Intelligent Electromagnetic Flowmeter: Working Principle
Intelligent Electromagnetic Flowmeter: Working Principle
Intelligent Electromagnetic Flowmeter: Working Principle
MFE600 Intelligent
Electromagnetic Flowmeter
Working Principle
The working principle of Electromagnetic Flowmeter is
based on Faraday's Law of Electromagnetic Induction,
that is, when the conductive liquid flows through the
electromagnetic flowmeter, the induced electromotive
force will be produced in the liquid conductor, and the
induced electromotive force is directly proportional to the
velocity of conductive liquid, magnetic flux density and
width of conductor (interior diameter of flowmeter).
Such induced electromotive force is detected by a pair of
electrodes on the tube wall of the flowmeter, and the rate
of flow can be acquired by mathematical operation. The
equation of induced electromotive force is as follows:
Introduction
MFE600 Intelligent Electromagnetic Flowmeter is E = K×B×V×D
designed and manufactured with the most advanced E: Induced electromotive force
accuracy, reliability, good stability and long service life. B: Magnetic flux density
of the product structure design, material selection, D: Interior diameter of measuring pipe
ensure high quality in long term use. The product has Fluid
Electrode
display. With fully practical function, visual display,
easy operation, it saves troubles for on-site installation interior Diameter of Measuring Pipe
FIow Direction
operation and maintenance. MFE600 can be widely
used in industrial fields such as petroleum, chemical,
metallurgy, water supply and drainage, steel, coal,
paper, food, textile, environmental protection and
other municipal administration, water conservancy
construction field etc.
www.microsensorcorp.com V3.1.1
02 MFE600 Intelligent Electromagnetic Flowmeter
www.microsensorcorp.com V3.1.1
MFE600 Intelligent Electromagnetic Flowmeter 03
Performance Upper limit alarm: the transient flux is larger than the
Electromagnetic Flowmeter Converter Components: upper limit of setting value
Input signal: signal emitted from the sensor directly Lower limit alarm: the transient flux is smaller than the
proportional to the flow. lower limit of setting value
Output signal: 4mA ~ 20mA DC (load resistance 0Ω ~ Damping function: available to set from 0.2s ~ 100s
750Ω). (63% response time)
Select pulse / alarm output by parameter setup Normal Working Condition
Pulse output: (pulled up resistor already) Environment Temperature: -20℃ ~60℃
4mA ~ 20mA DC Output: Current output is active output. Rated Voltage of Power Supply:
Alarm output: rated value 30V DC, 100mA 220V AC: 100V~240V AC
Communication signal: RS485 communication protocol DC: 24V DC
(optional);
RS232 communication protocol (optional) Installation and Structure
Load Resistance: 250Ω ~ 600Ω (including cable Installation:
resistance) Separate model: converter, 50mm pipe or plane installation
Load Capacitance: 0.22μF (Max) Integrated model: combined with the sensor
Load inductance: 3.3mH (Max) Wire connector: ISO M20 × 1.5 female thread
Space between split cables: ≤100m Wire Terminals: M3 screw
Input impedance of receiving instrument: ≥10kΩ (@ Housing material: aluminum alloy
2.4kHz) Structure:
Measurement Range setting: Protection class: IP65 (general type); IP68 (waterproof)
The volumetric flux is set by the setup of volume unit,
flux value and diameter of flowmeter. MFE600 Electromagnetic Flowmeter Performance
3
Volume unit: m Introduction(Flange)
Velocity unit: m/s
Diameter of flowmeter: mm
Transient flux display: display flux unit, and the
percentage of range.
Integrated flux display: display forward and reverse
integrated flux and total integrated flux.
Pulse output: By setting an impulse ratio, the pulse
quantity expressed in any flux unit can be output.
