M
Monel 400 gold plated Silicone oil NACE V
Tantalum Silicone oil NACE T
AISI 316L SST (1.4435) Inert fluid NACE 3) A
Hastelloy C-276 Inert fluid NACE 3) F
Monel 400 Inert fluid NACE 3) C
Monel 400 gold plated Inert fluid NACE 3) Y
Tantalum Inert fluid NACE 3) D
Process connection material / Process connection
AISI 316L SST (1.4404 / 1.4408) 1/4-18 NPT-f direct NACE A
AISI 316L SST (1.4404 / 1.4408) 1/4-18 NPT-f direct (DIN 19213) NACE C
AISI 316L SST (1.4404 / 1.4408) 1/2-14 NPT-f through adapter NACE B
Hastelloy C-276 1/4-18 NPT-f direct NACE D
Hastelloy C-276 1/4-18 NPT-f direct (DIN 19213) NACE F
Hastelloy C-276 1/2-14 NPT-f through adapter NACE E
Monel 400 1/4-18 NPT-f direct NACE G
Monel 400 1/4-18 NPT-f direct (DIN 19213) NACE L
Monel 400 1/2-14 NPT-f through adapter NACE H
Kynar (PVDF) (axial) 1/4-18 NPT-f direct (max. 1 MPa) P
AISI 316L SST (1.4404 / 1.4408) (vertical) 1/4-18 NPT-f direct NACE Q
Bolts / Gaskets
AISI 316L SST (NACE - non exposed) Viton 4) 3
AISI 316L SST (NACE - non exposed) PTFE (Max. 10 MPa) 5) 4
AISI 316L SST (NACE - non exposed) EPDM 5) 5
AISI 316L SST (NACE - non exposed) Perbunan 5) 6
AISI 316L SST FEP (Only available with Kynar [PVDF] process connection) T
15
Series 2600T Pressure Transmitters SS/267CS/269CS
Model 267CS/269CS Multivariable
16
Series 2600T Pressure Transmitters SS/267CS/269CS
Model 267CS/269CS Multivariable
17
Series 2600T Pressure Transmitters SS/267CS/269CS
Model 267CS/269CS Multivariable
18
Series 2600T Pressure Transmitters SS/267CS/269CS
Model 267CS/269CS Multivariable
267CS, 269CS bolting identified by “NACE” are in compliance to the requirements of NACE MR0175 when considered “non exposed bolting”
Trademarks
TM
Hastelloy is a trademark of Cabot Corporation
TM
Monel is a trademark of International Nickel Corporation
TM Viton is a trademark of DuPont Dow Elastomers
19
Contact us