Pulse width: Duty ratio of 50% or fixed pulse width is
available for users to choose. Integrated Separated
www.microsensorcorp.com V3.1.1
04 MFE600 Intelligent Electromagnetic Flowmeter
Electrode Material 316L, Hc, Hb, Titanium, Tantalum, Platinum iridium, Tungsten carbide
Velocity ≤ 15 m/s
Output signal 4mA~20mA DC current; Pulse/ Frequency, Alarm after Upper and Lower limits
Power supply 220V AC, 24V DC, 3.6 V battery power supply
www.microsensorcorp.com V3.1.1
MFE600 Intelligent Electromagnetic Flowmeter 05
Electrode Material 316L, Hc, Hb, Titanium, Tantalum, Platinum iridium, Tungsten carbide
Velocity ≤ 15 m/s
Output signal 4mA~ 20mA DC current; Pulse/ Frequency, Alarm after Upper and Lower limits
Power supply 220V AC, 24V DC, 3.6 V battery power supply
www.microsensorcorp.com V3.1.1
06 MFE600 Intelligent Electromagnetic Flowmeter
Model Selection
The flowmeter model selection is very important in application of instrument. The related information shows that in
practical application of instrument, 2/3 failures are caused by incorrect selection of model and incorrect installation
of instrument to which the special attention shall be paid.
1. Technological data collection
a. The measured fluid name and its chemical substances
b. Maximum flux, minimum flux and normal flux
c. Maximum working pressure;
d. Maximum temperature, minimum temperature.
2. The measured liquid shall have certain conductivity, electrical conductivity ≥5μS/cm.
3. The maximum flux and the minimum flux shall meet the values in the measurable flux range table.
4. The actual maximum working pressure shall be less than the rated working pressure of flowmeter.
5. The maximum working temperature and the minimum working temperature shall meet the temperature
requirements stipulated for flowmeter.
6. Whether negative pressure exists or not in the processing pipeline shall be confirmed.
You can also select the appropriate flowmeter electromagnetic flowmeter according to actual use, and if the
interior diameter of the electromagnetic flowmeter selected differs from that of the existing process pipe, then pipe
reduction or expansion shall be considered.
a. If the pipeline should be contracted, whether the pressure loss caused by the pipe contraction will affect the
process flow or not shall be considered.
b. Considering the measurement accuracy and price, you can choose a smaller diameter electromagnetic
flowmeter, which can reduce the investment relatively.
c. When measuring clean water, the economic velocity is 2m/s ~3m/s; when measuring the solution of
crystallization, the velocity shall be increased approximately to common velocity of ≥2 m/s ,in order to prevent the
electrode of electromagnetic from flowmeter being covered.
www.microsensorcorp.com V3.1.1
MFE600 Intelligent Electromagnetic Flowmeter 07
www.microsensorcorp.com V3.1.1
08 MFE600 Intelligent Electromagnetic Flowmeter
lugs.
RS232
2
Modbus GND
RS485 3 RS232 3 T+/A
4. All the power cable and non 4-core 24V DC signal 22 220V
20 PE
10
11
EX2
S1
19 -24V 12 S0
cable must be equipped with metal cable protection 18 +24V 13 S2
tube.
Integrated Type Wire Connection
1 T-/B
RS485 Communication Output
2 RS232 GND
RS232 Communication Output (optional)
3 T+/A
6 COM
Empty(Null)
9 EX1
Excitation Current
10 EX2
11 S1 Electrode wire
12 S0 Grounding wire
13 S2 Electrode wire
20 PE
21 220V
220V AC power supply access point
22 220V
19 -24V
24V DC power supply access point
18 +24V
IN+
Short Circuit When lugs is connected to (IN+), the flux output is positive; when lugs is con-
lugs IN- nected to (IN-), the flux output is negative.
www.microsensorcorp.com V3.1.1
MFE600 Intelligent Electromagnetic Flowmeter 09
F2-24VDC
F1-24VDC
F2-220V
NTC-24V
NTC-24V
Pcom
Tcom
RS232GND
SGND
SIG2
SIG1
T+/A
DS2
Pout
Tout
DS1
EX1
EX2
T-/B
HA
LA
IN-
1 2 3 4 5 6 7 8
91 0111 21314
J01
shielded
shielded
network
network
220V 220V +24V -24V IN+
1 T-/A
RS485 Communication Output
2 RS232 GND
RS232 Communication Output(optional)
3 T+/B
10 EX1
Excitation Current
11 EX2
220V
220V AC power supply access point
220V
-24V
24V DC power supply access point
+24V
IN+ When lugs is connected to (IN +) , the flux output is positive; when lugs is con-
Short Circuit lugs
IN- nected to (IN-) , the flux output is negative.
www.microsensorcorp.com V3.1.1
10 MFE600 Intelligent Electromagnetic Flowmeter
Version Code Example: MFE600-200-103- internal grounding electrode, temperature <60 ℃ ; IP65
1.0E1-0001-0010 (max) protection, integrated, with 4mA~20mA DC(frequency
Explanation: MFE600 Electromagnetic flowmeter; or pulse output) and RS485 digital signal; carbon steel
DN200 diameter; with fixed stainless steel electrodes housing and flange, with companion mounting flange
and Neoprene lining; with rated pressure of 1.0MPa and (including bolts and nuts), 220VAC power supply.
www.microsensorcorp.com V3.1.1
MFE600 Intelligent Electromagnetic Flowmeter 11
Electromagnetic Flowmeter Outline Construction
Instrument Outline Dimension (mm) Flange Connection Dimension (mm)
Diameter(DN) RatedPressure(MPa) Weight(kg)
a Bf c D D0 n×A
10 150 322 82 90 60 4-Φ14 7
15 150 322 82 95 65 4-Φ14 8
20 150 322 78 105 75 4-Φ14 8
25 150 312 78 115 85 4-Φ14 8
32 4.0 150 327 74 135 100 4-Φ18 9
40 150 335 74 145 110 4-Φ18 11
50 200 354 86 160 125 4-Φ18 12
65 200 366 92 180 145 8-Φ18 14
80 200 385 92 195 160 8-Φ18 15
100 250 406 114 215 180 8-Φ18 18
125 1.6 250 436 114 245 210 8-Φ18 20
150 300 465 136 280 240 8-Φ23 24
200 350 518 156 335 295 8-Φ23 44
250 400 570 202 390 350 12-Φ23 54
300 500 620 230 440 400 12-Φ23 76
350 500 675 278 500 460 16-Φ23 79
400 600 733 320 565 515 16-Φ23 100
450 600 782 374 615 565 20-Φ25 130
1.0
500 600 835 388 670 620 20-Φ25 140
600 600 940 408 780 725 20-Φ30 205
700 700 1048 520 895 840 24-Φ30 305
800 800 1160 580 1010 950 24-Φ34 415
900 900 1260 660 1110 1050 28-Φ34 505
1000 1000 1370 720 1220 1160 28-Φ34 635
1200 1200 1585 1130 1405 1340 32-Φ34 725
1400 1400 1810 1260 1630 1560 36-Φ36 1185
1600 0.6 1600 2040 1450 1830 1760 40-Φ36 1505
1800 1800 2250 1640 2045 1970 44-Φ39 2035
2000 2000 2460 1820 2265 2180 48-Φ42 2555
e e
DN10-25 DN32-2000
www.microsensorcorp.com V3.1.1
12 MFE600 Intelligent Electromagnetic Flowmeter
Select flowmeter type Flowmeter Diameter, Velocity and Flow Relation Graph
Integrated and Separated type
Both the integrated type and separated type have their
own advantages, and basic principles for selection are as
follows:
The separated type is generally used in situations
inconvenient for on-site maintenance and numerical
reading when commissioning is difficult or the flow meter
is often immersed in water and with other functions. It
is also used in poor application situations, such as high
temperature fluid, a position with vibration source and
explosive environment. In most cases, both the integrated
and separated type can meet usage requirements.
The Sensor Diameter and the Process Pipe Diameter
Connected
Generally, for the sake of easy installation, please do
not select reducing pipe, provided that the flux used in
the flowmeter pipe shall be within the range of 0.3m/s ~
10m/s. This kind of selection is usually applicable to a
newly-designed project for which not only current working
conditions are considered when choosing a velocity, but
also a situation of running at full load of the device in the
future shall be considered. For the relationships among
the flux, velocity and diameter, see curve graph, however,
sometimes we also choose a sensor with a different
diameter with the connected pipelinediameter, for example:
1. The velocity in the pipeline is low and the process flux
is stable. In order to meet the demand of the instrument
for flux range and improve local velocity of the flowmeter,
select a sensor with smaller diameter than the technological
pipeline and additionally connect a reducing pipe at front
and rear part of the sensor.
2. In terms of large diameter electromagnetic flowmeter,
the larger the diameter is, the higher the price will be. As
for the situations with low velocity in the pipeline and stable
technological parameter, small diameter flowmeter can
be chosen. This not only runs the flowmeter under good
working state, but also reduces investment cost.
www.microsensorcorp.com V3.1.1
MFE600 Intelligent Electromagnetic Flowmeter 13
a/2 a/2
V1 V2
d1 d1
d2
www.microsensorcorp.com V3.1.1
14 MFE600 Intelligent Electromagnetic Flowmeter
d1/d2 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
ξ1 0.018 0.023 0.0255 0.028 0.03 0.0308 0.0315 0.0323 0.0332
ξ3 0.01 0.02 0.07 0.15 0.26 0.43 0.64 0.9 1.25
d3 0.5
d3
a/2 a/2
0.08 d1 V1 V2 0.4 V2 V1
d2 d2 d1 24°
4°
0.3 20°
0.06
6° 16°
0.2
12°
ξ1 8°
4-8°
0.02 0.1
10°
0
1.0 1.2 1.4 1.6 1.8 2.0 1.0 1.2 1.4 1.6 1.8 2.0
d1d2 d1d2
Installation Direction
When installing the electromagnetic flowmeter, in general, Electromagnetic flowmeter must work in full pipe conditions,
the axis of the electrodes shall be approximately level that is to say, the flowmeter cannot work normally in
in horizontal installation. If the axis of the electrodes partially filled pipe or empty pipe conditions.
is perpendicular to the ground, bubbles will be easily The positive direction in which fluid flows is generally in the
collected near the electrodes located on the upper side, same direction as the arrows in the sensors. There must
while the electrode located at lower side and stopping the be enough installation and maintenance space close to the
liquid contacting with the same is covered by slurry. The flowmeter to prevent the flowmeter from being vibrated.
converter shall be installed above the pipeline to prevent During installation of the flowmeter, supports for supporting
water from entering the converter. pipeline shall be provided on the two sides of the flowmeter.
Stress is prevented from being affected because of pipeline
(O) (X)
vibration, impact and shrinkage. For heavily polluted fluid,
a consideration that a flowmeter is installed on the pipeline
should be given.
The positive direction of the liquid flow should be consistent
Slurry Electrode with the general direction of the arrow on the sensor,
Electrode and there must be sufficient space for installation and
maintenance to prevent the flowmeter from vibration.
www.microsensorcorp.com V3.1.1
MFE600 Intelligent Electromagnetic Flowmeter 15
Fluid Conductivity
Fluid Sealant
Please note below points during usage of fluid sealant:
Do not let it cover the surface of the electrode and
the grounding ring, because this will influence the
measurement of flux.
www.microsensorcorp.com V3.1.1
16 MFE600 Intelligent Electromagnetic Flowmeter
Mixed acid such as chromic acid and sulfuric acid solution not applicable for Hydrochloric
Hastelloy C(HC)
Oxidizing salts such as: Fe ++++, Cu ++, seawater acid
www.microsensorcorp.com V3.1.1
MFE600 Intelligent Electromagnetic Flowmeter 17
Ground ring materials selection air tightness. Disadvantages includes: poor moisture
Lining materials should be chose according to type and resistance, low water resistance and alkali resistance,
temperature of measured fluid. PFA is a kind of fluorinated poor solvent resistance. It applies to places requiring high
plastic, with good corrosion resistance to strong acid abrasive resistance, high strength and oil resistance.
and alkali. It can withstand high temperature, with no Neoprene Advantage
deformation and reduction in insulation resistance at high 10. Good adhesion, softness and abrasion resistance,
temperature. 99.9% high-purity alumina is used for making good water resistance, ageing resistance and other
ceramic lining fabrication so that the instrumentation can characteristics. In contrast, it has poor oil resistance, and
measure the flux with high precision. In comparison with is prone to ageing corrosion in environment with mixed oil
traditional high polymer material, ceramics cannot create and gas.
high temperature, high pressure deformation, and have
good wear resistance.
Polytetrafluoroethylene (PTFE) Advantages
1. High temperature resistance - working temperature is up
to 120℃ .
2. Low temperature resistance - good mechanical
toughness; even if the temperature drops to -20℃ , it still
can maintain 5% elongation.
3. Corrosion resistance - for many chemicals and solvents,
it presents inertness and is resistant to strong acid, strong
alkali, water and various organic solvent.
4. Weather resistance - boasting the best aging lifetime of
plastics
5. High lubrication - boasting the lowest coefficient of
friction in solid materials.
6. Non-adhesion -boasting the lowest surface tension in
solid materials and not adhering to any substances.
7. Non-hazardous - with physiological inertness and can be
implanted in human bodies for a long term as blood vessel
prosthesis and visceral organ, with no adverse reactions.
F46 Advantages
8. F46 has the same excellent corrosion resistance like
PTFE, but has higher temperature resistance than PTFE,
up to 140℃ . It can be used for sanitary products and jetted
molding, and is easier to be processed.
Polyurethane rubber Advantage
9. Code (UR), is the polymerization of polyester (or
polyether) with disocyanate compound. Performance: it is
a rubber with the highest abrasive resistance. Advantages
includes: high strength and elasticity, good oil resistance,
good ozone resistance, aging resistance, and good
www.microsensorcorp.com V3.1.1
18 MFE600 Intelligent Electromagnetic Flowmeter
Main performance and application range (for reference only) of Electromagnetic flowmeter liner
Lining Measurable medium
Performance Application range Notice
Material examples
www.microsensorcorp.com V3.1.1
MFE600 Intelligent Electromagnetic Flowmeter 19
1. High strength, no
1. It does not apply
deformation at high temp. and
to hydrofluoric acid,
pressure. 1. The slurry containing
nitric acid, aqua
2. It has the unique platinum - 1. Suitable for high hard solids, corrosive
regia, NaOH, 70%
alumina cermet electrode. temperature and pressure fluids, viscous fluids,
concentration sulfuric
3. It has a good anti-mud fluid, viscous fluid, corrosive high temperature high
Ceramics acid.
noise performance, suitable fluids. pressure fluid.
2. It can not be used
for permeable fluid. 2. Permeable fluids, slurries 2. Chromium sulfate, 25%
for measurement of
4. Good wear resistance, containing solid particles. sodium hypochlorite, nitric
copper sulfate, sodium
and the wear resistance is acid and the like.
salts and other salts
10 times that of polyurethane
materials.
rubber.
www.microsensorcorp.com V3.1.1
20 MFE600 Intelligent Electromagnetic Flowmeter
Sensor Grounding
Since the voltage of inductive signal of electromagnetic
flowmeter is small, it is easily affected by noise. Its
reference potential must be the same to the measured
liquid potential. Therefore, the reference potential of the
sensor (terminal potential), the reference potential of
converters and amplifiers are also the same to measured
liquid potential, and the liquid potential have to be the same
as the ground potential. The electromagnetic flowmeter is
equipped with a ground loop, which is for establishing a
liquid ground via contact with liquid, and for protecting lining
meanwhile.
The instrument grounding is shown as below: